Power Distribution Module


EQ38XX

Description
The EQ38XX Power Distribution Module (PDM)
integrates isolation, conditioning, ground fault
monitoring, and distribution to five outputs that power
the controller, cabinet devices, and field devices. The
PDM is designed to provide continuous power to the
outputs by relying upon two independent 24 Vdc input
power sources. One power source must be derived
from a line power source and the other source must be
from a backed-up power source.

“local power” output current rating—


Features 10 Amperes alarm current,
2 Amperes standby current.
• Automatic Resetting Overload Protection for field
devices (No fuses to replace) current allocations among outputs—
• Ground Fault Monitoring Alarm Current: 10 Amperes, 15 minutes maximum.
Controller current + Field power current 1 + Field
• Visual LED Indicators for Power and each power power current 2 + Local output current ≤ 10 Amperes.
input
Note: Field power 1 and Field power 2 must not
• Visual LED Indicators for Ground Faults exceed 1.5 Amperes each.
• Anodized Aluminum heat sink Standby current: 2 Amperes, no time limit.
• Panel Mount Controller current + Field power current 1 + Field
power current 2 + Local output current ≤ 2 Amperes.
Note: Field power 1 and Field power 2 must not exceed
Specifications 1.5 Amperes each, or 2 Amperes combined.

Input Voltage— Temperature Range—


24 Vdc nominal, 18 to 30 Vdc. Operating: –40°F to 176°F (–40°C to 80°C)
Storage: –67°F to 185°F (–55° to 85°C).
Input Current—
10 Amperes maximum (per input). Humidity—
5 to 95% RH (non-condensing).
Output Voltage—
27.5 Vdc +/- 0.5 Vdc. Vibration—
FM3260, CSA C22.2 #152, EN 61779-4.
“controller” output current rating—
0.3 Ampere per Controller, 2 Controllers maximum dimensions—
(0.6 Ampere). See Figure 1.

“field power” output current rating— Weight—


1.5 Amperes maximum (each), current limited. 3.25 lbs. (1.48 kg).

2.1
2.1 ©Detector Electronics Corporation 2012 Rev: 5/12 95-8558
10.000
0.5000
9.000 1.766
0.7500
7.500

.530

3.072
4.155

POWER POWER GROUND


FAULT FAULT

.619 P1 P2 P3 P4

2.027
Figure 1—Dimensions of Power Distribution Module in Inches

certification— Special Conditions for Safe Use:


FM / CSA: Class I, Div. 2, Groups A, B, C, D (T3A) The PDM module shall be used in an area of no more
(EQ3800 only) Class I, Zone 2, Group IIC (T3) than pollution degree 2 conforming to IEC 60660-1, and
in an enclosure that complies with all relevant requirements
ATEX: ATEX Directive Compliant of IEC/EN 60079-15:2005, rated at least IP54; and shall
II 3 G
FM
APPROVED
®

be connected to supply circuits where the rated voltage


Ex nA IIC Gc cannot be exceeded by 40% caused by transient
DEMKO 02 ATEX 133865U disturbances.
Tamb = –40°C to +80°C
The maximum surface temperature inside the PDM
IEC: IECEx ULD 10.0004U module can not exceed 195°C.

Compliance to: The PDM module may only be installed, connected or


EN 60079-0:2009; 60079-15:2005 removed when the area is known to be non-hazardous.
IEC 60079-0:2007; 60079-15:2005
For ambient temperatures below –10°C and above
CE: EMC Directive Compliant. +60°C, use field wiring suitable for both minimum and
maximum ambient temperatures.
Refer to the Eagle Quantum Premier manual (form
number 95-8533) for system certification details. The screw terminals are to be tightened with a
minimum torque of 0.5 Nm.

Monitoring Integrity of Signaling Channels

Signaling Path Circuit Designation

Power Distribution Module, Supervised Loss of power per ANSI/NFPA 72:2010, Cl. 10.17.3.
Input Power

Power Distribution Module, Not Limited, Unsupervised per ANSI/NFPA 72:2010, Cl. 10.17.1,
Controller Power & Ground Fault Monitored exceptions #10.17.1.8. & #10.17.1.9, when installed within a
Local Device Power Output common enclosure or located within 20 ft (6M) in conduit.

Power Distribution Module, Internally Limited to 1.5 A, Single open or ground-fault per ANSI/NFPA 72:2010, Cl. 10.17.1.
Field Device Power Output Ground Fault Monitored

2.1 2 95-8558
OPERATION INSTALLATION
The Power Distribution Module is designed to provide
Enclosure Requirements
isolated power to a limited number of devices that
make up a small Eagle Quantum Premier system. This The Power Distribution Module (PDM) must be properly
device relies upon two 24 vdc power sources in order installed in a suitable metallic NRTL listed and NEMA
to provide continuous power to the system. rated enclosure. The enclosure must provide space to
accommodate the module and the wiring. The
One power source must be derived from a line voltage enclosure should be rated for the temperature range of
power source and the other power source must be the location plus the temperature rise of the electronics
driven from a continuously backed-up power source. installed inside the enclosure.
The dual power sources must be capable of individually
providing continuous input power to the PDM, thereby Note
ensuring uninterrupted power for operating the The enclosure must provide a terminal for earth
connected equipment. ground.

If either PDM input power source fails, the PDM will


Mounting
signal the fault condition to the controller by removing
power on controller power input 2 and will illuminate To ensure that heat is properly dissipated within the
the appropriate power fault LED. The controller will enclosure, the PDM must be bolted to either a base
annunciate a power fault condition and actuate the plate or to the enclosure, with thermal grease applied
Fault relay (refer to Tables 1 and 2). to the heat sink.

The EQ3800 PDM signals an input power fault or


ground fault condition as a common fault and is Table 2—LED Status Indications
displayed on the EQP Controller as “Power Fail 2”.
LED LED
Status Description
The EQ3810 PDM signals an input power fault or Color Position
ground fault condition as two independent fault Green Power PDM is powered up
messages. An input power fault is displayed on the
Power input 1 has no
controller as “Power Fail 1”. A ground fault is displayed Yellow Left
Power voltage
on the controller as “Power Fail 2”. For additional
diagnostics information, refer to the LEDs on the PDM Fault Power input 2 has no
Yellow Right
module (see Table 2). voltage
Ground fault has been
Yellow Left detected on a Positive
Ground Output
Fault Ground fault has been
Yellow Right detected on a Negative
Output

Table 1—Power Loss Indications

Controller Display Controller Display Controller


PDM Input Power Loss
with EQ3800 PDM with EQ3810 PDM Fault LED

Line Power Source Power Fail 2 Power Fail 1 On

Backed-up Source Power Fail 2 Power Fail 1 On

Ground fault has been


Power Fail 2 Power Fail 2 On
detected on a Pos. Output

Ground fault has been


Power Fail 2 Power Fail 2 On
detected on a Neg. Output

2.1 3 95-8558
wiring System Wiring (ATEX)
For the connection of modules within the EQP system,
Wire the device as shown in Figure 2.
use fixed installed wiring, size 14-18 AWG (2.5 - 1.0
mm2).
Note
Wiring and equipment installation must meet or
For ambient temperatures below –10°C and above
exceed the latest revisions of the appropriate
+60°C, use wiring suitable for both minimum and
NFPA Standards, National Electrical Code (NEC),
maximum ambient temperatures.
and Authorities Having Jurisdiction (AHJ).

Note
All wiring shall be installed in accordance with
the manufacturer’s recommendations (Refer to
the Eagle Quantum Premier manual (form number
95-8533) for wiring and installation details).

EQ38XX
P1 P2 P3 P4
1+ 1– 2+ 2– 1+ 1– 2+ 2– 1+ 1– 2+ 2– 3+ 3– 4+ 4–
24 VDC LINE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
POWERED SOURCE
(CONTINUOUSLY LOCAL DEVICE FIELD DEVICE
CONTROLLER POWER POWER
POWERED)
POWER INPUT POWER
Intended to power Intended to power
24 VDC BACKED-UP devices within the devices external to
SOURCE EQ3XXX same cabinet. the cabinet.
(CONTINUOUSLY Not current limited, Current limited
POWERED) 2 GND 4 use external fuses. to 1.5 Amps.
Ground fault monitored. Ground fault monitored.
1 +24 VDC 3

B2189
INPUTS MONITORED FOR OPEN CIRCUIT TOTAL OF ALL OUTPUT CURRENTS NOT TO EXCEED
10 AMPS ALARM OR 2 AMPS STANDBY

Figure 2—Power Distribution Module Wiring Diagram

ORDERING INFORMATION
MODEL DESCRIPTION
EQ3800 Power Distribution Module, Standard
EQ3810 Power Distribution Module, EN54 Compliant (ATEX/CE/IECEx only)
TYPE MOUNTING OPTION
N None
TYPE APPROVAL
W FM/CSA/ATEX/CE/IECEx
E ATEX/CE/IECEx

Specifications subject to change without notice.


ER
ED BY UL
AN
Detector Electronics Corporation
T D
IS
Det-Tronics and the DET-TRONICS logo are registered trademarks or 6901 West 110th Street • Minneapolis, Minnesota 55438 USA
G

BS
RE

trademarks of Detector Electronics Corporation in the United States, other ISO 9001
countries, or both. Other company, product, or service names may be Operator: (952) 941-5665 or (800) 765-FIRE
REGIS
REGI

Customer Service: (952) 946-6491 • Fax (952) 829-8750


RM

TER TE
ED FIR RED FI

trademarks or service marks of others.


M
S

NO
. 6
A 23 82
05 • NO. 25

©Copyright Detector Electronics Corporation 2012. All rights reserved. http://www.det-tronics.com • E-mail: det-tronics@det-tronics.com

95-8558

You might also like