You are on page 1of 28

35-1150 kV

315-3500 A

Publication 11.2011
"IZOLYATOR" PLANT performs design, manufacturing, warranty and postwarranty service of highvoltage
bushings for various applications.

The enterprise is the main supplier of highvoltage bushings for power industry in Russia and CIS countries.

Hundreds of thousands of bushings were manufactured and are in operation now.

Production program:

bushings from 35 to high current bushings


1150 kV for power from 20 to 35 kV for
transformers and shunt transformerstobusbar
reactors connection

bushings from 110 to bushings from 35 to


500 kV for cable con- 220 kV for high voltage
nection of transformers circuitbreakers

wall bushings from 66 220 kV bushings for com-


to 220 kV plete SF6 insulated
switchgears

The bushings of any climaticdependent design version are available.

All the bushings are interchangeable with manufactured previously in regard of overall dimensions and connecting
dimensions.

Quality management sys- All the bushings are certi-


tem according to require- fied for compliance with
ments of international State Standard GOST
s t a d a r d 1069381 and other regula-
EN ISO 9001:2008 is oper- tory documents of Russia's
ating at the plant. Gosstandard.
The bushings also comply
with Standard IEC 60137.
Kinds of insulation

Highvoltage bushings for power trans-


formers and reactors are produced with
two kinds of internal condensertype insu-
lation: RIP (Resin Impregnated Paper) and
OIP (Oil Impregnated Paper).

Design of the bushing with


RIPinsulation
I
Internal RIPinsulation is the main
structural part of the bushing; it is the insu-
lating body formed by winding dielectric
paper divided by conductive grading layers
on the central tube (figure 1).
The grading layers serve for optimal
distribution of electric field in radial and
axial directions, providing the highest
dielectric strength values of both internal

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
II and external insulation, including the lower
part of the bushing placed inside the
transformer or reactor.
RIPinsulation is manufactured by wind-
ing crepe paper produced by «Weidmann
Systems International AG» (Switzerland) or
«Karl Fislage GmbH & Co.
KG»(Germany), then the paper is impreg-

SHED PROFILE II TEST TAP (side view)


I

Geometric dimensions may vary,


providing required creepage dis-
tance.

Figure 1 Design of bushing with condenser  type RIP  insulation.


3 1
nated with epoxy compound under vacuum and Silicone rubber insulation is offered as an
subsequently solidified under pressure. alternative to porcelain insulation at bushings
RIPinsulation has practically no gas inclu- with internal RIP  insulation (figure 2).
sions. The bushings equipped with such insulation
After thermal treatment and varnishing of have the following advantages:
external surface, the insulating body forms a absolutely dry, explosionproof design requir-
solid kernel, and a coupling is mounted on it ing no maintenance;
under press fit. high tracking resistance, hydrophobic behav-
The main advantages of RIPinsulation are ior of external insulation preventing
high reliability and long service life performance flashover without cleaning its surface, even
due to its low dielectric losses, low level of par- in case of simultaneous exposure to moisture
tial discharges in the insulation, and high ther- and contamination;
mal stability. external insulation fins having constant or
varying spread, according to individual cus-
External insulation covers the upper part of tomer's requirements;
the insulating body located outside the trans- seismic load resistance;
former or reactor and is made of porcelain or damageproof external insulation made of
silicone rubber. organicsilicon composition, reducing risk of
damage during transportation and mounting;
Porcelain insulation is the porcelain housing minimum weight;
with the flange mounted on its top. The joints environmental safety;
between the porcelain housing, connecting
stability of properties during the whole oper-
sleeve and the upper flange are sealed by gas-
ation life.
kets made of oil resistant rubber.
Silicone rubber insulation is moulded of
Compression of gaskets is provided by the
elastic material created on the basis of
spring tightening device ensuring stable strain
proprietary organicsilicon compositions of
in case of length change of the insulating body
RTV2 type by «Wacker Chemie GmbH»,
and porcelain housing in the range from 60 to
Germany.
+120°С.
Moulded and polymerization takes place
The space between the insulating body and
directly at the insulating body, thus completely
porcelain housing is stuffed with filler for pro-
excluding usage of filler including the trans-
tection from moistering.
former oil. Besides, no spring tightening device
The design of the bushing ensures its is needed.
reliable leaktightness.
Leaktightness of the transformer is ensured
Pressure compensator is intended for
even in case of damaging the bushing's porce-
compensating changes of oil volume caused by
lain housing. The spring tightening device is
temperature variations. It is used only in the
placed under the protective casing,
bushings with external porcelain insulation
leaktightness between the central tube and the
where transformer oil is used as a filling materi-
upper flange is provided by two rubber Oring
al. The compensator is provided by the gas
gaskets.
cushion located in the upper part of the bush-

2
ing.
Oil level is checked visually through the
oillevel sight glass at the protective housing.

Test tap connected to the last grading


layer of the insulating body serves for check-
ing the internal insulation. The test tap shall
be obligingly grounded when measurements
are not performed (figures 1,2).
The design of test tap equipped with
springloaded contact anticipates connection
I of diagnostic tools during operation.

Transportation and storage of the bush-


ing require protection against moisture and
mechanical damage of the lower part of the
varnished surface of the body, submerged in
transformer oil during operation. Polyethylene
II cover with silica gel desiccant and bakelite or
tin cylinder is used for this purpose.

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
Shield installed at the bottom part of the
bushing and intended for the electric field
compensation

I SHED PROFILE II TEST TAP


(except ГКПТIII90110/2500)

Geometric dimensions may vary,


providing required creepage dis-
tance.

Figure 2 Design of bushing with silicone rubber insulation.

3
Design of the bushing with
OIPinsulation
Internal OIP insulation is the main structural
part of the bushing. It is the insulating body formed
by winding dielectric paper divided by conductive
grading layers on the central or winding tube (fig-
ure 3).
The grading layers serve for optimal distribution
of electric field in radial and axial directions, provid-
ing the highest dielectric strength values of both
internal and external insulation, including the lower
part of the bushing placed inside the transformer or
reactor.
For bushings with pulledthrough type connec-
tion*, which have high current rating, winding is
made around a separate tube so that a channel is
formed between the central tube and the winding
tube, where oil circulates to cool and level the tem-
perature of the insulation body during operation.
For bushings with other type of connection, the
inside space of the central tube serves as such a
channel.
I In 750 kV bushings for reactors and 1150 kV
bushings for transformers (figure 4), internal insu-
lation is divided into two parts  the inner and the
outer insulation, so that additional oil circulation
channel is formed to achieve better cooling.
Prior to assembly the frame is vacuum dried.
After assembly the bushing is vacuum treated and
impregnated with transformer oil. Thermovacuum
treatment parameters ensure high reliability and
* See section "Connection".

TEST TAP (side view)


I

Figure 3 Design of bushing with condensertype OIPinsulation and gas cushion.

4
longterm performance of insulation during operation of the bushing.
External porcelain insulation consists of the upper and bottom
housings. Together with the coupling and the protective casing,
they form a hermetically sealed oilfilled cavity where the insulation
body is placed.
The top and bottom butt ends of the cavity are covered by
flanges. The joints between the porcelain housings, coupling and
protective casing are sealed by gaskets made of oil resistant rub-
ber. Stable compression of gaskets is provided by spring tightening
device, compensating the length change of the parts when temper-
ature varies in the range from 60 to +120°С. Compression of gas-
kets sealing joints between the central tube and the flange is
ensured by bolts.
Pressure compensator is intended for compensation of
changes of oil volume caused by temperature variations and is
located in the upper part of the bushing or in the external pressure
tank mounted at the transformer tank lid.
Gas cushion or leakproof metal bellows may be used as com-
pensator.
Oil level in the bushings with gas cushion is checked visually
through the oillevel sight glass at the protective housing.
Leaktightness of the bushing with bellows compensator is
checked by pressure indicator  manometer.
Test tap connected to the last grading layer of the insulating

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
body serves for checking the internal insulation. The test tap shall
be obligingly grounded when measurements are not performed (fig.
3).
The shield for leveling electric field is mounted in the lower part
of the bushing, except the bushings for reactors and some types of
transformers which have the shield as integral part of the design.
The shield is not mounted at the upper part of the bushings
(except 1150 kV bushings): special tests confirmed absence of
corona discharge for voltage which is 10% higher than the highest
operating phase voltage.

Modification
Earthquakeresistant bushings marked with "C" letter were addi-
tionally tested for maintaining operability in case of earthquakes
having magnitude up to 9 according to MSK64 scale, and guaran-
tee keeping of operating parameters in case of earthquakes.
Highaltitude bushings marked with "в" letter are intended for Figure 4
usage at altitude over 1000 m above sea level.
1150kV bushing minus upper and
bottom shield.

5
Connection
Depending on the method of connec-
tion to the transformer coil or reactor
coil, the bushings are classified as
follows.
1. Pulledthrough type bushings,
which are connected by means of
pulling the copper cable of the tap (see
table 1) with soldered contact stud
BOTTOM PART
through the central tube of the bushing OF PULLED-THROUGH
TYPE BUSHING
(figure 5).
The contact stud is supplied with the
bushing and is soldered to the tap at the
place of installation of the bushing.
2. The bottomconnected bushings,
featuring connection implemented by
clamping the tap cable with special bolts
(figures 6a, b) or nuts (figure 6c) at the
bottom contact tip of the bushing. Currentcarrying system of pulledthrough type
Figure 5 bushings.
The bottomconnected bushings
with plugin connector, featuring con-
nection implemented by inserting the
а b
plug located at the bottom end of the
bushing into the socket at the end of the
tap (figure 6d).
In the first case, the tap cable from
the transformer winding serves as the
conductor, while in the second case 
the bushing's central tube.

Table 1
Rated current, A Cable crosssection, mm2 c d
400 1 x 150
500 1 x 185
630 1 x 300
800 1 x 300
1 х 500
1000 2 х 300
3 х 185
1250 3 х 240
1600 4 х 300
2000 4 x 400
2500 4 х 500 Kinds of bottomconnected bushings.
Figure 6

6
а For connecting leadin from the busbar, the terminal is
screwed to the threading of the upper contact stud (figure 7).
The terminal is supplied together with the bushing and is
fixed to the contact stud at the place of installation.

b Technical data
The main information for choosing the bushing is con-
tained in its code designation (figure 8).
Technical specifications, overall, fitting and connecting
dimensions of the bushings are presented at figures 57 and
in table 2.

c
80

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
в  High altitude
d
Г  Hermetic design version
Д  Extended lower part (standard length by default)
К  Internal RIPinsulation
М  Internal OIPinsulation
П  External silicone rubber insulation (porcelain by default)
Р  Bushing for shunt reactors
Т  Bushing for transformers (autotransformers)

e III60220/2000
Rated current, A
Rated voltage, kV
Limit angle of vertical orientation, angular degree
External insulation category depending on ambient
contamination, according to GOST 992089 and
Standard IEC 60137

Key to bushing designation


Figure 7 Kinds of termi- Figure 8 code.
nal plates.

7
Table 2. Part 1 of 7 Technical data of high voltage bushings.

Test voltage, kV

Connection type, figure No.


Phase to earth voltage, kV
Type of internal insulation

Creepage distance, mm

Test cantilever load, N


Bushing type

Lightning impulse
Rated voltage, kV

Rated current, A
Drawing No.

Switching impulse
1 minute, 50 Hz

250 /2500 μs

Weight, kg
1.2/50 μs
40.5 kV bushings

ГКТIII-60-40,5/3500
ИВУЕ.686351.154 RIP 40,5 25 3500 95 — 190 1160 3150 95 7e

36 kV bushings

ГКТIV-60-36/1250
ИВУЕ.686351.168 RIP 72,5 42 1250 140  325 1800 2000 110 5,7e

52 kV bushings

ГКТIV-60-52/630
ИВУЕ.686351.167 RIP 52 30 630 95 — 250 1900 1600 60 5

ГКТIV-60-52/800
ИВУЕ.686351.167-01 RIP 52 30 800 100 — 250 1900 1250 60 5

ГКТПIV-90-52/2000
ИВУЕ.686351.257 RIP 52 30 2000 70 — 170 1650 1250 50

72.5 kV bushings

ГКТIII-60-72,5/630
ИВУЕ.686351.101 RIP 72,5 42 630 140 — 325 1810 1000 62 5,7а

ГКТПIII-90-72,5/630
ИВУЕ.686351.201 RIP 72,5 44 630 140 — 325 1800 2000 29,5 5,7а

ГКТIII-60-72,5/2000
ИВУЕ.686351.102 RIP 72,5 44 2000 140 — 325 1810 3150 143 5,7e

ГКТПIII-90-72,5/2000
ИВУЕ.686351.202 RIP 72,5 44 2000 140 — 325 1800 3150 78 5,7e

126 kV bushings

ГКТIII60126/800
ИВУЕ.686352.103 RIP 126 73 800 230  550 3150 1250 89 5,7а
TOP VIEW
Enlarged ГКТПIII90126/800
ИВУЕ.686352.203 RIP 126 73 800 230  550 3150 1250 42 5,7а

ГКТIII60126/800
ИВУЕ.686352.303 RIP 126 73 800 230  550 3150 1250 86 5,7а

ГКТIII60126/800
ИВУЕ.686352.10301 RIP 126 73 800 230  550 3150 1250 87 5,7а

8
Overall, fitting and connecting dimensions of high voltage bushings.

Dimensions, mm

length of bushing
length of bottom

height of central

transformer tap

housing/shield
current trans-
Bushing type

former length
Bottom Pulled  throungh type

passthrough
Mounting flange*
Drawing No. shield connection

diameter
distance
arcing

length
flange

max.
part

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 l
nholes n1holes

40.5 kV bushings

ГКТIII-60-40,5/3500
ИВУЕ.686351.154 1645 670 400 125 460 — 183 106 270 225 20/6 25 ― — — — — ― ―

36 kV bushing

ГКТIV-60-36/1250
ИВУЕ.686351.168 1480 470 300 460 183 106 290 250 15/8 ― ― ― ― ― ― ―

52 kV bushings

ГКТIV-60-52/630
ИВУЕ.686351.167 1360 550 300 125 620 1365 186 106 290 250 15/8 ― ― 50 80 30

ГКТIV-60-52/800
ИВУЕ.686351.167-01 1400 315 125 620 1130 186 106 290 250 15/8 25 ― ― 5 36 50 80 30

ГКТПIV-90-52/2000
ИВУЕ.686351.257 1385 500 250 115 560 ― 106 225 200 15/6 ― ― ― ― ― ― ―

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
72.5 kV bushings

ГКТIII-60-72,5/630
ИВУЕ.686351.101 1360 315 125 620 1130 186 106 350 300 20/8 ― ― 30 36 50 80 30

ГКТПIII-90-72,5/630
ИВУЕ.686351.201 1235 315 607 970 148 106 350 300 20/8 ― ― 30 36 50 80 30

ГКТIII-60-72,5/2000
ИВУЕ.686351.102 1980 785 300 620 1643 255 165 528 480 24/9 60 165 32/4 89 ― ― ―

ГКТПIII-90-72,5/2000
ИВУЕ.686351.202 1825 785 500 598 1470 220 165 528 480 24/9 60 165 32/4 89 ― ― ―

126 kV bushings

ГКТIII60126/800
ИВУЕ.686352.103 2080 660 200 125 1000 1850 186 106 350 300 24/8 25   30 36 50 80 30

ГКТПIII90126/800
ИВУЕ.686352.203 2030 660 200 125 1055 1770 106 350 300 24/8 25   30 37 50 80 30

ГКТIII60126/800
ИВУЕ.686352.303 2080 660 200 1000 1850 186 106 350 300 24/8   30 36 50 80 30

ГКТIII60126/800
ИВУЕ.686352.10301 2190 770 300 125 1000 1960 186 106 290 250 15/8 25   30 36 50 80 30

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

9
Table 2. Part 2 of 7 Technical data of high voltage bushings.

Test voltage, kV

Connection type, figure No.


Phase to earth voltage, kV
Type of internal insulation

Creepage distance, mm

Test cantilever load, N


Bushing type

Lightning impulse
Rated voltage, kV

Rated current, A
Drawing No.

Switching impulse
1 minute, 50 Hz

250 /2500 μs

Weight, kg
1.2/50 μs
126 kV bushings (continuation)

ГКТПIII90126/800
ИВУЕ.686352.20301 RIP 126 73 800 230  550 3150 1250 40 5,7а

ГКТIII60126/800
ИВУЕ.686352.30301 RIP 126 73 800 230  550 3150 1250 85 5,7а

ГКТIII60126/800
ИВУЕ.686352.10302 RIP 126 73 800 230  550 3150 1250 92 5,7а

ГКТПIII90126/800
ИВУЕ.686352.20302 RIP 126 73 800 230  550 3150 1250 44 5,7а

ГКТIII60126/800
ИВУЕ.686352.30302 RIP 126 73 800 230  550 3150 1250 88 5,7а

ГКТIII60126/800
ИВУЕ.686352.10303 RIP 126 73 800 230  550 3150 1250 102 5,7а

ГКТПIII90126/800
ИВУЕ.686352.20303 RIP 126 73 800 230  550 3150 1250 55 5,7а

ГКТIII60126/800
ИВУЕ.686352.30303 RIP 126 73 800 230  550 3150 1250 98 5,7а

ГКТIV60126/800
ИВУЕ.686352.10304 RIP 126 73 800 230  550 3900 1250 112 5,7а

ГКТПIII90126/800
ИВУЕ.686352.20304 RIP 126 73 800 230  550 3150 1250 41 5,7а

ГКТIII60126/800
ИВУЕ.686352.30304 RIP 126 73 800 230  550 3900 1250 100 5,7а

ГКТПIII-90-126/800
ИВУЕ.686352.203-05 RIP 126 73 800 230 — 550 3150 1250 41 5,7а

TOP VIEW ГКТПIII-90-126/800


Enlarged ИВУЕ.686352.203-06 RIP 126 73 800 230 — 550 3150 1250 39 5,7а

ГКТПIV-90-126/800
ИВУЕ.686352.203-07 RIP 126 800

ГКТIV-60-126/800
ИВУЕ.686352.303-05 RIP 126 73 800 230 — 550 3150 1250 98 5,7а

ГКТIII-60-126/2000
ИВУЕ.686352.104 RIP 126 73 2000 230 — 550 3150 4000 155 5,7e

10
Overall, fitting and connecting dimensions of high voltage bushings.

Dimensions, mm

length of bushing
length of bottom

height of central

transformer tap

housing/shield
current trans-
Bushing type

former length
Bottom Pulled  throungh type

passthrough
Mounting flange*
Drawing No. shield connection

diameter
distance
arcing

length
flange

max.
part

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 l
nholes n1holes

126 kV bushings

ГКТПIII90126/800
ИВУЕ.686352.20301 2140 770 300 125 1055 1880 106 290 250 15/8 25   30 37 50 80 30

ГКТIII60126/800
ИВУЕ.686352.30301 2190 770 300 1000 1960 186 106 290 250 15/8   30 36 50 80 30

ГКТIII60126/800
ИВУЕ.686352.10302 2390 970 500 125 1000 2160 186 106 290 250 15/8 25   30 36 50 80 30

ГКТПIII90126/800
ИВУЕ.686352.20302 2340 970 500 125 1055 2080 106 290 250 15/8 25   30 37 50 80 30

ГКТIII60126/800
ИВУЕ.686352.30302 2390 970 500 1000 2160 186 106 290 250 15/8   30 36 50 80 30

ГКТIII60126/800
ИВУЕ.686352.10303 2390 970 200 125 1000 2160 186 106 535 480 24/9 25   30 36 50 80 30

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
ГКТПIII90126/800
ИВУЕ.686352.20303 2340 970 200 125 1055 2080 106 535 480 24/9 25   30 37 50 80 30

ГКТIII60126/800
ИВУЕ.686352.30303 2390 970 200 1000 2160 186 106 535 480 24/9   30 36 50 80 30

ГКТIV60126/800
ИВУЕ.686352.10304 2390 770 300 125 1200 2160 186 106 290 250 15/8 25   30 36 50 80 30

ГКТПIII90126/800
ИВУЕ.686352.20304 1980 610 300 125 1055 1715 106 290 250 15/8 25   30 37 50 80 30

ГКТIII60126/800
ИВУЕ.686352.30304 2390 770 300 1200 2160 186 106 290 250 15/8   30 36 50 80 30

ГКТПIII-90-126/800
ИВУЕ.686352.203-05 1980 610 300 1055 1715 148 106 290 250 15/8 25 ― ― 30 37 50 80 30

ГКТПIII-90-126/800
ИВУЕ.686352.203-06 1845 475 170 1055 1630 148 106 290 250 15/8 25 ― ― 30 37 50 80 30

ГКТПIV-90-126/800
ИВУЕ.686352.203-07

ГКТIV-60-126/800
ИВУЕ.686352.303-05 2280 660 200 1200 2050 186 106 350 300 24/8 ― ― 30 36 50 80 30

ГКТIII-60-126/2000
ИВУЕ.686352.104 2275 720 400 960 1920 260 165 420 380 22/12 60 165 32/4 89 ― ― ―

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

11
Table 2. Part 3 of 7 Technical data of high voltage bushings.

Test voltage, kV

Connection type, figure No.


Phase to earth voltage, kV
Type of internal insulation

Creepage distance, mm

Test cantilever load, N


Bushing type

Lightning impulse
Rated voltage, kV

Rated current, A
Drawing No.

Switching impulse
1 minute, 50 Hz

250 /2500 μs

Weight, kg
1.2/50 μs
126 kV bushings (continuation)
ГКТПIII-90-126/2000
ИВУЕ.686352.204 RIP 126 73 2000 230 — 550 3150 4000 85 5,7e
ГКТIII-60-126/2000
ИВУЕ.686352.104-01 RIP 126 73 2000 230 — 550 3150 4000 165 5,7e
ГКТПIII-90-126/2000
ИВУЕ.686352.204-01 RIP 126 73 2000 230 — 550 3150 4000 92 5,7e
ГКТIV-60-126/2000
ИВУЕ.686352.104-02 RIP 126 73 2000 230 — 550 3900 4000 200 5,7e
ГКТПIV-90-126/2000
ИВУЕ.686352.204-02 RIP 126 73 2000 230 — 550 3900 4000 94 5,7e
ГКТIV-60-126/2000
ИВУЕ.686352.104-03 RIP 126 73 2000 230 — 550 3900 4000 205 5,7e
ГКТПIV-90-126/2000
ИВУЕ.686352.204-03 RIP 126 73 2000 230 — 550 3900 4000 100 5,7e
ГКТIV-60-126/2000
ИВУЕ.686352.104-04 RIP 126 73 2000 230 — 550 3900 4000 202 5,7e
ГКТПIV-90-126/2000
ИВУЕ.686352.204-04 RIP 126 73 2000 230 — 550 3900 4000 95 5,7e
ГКТIII-60-126/2000
ИВУЕ.686352.104-05 RIP 126 73 2000 230 — 550 3150 4000 172 5,7e
ГКТIII-60-126/2000
ИВУЕ.686352.104-06 RIP 126 73 2000 230 — 550 3150 4000 182 5,7e
ГКТIII-60-126/2000
ИВУЕ.686352.106 RIP 126 73 2000 230 —
ГКТIII-60-126/2000
ИВУЕ.686352.107 RIP 126 73 2000 230 — 550 3150 1600 125 7e
ГКТПIII-90-126/2500
ИВУЕ.686352.207 RIP 126 76 2500 230 — 550 3150 4000 75 7e
ГКТIII-60-126/2000
TOP VIEW ИВУЕ.686352.107-01 RIP 126 73 2000 230 — 550 3150 1600 130 7e
Enlarged
ГКТПIII-90-126/2500
ИВУЕ.686352.207-01 RIP 126 76 2500 230 — 550 3150 4000 78 7e
ГКТIII-60-126/2000
ИВУЕ.686352.150 RIP 126 2000 —
ГКТПIV-90-126/1250
ИВУЕ.686352.208 RIP 126 1250 —
ГКТПIII-90-126/800
ИВУЕ.686352.248 RIP 126 76 800 230 — 550 3150 3150 40 5,7а

12
Overall, fitting and connecting dimensions of high voltage bushings.

Dimensions, mm

length of bushing
length of bottom

height of central

transformer tap

housing/shield
current trans-
Bushing type

former length
Bottom Pulled  throungh type

passthrough
Mounting flange*
Drawing No. shield connection

diameter
distance
arcing

length
flange

max.
part

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 l
nholes n1holes

126 kV bushings
ГКТПIII-90-126/2000
ИВУЕ.686352.204 2210 720 400 1045 1890 220 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТIII-60-126/2000
ИВУЕ.686352.104-01 2575 1020 400 960 2220 260 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТПIII-90-126/2000
ИВУЕ.686352.204-01 2510 1020 400 1045 2190 220 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТIV-60-126/2000
ИВУЕ.686352.104-02 2620 720 400 1305 2265 260 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТПIV-90-126/2000
ИВУЕ.686352.204-02 2460 720 400 1295 2140 220 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТIV-60-126/2000
ИВУЕ.686352.104-03 2920 1020 400 1305 2565 260 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТПIV-90-126/2000
ИВУЕ.686352.204-03 2760 1020 400 1295 2440 220 165 420 380 22/12 60 165 32/4 89 ― ― ―

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
ГКТIV-60-126/2000
ИВУЕ.686352.104-04 2670 770 400 1305 2315 260 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТПIV-90-126/2000
ИВУЕ.686352.204-04 2510 770 400 1295 2190 220 165 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТIII-60-126/2000
ИВУЕ.686352.104-05 2575 1020 400 960 2220 260 165 528 480 24/9 60 165 32/4 89 ― ― ―
ГКТIII-60-126/2000
ИВУЕ.686352.104-06 2575 1020 400 960 2220 260 165 690 650 24/12 60 165 32/4 89 ― ― ―
ГКТIII-60-126/2000
ИВУЕ.686352.106
ГКТIII-60-126/2000
ИВУЕ.686352.107 2422 925 300 125 1000 ― 105 290 250 15/8 25 210 190 ― ― ― ― ―
ГКТПIII-90-126/2500
ИВУЕ.686352.207 2360 925 300 1055 ― 105 290 250 15/8 210 190 ― ― ― ― ―
ГКТIII-60-126/2000
ИВУЕ.686352.107-01 2515 1020 500 125 1000 ― 105 290 250 15/8 25 210 190 ― ― ― ― ―
ГКТПIII-90-126/2500
ИВУЕ.686352.207-01 2455 1020 500 1055 ― 105 290 250 15/8 210 190 ― ― ― ― ―
ГКТIII-60-126/2000
ИВУЕ.686352.150
ГКТПIV-90-126/1250
ИВУЕ.686352.208
ГКТПIII-90-126/800
ИВУЕ.686352.248 2175 805 400 1055 1915 148 106 400 350 24/6 60 120 30

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

13
Table 2. Part 4 of 7 Technical data of high voltage bushings.

Test voltage, kV

Connection type, figure No.


Phase to earth voltage, kV
Type of internal insulation

Creepage distance, mm

Test cantilever load, N


Bushing type

Lightning impulse
Rated voltage, kV

Rated current, A
Drawing No.

Switching impulse
1 minute, 50 Hz

250 /2500 μs

Weight, kg
1.2/50 μs
145 kV bushings
ГКТIV-60-145/630
ИВУЕ.686352.166 RIP 145 84 630 275 — 650 4495 3150 190 5

172 kV bushings
ГКТIII-60-172/800
ИВУЕ.686352.109 RIP 172 100 800 275 — 650 3900 1250 190 5,7а
ГКТIII-60-172/800
ИВУЕ.686352.109-01 RIP 172 100 800 275 — 650 3900 1250 195 5,7а
ГКТПIII-90-172/800
ИВУЕ.686352.209 RIP 172 104 800 275 — 550 4250 4000 100 5,7а
ГКТIII-60-172/1000
ИВУЕ.686352.111 RIP 172 104 1000 275 — 650 4250 4000 265 5,7c
ГКТIII-60-172/1000
ИВУЕ.686352.111-01 RIP 172 104 1000 275 — 650 4250 4000 255 5,7c
ГКТIII-60-172/1000
ИВУЕ.686352.112 RIP 172 104 1000 275 — 650 4250 4000 220 5,7c
ГКТIII-60-172/2000
ИВУЕ.686352.110 RIP 172 104 2000 275 — 650 4320 5000 280 5,7e
ГКТПIII-90-172/2000
ИВУЕ.686352.210 RIP 172 104 2000 275 — 650 4250 5000 160 5,7e

252 kV bushings
ГКТIII-60-252/1000
ИВУЕ.686353.115 RIP 252 153 1000 460 — 1050 6300 1600 292 5,7b
ГКТIII-60-252/2000
ИВУЕ.686353.114 RIP 252 146 2000 460 — 1050 6300 5000 455 5,7e
ГКТПIII-90-252/2000
ИВУЕ.686353.214 RIP 252 146 2000 460 — 1050 6300 5000 270 5,7e
ГКТIII-60-252/2000
ИВУЕ.686353.113 RIP 252 146 2000 460 — 1050 6300 4000 400 5,7e
TOP VIEW ГКТПIII-90-252/2000
Enlarged
ИВУЕ.686353.213 RIP 252 146 2000 460 — 1050 6300 5000 230 5,7e
ГКТПIV-90-252/2000
ИВУЕ.686353.213-02 RIP 252 146 2000 460 — 1050 7900 5000 255 5,7e
ГКТIII-60-252/2000
ИВУЕ.686353.113-01 RIP 252 146 2000 460 — 1050 6300 4000 427 5,7e
ГКТПIII-90-252/2000
ИВУЕ.686353.213-01 RIP 252 146 2000 460 — 1050 6300 5000 250 5,7e

14
Overall, fitting and connecting dimensions of high voltage bushings.

Dimensions, mm

length of bushing
length of bottom

height of central

transformer tap

housing/shield
current trans-
Bushing type

former length
Bottom Pulled  throungh type

passthrough
Mounting flange*
Drawing No. shield connection

diameter
distance
arcing

length
flange

max.
part

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 l
nholes n1holes

145 kV bushings
ГКТIV-60-145/630
ИВУЕ.686352.166 2640 800 300 1380 2385 260 165 350 310 16/12 ― ― 5 56 70 130 30

172 kV bushings
ГКТIII-60-172/800
ИВУЕ.686352.109 2695 850 300 1363 2435 260 165 350 310 22/12 ― ― 30 56 70 130 30
ГКТIII-60-172/800
ИВУЕ.686352.109-01 2695 850 400 1363 2435 260 165 400 350 24/6 ― ― 30 56 70 130 30
ГКТПIII-90-172/800
ИВУЕ.686352.209 2575 850 300 1400 2265 220 165 350 310 22/12 ― ― 30 56 70 130 30
ГКТIII-60-172/1000
ИВУЕ.686352.111 2920 1075 300 1380 2670 260 165 670 620 24/9 ― ― 19/4 56 70 130 40
ГКТIII-60-172/1000
ИВУЕ.686352.111-01 2920 1075 450 1380 2670 260 165 530 480 24/9 ― ― 19/4 56 70 130 40
ГКТIII-60-172/1000

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
ИВУЕ.686352.112 3030 1180 300 1325 2770 260 165 670 620 24/9 ― ― 28/3 85 130 40
ГКТIII-60-172/2000
ИВУЕ.686352.110 3125 1000 500 1475 2765 300 198 420 380 22/12 60 165 32/4 89 ― ― ―
ГКТПIII-90-172/2000
ИВУЕ.686352.210 2960 1000 500 1450 2460 270 198 420 380 22/12 60 165 32/4 89 ― ― ―

H i g h vo l t a g e b u s h i n g s f o r p owe r t ra n s f o r m e r s a n d re a c t o r s
252 kV bushings
ГКТIII-60-252/1000
ИВУЕ.686353.115 3805 1025 400 1960 3490 450 400 22/12 60 165 30 56 ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.114 4800 1905 1140 2025 4470 276 198 760 720 24/16 90 251 32/4 89 ― ― ―
ГКТПIII-90-252/2000
ИВУЕ.686353.214 4530 1905 1140 2100 4025 760 720 24/16 91 251 32/4 89 ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.113 4275 1380 600 2025 3945 276 198 600 560 24/16 90 251 32/4 89 ― ― ―
ГКТПIII-90-252/2000
ИВУЕ.686353.213 4005 1380 600 2100 3500 600 560 24/16 91 251 32/4 89 ― ― ―
ГКТПIV-90-252/2000
ИВУЕ.686353.213-02 4505 1380 700 2600 4000 600 560 24/16 91 251 32/4 89 ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.113-01 4275 1380 600 2025 3765 276 198 760 720 24/16 90 251 32/4 89 ― ― ―
ГКТПIII-90-252/2000
ИВУЕ.686353.213-01 4005 1380 600 2100 3500 760 720 24/16 91 251 32/4 89 ― ― ―

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

15
Table 2. Part 5 of 7 Technical data of high voltage bushings.

Test voltage, kV

Connection type, figure No.


Phase to earth voltage, kV
Type of internal insulation

Creepage distance, mm

Test cantilever load, N


Bushing type

Lightning impulse
Rated voltage, kV

Rated current, A
Drawing No.

Switching impulse
1 minute, 50 Hz

250 /2500 μs

Weight, kg
1.2/50 μs
252 kV bushings (continuation)
ГКТIII-60-252/2000
ИВУЕ.686353.116 RIP 252 153 2000 460 — 1050 6300 2500 370 7c
ГКТПIII-90-252/2000
ИВУЕ.686353.216 RIP 252 146 2000 460 — 1050 6300 5000 190 7c
ГКТIII-60-252/2000
ИВУЕ.686353.117 RIP 252 153 2000 460 — 1050 6300 5000 390 5,7e
ГКТIII-60-252/2000
ИВУЕ.686353.118 RIP 252 146 2000 460 — 1050 6300 4000 320 6а,7b
ГКТIII-60-252/2000
ИВУЕ.686353.119 RIP 252 146 2000 460 — 1050 6300 4000 310 6а,7e
ГКТIII-60-252/2000
ИВУЕ.686353.119-01 RIP 252 146 2000 460 — 1050 6300 4000 315 6а,7e
ГКТIV-60-252/2000
ИВУЕ.686353.119-02 RIP 252 146 2000 460 — 1050 7900 4000 365 6а,7e
ГКТIII-60-252/2000
ИВУЕ.686353.119-03 RIP 252 146 2000 460 — 1050 6300 4000 320 6а,7e
ГКТIII-60-252/2000
ИВУЕ.686353.122 RIP 252 2000
ГКТIII-60-252/3150
ИВУЕ.686353.153 RIP 252 152 3150 425 — 950 6300 4000 490 6а
ГКТIII-60-252/2000
ИВУЕ.686353.164 RIP 252 146 2000 460 — 1050 6300 4000 310 6а,7c
ГКТIII-60-252/2000
ИВУЕ.686353.164-01 RIP 252 146 2000 460 — 1050 6300 4000 315 6а,7c
ГКТIV-60-252/2000
ИВУЕ.686353.164-02 RIP 252 146 2000 460 — 1050 7900 4000 365 6а,7c
ГКТIII-60-252/2000
ИВУЕ.686353.164-03 RIP 252 146 2000 460 — 1050 6300 4000 320 6а,7c
ГКТПIV-90-252/1600
TOP VIEW ИВУЕ.686353.223 RIP 252 1600 —
Enlarged
ГКТПIV-90-252/800
ИВУЕ.686353.249 RIP 252 146 800 460 — 1050 7900 4000 282 5,7b

363 kV bushings
ГКТIII-60-363/1000
ИВУЕ.686354.171 RIP 363 210 1000 510 950 1175 9050 2500 650 5,7b
ГКТПIII-90-363/1000
ИВУЕ.686354.224 RIP 363 210 1000 510 950 1175 9050 2500 960 5,7b

16
4
Overall, fitting and connecting dimensions of high voltage bushings.

Dimensions, mm

length of bushing
length of bottom

height of central

transformer tap

housing/shield
current trans-
Bushing type

former length
Bottom Pulled  throungh type

passthrough
Mounting flange*
Drawing No. shield connection

diameter
distance
arcing

length
flange

max.
part

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 l
nholes n1holes

252 kV bushings
ГКТIII-60-252/2000
ИВУЕ.686353.116 4155 1535 600 1960 ― 165 670 620 24/16 175 ― ― ― ― ―
ГКТПIII-90-252/2000
ИВУЕ.686353.216 4025 1535 600 2145 ― 225 165 670 620 24/16 70 175 ― ― ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.117 3965 1070 400 2025 3625 276 198 600 560 24/16 90 251 32/4 89 ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.118 3845 1225 300 1960 ― 238 165 450 400 22/12 230 239 ― ― ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.119 3760 1030 300 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.119-01 3860 1130 400 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―
ГКТIV-60-252/2000
ИВУЕ.686353.119-02 4260 1130 400 2360 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
ГКТIII-60-252/2000
ИВУЕ.686353.119-03 3960 1230 500 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.122
ГКТIII-60-252/3150
― ― ― ― ― ―

H i g h vo l t a g e b u s h i n g s f o r p owe r t ra n s f o r m e r s a n d re a c t o r s
ИВУЕ.686353.153 4330 1380 710 2025 276 198 400 350 22/8 230 240
ГКТIII-60-252/2000
ИВУЕ.686353.164 3655 1030 300 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.164-01 3755 1130 400 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―
ГКТIV-60-252/2000
ИВУЕ.686353.164-02 4155 1130 400 2360 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―
ГКТIII-60-252/2000
ИВУЕ.686353.164-03 3855 1230 500 1960 ― 238 165 450 400 22/12 25 230 240 ― ― ― ― ―
ГКТПIV-90-252/1600
ИВУЕ.686353.223
ГКТПIV-90-252/800
ИВУЕ.686353.249 4990 1880 1045 2600 4690 270 210 550 500 24/12 120 251 30 89 ―

363 kV bushings
ГКТIII-60-363/1000
ИВУЕ.686354.171 5815 2160 600 2770 5220 296 225 818 770 24/16 91 251 30/2 89 — — —
ГКТПIII-90-363/1000
ИВУЕ.686354.224 5673 2160 600 2970 5220 270 240 818 770 24/16 91 251 30/2 89 — — —

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

17
Table 2. Part 6 of 7 Technical data of high voltage bushings.

Test voltage, kV

Connection type, figure No.


Phase to earth voltage, kV
Type of internal insulation

Creepage distance, mm

Test cantilever load, N


Bushing type

Lightning impulse
Rated voltage, kV

Rated current, A
Drawing No.

Switching impulse
1 minute, 50 Hz

250 /2500 μs

Weight, kg
1.2/50 μs
363 kV bushings(continuation)
ГКТПIII-90-363/1000|
ИВУЕ.686353.224-01 RIP 363 210 1000 510 950 1175 9050 2500 320 5,7b
ГКТIII-60-363/2500
ИВУЕ.686354.125 RIP 363 210 2500 510 950 1175 8000 3150 620 5,7d
ГКТПIII-90-363/2500
ИВУЕ.686354.225 RIP 363 210 2500 510 950 1175 9000 3150 300 5,7e
ГКТIII-60-363/1250
ИВУЕ.686354.147 RIP 363 210 1250 510 950 1175 9050 2500 600 6а,7а
ГКТIII-60-363/1250
ИВУЕ.686354.147-01 RIP 363 210 1250 510 950 1175 9050 2500 612 6а,7а

550 kV bushings
ГКТIII-60-550/800
ИВУЕ.686355.128 RIP 550 334 800 680 1230 1550 13150 4000 1200 7а
ГКТIII-60-550/1600
ИВУЕ.686355.173 RIP 550 300 1600 680 1230 1550 13150 5000 1900 7e
ГКТIII-60-550/630
ИВУЕ.686355.173-01 RIP 550 303 630 680 1230 1550 13150 3150 1400 7e
ГКТIII-60-550/2500
ИВУЕ.686355.172 RIP 550 303 2500 680 1230 1550 13150 2500 1230 5,7e
ГКТIII-60-550/2500
ИВУЕ.686355.172-01 RIP 550 303 2500 680 1230 1550 13150 2500 1230 5,7e
ГКРIII-30-550/315
ИВУЕ.686355.129 RIP 550 303 315 680 1230 1550 13735 2500 1150 5,7e
ГКТIII-60-550/1250
ИВУЕ.686355.146 RIP 550 334 1250 680 1230 1550 15125 4000 1200 5,7e
ГКТIII-60-550/1251
ИВУЕ.686355.146-01 RIP 550 334 1250 680 1230 1550 15125 4000 1180 5,7e
ГКТIII-60-550/1600
ИВУЕ.686355.146-02 RIP 550 334 1600 680 1230 1550 15125 4000 1200 5,7e
TOP VIEW
Enlarged
600 kV bushings
ГКТПIII-90-600/800
ИВУЕ.686355.262 RIP 600 800

800 kV bushings
ГМТII-30-750/1000
ИВЕЮ.686345.011 OIP 800 462 1000 975 1550 2400 15750 2500 2750 5,7e

18
4
Overall, fitting and connecting dimensions of high voltage bushings.

Dimensions, mm

length of bushing
length of bottom

height of central

transformer tap

housing/shield
current trans-
Bushing type

former length
Bottom Pulled  throungh type

passthrough
Mounting flange*
Drawing No. shield connection

diameter
distance
arcing

length
flange

max.
part

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 l
nholes n1holes

363 kV bushings
ГКТПIII-90-363/1000
ИВУЕ.686353.224-01 5000 1490 600 2965 4550 225 450 400 22/12 91 251 30/2 89 ― ― ―
ГКТIII-60-363/2500
ИВУЕ.686354.125 5290 1620 600 2770 4970 296 225 600 560 24/16 91 251 32/2 89 — — —
ГКТПIII-90-363/2500
ИВУЕ.686354.225 5140 1615 600 2970 4820 270 240 600 560 24/16 90 250 32/4 89 — — —
ГКТIII-60-363/1250
ИВУЕ.686354.147 4685 1155 300 2770 ― 296 225 450 400 22/12 230 239 ― ― ― ― ―
ГКТIII-60-363/1250
ИВУЕ.686354.147-01 4885 1355 500 2770 ― 296 225 450 400 22/12 230 239 ― ― ― ― ―

550 kV bushings
ГКТIII-60-550/800
ИВУЕ.686355.128 6462 1790 600 3670 ― 296 275 720 660 24/12 330 296 ― ― ― ― ―
ГКТIII-60-550/1600

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
ИВУЕ.686355.173 7855 2750 1000 3955 ― 1200 1130 24/16 277 490 ― ― ― ― ―
ГКТIII-60-550/630
ИВУЕ.686355.173-01 8665 3850 2000 3670 — 296 275 1200 1130 24/16 490 — — — — —
ГКТIII-60-550/2500
ИВУЕ.686355.172 7470 2600 1000 3670 6520 296 275 1200 1130 24/16 175 282 28/4 89 — — —

H i g h vo l t a g e b u s h i n g s f o r p owe r t ra n s f o r m e r s a n d re a c t o r s
ГКТIII-60-550/2500
ИВУЕ.686355.172-01 7540 2670 1000 3670 6520 296 275 1200 1130 24/16 280 400 28/4 89 — — —
ГКРIII-30-550/315
ИВУЕ.686355.129 7330 2205 700 3970 6625 296 320 1200 1130 24/16 30 — — —
ГКТIII-60-550/1250
ИВУЕ.686355.146 7515 2080 900 237 4240 6980 296 275 720 660 24/12 37 190 290 20/4 69 ― ― ―
ГКТIII-60-550/1251
ИВУЕ.686355.146-01 7215 1780 600 237 4240 6680 296 275 720 660 24/12 37 190 290 20/4 69 ― ― ―
ГКТIII-60-550/1600
ИВУЕ.686355.146-02 7515 2080 900 237 4240 6980 296 275 720 660 24/12 37 190 290 24/4 69 ― ― ―

600 kV bushings
ГКТПIII-90-600/800
ИВУЕ.686355.262

800 kV bushings
ГМТII-30-750/1000
ИВЕЮ.686345.011 9430 2720 810 160 4900 7690 580 590 820 740 24/12 35 280 400 28/3 69 — — —

* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

19
4
Table 2. Part 7 of 7 Technical data of high voltage bushings.

Test voltage, kV

Connection type, figure No.


Phase to earth voltage, kV
Type of internal insulation

Creepage distance, mm

Test cantilever load, N


Bushing type

Lightning impulse
Rated voltage, kV

Rated current, A
Drawing No.

Switching impulse
1 minute, 50 Hz

250 /2500 μs

Weight, kg
1.2/50 μs
800 kV bushings (continuation)
ГМТII-30-750/1000
ИВЕЮ.686345.009 OIP 800 455 1000 975 1550 2400 15750 2500 2700 5,7e
ГМТII-30-750/1000
ИВЕЮ.686345.011-01 OIP 800 462 1000 975 1550 2400 15750 2500 2840 5,7e
ГМТII-30-750/1000
ИВЕЮ.686345.009-01 OIP 800 455 1000 975 1550 2400 15750 2500 2790 5,7e
ГМТII-30-750/1250
ИВЕЮ.686345.010 OIP 800 462 1250 950 1550 2400 17700 2500 2800 6b,7d
ГМТII-30-750/1250
ИВЕЮ.686345.013 OIP 800 462 1250 975 1550 2400 17700 2500 2580 6b,7d
ГМТII-30-800/1000
ИВУЕ.686346.145 OIP 800 1000
ГМТII-30-800/1000
ИВУЕ.686346.145-01 OIP 800 1000
ГКРII-60-800/315
ИВУЕ.686356.165 RIP 800 486 315 950 1550 2100 15750 4000 2110 5,7e

1200 kV bushings
ГМТ-20-1150/1250
2ШЦ.800.119 OIP 1200 694 1250 1150 1900 2700 18000 2500 11690 5,7d

TOP VIEW
Enlarged

20
Overall, fitting and connecting dimensions of high voltage bushings.

Dimensions, mm

length of bushing
length of bottom

height of central

transformer tap

housing/shield
current trans-
Bushing type

former length
Bottom Pulled  throungh type

passthrough
Mounting flange*
Drawing No. shield connection

diameter
distance
arcing

length
flange

max.
part

L L1 L2 L3 L4 L5 D D3 D1 D2 d S L6 D4 d1 d2 d3 d4 l
nholes n1holes

800 kV bushings
ГМТII-30-750/1000
ИВЕЮ.686345.009 9430 2720 810 160 4900 7690 580 590 820 740 24/12 35 280 400 28/3 69 — — —
ГМТII-30-750/1000
ИВЕЮ.686345.011-01 9430 2720 810 160 4900 7690 580 590 1200 1130 24/16 35 280 400 28/3 69 — — —
ГМТII-30-750/1000
ИВЕЮ.686345.009-01 9430 2720 810 160 4900 7690 580 590 1200 1130 24/16 35 280 400 28/3 69 — — —
ГМТII-30-750/1250
ИВЕЮ.686345.010 10080 2720 810 160 5525 — 580 590 820 740 32/12 35 280 400 — — — — —
ГМТII-30-750/1250
ИВЕЮ.686345.013 9640 2410 810 160 5525 — 580 590 820 740 32/12 35 280 400 — — — — —
ГМТII-30-800/1000
ИВУЕ.686346.145
ГМТII-30-800/1000
ИВУЕ.686346.145-01

H I G H VO LTAG E B U S H I N G S F O R P OW E R T R AN S F O R M E R S AN D R E AC TO R S
ГКРII-60-800/315
ИВУЕ.686356.165 8515 2605 750 4900 7910 415 405 1200 1130 24/16 — — 30 72

1200 kV bushings
ГМТ-20-1150/1250
2ШЦ.800.119 11815 2855 800 230 7500 11063 530 850 1200 1130 25/16 31 — — 28/4 85 — — —

H i g h vo l t a g e b u s h i n g s f o r p owe r t ra n s f o r m e r s a n d re a c t o r s
* Connecting dimensions of the mounting flange may be modified according to Customer's requirements.

21
4
Testing and operation Interchangeability

Every type of bushing passed accept- The range of products being manufac-
ance tests for compliance with all require- tured includes not only the bushings cur-
ments of State Standard GOST 1069381 rently mounted on the newly made trans-
and Standard IEC 60137. formers and reactors, but also those
Every manufactured bushing is designed instead of the bushings manu-
subjected to handover tests for the purpose factured previously. In this case, adequa-
of checking its compliance with the require- cy of the submerged bushing parts and
ments in regard of the type and quality of the length of the pulledthrough tap, as
manufacture, including test measurement of well as fitting dimensions of the mounting
partial discharge level and tgδ of the insula- flange, are observed; if necessary, this is
tion, according to the mentioned documents. coordinated with the transformer and
reactor manufacturers.
The advantage of the bushings with solid
insulation as compared to oil impregnated
paper insulation is that oil contained in them
is not intended for active insulation.
Therefore, they need no regular condition
monitoring. Technical maintenance requires
only periodic (once in 4 years) measurement
of tgδ of the bushing insulation.

WEIGHT DATE OF MANUFACTURE

DRAWING NUMBER BUSHING TYPE

SERIAL NUMBER NUMBER OF TECHNICAL SPECIFICATIONS

OR STATE STANDARD

Figure 9 Nameplate.

22
NOTES

23
NOTES

24
HIGH QUALITY OF OUR PRODUCTS ENSURE LONGTERM SAFE AND RELIABLE OPERATION
OF EQUIPMENT AT ELECTRIC POWER SUBSTATIONS UNDER ANY CONDITIONS AT THE MOST
IMPORTANT OBJECTS

110 kV/630 A bushings on the 40 MVA power transformer. 220 kV/2000 A bushings on the 200 MVA power transformer.

750 kV bushings on the shunt reactors 110 MVA. 330 kV bushings on the 125 MVA power transformer.
Massa Ltd. Company
77 Lenina st., Pavlovskaya Sloboda village, Istra district,
Moscow region 143581, Russia
Tel.: +7 (495) 727 3311
Fax: +7 (495) 727 3320
E-mail: aleksey.gavrilov@mosizolyator.ru
andrey.shornikov@mosizolyator.ru
www. mosizolyator.com

«Izolyator» Plant reserves the right to make changes in the subsequent publications of the catalogue
according to new developments, as well as Customer’s remarks and requests.