You are on page 1of 45
Appendix A ‘Appendix Ato this documents included for exolanatory purposes only ‘and does not form part of the requirements. The bold-ace reference >humbers that introduce each item apply tothe requirementin the Code ‘Symbols and Abbreviations “The folowing symbols and abbreviations are used inthe clagrams of Appendix A. 86 Bathroom Group BT Batiub CO cleanout DF Drinking Fountain FAL Fresh Air inet FD Floor Drain HO Hub Drain LAV Lavatory Basin LT Laundry Tray (Tub) WC Water Closet A-4.1.3.2. Plumbing System. The definition of plumbing is defined in the current Bullding Code Act, 1982. Each of the three systems appearing in Part 1 definiton are themselves defines, with the fend result that plumbing system encompasses all elements, (Other piping systems as listed below are exclided from plumbing system since the definition of water system limits the system tothe point of juncture with outlets, fixtures, etc. Similarly, a drainage system stats atthe fixture oF plumbing apaliance & drains, Plumbing sytem means a system of connecting piping, fitings, valves, feauipment, titres and appurtenances contained in plumbing, but dows notinctude (@)_a system of piping, () forthe space heating in which water is used as a medium to transfer heat, (i) in which liquids or vapours are circulate forthe purpose of cooling oF refrigeration, (ii) trough which aris passed forthe purpose of contraing the temerature, humidity or motion of air passing through the eystem, (iv) that conveys water forthe purpose of providing water ornutilents to soll (©) that conveys water forthe purpose of landscaping oF for the care of animals, birds oF fish, (i) that ransmits force by means of water or by means of aliquid other than water in which water is used for cooling (vi) that conveys liquids for the purpose of melting ice oF (vi) that used water in the conveyance of flammable gas or fuel or (6) well, a well pump installed forthe purpose of conveying water trom a wel, a pressure tank and pump ifthe tank and Pump are combined as a unt the piping between any well pump and the well, th piping betwoen a well pump and a pressure tank that i installed separate fom the pump and the connection ofthe piping fo such pressure tank, and when thers no well pump. any piping connected tothe wil for a sistance of tree feet fom the outside ofthe well Anta? ‘BACKFLOW PREVENTER Normal Flow - Checks Open - Vent Closed With flow through valve, primary check (1) opens away from siaphragm (2). Atmospheric vent remains closed by deflection of slaphragm seal (2). Secondary check (4) opens away from dovnsteam seat (5) permiting flow of water through the valve Negative Supply Pressure - Checks Closed - Vent Open 2 013 56 4 \With a back-siohonage condition created, secondary check (4) ‘seals lighty against downstream seat (5). Primary check (1) seals tightly against diaphragm (2). Atmospheric vent (8) is now open permiting air to enter air break chamber. In the event of fouling of downstream check valve, leakage would bbe vented to atmosphere through the vent port thereby safeguarding the potable water system from contamination as Anta? BACK SIPHONAGE PREVENTER 1) Normal operation with valve open ute, Inlet ') Backflow condition with valve closed. Open to outiet ‘Atmosphere Intet a4 Ane = ——— Faves teat erat — { Revered vite t Ope {or Low Pressure) When there is low pressure or the water is shut-off and the riser is raining, non-potable water is fed tothe lower fixtures form the extra hose fn the Launcry Tray (Tub) faucet, the ilvalve below the water level inthe toilet tank or the handheld hose left in a bathtub filed with water. as Ane BRANCH VENT, BACK VENT, CONTINUOUS VENT Continuous Inca Vent AA aA2 DRAINAGE SYSTEM asi AA aA2 ‘VENTING SYSTEM asi Ane DEVELOPED LENGTH Developed length means the length along the centre line of the pipe and fitings, ‘as Developed length equalsA+8+C+D ——ornocas Developed lenath equals A+B +C+D ar Ane DRAINAGE AND VENTING SYSTEMS Je f Ee oe _| 2 as FIXTURE OUTLET PIPE AND TRAP ARM. Lavatory Basin Water Closet we we SF Trap Arm ae S Cour penne L lh _| . Fe \ reneene ~ cleanout HEADER Upper end of header terminates into open air Upper end of header terminates into open air Header Hl tet rte ‘Although a header is similar to a branch vent, it serves the special purpose of connecting the tops of stack vents or vent stacks. Use Table 75.8.3. for sizing. aso Arana NoNALLY HORZOATA AND NOMNALLY VERTICAL vet a s me os og slo we Vota oonn Jf 4 Nominal Horizontal Nominally Vertical Ane OFFSET ELEVATION VIEW : i PLAN VIEW (Horizontal Pipe) 4 Claret we Anz Ane Corporation ‘Stop Public Water Main PLUMBING SYSTEMS Propery | Bulking Contl Vavo tine | (Stop and Waste) Expansion i Corporation 14m. teem Wa | cag Se” | i See PubkeSantay |. santa Biting Sever | Public Storm + Storm Buling Sewer! Sewer ' Venting System Water Waste Distribution Stack Piping Sanitary Building Drain | Stack Vented ~ {Bathroom Group ester 1 jae some a 1] 442 tL ae |p |) Ff Ne wy | ea PT ah Grane Per Foundation iam ome stom dng Orain 713RO6B ATASA. ‘SERVICE PIPING (a) Permitted — — — — Property tine — — — YI | | | | | | | | seers | Ly} jd Sanitary Building Sewer Public Water Public Sanitary Main Sewer (0) Nat Permitted - services shall not cross adjacent Property Lines nor serve more than one auxliary building. — — — Property tine — — — ee ee | jy | | friar euatna seme vnwrsenicerpe _| Public wate? ube Sana ‘Maln ‘Sewer " 4 ATASA. ‘SERVICE PIPING (6) Permitod Semi-Detached Row Housing Water Service Pipe fa Sanitary Building Sewer Public Water Public Sanitary Main Sewer (4) Permitted Semi-Detached Row Housing + Water Service Pipe |— Sanitary Bullting Sewer Publi Water Public Sarita Main ‘Sewer ‘The layout as shown in diagram (4) above may require special arrangements ‘ensure that access can be provided to all part ofthe service pipes. 47.22.51) WATER CLOSET BOWL CONTOURS. {2} Regular Rim Contour for Water Closot Bowls 18mm Diameter witout { Counters 13mm Diameter without Counters ati A223. SHOWERS {a} Permitted - Floor Slopes to Gutter away ram other showers, with a maximum of Six Individdalized Shower Heads per Drain Shower! Floor Drain in Gutter F-4—4—4—-f-F-F Aaa EDA me ALATA big Me FR] - | eg a Foor Stopes} ago bo anor ome 4 I| = below level of Building Drain oF ve ‘Sewage Tank ce aoe (sum) ves susmersbie heb veces Ejector Pump ——tiar_| e — Vere a sump otnkrcsives sewage thal be watertight, air tight and shall bo vented aaT a8 A-7.4.6.4(1) Backwater Valve or Gate Valve. The instalation fof a backwater valve or gate valve in a building drains or ina building ‘sewer may have proven acceptable on the basis of past performance in ‘some locales, ana their acceplance under Subsection 2.7.2 ofthe Code may be warranted. In adgional,fullport backwater valve have been accepted by other provinces in Canada, A-7.4.6.4.{5) Protection from Backflow Caused by ‘Surcharge. Those requirements are intended to apply when in the ‘opinion of the local authority having jurisdiction there is danger of backup ‘tom a publie sewer ATATAI9) ‘CLEANOUTS FOR FOOD DISPLAY DRIP PIPES. < LN sents 7 oe rer A-7.4.7-1.{10) Cleanouts for Fixture Drains. A trap cleanout lug is not accoptable as a cleanout for the fature drain; hence; either a separate cleanout ora trap with a removable trap dip must be installed. AAT, CLEANOUT CONNECTIONS (2) Permitted - Horizontal Change in Direction (PLAN VIEW) cma be 3 me | (©) Not Permitted - Horizontal Change in Direction (PLAN VIEW) i (6) Permitted - Horizontal Change in Direction (eLevarion view (PLAN view) R Va " ete Pecmitted angle of connections to clean-outs as per 7.4.7.4.(4) aso VENTING NOT REQUIRED {2} Removing Vent Pipes for Floor Drains inch Soi ‘Stack Extending to Open Air 3 inch ‘cleanout inch Sanitary Building Drain Primer ‘inch or Larger Floor Drain 450mm ~ Foxture Drain ean {(b} Removing the vent from a Floor rain () Connect to @ Horizontal Drainage Pipe that terminates in a 3inch Stack (i) Minimum 3.inch in Size (i Minimum Lenath 450mm \ VJ Let maximum Fat etre Drain Diameter (¥) Minimum Siope for 3inch 4 in 60 (7.4.8.4.(1) <-—— {toa developed length of 3.6 m) c (ui) Mimimum Siope for inch + in 60 (to a developed length of 4.8m) c asa ATS. oy A a <— QQ. & “SS veetng ot © Goes eZ Re A SS. a LE Z ZO << 7.1.6.1(2) A combined building drain ora combined building sewer shall not be instal. ass ATSAA(4) VENTING NOT REQUIRED (©) Indirect Drainage System (Less than three storeys high) ‘or traps which form part of an indirect crainage system, ~ air Break ™ Hub Drain tobe ventes in appropriate manner. as6 SIZING OF WET VENTS USING TABLE 7.5.81. “The fiures connected to the wet vent above the most downstream fixture must not exceed a maximum of2 fixture units fora minmum 1 1/2-inch wet vert “The wet vent portion must not reduc in size, (2) Bathtub being Wet Vented by a Lavatory Basin 1% | Continuous | —_.—S_—-vent = 13" Wet QS | ent — (2F.U.max) 2 fixture drain - diameter minimum (b) Shower being Wet Vented by a Lavatory Basin 4 VY ron — 18 Wet Vent (2 F-U. max.) ‘SANITARY — TEE (TY) ~ ‘The downstream trap arms) may connection vertically or horizontally to the wet vent withthe wet vent ending atthe most downstream fixture rap arm The most downstream trap arm is not included in the total fixture unis of the wet vent ast SIZING OF WET VENTS USING TABLE 7.5.81. (6) Bathtub being Wet Vented by two Dual Vented Lavatory Basins 1% ~ Continuous Dual ‘Vent 1 Wet Vent. —t (FU. max) ae 500mm Maximum © (@) Floor Drain being Wet Vented by a Kitchen Sink er 1% ClO — continuous roomy | ‘Vent 1% Wet ro Vent o (me The most downstveam trap arm is notinckided in the total fixture units of the wet vent ‘A Brinch wet vent can have 12 fixture units upstream ofthe 3-inch p-trap (oor dain) Asti SIZING OF WET VENTS USING TABLE 7.5.81. “The fiures connected to the wet vent above the most downstream fixture must rot exceed a maximum of 4 fixture units for a minmum 2-inch wet ve “The wet vent portion must not reduc in size, (@) A Lavatory Basin and a Bathtub wet venting through a Shower, ' 1" | _Continious 7 vert iv 1 | Zwet . vert p—urtins ‘rax) SANITARY TEE (TY) ~ (0) Shower being Wet Vented by a Klchen Sink wih a Lavatory Basin Separately Vented ve ‘ature ~ continuous (2FUmaK), + Vent NS coven re — Vent SANITARY _ aru, mm TEE (TY) — J 2 7.52.1.) Any separately vented branches or fixture drains connecting to the wet vent on the same storey must not exceed a total of 2 foture units. A752.4.(1) SIZING OF WET VENTS USING TABLE 7.5.81. “The fixtures connected to the wet vent above the water closet must not ‘exceed a maximum of 3 fixture units for a minmum 2-inch wet vent. “The wet vent portion must not reduce in size, {©} Water Closet boing Wet Vented by a Lavatory Basin ae Continuous Vent ‘Wet Venting Fixture must eran trough a Continuous Vent ~ vt Yo wm — a 3 yoxiram () ALavatory Basin and a Kitchen Sink Wet Venting through a downstream Water Closet 1% Lye Continous eet (SFU. max) Wet Vent Connection to rormesee ‘Vertical Leg Astv ASA) SIZING OF WET VENTS USING TABLE 7.5.81. (0) A Lavatory Basin and a Bathtub Wet Venting through a downstream Water Closet, Lo continous i Ver — wo | | CI om \¢ i raa/ Nie (b)_ Dual Vented Lavatory Basins Wet Venting a Water Closet 1" Continuous Vent ‘The bathtub exceeds tho limit of 3 fixture units for a 2-inch wet vent and ‘must connect downstream of the Wet Vent and be individually vented as AT5.24.(1).(b), & (e) ‘WET VENTING A RESIDENTIAL BATHROOM GROUP (FORMERLY MODIFIED STACK VENTING, A FORM OF STACK VENTING) The fixtures connected to the wet vent above the water closets) must (i) not be larger than 2-inch (except for a floor drain as per 7.5.1 1.(3), (i) not exceed a maximum of 8 fixture units fora minmum 3-inch ‘wet vent, ane the size ofthe wet vent portion must not be reduced in size. “The numberof installed water closets in not greater than two, connected at the same level toa vertical part ofthe stack and must be downstream of all other fixtures. L ' ent EP aaa in| : 1 — F true i dai a 1 L conta 5 “ NS | com eC +i fixture dean ASB ATS2A.(1()- WET VENTING (FORMERLY STACK VENTING) (@) Vertical Stack Vent (©) Horizontal Contivation of the Sol Stack. eelaaaef ‘natty verte. ‘Any fixture connected downstream ofthe Wet Vented (Stack Vented) ‘Water Closet must be individually vented. ATS24.(1). SINGLE STOREY WET VENTING (FORMERLY MODIFIED STACK VENTING) Each floor level contains a water closet, bathtub, lavatory anda kitchen sink a : a Ase as Jae Table 7.58.3. Sizing Branch Vents, Headers, Continuous Vents and Circuit Vents by anticipating 3m per Noor and calculating the total fixture uns, Asti (m, & MULT/-STOREY WET VENTING Stack Vent 2incnsie [4 orless ‘Wet Vented portion must \ be ful size twoughout 1. Maxirum Ofet (retambezincner pM Niaximum discharge per storey of 4 fixture units above first storey less ~ ()- 25m for larger than 2inch 22. No connection permited n offset wet Venting ~ portion stats nero (ee table 75.8.1) \Whon the Wet Vent extends higher than four sloreys the Stack Vent ‘must extend through the roof the same size as the Wet Vent ast AT52.4.(1) MULT/-STOREY WET VENTING (&) Permitted saben 0) Not Permited — ' ' a oe Se Te) Rion lL DA cone tory ie AT52.4.(1) ‘CONNECTIONS TO DRAINAGE SYSTEM USING WET VENTING (2), Two Lavatory Basins, a Bathtub and a Shower Drain Wet Venting through a downstream Water Closet rod a ogee NI SK ran TeaROESN (©) A Lavatory Basin and a Siphon Jet Urinal Wel Venting through a Water Closet | stk | Nee Letcy | setae MP ‘Soak Ww waren) sore Bt en Not A601 AT52.4.(1) ‘CONNECTIONS TO DRAINAGE SYSTEM USING WET VENTING (6) ALavatory Basin, a Separately vnted Kitchen Sink and a Bathtub Wet Venting through a downstream Wator Close. a see AS | nia Sonn tare | ene = ‘Waste Pine \ Le i) seperate fe (4) Dual Lavatory Basins, two Shower Drains with two shower valves each and a Separately vented Lavatory Basin Wel Venting through a downstream Water Closet, Se en) Tewerats tame | me ey ane ml Leeos ee when vist bet ne aro) AT52.4.(1) ‘CONNECTIONS TO DRAINAGE SYSTEM USING WET VENTING (©) An ico Box, a Lavatory Basin, and a separately vented Bar Sink ‘Wet Venting through a downstream Commercial Dishwasher Teanga bem aaa = a | mg Ene Wo jects em tse | ‘Soil or Waste Staci? —< NY ! veg | eusit ctr Bae ~ sft cet Vesrive an some ( ALavatory Basin, a separately vented Kitchen Sink, and a Bathtub ‘Wet Venting through a downstream Water Closet the sept vera | emo use Scena HOT”— Uanny Pron bots nen tae . ing vee. i a) ' | conto Wl porn i ae 1 eten saan mS ire et too Stoney Varod onieckt ana) AT52.4.(1) ‘CONNECTIONS TO DRAINAGE SYSTEM USING WET VENTING (9) A Lavatory Basin and a Bathtub Wet Venting through a downstream Water Closet, conmous | ver | i (h) Dual Lavatory Basins and a Floor Drain Wet Venting ‘through a Bath Tub. (fim Uns ‘ron pee) Aso areas. ecu vemc | cnet si 1 ae one i i k - _ Ee ggscoc00 “The Circuit Vent must connect in front ofthe most upstieam fixture ‘A maximum of 8 fixtures between vents ‘A Relief Vent must be installed infront of the most downstream Circuit Vented fixture. A Stack Vent may serve as a Relief Vent Fixtures 2.nch and larger require a minimum 3-inch horizontal branch, Foaures smaller than 2-inch must be separately vented or require a ‘separate minumum 2-inch horizontal branch. Asti AT53.4.(2) ‘ORCUTT VENTING (0) Trap sizes smaller than 2-inch permitted winen separately vented oe, ini (0) One Circuit Vented branch with 2nch and larger traps, a second separate Circult Vented branch with traps smaller than 2-inch, A753.1.44) CIRCUIT VENTING AND RELIEF VENTING (6) A Stack Vent (Wet Vent) with a maximum of 6 Fixture Units can ‘serve as a Relief Vent, sukvent | ete vot i WI seer (©) Accu Vor branch wih a Wet Veroa Waa Closet wae fo, | Ae vga] he Le fg erate) tecigarreervens ive ie {A Soil or Waste Pipe (being horizontal or vertical) having a hydraulic load ‘ot greater than 6 fixture units may act as araie vent for a branch thats being circuit vented. Ast A75.3.1.(4). & (5) CIRCUIT VENTING AND RELIEF VENTING (©) A Rotit Vents required since the Soll or Wasle Stack has discharge from more than 6 fixture unt. 4 Sree A torus wt SN ° (1) Not Permitted -& Soil Stack (or Waste Stack) acting as a Relit Vent rod ‘clout Vent - Bate Tre | ne ‘Sol or NO LAS waste Sack ne rma Sa NI CON Joe Joe eons ast AT53.145). COMBINED RELIEF VENTING (@) Not Permitted - Tho WYE fiting is nota symmetrical fiting and the Relief Ventis connected downstream. (©) Permitted - Symmeticaly connected Combined Relief Vent Le are vitae ge Eh eave | EE Tee see) | SyA4e ! q AS | ! Mu 1 Cheuk vent I S| Binh St | err ' ‘Con ‘A Soll or Waste Pipe (being horizontal or vertical having a hydraulic oad ‘not areater than 6 fisture units may act as a relief vent fora branch thats boing circuit vented. 62 AT53.146). ADDITIONAL CIRCUIT VENTING (@) Any change of direction grater than 45" tothe Circuit Vented branch requires an appropriatey installed Acditional Circuit Vent. stra be Choa ame (0) An Additional Circuit Vents required for every group of 8 or less Circuit Vente fixtures, Chavon ere she) | (iam AN | ere 7.8.7.3. Additional Citcil Vents and Reef Vents are sized by the trap arms connecting to the branch or one size smaller than the Circuit Vent, but need not be larger than 2-inch AT53.447). SIZING ADOMTIONAL CIRCUIT VENTS (6) Not Permitted - A Soil or Waste pipe serving as an Additonal Circuit Vent ee | ae cua vend es cat Wet Vent L* | veuven | gw we wen] Caahe ve ' we Js Jp lita! om LT Vee (@) An Additional Creat Vent is if there are more than & Circuit Vented fixtures between vents sorving the norizontal branch, bau T | ite, YX oN ‘A Soll or Waste pipe may serve as an Adkitional Cult Vent provised it Is sized as a wet vent and is 2inch minimum A621 AT534.(8). &7-5.7-3.1-(2) SIZING CIRCUIT, ADDITIONAL CIRCUIT AND RELIEF VENTS. (e}, Dual vented trap arms wih a maximum of 1.5 fixture units may connect ta the vorical section ofa Circuit, Additional Circuit or Reif vent in accordance with 75.4.5,(1) rat vot Laer. TA) feseen Sea ay V \ { gem: (f) One Circuit Vented branch witn2-inch and larger traps, a second separate Circuit Vented branch with traps smaller than 2-inch, | gf Ls BN | sete | NL ote ee we I os ‘The sizeof the Circut Vent is done using the size ofthe trap arm and Table 7.5.8.3. ‘The size of the Additonal Cicult Vent and Relief Ventis one size smaller than the sizeof the Circuit Vent AG2iv A7-54.2(3)8(8) (GREASE INTERCEPTOR INSTALLATION j SF reer, oe ‘tonto rh eomer 7.4.43.) AllGrease and Ol Interceptors require an intemal flow control and if the height ofthe discharge exceeds §-eet, a Secondary Flow Control is require (venting forthe Secondary Flow Control is determine by the manufacturer), ag 3 AT 55.28). & 75.5-3.(1)- ‘VENTING CORROSIVE PIPING, NEUTRALIZING TANKS AND DILUTING TANKS ‘feral Na) eres T KA LH ae <_| « u =D | eg OS ion Tank (large quantities Acid "of water) 1 evratzer \ tine ees) | 7.2.8.1.(2) The trap seal depth on fhtures draining to an acid waste system shall be a minimum of 50mm. 7.4.44.(1) A finture disharging corrosive or acid waste tothe sanitary system must connect using a trap or an indirect connection, a AT SAS. Asai ‘YOKE VENTS: AT SAA (OFFSET RELIEF VENT bar vee AM wey —T << ‘Ofieet Riel S| a tat mt vouih) ove ven Asi A-7-5.6.2.(1)8(2) VENT PIPE CONNECTION (2), Back Vent with Fiting 45° elbow above Horizontal Centre Line FITTING 45° ELBOW ~ Horizontal Cente Line vent sanary TEE (TY) "Pe satoee 7.5.2.1) Horizontal uns of Vent Pipe below the Flood Level Rim should be eliminated when structurally possible. (©) Connection of Bac Vent Pipe must be above horizontal conte & Vent Pigs Locations Horizontal Centre Line Fitings used to connect vent pipes to nominally horizontal sol or waste pipe are specified in Subsection 7.2.4 A756.3.(1) LOCATION OF VENT PIPES: {2} Change of Direction applies to tings between the P-Trap and the Vent \ | Vent Poo 4 60° pried penetration A ah santa ‘TEE (TY) (©) Five Rules between a P-Trap and its Protecting Vent () Max. Length 1500mm to 5m (oe Table 756.3) {) Minimum Length 2- Fixture Drain Diameters (Gi irirnurn Fall +n 80 0% 1.) T (900 74.8:1.(1) (iv) Maximum Fall iy & i uy 5 = 1 ees itn er {v) Maximum Change in Direction 135° (see A-1..5.2) =~ AT5.6.3.(2)8(3) LOCATION OF VENT PIPES, 45 4s | Aow SL vert j mi) pct > | eta Stack Water Closet Cumulative Change in Direction fora Water Closet ee Tro 7 T ‘e0R662 aso AIR GAP Flood Level Rim oT) ‘Supply a _- Minimum Level Fim Tank A-7.6.1.1. Potable Water Design Systems. The design procedures contained in Chapter 44 ofthe ASHRAE 1903 HVAC Applications Handbook in ASPE Data Book. Chapter 3 "Cold Water Systems", ASPE 3 (1988) and in [ASPE Data Book, Chapler 4 “Service Hot Waler Systems, ASPE 4 (1989) are considered good engineering practice inthe field of potable water systems. As an altemative, procedures contained in the Appentaix A of the National Plumbing Code of Canada 2008 are also acceptable. ar A-7.6.4.10.(1) Check Valves. When a check vale is required by Article 778.1.10., ora backllow preventer by Acie 7.8 2.3., ora pressure reducing valve by Article 78.3.3 of the OBC, protection against thermal expansion may 12.6) Releif Valves. A root valve shall not be routed through ‘oF discharge to an area where freezing temperatures may occur 2-7.6.1.13.(1) Wator Hammer Prevention. Wator hammeris a build-up of pressure in a length of horizontal or vertical pipe which occures when a valve or faucet is closed suddenly. The longer the pipe and the ~areater the water velociy the greaters the pressure exerted on te pipe, \whicn can be many times the normal static water pressure and be sufficient to burst the pipe. Ordinary kitcnen and bathroom faucets can be closed {quickly enough to cause water hammer with relatively low water pressure in the pipe. Means of preventing water ham vals or fauces, particularly where they are atthe end of long lengths of Pipes. This may be done by installing either water hammer arrester which fare manufactured forthe purpose of air chambers installed vertically that are fabricated ftom pieces of piping with a closed upper end and connected to the fed ofthe horizontal or vertical run of pipe. ‘The air chamiber should be 300 to 450 mm long it made from the same size pipe as the water pipe it serves. I'the chamber is made fram a pipe with larger dlameter than the water pipe, is length can be reduce accordingly. ‘Airchambers should be accessible ithe are the manufactured type withthe top ar valve and a stop-and-waste valve of are of the diaphragm iype. 4-7.6.2.12(1) Flushing and Disinfecting Water Service \Wator service pipes of 100 mm in size or larger shall be flushed and disinfected. Flushes sections shall be protected trom contamination. {After flushing is completes, water from the existing dstbution system shal be allowes to low ata controlled rate into the new piping. Liquid chlosine solution shal be intrauced so that the chlorine is distributed throughout the section being disinfected. The chlorine shall be applied so tat the chlorine concentration is 80 ma/L minimum throughout the section. Then the system shall be let charged with $0 mglL chlorine for 24 hours. Test the chiorine residual piping after 24 hours. If tests indicate a chiovine residual ofa least 25 mgiL, the section shall be fushed completely and recharged with water normal to the operation ofthe system. I the test dovs ‘not meet the requirements, the chlorination procedure shal be repeated unt Salisfactory results are obtained. After the system has been recharged, the disinfection procedure shall be repeated. The system shal not be put nto ‘operation until clearance has be given by the inspector appointed by the chiet bullaing official ATs

You might also like