You are on page 1of 1

1 Clearance Required

Vertical Height Of Conductor above ground = 6.7 m


Vertical Spacing Between Power Conductor = 4 m
Horizontal Spacing Between Power Conductor = 6.25 m
Height of Ground wire Above Top Most Power Conductor = 3.125 m

Total = 13.825 m

2 Maximum sag for power conductor

d = (W 2.L2)/8.Ph

Coefficient of Expansion = 0.00001992


Span of Tower = 240
Wind Intensity = 1.5 Kn/m^2
Power factor = 0.75
Unit Weight of Conductor = 16.76 N/m
Dia of Connductor = 0.03 mm
Dia of Strads = 3 mm
Number Of Strads = 61
Shape Factor = 0.67
Variation of Temperature = 5 c to 60
Permissible Tension in the conductor T1 = 35.6 Kn
Young Modulus of elasticity E = 0.842 10^5
Tension in the conductor
2
Effective area A = 431.1835917 mm
Temperature variation t2-t1 = 55 c

T22[(T2-T1)+((W1.L.E.A.l)/(24.T1.T1))+(t2-t1).a.E.A] = (W2.W2.L.L.E.A)/24
Wind Load W1 = 0.0226125 Kn/m
Weight of Conductor at minimum temperature with Wind = 0.028146452 Kn/m
Horizontal Component of wire pull P From Eq 1 given =Above
2
T2 [(T2-35.6)+
94.243407 = 2447561
T2^3 58.643407 T2 = 2447561.356
T2^3 + 58.6434067411536 T2 - 2447561.35608984=0
Ph = T2 = 17.884575 1.999811041

Maximum sag for power conductor = (W2.L2)/8.Ph


d = 6.747266781 m

Total Height of Tower

Height From Clearance = 13.825 m


Maximum Sag of Conductor = 6.747266781 m
Total = 20.57226678 m

Round Off Total Height = 21 m

Base Width Of tower = 5.25 m

Round Off Base Width = 5.5 m

TOP Width Of tower = 1.833333333 m

Round Off Top Width = 2m