You are on page 1of 27

4

Fault and Alarm Indicators

Overview 214
Main Processor Indicators 215
Communication Module Indicators 220
Analog Input Module Indicators 223
Analog Input/Digital Input Module Indicators 226
Analog Output Module Indicators 229
Digital Input Module Indicators 232
Digital Output Module Indicators 235
Pulse Input Module Indicators 239
Solid-State Relay Output Module Indicators 242

Planning and Installation Guide for Trident v2 Systems


214 Chapter 4 Fault and Alarm Indicators

Overview
Indicators are lights on the front panel of each module that identify the state of each module.
Each module includes indicators that identify the general state of the module and other
indicators related to the function of the module.

The Trident controller can be repaired while operating. However, the


integrity of the controller can only be assured if the operator follows
repair procedures correctly. If in doubt about the procedures, the
operator should take whatever steps are necessary to ensure the safety of
the plant and personnel, and then contact Invensys for assistance in
implementing the repair procedures.

The types of indicators include:


• Status indicators which identify the processing state of the module. Each module
includes a Pass, Fault, and Active indicator.
• A lock indicator which identifies whether the module is unlocked.
• Mode indicators which identify the current operating state of the controller. (Only on
MP Modules.)
• Field power and power load indicators which identify whether a power problem has
occurred. (Only on some I/O modules.)
• Communication indicators which identify the type of communication occurring. (Only
on MPs and CMs.)
• Points indicators which identify whether the point is energized.
• Alarm indicators which identify alarm conditions for the controller. (Only on MP
Modules.)

Fault and Alarm Indicators


Fault indicators identify potentially serious problems with a module. Alarm conditions identify
abnormal field conditions such as loss of power and loss of communication.
If a fault or alarm indicator is on, you should consult the appropriate section of this chapter and
take appropriate action. This action may include replacing a faulty module or repairing a faulty
circuit or device.

Identifying Fault and Alarm Conditions


You can identify alarm and fault conditions in these ways:
• By examining the indicators on the front panel of each module and comparing the
indicators with the descriptions in this chapter
• By using the Enhanced Diagnostic Monitor

Planning and Installation Guide for Trident v2 Systems


Main Processor Indicators 215

Main Processor Indicators


This section describes indicators for the MP Module, including:
• MP Status Indicators on page 216
• MP System Mode Indicators on page 217
• MP Alarm Indicators on page 218
• MP Communication Indicators on page 219

п­­ øÙ®»»²÷
ÐßÍÍ
ÓРͬ¿¬«­ ÚßËÔÌ Ú¿«´¬ øλ¼÷
ײ¼·½¿¬±®­
ßÝÌ×ÊÛ

ß½¬·ª» øÇ»´´±©÷

ÓÑÜÛ Î»³±¬» Ó±¼» øÙ®»»²÷


ÎÛÓÑÌÛ
ͧ­¬»³ Ó±¼» Ϋ² Ó±¼» øÙ®»»²÷
ÎËÒ
ײ¼·½¿¬±®­ ÐÎÑÙÎßÓ Ð®±¹®¿³ Ó±¼» øÇ»´´±©÷
ØßÔÌ
Ø¿´¬ Ó±¼» øÇ»´´±©÷

ßÔßÎÓÍ Ú·»´¼ б©»® øλ¼÷


Ú×ÛÔÜ ÐÑÉÛÎ
Ô±¹·½ б©»® øλ¼÷
ÔÑÙ×Ý ÐÑÉÛÎ
ß´¿®³
ײ¼·½¿¬±®­ ÍÇÍÌÛÓ ßÔßÎÓ Í§­¬»³ ß´¿®³ øλ¼÷
ÐÎÑÙÎßÓ ßÔßÎÓ
ÑÊÛÎ ÌÛÓÐÛÎßÌËÎÛ
Ю±¹®¿³ ß´¿®³ øÞ´«»÷

Ѫ»® Ì»³°»®¿¬«®» øλ¼÷

ÔÑÝÕ
˲´±½µ øλ¼÷

ÝÑÓÓËÒ×ÝßÌ×ÑÒÍ
ÌÈ
×Ñ ÞËÍ
ÎÈ
ÌÈñÎÈ ×ñÑ Þ«­ øÙ®»»²ñÙ®»»²÷

ÌÈ
ÝÑÓÓ ÞËÍ ÌÈñÎÈ Ý±³³«²·½¿¬·±² Þ«­ øÙ®»»²ñÙ®»»²÷
ÎÈ
ݱ³³«²·½¿¬·±²
ײ¼·½¿¬±®­ ÌÈ
ÍÛÎ×ßÔ ÌÈñÎÈ Ó±¼¾«­ øÙ®»»²ñÙ®»»²÷
ÎÈ

Ô×ÒÕ Ô·²µ Ì®·Í¬¿¬·±²øÙ®»»²÷


ÌÎ×ÍÌßÌ×ÑÒ ÌÈ
ÎÈ
ÌÈñÎÈ Ì®·Í¬¿¬·±² øÙ®»»²ñÙ®»»²÷

ÓÐ

Figure 102 MP Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


216 Chapter 4 Fault and Alarm Indicators

MP Status Indicators
The MP status indicators identify the processing state for the MP Module.
A fault light indicates that the processor has an internal fault.

Normal States

Pass Fault Active Lock Description Action


Green No Yellow No Module is operating normally. Normal status. No action
steady light blinking light Active indicator blinks once per is required.
scan when executing a control
program.
Green No No No Module is operating normally.
steady light light light Possible conditions include:
Control program has not been Load control program.
loaded into the MP.
Control program has been Start control program.
loaded into the MP, but has not
been started up.
Module has just been installed Wait for the module to be
and is currently being educated educated.
by the other MP Modules.

Fault States

Pass Fault Active Lock Description Action


No Red —a No Module may have failed. See mode indicator status
light steady light Possible conditions include: for power-up states.
Module may be in the process If the Pass indicator does
of power-up self-test. not go on within five
minutes, replace the
module.
Module has detected a fault. Module is operational, but
should be replaced.
No Red — Red Module is unlocked from the Lock module using a
light steady steady baseplate. 1/4-inch flat-blade
screwdriver.
Green Red — — Indicators/signal circuitry on Replace the module.
steady steady the module are
malfunctioning.
No No — — Indicators/signal circuitry on Replace the module.
light light the module are malfunctioning
a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


Main Processor Indicators 217

MP System Mode Indicators


The MP system mode indicators identify the current operating state of the controller.
(Operational modes are set in TriStation 1131 software. For more information, see the TriStation
1131 Developer’s Guide.)

Remote Run Program Halt Description


Green Green Yellow No Normal operation with write capability.
steady steady steady light Allows writes to program variables by TriStation 1131
software, Modbus master, and external hosts.
Allows control of the controller from TriStation 1131
software, including Download All and Download
Change.
Green Green No No Normal operation with read-write capability.
steady steady light light Allows writes to program variables by Modbus
masters and external hosts. (Download All and
Download Change by TriStation 1131 software are not
allowed.)
No Green No No Normal operation with read-only capability.
light steady light light MP Modules execute the previously loaded control
program. Attempts to modify program variables by
Modbus masters and external hosts are rejected.
No No Yellow Yellow Control program loading and checkout is enabled.
light light steady steady Allows control of the controller from the TriStation
1131 control program, including Download All and
Download Change. Control program has also been
stopped.
Green Green Yellow Yellow Indicators change every few seconds; module is in its
slow slow slow slow power-up state.
blinking blinking blinking blinking
Green Green Yellow Yellow Module is ready to download new internal firmware.
fast fast fast fast Condition is caused by removing the MP Baseplate
blinking blinking blinking blinking address plug before module power-up.
No No No Yellow Control program has stopped.
light light light steady
Green Green Yellow Yellow Module is faulty or has detected a bad address plug.
steady steady steady steady

Planning and Installation Guide for Trident v2 Systems


218 Chapter 4 Fault and Alarm Indicators

MP Alarm Indicators
The MP alarm indicators identify alarm conditions for the controller.

Field Logic System Program Over


Description Action
Power Power Alarm Alarm Temp
—a Red Red — — System power Correct the problem.
steady steady supply is
missing/bad.
Red — Red — — Field power supply Correct the problem.
steady steady is missing/bad.
— — Red — — MP or I/O module Identify the condition by
steady is malfunctioning. looking at the Pass or
Fault indicators of other
modules or by using the
TriStation 1131
Diagnostic Panel.
Replace faulty module.
I/O module has Correct field fault.
detected a field
fault.
Control program Check control program
has detected an for bypass or overridden
alarm condition. points or other abnormal
condition.
— — — Blue — Control program Identify the fault
steady has detected an condition by using the
alarm condition. control program.
Alarm contacts also Correct the condition.
indicate an alarm
(open contacts).
— — Red — Red Normal operation, Correct the
steady steady but the ambient environmental problem
temperature is too or the controller may fail
high (greater than prematurely.
140°F/60°C).
a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


Main Processor Indicators 219

MP Communication Indicators
The MP communication indicators identify the type of communication occurring on the
controller. The TX light indicates the MP is transmitting a message and the RX light indicates
the MP is receiving a message.

IÚO Bus Comm Bus Serial TriStation


RX/TX RX/TX RX/TX Link RX/TX Description
Green —a — — — Normal response. MP is polling and
blinking sending responses to the I/O
modules.
— Green — — — Normal response. MP is polling and
blinking sending responses to the CMs.
— — Green — — Normal response. MP is polling and
blinking sending responses to the Modbus
master.
— — — Green Green MP is communicating with TriStation
steady blinking 1131 software.
— — — No — MP is not communicating with
light TriStation 1131 software or a network
hub.
Note: The hub or Ethernet card in the
PC running the TriStation 1131
software has a link indicator that
shows whether a hardware connection
has been established with the MP.

a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


220 Chapter 4 Fault and Alarm Indicators

Communication Module Indicators


This section describes indicators for the CM, including:
• CM Status Indicators on page 221
• CM Communication Indicators on page 222

Figure 103 CM Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


Communication Module Indicators 221

CM Status Indicators
The CM status indicators identify the processing state for the CM.
A fault light indicates that the processor has an internal fault.

Normal States

Pass Fault Active Lock Description Action


Green No Green No Module is operating Normal status. No action is
steady light steady light normally. required.
Green No Green No Module is downloading Normal status. To cancel,
steady light blinking light firmware. pull module then re-seat
module.
Green No No light No Module is operating
steady light light normally. Possible
conditions include:
Control program has not Load control program.
been loaded into the MP.
Control program has been Start control program.
loaded into the MP, but has
not been started up.
Module has just been Wait for module to be
installed and is currently educated.
being educated by the other
MP Modules.

Fault States

Pass Fault Active Lock Description Action


No Red No light No Module may have failed. See mode indicator status for
light steady light Possible conditions include: power-up states.
Module may be in the If the Pass indicator does not
process of power-up self- go on within five minutes,
test. replace module.
No Red Green No Module has detected a Module is operational, but
light steady steady light minor error. should be replaced.
No Red —a Red Module is unlocked from the Lock module.
light steady steady baseplate.
Green Red — — Indicators/signal circuitry Replace the module.
steady steady on the module are
malfunctioning.
No No — — Indicators/signal circuitry Replace the module.
light light on the module are
malfunctioning

Planning and Installation Guide for Trident v2 Systems


222 Chapter 4 Fault and Alarm Indicators

a. This symbol ( — ) means the indicator is not important for this condition.

CM Communication Indicators
The CM communication indicators identify the type of communication occurring on the
controller. The TX light indicates the CM is transmitting a message and the RX light indicates
the CM is receiving a message.

Serial 1 Serial 2 Serial 3 Net 1 Net 2


RX/TX RX/TX RX/TX Link RX/TX Link RX/TX Description
Green —a — — — Normal response. CM is
blinking communicating with the
attached Modbus
master/slave device.
— Green — — — Normal response. CM is
blinking communicating with the
attached Modbus
master/slave device.
— — Green — — Normal response. CM is
blinking communicating with the
attached Modbus
master/slave device.
— — — Green Green — — CM is communicating
steady blinking with TriStation 1131
software or with an
Ethernet device through
the Net 1 port.
— — — — — Green Green CM is communicating
steady blinking with TriStation 1131
software or with an
Ethernet device through
the Net 2 port.

a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


Analog Input Module Indicators 223

Analog Input Module Indicators


This section describes the AI Module indicators including:
• AI Status Indicators on page 224
• AI Field Power Indicator on page 225

п­­ øÙ®»»²÷
ÐßÍÍ
ß× Í¬¿¬«­ ÚßËÔÌ
Ú¿«´¬ øλ¼÷
ײ¼·½¿¬±®­ ßÝÌ×ÊÛ ß½¬·ª» øÙ®»»²÷
Ú×ÛÔÜ ÐÉÎ
Ú·»´¼ б©»®
ײ¼·½¿¬±® Ú·»´¼ б©»® øÇ»´´±©÷

ÔÑÝÕ
˲´±½µ øλ¼÷

ß×

Figure 104 AI Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


224 Chapter 4 Fault and Alarm Indicators

AI Status Indicators
The AI status indicators identify the processing state for the AI Module.
A fault light indicates that the module has an internal fault.

Normal States

Pass Fault Active Lock Description Action


Green No Green No Module is operating normally. No action is required.
steady light steady light

Fault States

Pass Fault Active Lock Description Action


Green No No No Module may have failed. If this is the hot-spare
steady light light light Possible conditions include: module, no action is
Control program has not required.
been loaded into the MP.
Control program has been If the module is active,
loaded into the MP, but has replace module.
not been started up.
Module has just been
installed and is currently
running start-up diagnostics.
The other module is active.
No Red —a No Module may be in the If the Pass indicator does not
light steady light process of power-up self- go on within five minutes,
test. replace the module.
Module has detected a fault. Module is operational, but
should be replaced.
Module has detected Check sensor signal
marginal input voltage in a strength.
steady-state condition. Check sensor positioning.
— — — Red Module is unlocked from the Lock module using a
steady baseplate. 1/4-inch flat-blade
screwdriver.
Green Red — — Indicators/signal circuitry Replace the module.
steady steady on the module are
malfunctioning.
No No — — Indicators/signal circuitry Replace the module.
light light on the module are
malfunctioning

a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


Analog Input Module Indicators 225

AI Field Power Indicator


The AI field power indicator is lit when a field power problem has occurred.

Field
Description Action
Power
Yellow Field power or logic power from one To isolate the missing power source, use the
steady or more of the redundant sources is TriStation 1131 software.
missing. To determine the actual state, use a voltmeter,
then correct the problem in the external circuit.
If these steps do not solve the problem, replace
the module.

Planning and Installation Guide for Trident v2 Systems


226 Chapter 4 Fault and Alarm Indicators

Analog Input/Digital Input Module Indicators


This section describes the AI/DI Module indicators including:
• AI/DI Status Indicators on page 227
• AI/DI Field Power Indicator on page 228

п­­ øÙ®»»²÷
ÐßÍÍ
ß×ñÜ× Í¬¿¬«­ ÚßËÔÌ
Ú¿«´¬ øλ¼÷
ײ¼·½¿¬±®­ ßÝÌ×ÊÛ ß½¬·ª» øÙ®»»²÷
Ú×ÛÔÜ ÐÉÎ
Ú·»´¼ б©»®
Ú·»´¼ б©»® øÇ»´´±©÷
ײ¼·½¿¬±®
ï
î
í
ì
ë
ê
é
б·²¬­ è
ײ¼·½¿¬±®­ ç
ï›ïê Ü× Ð±·²¬­ øÙ®»»²÷
ïð
ïï
ïî
ïí
ïì
ïë
ïê

ÔÑÝÕ
˲´±½µ øλ¼÷

ß×ñÜ×

Figure 105 AI/DI Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


Analog Input/Digital Input Module Indicators 227

AI/DI Status Indicators


The AI/DI status indicators identify the processing state for the AI/DI Module.
A fault light indicates that the module has an internal fault.

Normal States

Pass Fault Active Lock Description Action


Green No Green No Module is operating normally. No action is required.
steady light steady light

Fault States

Pass Fault Active Lock Description Action


Green No No No Module may have failed. If this is the hot-spare
steady light light light Possible conditions include: module, no action is
Control program has not required.
been loaded into the MP.
Control program has been If the module is active,
loaded into the MP, but has replace module.
not been started up.
Module has just been
installed and is currently
running start-up diagnostics.
The other module is active.
No Red —a No Module may be in the If the Pass indicator does not
light steady light process of power-up self- go on within five minutes,
test. replace the module.
Module has detected a fault. Module is operational, but
should be replaced.
Module has detected Check sensor signal
marginal input voltage in a strength.
steady-state condition. Check sensor positioning.
— — — Red Module is unlocked from the Lock module using a
steady baseplate. 1/4-inch flat-blade
screwdriver.
Green Red — — Indicators/signal circuitry Replace the module.
steady steady on the module are
malfunctioning.
No No — — Indicators/signal circuitry Replace the module.
light light on the module are
malfunctioning

a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


228 Chapter 4 Fault and Alarm Indicators

AI/DI Field Power Indicator


The AI/DI field power indicator is lit when a field power problem has occurred.

Field
Description Action
Power
Yellow Field power or logic power from one To isolate the missing power source, use the
steady or more of the redundant sources is TriStation 1131 software.
missing. To determine the actual state, use a voltmeter,
then correct the problem in the external circuit.
If these steps do not solve the problem, replace
the module.

Planning and Installation Guide for Trident v2 Systems


Analog Output Module Indicators 229

Analog Output Module Indicators


This section describes the AO Module indicators including:
• AO Status Indicators on page 230
• AO Field Alarm Indicator on page 231

Figure 106 AO Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


230 Chapter 4 Fault and Alarm Indicators

AO Status Indicators
The AO status indicators identify the processing state for the AO Modules. A fault light
indicates that the module has an internal fault or is missing field power.

Normal State

Pass Fault Active Lock Description Action


Green No Green No Module is operating normally. No action is required.
steady light steady light

Fault States

Pass Fault Active Lock Description Action


Green No light No No Module may have failed. If this is the hot-spare
steady light light Possible conditions include: module, no action is
Control program has not required.
been loaded into the MP.
Control program has been If the module is active,
loaded into the MP, but has replace module.
not been started up.
Module has just been
installed and is currently
running start-up diagnostics.
The other module is active.
No light Red —a No Module may be in the If the Pass indicator
steady light process of power-up self- does not go on within
test. five minutes, replace the
module.
Field power is missing, if Restore field power and
field power light is also on. reseat the module.
Module has detected a fault. Module is operational,
but should be replaced.
Module has detected Check sensor signal
marginal input voltage in a strength.
steady-state condition. Check sensor
positioning.
— — — Red Module is unlocked from the Lock module using a
steady baseplate. 1/4-inch flat-blade
screwdriver.
Green Red — — Indicators/signal circuitry Replace the module.
steady steady on the module are
malfunctioning.

Planning and Installation Guide for Trident v2 Systems


Analog Output Module Indicators 231

Pass Fault Active Lock Description Action


No light No light — — Indicators/signal circuitry Replace the module.
on the module are
malfunctioning
a. This symbol ( — ) means the indicator is not important for this condition.

AO Field Alarm Indicator


The AO field fault indicator is lit when a field power problem has occurred.

Field
Description Action
Alarm
Yellow Field power or logic power from one or To isolate the missing power source, use the
steady more of the redundant sources is TriStation 1131 software.
missing or a field error is detected. A To determine the actual state, use a voltmeter,
field error may be an open load or an then correct the problem in the external circuit.
out-of-compliance error.
If these steps do not solve the problem, replace
the module.

Planning and Installation Guide for Trident v2 Systems


232 Chapter 4 Fault and Alarm Indicators

Digital Input Module Indicators


This section describes the DI Module indicators including:
• DI Status Indicators on page 233
• DI Field Power Indicator on page 234
• DI Point Indicators on page 234

DI 24v

Figure 107 DI Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


Digital Input Module Indicators 233

DI Status Indicators
The DI status indicators identify the processing state for the DI Module.
A fault light indicates that the module has an internal fault.

Normal State

Pass Fault Active Lock Description Action


Green No Green No Module is operating normally. No action is required.
steady light steady light

Fault States

Pass Fault Active Lock Description Action


Green No No No Module may have failed. If this is the hot-spare
steady light light light Possible conditions include: module, no action is
Control program has not required.
been loaded into the MP.
Control program has been If the module is active,
loaded into the MP, but has replace module.
not been started up.
Module has just been
installed and is currently
running start-up diagnostics.
Other module is active.
No Red —a No Module may be in the If the Pass indicator does not
light steady light process of power-up self- go on within five minutes,
test. replace the module.
Module has detected a fault. Module is operational, but
should be replaced.
— — — Red Module is unlocked from the Lock the module using a
steady baseplate. 1/4-inch flat-blade
screwdriver.
Green Red — — Indicators/signal circuitry Replace the module.
steady steady on the module are
malfunctioning.
No No — — Indicators/signal circuitry Replace the module.
light light on the module are
malfunctioning
a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


234 Chapter 4 Fault and Alarm Indicators

DI Field Power Indicator


The DI field power indicator is lit when a field power problem has occurred.

Field
Description Action
Power
Yellow Field power or logic power from To isolate the missing power source, use the
steady one or more of the redundant TriStation 1131 software.
sources is missing. Correct the problem in the field circuit.
If these steps do not solve the problem, replace the
module.

DI Point Indicators
The DI point indicators identify whether the point is energized or not energized.

Point (1-32) Description


Green steady Field circuit is energized.
No light Field circuit is not energized.

Planning and Installation Guide for Trident v2 Systems


Digital Output Module Indicators 235

Digital Output Module Indicators


This section describes the DO Module 3401 and SDO Module 3411 indicators, including:
• Status Indicators on DO and SDO Modules on page 237
• Power/Load Indicator on DO and SDO Modules on page 238
• Point Indicators on DO and SDO Modules on page 238
• Point Indicators on DO and SDO Modules on page 238
• Load Indicators on SDO Modules on page 238

п­­ øÙ®»»²÷
ÐßÍÍ
ÜÑ Í¬¿¬«­ Ú¿«´¬ øλ¼÷
ÚßËÔÌ
ײ¼·½¿¬±®­ ßÝÌ×ÊÛ ß½¬·ª» øÙ®»»²÷
ÐÉÎñÔÑßÜ
Ú·»´¼ б©»®
б©»®ñÔ±¿¼ øÇ»´´±©÷
ײ¼·½¿¬±®
ï
î
í
ì
ë
ê
é

б·²¬­ è
ï ïê б·²¬­ øÙ®»»²÷
ײ¼·½¿¬±®­ ç
ïð
ïï
ïî
ïí
ïì
ïë
ïê

ÔÑÝÕ
˲´±½µ øλ¼÷

ÜÑ îìª

Figure 108 DO Module 3401 Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


236 Chapter 4 Fault and Alarm Indicators

п­­ øÙ®»»²÷
ÐßÍÍ
ͬ¿¬«­ Ú¿«´¬ øλ¼÷
ÚßËÔÌ
ײ¼·½¿¬±®­ ßÝÌ×ÊÛ ß½¬·ª» øÙ®»»²÷
ÐÉÎñÔÑßÜ
Ú·»´¼ б©»®
б©»®ñÔ±¿¼ øÇ»´´±©÷
ײ¼·½¿¬±®
ï
î
í
ì
ë
ê
é

б·²¬ ÐÑ×ÒÌÍ
è
ï›ïê б·²¬­ øÙ®»»²÷
ײ¼·½¿¬±®­ ç
ïð
ïï
ïî
ïí
ïì
ïë
ïê

ÔÑÝÕ
˲´±½µ øλ¼÷

ï
î
í
ì
ë
ê
é

Ô±¿¼ ÔÑßÜ è
ï›ïê б·²¬­ øÇ»´´±©÷
ײ¼·½¿¬±®­ ç
ïð
ïï
ïî
ïí
ïì
ïë
ïê

ÍÜÑ îìÊÜÝ

Figure 109 SDO Module 3411 Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems


Digital Output Module Indicators 237

Status Indicators on DO and SDO Modules


The status indicators on the DO and SDO modules identify the processing state.
A fault light indicates that the module has an internal fault. If you have a field fault and a
module fault, resolve the field fault first.

Normal State

Pass Fault Active Lock Description Action


Green No Green No Module is operating normally. No action is required.
steady light steady light

Fault States

Pass Fault Active Lock Description Action


Green No No No Module may have failed. If this is the hot-spare
steady light light light Possible conditions include: module, no action is required.
Control program has not
been loaded into the MP.
Control program has been If the module is active,
loaded into the MP, but has replace module.
not been started up.
Module has just been
installed and is currently
running start-up diagnostics.
Other module is active.
No Red —a No Module may be in the If the Pass indicator does not
light steady light process of power-up self- go on within five minutes,
test. replace the module.
Excessive load current Correct field fault condition.
required.
Module has detected a fault. Module is operational, but
should be replaced.
— — — Red Module is unlocked from the Lock module using a
steady baseplate. 1/4-inch flat-blade
screwdriver.
Green Red — — Indicators/signal circuitry Replace the module.
steady steady on the module are
malfunctioning.
No No — — Indicators/signal circuitry Replace the module.
light light on the module are
malfunctioning
a. This symbol ( — ) means the indicator is not important for this condition.

Planning and Installation Guide for Trident v2 Systems


238 Chapter 4 Fault and Alarm Indicators

Power/Load Indicator on DO and SDO Modules


The power/load indicator on DO and SDO modules is lit when a power/load problem has
occurred.

Power/Load Description Action


Yellow For at least one point, the To isolate the suspected point or determine the
steady commanded state and the commanded state of the point, use the TriStation
measured state do not agree, 1131 software.
logic power for one or more of To determine the actual state of the output, use a
the redundant sources is voltmeter, then correct the problem in the external
missing, or field power for circuit.
one or both redundant
sources is outside the Verify that load current is within product
operational range. specification.
If these steps do not solve the problem, replace the
module.

Point Indicators on DO and SDO Modules


The point indicators on DO and SDO modules identify whether the point is energized or not
energized.

Point (1-16) Description


Green steady Field circuit is energized.
No light Field circuit is not energized.

Load Indicators on SDO Modules


The load indicators on SDO modules identify whether there is a fault in the field circuitry.

Point (1-16) Description Action


Yellow steady A fault is detected in the field circuit or Check for shorted or open loads and fix.
the load is not connected to one or Connect all output points that are not
more output points. connected.
Use the TriStation 1131 software to set the
DO Point Options to Non-Supervised for
unused points and points being used to
drive loads that do not draw the
minimum current required for
supervision.
No light The field circuit is operating properly. No action is required.

Planning and Installation Guide for Trident v2 Systems


Pulse Input Module Indicators 239

Pulse Input Module Indicators


This section describes the PI Module indicators including:
• PI Status Indicators on page 240
• PI Field Fault Indicator on page 241
• PI Point Indicators on page 241

Figure 110 PI Front Panel Indicators

Planning and Installation Guide for Trident v2 Systems

You might also like