RELAY 66 PROTECTION SETTING

1) Operation Mode Iit


2) Start detection amp 5.75 [In]
3) Motor Start up Amp 5 [In]
4) Motor start up time 2.2 s
5) Cumulative time limit 5
6) Lock rotor time 60 S
7) Counter Red Rate 2.2 s/hr
8) Emg start Red rate Omit**
9) Restart inhibit time 0
10) Str over delay time 100ms (As per relay catalogue }
11) motor standstill A 0.12 In {default} Current limit
to check for motor standstill
condition

** Start time reduction factor when emergency start is On


No emergency start on
RELAY 49 PROTECTION SETTING

1) Env . Temp. Mode FLC Only


2) Current Reference 0.53 [In]
3) Env Temp Set OMIT
4) Alarm Thermal Value 90-95 %
5) Thermal Restart Value 68 %
6) Overload Factor 1.1
7) Weighting Factor 50
8) Time Constant Normal 180 Sec
9) Time Constant Start 180 Sec
10) Time Constant Stop --
SAMPLE CALCULATION FOR RELAY 66

1) Cumulative Time Lim

N=3 t= 2.2 at 80% voltage

Lim= (3-1) * 2.2 + safety margin

=4.4 + safety margin

=5

2) Locked Rotor time


Permissible Stalling time of motor= min 18 sec---- max 60 sec

Motor starting time 1 sec

Permissible stalling time> motor starting time no stalling protection required

3) Counter Red Rate


Motor manufacturer has not given max start per hour. So no of max. consecutive cold start= 3 has been
assumed as max no of start per hour. Starting time is taken as 2.2 S 80 % Voltage

Counter Red Rate = 2.2/1= 2.2 s/hr


RELAY 49 PROTECTION SETTING CALCULATIONS

1. Thermal Restart Value

The startup time is 1 Sec


Time constant start is 180 seconds.
Using the trip curve with no prior load, the operation time at 6 x rated current is 4.6 seconds, one
motor startup uses (1 / 4.6) thermal capacity

Thermal restart level = 100-{( 1*100/4.6)+ 5}= @68 %