2) Start detection amp 5.75 [In] 3) Motor Start up Amp 5 [In] 4) Motor start up time 2.2 s 5) Cumulative time limit 5 6) Lock rotor time 60 S 7) Counter Red Rate 2.2 s/hr 8) Emg start Red rate Omit** 9) Restart inhibit time 0 10) Str over delay time 100ms (As per relay catalogue } 11) motor standstill A 0.12 In {default} Current limit to check for motor standstill condition
** Start time reduction factor when emergency start is On
No emergency start on RELAY 49 PROTECTION SETTING
1) Env . Temp. Mode FLC Only
2) Current Reference 0.53 [In] 3) Env Temp Set OMIT 4) Alarm Thermal Value 90-95 % 5) Thermal Restart Value 68 % 6) Overload Factor 1.1 7) Weighting Factor 50 8) Time Constant Normal 180 Sec 9) Time Constant Start 180 Sec 10) Time Constant Stop -- SAMPLE CALCULATION FOR RELAY 66
1) Cumulative Time Lim
N=3 t= 2.2 at 80% voltage
Lim= (3-1) * 2.2 + safety margin
=4.4 + safety margin
=5
2) Locked Rotor time
Permissible Stalling time of motor= min 18 sec---- max 60 sec
Motor starting time 1 sec
Permissible stalling time> motor starting time no stalling protection required
3) Counter Red Rate
Motor manufacturer has not given max start per hour. So no of max. consecutive cold start= 3 has been assumed as max no of start per hour. Starting time is taken as 2.2 S 80 % Voltage
Counter Red Rate = 2.2/1= 2.2 s/hr
RELAY 49 PROTECTION SETTING CALCULATIONS
1. Thermal Restart Value
The startup time is 1 Sec
Time constant start is 180 seconds. Using the trip curve with no prior load, the operation time at 6 x rated current is 4.6 seconds, one motor startup uses (1 / 4.6) thermal capacity