You are on page 1of 1

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

PRJL1
LEYENDA EQUIPOS DE 220 kV LEYENDA EQUIPOS DE 33 kV
A TTPPJL1 A
245KV 198KV, 10KA
1050KV@1481, 1050KV@1481
220 0.110 0.110 0.110 ZnO C/CONTADOR
, , ,
√3 √3 √3 √3 cl 3.
50VA-3P
50VA-3P
TOJL1
1200A
20VA-CL0.2 0.315mH
F1= 200KHz
F2= 500KHz
89JL1-1
245KV
1050KV@1481
89JL1-1T
245KV
B 2000A - 31.5KA, 3s 1050KV@1481 B
2000A - 31.5KA, 3s

52JL1
245KV-TRIPOLAR
SF6
1050KV@1481
2000A - 31.5KA, 1s
TTCCJL1
245KV
1050KV@1481
TTPPJB 600-1200/1/1/1/1A
245KV 20VA, 5P20
1050KV@1481, 20VA, 5P20
220 0.110 0.110 0.110
, , ,
√3 √3 √3 √3
89JL1-2 20VA, 5P20
20VA, CL0.2
245KV
C 50VA-3P
50VA-3P
1050KV@1481 C
2000A - 31.5KA, 3s
20VA-CL0.2

89JT1-1 89JT2-1
245KV 245KV
1050KV@1481 1050KV@1481
2000A - 31.5KA, 3s 52JT1 2000A - 31.5KA, 3s 52JT2
245KV-TRIPOLAR 245KV-TRIPOLAR
SF6 SF6
1050KV@1481 1050KV@1481
2000A - 31.5KA, 1s 2000A - 31.5KA, 1s
TTCCJT1 TTCCJT2
245KV 245KV
D 1050KV@1481 1050KV@1481 D
600-300/1/1/1/1A 600-300/1/1/1/1A
20VA, 5P20 20VA, 5P20
20VA, 5P20 20VA, 5P20
20VA, 5P20 20VA, 5P20
20VA, CL0.2 20VA, CL0.2
PRJT1 PRJT2
198KV, 10KA 198KV, 10KA
1050KV@1481 1050KV@1481
ZnO C/CONTADOR ZnO C/CONTADOR
cl 3. cl 3.

T1 T2
TRANSFORMADOR DE POTENCIA TRANSFORMADOR DE POTENCIA
220 ±10X1%/33KV 220 ±10X1%/33KV
E 70 / 90 MVA (ONAN-ONAF) 70 / 90 MVA (ONAN-ONAF) E
YNd11 YNd11

F F

G G

H H

L L

R.L.R. C.A.M. M.M.P


01 03/04/17
PRODIEL PRODIEL PRODIEL
E.V.S. C.A.M. M.M.P.
M 00 24/11/16 M
PRODIEL PRODIEL PRODIEL
REV. DATE DESCRIPTION PREPARED CHECKED APPROVED
CONTRACTOR'S LOGO PROJECT:
INGENIERIA DE DETALLE DE SET RUBÍ AMPLIACIÓN SET MONTALVO
Y LINEA DE TRANSMISIÓN
FILE NAME:

CLASSIFICATION: FORMAT: SCALE: PLOT SCALE: SHEET:

N FOR VALIDATION A1 S/E 1:1 1 di / of 1 N


UTILIZATION SCOPE: TITLE:

ESQUEMA UNILINEAL GENERAL


Engineering & Construction
DETAILED DESIGN SUBESTACION RUBI
EGP VALIDATION
VALIDATED BY JF.Mateo
EGP CODE
O VERIFIED BY O. Jimenez GROUP FUNCTION TYPE ISSUER COUNTRY TEC. PLANT SYSTEM PROGRESSIVE REVISION O
COLLABORATORS EGP EEC D 2 7 P EP 5 8 0 2 5 1 6 0 4 5 0 1
abr.-17 This document is property of Enel Green Power SpA. It is strictly forbidden to reproduce this document, in whole or in part, and to provide to others any related information without the previous written consent by Enel Green Power SpA.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16