Professional Documents
Culture Documents
DOI 10.1007/s40091-015-0094-5
ORIGINAL RESEARCH
Received: 3 November 2014 / Accepted: 7 June 2015 / Published online: 27 June 2015
The Author(s) 2015. This article is published with open access at Springerlink.com
Abstract A structure is subjected to progressive collapse Keywords Progressive collapse UFC ELS AEM
when an element fails, resulting in failure of adjoining Infilled walls Catenary action Collapsed area and
structural elements which, in their turn, cause further rotation limits
structural failure leading eventually to partial or total col-
lapse. The failure of a primary vertical support might occur
due to extreme loadings such as bomb explosion in a ter- Introduction
rorist attack, gas explosion and huge impact of a car in the
parking area. Different guidelines such as the General Several structural, progressive collapses took place
Services Administration (GSA 2003) and the Unified worldwide in the last decades. For example, in 1968, the
Facilities Criteria (UFC 2009) addressed the structural collapse of Ronan Building in East London took place due
progressive collapse due to the sudden loss of a main to a gas explosion on the 18th floor. In 1995, the Murrah
vertical support. In the current study, a progressive collapse Federal Office Building in Oklahoma City collapsed due to
assessment according to the UFC guidelines is carried out a terrorist bomb explosion on the ground floor. In 2001, the
for a typical ten-story reinforced concrete framed structure famous World Trade Center, New York, collapsed due to
designed according to codes [(ACI 318-08) and (ASCE planes impacting on the towers’ upper levels primary,
7-10)] for minimum design loads for buildings and other vertical structural (Shankar 2004). The status of reinforced
structures. Fully nonlinear dynamic analysis for the struc- concrete structures regarding their vulnerability to pro-
ture was carried out using Applied Element Method gressive collapse has become an important question.
(AEM). The investigated cases included the removal of a Guidelines for designing buildings against progressive
corner column, an edge column, an edge shear wall, collapse have been recently developed such as the General
internal columns and internal shear wall. The numerical Service Administration (GSA) (General Service Adminis-
analysis showed that simplification of the problem into 3D tration 2003) guidelines and the Unified Facilities Criteria
bare frames would lead to uneconomical design. It was (UFC) guidelines (Unified Facilities Criteria 2009). Those
found for the studied case that, the infilled masonry walls guidelines describe two main methods: direct one (Alter-
have a valuable contribution in mitigating progressive native Path Method) and indirect one (Tie Method). For the
collapse of the reinforced concrete framed structures. APM, guidelines allow neglecting slab contribution and
Neglecting these walls would lead to uneconomical design. rely only on framing actions of beams and columns.
Moreover, the contribution of nonstructural infilled walls is
not considered. The contribution of the infilled walls and
its effect during different load cases was studied in dif-
& Huda Helmy
dr_hudahelmy@yahoo.com
ferent researches. Hao et al. (2002) found that that the
infilled masonry affects not only the damage level but also
1
Applied Science Int., Cairo, Egypt the damage pattern of the frames. They showed that the
2
Department of Structural Engineering, Cairo University, empirical damage criterion for surface structures on an
Giza, Egypt underground explosion site is rather conservative for
123
234 Int J Adv Struct Eng (2015) 7:233–247
modern reinforced concrete structures, but it appears to be AP method, the structure should be capable of bridging
reasonable for the masonry infilled in the frame. (Razzaghi over missing structural elements. The TF approach
and Javidnia 2015) found that infilled walls play a vital role enhances continuity, ductility, and structural redundancy
in seismic performance of RC structures. (Tsai and Huang by requiring ‘‘ties’’ to keep the structure together in the
2013) found that the influence of the partially infilled walls event of an abnormal loading. In this study, only AP
differs from each type. They may increase the collapse method is of main concern.
resistance of the building frame under column loss but with According to UFC code, the load combination depends
decreased ductile capacity. From the structural aspect, with on the analysis type, static or dynamic. In the current study,
a constant opening rate of 60 %, the wing-type wall is a the analysis type is dynamic. For the dynamic analysis, the
better option than the parapet- and panel-type walls. The gravity load for the entire structure will be [(0.9 or
panel-type wall appears to be the worst choice since shear 1.2DL) ? (0.5LL or 0.2S)] (UFC 2009; ASCE/SEI 2005).
failure of their connected beam members may be induced. Lateral loads must be taken into consideration with a value
The authors have investigated the effect of slabs in an of [0.002 9 (sum of the gravity loads (DL ? LL))]. For
earlier study using the applied element method (Helmy each removal case, four analyses must be carried out. In
et al. 2012) and found out that the slabs’ contribution each analysis the lateral load will be applied in one of the
cannot be ignored; otherwise, this will lead to uneconom- main directions, i.e., east to west, west to east, north to
ical design. In the current study, the role of infilled walls is south and south to north. The analysis specified by UFC
investigated. The analysis is carried out two times, once assumes a sudden removal of a primary support like col-
using 3D skeletal frame excluding slabs and walls and the umns or walls. The removed column or wall has different
second one using 3D frame including nonstructural infilled locations depending on the structural system as shown in
walls. In the current study, a progressive collapse assess- Fig. 1. In case of a wall having ‘‘C’’ shape, either the flange
ment of a typical ten-story reinforced concrete structure or the web will be removed. The removal does not impede
was carried out according to the UFC guidelines. The into the connection or the horizontal elements that attached
structure was designed according to ACI 318-08 (ACI to the column at the floor level. This is to reserve the
2008) and ASCE 7-10 (ASCE 2010) guidelines. Fully continuity in the horizontal members. AP analyses is car-
nonlinear dynamic analysis for the structure due to removal ried out for parking story, story with public area, first story,
of a primary vertical element is carried out using the story directly below the roof, story at mid height and story
Applied Element Method (AEM). AEM is based on dis- above the location of a column splice or change in column
crete crack approach and is capable of following the size. For each analysis, the rotations of each of the beam,
structure’s behavior to its total collapse (Galal and El-Sawy column and joint must be checked. The beam rotation is
2010; Sasani and Sagiroglu 2008; Salem et al. 2011; Park checked using Table (4-1) in the UFC, while the column
et al. 2009; Helmy et al. 2009; Sasani 2008; Wibowo et al. and joint rotation is check using Tables (6–8) and (6–9) in
2009; Tagel-Din and Rahman 2004; Salem 2011). the ASCE 41 (ASCE 41 2006).
The objective of this study is to evaluate the contribution of Literature has shown that the Applied Element Method
the nonstructural infilled walls in prevention of the pro- (AEM) theory gives good estimations for large displace-
gressive collapse of multistory reinforced concrete struc- ments and deformations of structures undergoing collapse
tures designed according to the ACI 318-08 guidelines and
subjected to a loss of primary vertical support. The regu-
lation and guidance of the UFC guidelines are adopted for
the analysis.
UFC guidelines
123
Int J Adv Struct Eng (2015) 7:233–247 235
(Galal and El-Sawy 2010; Meguro and Tagel-Din (2000, For reinforcement springs, the model presented by
2001); Sasani and Sagiroglu 2008; Salem et al. 2011; Park Ristic et al. (Ristic et al. 1986) is used as shown in
et al. 2009; Helmy et al. 2009; Sasani 2008; Wibowo et al. Fig. 4c. The stiffness of reinforcement is calculated based
2009; Tagel-Din and Rahman 2004; Tagel-Din and Meguro on the strain from the reinforcement spring, loading status
2000a, b; Salem 2011). AEM is a modeling method (either loading or unloading) and the previous history of
adopting the concept of discrete cracking. As shown in steel spring which controls the Bauschinger effect. The
Fig. 2a, the structure in the AEM is modeled as an main advantage of this model is that it can consider easily
assembly of elements connected together along their sur- the effects of partial unloading and Bauschinger effect
faces through a set of normal and shear springs. The two without any additional complications to the analysis. The
elements shown in Fig. 2b are assumed to be connected by rupture strain of reinforcement is defined in ELS. For
normal and shear springs located at the contact points, steel springs, the relationship between shear stress and
which are distributed on the element faces. These con- shear strain is assumed to remain linearly and elastic as
necting springs represent the state of stresses, strains and shown in Fig. 4d.
connectivity between elements. They can represent both The solution for the dynamic problem adopts implicit
concrete and steel reinforcing bars. step-by-step integration (Newmark-beta) method (Bathe
Each single element has 6 df: three for translations and 1982; Chopra 1995). The equilibrium equations represent a
three for rotations. Relative translational or rotational dis- linear system of equations for each step. The solution of the
placement between two neighboring elements cause stres- equilibrium equations is commonly solved using Cholesky
ses in the springs located at their common face as shown in upper-lower decomposition. Once elements are separated,
Fig. 3. Two neighboring elements can be totally separated the stiffness matrix becomes singular. However, the sta-
once the springs connecting them rupture. Fully nonlinear bility of the overall system of equilibrium equations is kept
path-dependant constitutive models are adopted in the because of the existence of the mass matrix. Separated
AEM as shown in Fig. 4. For concrete in compression, an elements may collide with other elements. In that case, new
elasto-plastic and fracture model is adopted (Maekawa and springs are generated at the contact points of the collided
Okamura 1983) as shown in Fig. 4a. When concrete is elements. The bricks are simulated as built in reality, in a
subjected to tension, a linear stress strain relation ship is staggered pattern and connected by mortar as shown in
adopted until cracking of the concrete springs, where the Fig. 5.
stresses then drop to zero. The residual stresses are then
redistributed in the next loading step by applying the Applied element modeling of masonry
redistributed force values in the reverse direction. For
concrete springs, the relationship between shear stress and The anisotropy of material with brick units and mortar
shear strain is assumed to remain linear till the cracking of joints is considered in analysis as shown in Fig. 5. In spring
concrete. Then, the shear stresses drop down as shown in level, springs that lie within one unit of brick are termed as
Fig. 4b. The level of drop of shear stresses depends on the ‘Unit springs’. For those springs, the corresponding domain
aggregate interlock and friction at the crack surface. material is brick as isotropic nature and they are assigned to
Z Y Element 1 Element 2
Reinforcing
x
bar
123
236 Int J Adv Struct Eng (2015) 7:233–247
X Z
Normal Stresses
Normal Stresses
X
Shear Stresses x-z & x-y
Shear Stresses x-z
Y
Z
123
Int J Adv Struct Eng (2015) 7:233–247 237
123
238 Int J Adv Struct Eng (2015) 7:233–247
123
Int J Adv Struct Eng (2015) 7:233–247 239
Analysis results and discussion mesh was chosen to be used in the analysis in the current
study.
Mesh sensitivity
Rotation of structural components
A mesh sensitivity study was carried out for the case of
edge column removal using four different mesh sizes. According to the UFC code, the rotations of all the beams,
Different mesh discretizations are shown in Table 2. Fig- columns and joints due to support loss must be checked.
ure 11 shows the relation between the mesh category and The beam and column rotation is calculated by dividing the
the deflection for an element just above the removed col- maximum deflection of the member by the member length
umn. The change in the deflection from mesh #3 to #4 was as shown in Fig. 12. The joint rotation is the relative
found to be negligible enough. Consequently, the third rotations of the connected members.
123
240 Int J Adv Struct Eng (2015) 7:233–247
Fig. 7 continued
123
Int J Adv Struct Eng (2015) 7:233–247 241
Concrete 22,135 25 2 – –
Reinforcement 200,000 – – 360 520
generally noticed with low level of stresses in stirrups. The by increasing margin of safety for the columns. In addition,
contribution of membrane action of the beams’ reinforce- the strength reduction factors specified by ACI are consid-
ment was too small to prevent the structure collapse. ered also a margin of safety for column capacities.
The collapsed areas were the bays directly connected to In the internal shear wall removal case, the beam max-
the removed column. The structure showed a high potential imum rotation was 0.32, 0.14 and 0.07 for the ground,
for progressive collapse and therefore it must be redesigned fifth and eighth floors, respectively. All these values are
according to UFC guidelines. less than the UFC limits (3.38) as shown in Fig. 17. The
In the internal shear wall removal case, the existence of maximum column rotation was 0.07, 0.07 and 0.13 for
the shear wall in all the upper floors with its huge section the ground, fifth and eighth floors, respectively. Similarly,
helped by safely spanning the three unsupported bays and these values are less than the ASCE 41 limits (0.86, 0.85
prevented the structure collapse in the ground, fifth and and 1.0, respectively). The joint rotations were 0.37,
eighth floors. Additionally, the existence of the remaining 0.13 and 0.14 for the ground, fifth and eighth floors,
parts of the core helped in supporting the structure, in lieu of respectively, which are also less than the ASCE 41 limit
the removed wall, and prevented the structure collapse as which is (1.15).
shown in Fig. 15. After the wall removal, its vertical load In the case of the tenth floor, the 3D frame analysis
transferred to the remaining parts of the core and to the showed partial progressive collapse in the case of internal
adjacent columns. Figure 16 shows two successive views for shear wall removal from the tenth floor. This collapse is
the axial forces in the columns and walls before and after the explained by the fact that, there are no floors above the
wall removal from the ground floor. In such a case, the axial tenth floor and hence no Virendeel action could be acti-
load in the core web increased by 150 % of the gravity loads, vated above the removed support. The beams thus spanned
while the axial load in the other flange increased by 40 % of two continuous bays and therefore failed due to insufficient
the gravity loads. All the axial forces that resulted from the bottom reinforcement.
column removal were still less than their ultimate capacities.
This is explained by the fact that the columns were designed Behavior of coupled frame-wall system
according to the (ACI 318-08) code which implements
higher load factors as compared to UFC guidelines The 3D frame analysis, without slabs, but including infilled
(1.2DL ? 1.6LL instead of 1.2DL ? 0.5LL). This helped walls in the bays above the removed support was carried
123
242 Int J Adv Struct Eng (2015) 7:233–247
(a)
(b)
Fig. 11 The relation between the mesh category and the maximum
3 2 1 deflection above the removed column
5 4
1 19198 1 9 1 9 10 59592
2 2 9 2 9 10 2 9 2 9 10 10 9 10 9 2
3 3 9 3 9 16 3 9 3 9 20 14 9 14 9 2
4 4 9 4 9 20 4 9 4 9 25 14 9 14 9 2
a
Number of elements in cross sections and in the longitudinal
direction for beams and column, or number of elements in the slab
plan and its depth
123
Int J Adv Struct Eng (2015) 7:233–247 243
123
244 Int J Adv Struct Eng (2015) 7:233–247
Fig. 16 Axial forces in columns (ton) before and after the internal shear wall removal from the ground floor
(3:1), the window opening area can reach 45 % of the In the case of the first internal column removal, using one
wall area. The collapse prevention was due to the infilled infilled wall above the removed column in nine successive
frame behavior. Figure 18 shows the structure’s collapse floors or more prevent the structure collapse. The nine
for the aspect ratios (2:1) with window opening area floors represent 90 % from the whole number of the
40 %. The maximum beam rotation was 0.2 and 0.24 structure floors. Figure 20 shows the collapse shape in case
for aspect ratio (2:1) and (3:1), respectively. The two of using one wall in eight successive floors only. The
rotation values are less than the UFC rotation limits maximum beam rotation was 0.45 which is less than the
(3.61). UFC limits (3.61).
Using two masonry walls in the same plane above the
Edge column removal removed column in five successive floors above the
removed column prevent the structure collapse. The five
Using window opening area with area less than or equal to floors represent 50 % of all the floors of the structure. The
35 % of the wall area with any aspect ratio will enable the maximum beam rotation was 0.22 which is less than the
wall to prevent the structure collapse in case of edge col- UFC limits (3.61).
umn removal. The results show that the window opening Using two perpendicular masonry walls in four succes-
aspect ratio has no effect while the area of the opening is sive floors or more above the removed column prevented
the main affecting parameter. The maximum beam rotation the structure collapse. The four floors represent 40 % of all
was 0.19 and 0.23 for aspect ratio (2:1) and (3:1) the floors of the structure. The maximum beam rotation
respectively. The two rotation values are less than the UFC was 0.23 which is less than the UFC limits (3.61). The
123
Int J Adv Struct Eng (2015) 7:233–247 245
Removed
column
Fig. 18 Collapse shape for window opening with aspect ratio of (2:1) Fig. 19 Structure’s collapse in case of using masonry walls in all the
floors
123
246 Int J Adv Struct Eng (2015) 7:233–247
123
Int J Adv Struct Eng (2015) 7:233–247 247
4. The collapse can be prevented by ‘‘meeting the UFC Department Of Defense. DoD (2009) Design of buildings to resist
limits’’ in case of internal column failure if any of the progressive collapse, unified facilities criteria (UFC, 4-023-03).
U.S. Department of Defense, USA
following conditions are satisfied: Galal K, El-Sawy T (2010) Effect of retrofit strategies on mitigating
progressive collapse of steel frame structures. J Constr Steel Res
66(4):520–531
• Four perpendicular walls above bays surrounding General Service Administration (GSA) (2003) Progressive collapse
the lost column in successive floors representing at analysis and design guidelines for new federal office buildings
least 50 % of all the floors of the structure. and major modernization projects. USA
Hao H, Ma GW, Lu Y (2002) Damage assessment of masonry infilled
• Three perpendicular walls above bays surrounding
RC frames subjected to blasting induced ground excitations. Eng
the lost column in successive floors representing at Struct 24(6):799–809
least 70 % of all the floors of the structure. Helmy H, Salem H, Tageldin H (2009) Numerical simulation of
• Two perpendicular walls above bays surrounding Charlotte Coliseum demolition using the applied element
method. USNCCM-10 conference-Ohio-USA; 2009
the lost column in successive floors representing at
Helmy H, Salem H, Mourad S (2012) Progressive Collapse Assess-
least 90 % of all the floors of the structure. ment of Framed Reinforced Concrete Structures According to
UFC Guidelines for Alternative Path Method. Eng Struct
5. The collapse cannot be prevented in case of first row of 42:127–141
internal column by using two walls in the same plane Maekawa K, Okamura H (1983) The deformational behavior and
in all the floor above the failed column. The collapse constitutive equation of concrete using the elsto-plastic and
can be prevented in case of the failure of all the other fracture model. J Fac Eng Univ Tokyo (B) 37(2);253–328
Meguro K, Tagel-Din H (2000) Applied element method for structural
internal column by using one wall in all the floors or analysis: theory and application for linear materials. Struct Eng
two walls in the same plane in five successive floors Earthq Eng Int J Jpn Soc Civ Eng (JSCE) 17(1);21s–35s
above it. Meguro K, Tagel-Din H (2001) Applied element simulation of RC
6. The masonry walls cannot prevent the structure’s structures under cyclic loading. ASCE 127(11):1295–1305
Park H, Suk C, Kim S (2009) Collapse modeling of model RC
collapse in case the edge shear wall collapses. structures using the applied element method. J Korean Soc Roc
7. The area of the window opening has a significant effect Mech Tunn Undergr Space 19(1);43–51
on the wall’s ability to resist the structure’s collapse, Razzaghi MS, Javidnia M (2015) Evaluation of the effect of infill
while the aspect ratio does not. walls on seismic performance of RC dual frames. Int J Adv
Struct Eng (IJASE) 7(1):49–54
8. Using window opening area less than 40 and 35 %, of Ristic D, Yamada Y, Iemura H (1986) Stress-strain based modeling of
the wall area above the bays surrounding the removed hysteretic structures under earthquake induced bending and
column for corner column and edge column, respec- varying axial loads. Research report No. 86-ST-01, School of
tively, enables the wall to prevent the structure’s Civil Engineering, Kyoto University, Kyoto, Japan; 1986
Salem H (2011) Computer-aided design of framed reinforced concrete
collapse and the structure then meets the UFC limits. structures subjected to flood scouring. J Am Sci 7(10):191–200
Salem H, El-Fouly A, Tagel-Din H (2011) Toward an economic
design of reinforced concrete structures against progressive
Open Access This article is distributed under the terms of the
collapse. Eng Struct 33:3341–3350
Creative Commons Attribution 4.0 International License (http://cre-
Sasani M (2008) Response of a reinforced concrete infilled-frame
ativecommons.org/licenses/by/4.0/), which permits unrestricted use,
structure to removal of two adjacent columns. Eng Struct
distribution, and reproduction in any medium, provided you give
30:2478–2491
appropriate credit to the original author(s) and the source, provide a
Sasani M, Sagiroglu S (2008) Progressive collapse resistance of hotel
link to the Creative Commons license, and indicate if changes were
San Diego. J Struct Eng 134(3):478–488
made.
Shankar N (2004) Progressive collapse basics. In: NASCC
Proceedings
Tagel-Din H, Meguro K (2000a) Applied element method for
References simulation of nonlinear materials: theory and application for
RC structures. Struct Eng Earthq Eng Int J Jpn Soc Civ Eng
ACI 318-08 (2008) Building code requirements for structural concrete (JSCE) 17(2);123s–148s
and commentary. American Concrete Institute, MI Tagel-Din H, Meguro K (2000b) Applied element method for
ASCE/SEI 7-05 (2005) Minimum design loads for buildings and other dynamic large deformations analysis of structures. Struct Eng
structures. American Society of Civil Engineers, NY Earthq Eng Int J Jpn Soc Civ Eng (JSCE) 17(2);215s–224s
ASCE/SEI 41/06 (2006) Seismic rehabilitation of existing buildings, Tagel-Din H, Rahman N (2004) Extreme loading: breaks through
American Society of Civil Engineers, NY finite element barriers. Struct Eng 5(6):32–40
Applied Science International (2004–2015) LLC. http://www.apllieds Tsai MH, Huang TC (2013) Progressive collapse analysis of an RC
cienceint.com building with exterior partially infilled walls. Struct Des Tall
Bathe K (1982) Solution of equilibrium equations in dynamic Spec Build 22(4):327–348
analysis. Prentice Hall, Englewoods Cliffs Wibowo H, Reshotkina S, Lau D (2009) Modelling progressive
Chopra A (1995) Dynamics of structures: theory and applications to collapse of RC bridges during earthquakes, CSCE Annual
earthquake engineering. Prentice Hall, Englewoods Cliffs General Conference; 2009; GC-176-1-11
123