4
INSTRUMENTATION AND
CONTROL SERVICING NC II Competency Based Learning Material
‘TAG NUMBER IDENTIFICATION
Example:
TRE Ce steal
T- First Letter
R- Succeeding Letter
- Succeeding Letter
3- Loop Number
A- Suffix Letter (usually not needed)
letter First Letter Succeeding Letter
Process or Initiating ‘Modifier Readout or Output [Modifier
Variable Passive Function | Function
a Analysis * ‘Alarm
3 Burner, Combustion User's choles Users holes Users Choice
c Users Chole Contr!
D. Users Choice ‘Bierentia
E Voltage Primary
Element/Sensor
F Flow Rate Ratio (Fraction)
s Users Choice ‘Glass /Viewing Device
cl Hand igh
L ‘Current (lecrcal indicate
7 Power Sean
K Time, Time Schedule Time Rate of ‘Contral Station
Change
n Level Light low.
M. Users Choice ‘Moment ‘idle
N. Users Chole Users Choice Users choles Users Choice
o Users holes Orifice, Restriction
P Pressure, Vacuum Point, Test
Connection)
@ ‘Quantity Tategrate,Totalize
R Radiation Record or Print
s Speed, Frequency Safety ‘Switch
T Temperature Transmit
vu, Moleivariable® Mulfunetion ‘Multifunction | — Multifunction
V_| Vibration, Mechanical Analysis Valve, Damper,
Lower
w Weight Force Wail
x Unclassified as Undassfied Undlassfe Unclassified
¥ Event, State or Presence Y Axis Relay or Compute ™
z Position, Dimension Taxis Driver, Actuator,
Unclassified Final
Control Element
(*) When used, explanation is shown adjacent to instrument symbol