This document is an entry from the Siemens Industry Online Support. The following
Terms of Use apply (www.siemens.com/terms_of_use).
The following link takes you directly to the download page of this document.
http://support.automation.siemens.com/WW/view/en/65766912
Caution
The functions and solutions described in this entry are mainly limited to the
realization of the automation task. Please take into account furthermore that
corresponding protective measures have to be taken up in the context of Industrial
Security when connecting your equipment to other parts of the plant, the enterprise
network or the Internet. For more information, please refer to entry ID 50203404.
http://support.automation.siemens.com/WW/view/en/50203404
Question
How do you migrate a SIMATIC WinAC MP project from SIMATIC WinCC flexible
2008 SP3 to SIMATIC WinCC (TIA Portal) V11/V12?
Answer
The instructions and notes listed in this document provide a detailed answer to this
question.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
2 Version 1.1, Entry ID: 65766912
Table of Contents
Table of Contents
1 Introduction ........................................................................................................ 4
2 Preparing HMI Device for the Migration .......................................................... 5
2.1 Updating operating system................................................................... 5
2.2 Transferring option ............................................................................... 6
3 Migrating a Project ............................................................................................ 7
3.1 Migrating STEP 7 and WinCC flexible project...................................... 7
3.2 Final check of the migrated components ............................................. 9
4 Additional Checks after the Migration ........................................................... 10
4.1 Checking the IP address (HMI device)............................................... 10
4.2 Checking the standard images in the project library .......................... 11
4.3 Checking the provided system functions............................................ 13
4.4 Checking the provided HMI tags ........................................................ 14
5 Downloading the Project................................................................................. 15
5.1 Downloading the entire project to the device ..................................... 15
5.2 Transferring HMI project separately ................................................... 20
6 Transferring STEP 7 Program Blocks ........................................................... 21
6.1 Transferring program blocks individually............................................ 21
6.2 Transferring program blocks completely ............................................ 22
7 Online and Diagnostics ................................................................................... 23
7.1 Establishing online connection ........................................................... 23
7.2 Diagnostic buffer ................................................................................ 24
7.3 Task card “Online tools" ..................................................................... 25
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 3
1 Introduction
1 Introduction
The following FAQ deal with the migration of SIMATIC WinAC MP projects (SIMATIC WinCC
flexible 2008 SP3) to SIMATIC WinCC (TIA Portal) V11 SP2 Update 3 or newer. A migration of
SIMATIC WinCC flexible 2008 SP3 projects is only possible from SIMATIC WinCC (TIA Portal)
V11 SP2 Update 3.
Note Compatibility
The SIMATIC MP377 Daylight 15" Touch operator panel is only supported with
WinCC V12!
Figure 1-1
• The following TIA Portal components are required (min. WinCC Comfort):
Figure 1-2
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
4 Version 1.1, Entry ID: 65766912
2 Preparing HMI Device for the Migration
Instruction
In order to update the operating system on the operator panel, proceed as follows:
1. Open the TIA Portal.
2. Select the HMI operator panel that is to be updated in the project navigation.
3. In order to update the operating system of the HMI operator panel, select the “Update
operating system" command in "Online > HMI device maintenance”.
SIMATIC ProSave opens. The "OS Update" tab is visible.
Figure 2-1
Result
The operator panel is automatically restarted once the operator panel is updated. The
previously saved device configuration is automatically restored on the operator panel once the
operating system has been updated.
The full configuration (STEP 7 and HMI part) is downloaded via the “Extended
download to device” dialog. This process carries out an automatic update of the
operating system.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 5
2 Preparing HMI Device for the Migration
Figure 2-2
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
6 Version 1.1, Entry ID: 65766912
3 Migrating a Project
3 Migrating a Project
3.1 Migrating STEP 7 and WinCC flexible project
Instruction
In order to migrate a STEP 7 project (with HMI project) to the TIA Portal, proceed as follows:
1. Open the TIA Portal.
2. Select the portal view.
Figure 3-1
Figure 3-2
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 7
3 Migrating a Project
Result
The following message is displayed after a successful migration.
Figure 3-3
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
8 Version 1.1, Entry ID: 65766912
3 Migrating a Project
• HMI components
Figure 3-4
• WinAC MP components
Figure 3-5
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 9
4 Additional Checks after the Migration
Figure 4-1
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
10 Version 1.1, Entry ID: 65766912
4 Additional Checks after the Migration
Figure 4-2
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 11
4 Additional Checks after the Migration
● WinAC_MP_Tuning
Figure 4-3
The preconfigured standard images are stored in a global library. The provided images are
already switched with internal tags and respective WinAC MP system functions.
The "WinAC_MP_Tags" copy template is additionally available to you in WinCC V11 SP2.
Figure 4-4
This copy template (WinAC_MP_Tags) is required, since the existing tag connections are not
supported because of moving the preconfigured WinAC MP standard images to the respective
TIA Portal project. They have to be moved separately first to a newly created tag table. The
preconfigured WinAC MP standard images (Home Screen and Tuning Screen) are provided
with internal tags by being moved to the new tag table. Due to this, all already existing WinAC
MP system functions are supported.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
12 Version 1.1, Entry ID: 65766912
4 Additional Checks after the Migration
Figure 4-5
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 13
4 Additional Checks after the Migration
Figure 4-6
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
14 Version 1.1, Entry ID: 65766912
5 Downloading the Project
Prerequisite
● The following transfer settings have to be made on the HMI device:
– Channel 2: Ethernet
– Enable Channel “enabled"
– Remote Control “enabled"
● The project was migrated.
● The project data is consistent.
● The device to be loaded is available via online access.
● The additional settings and the IP address of the respective HMI device have been
checked.
● The TIA Portal is open.
● The project view is open.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 15
5 Downloading the Project
Instruction
In order to load the project to the device, proceed as follows.
1. Select the device in the project navigation.
Figure 5-1
Figure 5-2
3. Select the “All” option in the context menu in the “Load to device" submenu.
–If you have not yet established an online connection, the “Extended download to
device" dialog opens and you first of all you have to select the interfaces via which you
would like to create the online connection to the device.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
16 Version 1.1, Entry ID: 65766912
5 Downloading the Project
The hardware configuration of WinAC MP 2008 has to be loaded via the PG/PC interface
"PN/IE”.
Figure 5-3
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 17
5 Downloading the Project
–If you have already created an online connection, the “Load preview" dialog opens. In this
dialog, you will be shown messages and actions required for loading.
All project-specific data in the target device is deleted. All predefined modules (here: the WinAC
MP) are centrally stopped or prepared for the download process. If you enable the “Overwrite
all" option box, all already existing configuration data is overwritten in the target system (HMI
device)!
Figure 5-4
Result
The selected project data is loaded to the device. A repeated input of the individual parameters
or values is no longer necessary. The transfer path to the HMI device is permanently stored for
other transfer processes in the system.
The WinAC MP device is restarted. Afterwards the device is in RUN mode.
Figure 5-5
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
18 Version 1.1, Entry ID: 65766912
5 Downloading the Project
The loading process should be completed successfully. Based on the output compiler
messages, warnings can be acquired fast and can be further processed.
Figure 5-6
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 19
5 Downloading the Project
Figure 5-7
4. Select the “Download to device > Software” command in the context menu.
Result
All changes are subsequently transferred to the HMI device.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
20 Version 1.1, Entry ID: 65766912
6 Transferring STEP 7 Program Blocks
Instruction
In order to add STEP 7 blocks and to load to the HMI device, proceed as follows:
1. Open the TIA Portal.
2 Open the project view.
3. Select the respective STEP 7 block in the project navigation by right clicking it.
4. Select the “Download to device > Software” command in the context menu.
Result
The preview for loading is displayed. Additional information is displayed in this dialog, such as
blocks that are not available online.
Figure 6-1
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 21
6 Transferring STEP 7 Program Blocks
Figure 6-2
4. Select the “Download to device > Software (all blocks)” command in the context menu.
Result
You have successfully migrated your WinAC MP project to TIA Portal V11 and transferred it to
the HMI device.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
22 Version 1.1, Entry ID: 65766912
7 Online and Diagnostics
Instruction
In order to determine diagnostic information, proceed as follows:
1. Open the TIA Portal.
2 Open the project view.
3. Open the respective device folder in the project navigation.
4. Select the “Online & diagnostics" action. The “Online accesses” dialog opens on the
desktop.
Figure 7-1
Result
Once the online connection is established, you have different diagnostic options.
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 23
7 Online and Diagnostics
Figure 7-2
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
24 Version 1.1, Entry ID: 65766912
7 Online and Diagnostics
WinAC MP und Multi Panel - Projektierung nach TIA Portal V11/V12 migrieren
Version 1.1, Entry ID: 65766912 25