You are on page 1of 20

g

Dead Tank Circuit Breakers


72.5– 800kV — Advanced Technology in a Compact, Reliable Design

with Primary Plus


TM

Pre-engineered solution set that digitizes XD|GE primary equipment and provides factory
installed and configured protection, monitoring, diagnostics and communications.

GE
Digital Energy
Dead Tank Circuit Breakers — 72.5–800kV

363kV Dead Tank SF6 Circuit Breaker 800kV Dead Tank SF6 Circuit Breaker

Robust, High Quality and Reliable Breaker Technology


For over a century, utilities around the world have relied on GE products and The XD|GE alliance provides end-to-end transmission solutions to meet the
services to increase power system reliability and improve grid resiliency and growing demand for electricity globally. The combined portfolios of GE and
responsiveness. As a global leader in grid infrastructure products and services, XD provide a comprehensive range of technology solutions for customers in
GE supports a broad set of utility applications ranging from transmission and the utility sector and energy intensive industries.
substation automation to distribution networks and smart metering, enabling
The XD|GE breaker offerings are robust in design and are based on proven
greater safety, connectivity and increased security.
technology, yielding high quality products suitable for an extensive range of
Through an alliance with XD Electric®, GE has extended its portfolio to applications. XD|GE’s breakers are compact in design and construction with
include high and ultra high-voltage power equipment supporting the highest advanced arc extinguishing technology and self-blast interrupting capability
transmission voltage levels in the world. XD Electric is one of China’s largest which significantly reduces product size and improves reliability.
primary equipment manufacturers dedicated to the research, application and
Designed with a modular spring operated mechanism and an integrated
development of high and ultra high-voltage power transmission equipment.
hydromechanical operating mechanism, these circuit breakers improve
XD Electric has a broad range of products to transform and direct the flow of
product reliability, reduce costs, and minimize maintenance requirements.
power for industrial, commercial and residential users.

2 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

Key Features & Benefits


Reduced Footprint
Current transformers equipped in the bushing insulators
allow for reduced space and foundations required for
installation.

Compact Design and Construction


Advanced arc extinguishing technology significantly reduces
product size and improves reliability.

Excellent Seismic Performance and


Pollution-Resistant Capability
The dead tank circuit breaker is well-suited for areas with
frequent earthquakes, high elevation or severe pollution.

Maintenance Free Design


Modular spring operated mechanism and integrated
hydromechanical operating mechanism improve product
reliability, reduce costs, and minimize maintenance
requirements.

Primary Plus

XD|GE offers Primary Plus™ for all its critical power delivery
equipment. Primary Plus is a pre-engineered solution set
that provides utilities and large industrial facilities with
a means to reduce the time and labor associated with
substation construction, expansion, and maintenance, while
utilizing technologies and methodologies familiar to existing
engineering resources.

XD|GE’s factory installed and configured solutions include:

• Digitized primary equipment by replacing labor-intensive,


individually terminated copper wires with standardized
physical interfaces and open communications protocols
(IEC 61850)
• Electrical protection systems optimized for each primary
asset and application to monitor and react to fault
conditions
• Highly secure and ruggedized communication network
equipment including industrial strength wireless, fiber optic
multiplexers, and Ethernet switches for an advanced and
72.5kV Dead Tank SF6 Circuit Breaker reliable communications infrastructure

3
Dead Tank Circuit Breakers — 72.5–800kV

72.5kV SF6 Insulated Breaker 126/145/252kV SF6 Insulated Breaker

The LW24-72.5 is an outdoor dead tank SF6 circuit breaker with self-blast Type LW24-126/145/252/T outdoor dead tank SF6 circuit breaker product line
interrupter technology and a spring operating mechanism. incorporates world class advanced technology at these kV ratings.

Self-blast technology is well established and deployed throughout the industry. Self-blast technology is used to reduce the operating energy and improve the
When interrupting a fault current, heat generated from arcing will compress the interrupting reliability. With this advanced technology, the arc is extinguished
SF6 gas in the compression cylinder. As a result, highly pressurized gas travelling by the highly pressured gas, which is a result of heat generated by the arc
through the nozzle will extinguish the arc. Self-blast technology is more efficient itself. Compared to traditional puffer technology, the operating energy of a
and requires less operating energy than other arc extinguishing methods. self-blast circuit breaker could be reduced up to 50%.

The operating mechanism used in this breaker, the CT20-II, is a spring driven The operating mechanism is a spring design, which makes the product
technology. The advantages of this spring operated mechanism include improved simple in construction and light in weight with higher reliability and less noise
stability and reliability, increased stability with ambient temperature changes, and in operation.
minimal to zero maintenance given the lack of oil or gas component.
This family of dead tank circuit breakers will have independent certifications
The LW24-72.5 product has received independent KEMA® certification. To from XIHARI, MHI, or KEMA depending on the rating class and design.
achieve certification, the product passed the back-to-back switching test as
well as the shunt reactor switching test.

This dead-tank breaker design is the most widely produced by XD|GE with
over 2,000 units shipped and in service over the last few years.

Normal Service Conditions Normal Service Conditions


2.1. Altitude 3000m 2.1. Altitude: ≤ 1000m (not more than 3000m in special condition)
2.2. Humidity monthly 90% 2.2. Humidity monthly 90%

2.3. Max. wind velocity 35m/s 2.3. Max. wind velocity 35m/s
2.4. Pollution class: IV class 2.4. Pollution class: III, IV class
2.5. Typical ambient temperature: -35°C to +40°C 2.5. Typical ambient temperature: -35°C to +40°C
2.6. Max. temperature difference daily: 25°C 2.6. Max. temperature difference daily: 25°C
2.7. Earthquake withstand density 9 degree 2.7. Earthquake withstand density 9 degree
2.8. Ice coating: ≤ 10mm 2.8. Ice coating: ≤ 10mm

2.9. Max. radiance from sun: 1000 W/m2 2.9. Max. radiance from sun: 1000 W/m2

72.5kV Dead Tank Circuit Breaker 126kV Dead Tank Circuit Breaker

4 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

363/550/800kV SF6 Insulated Breaker

The LW13A/23-363, LW13A-550, and LW13-800 family of products represent


the technology platform for the highest kV rated XD|GE dead tank breakers.
Single interrupting units per pole are utilized on breaker products from 363kV
to 550kV without parallel capacitors and pre-insertion resistors. In addition,
double interrupting unit designs are used for products from 363kV up to
800kV. Parallel capacitors and pre-insertion resistors are incorporated when
double interrupting units per pole are used.

Breakers from 363kV to 800kV can carry continuous current up to 5000A


and have interrupting capability for short circuit at either 50kV or 63kA, per
customer specification.

Breakers above 363kV are equipped with the CYA8 hydromechanical


mechanism. The fully integrated hydro-mechanical operating mechanisms are
maintenance-free designs with long-term stability and reliability.

363kV - 800kV series dead tank breakers are tested and certified per IEC®
standards by XIHARI®, the national HV lab in China.

Normal Service Conditions


363kV Dead Tank SF6 Circuit Breaker 50kA
2.1. Altitude: ≤ 1000m (not more than 3000m in special condition)
2.2. Humidity monthly 90%
2.3. Max. wind velocity 35m/s
2.4. Pollution class: III, IV class
2.5. Typical ambient temperature: -35°C to +40°C
2.6. Max. temperature difference daily: 25°C
2.7. Earthquake withstand density 9 degree
2.8. Ice coating: ≤ 10mm
2.9. Max. radiance from sun: 1000 W/m2

550kV Dead Tank SF6 Circuit Breaker

800kV Dead Tank Circuit Breaker 550kV Dead Tank SF6 Circuit Breaker

GEDigitalEnergy.com 5
Dead Tank Circuit Breakers — 72.5–800kV

Technology

1. Interrupter lnner Construction


Inner Construction of
of Interrupter
Interrupter
The figure below shows the principle construction of the interrupter. The
pressure of the gas in the puffer cylinder goes up when the gas is heated by Fixed main Fixed arcing Moving main Piston
the arc and then compressed by opening movement of the puffer cylinder. contact contact contact

This pressurized and compressed gas goes to the arc between the stationary
contact and moving contact. The nozzle concentrates the gas flow to the arc
for efficient cooling.

Trip spring
Trip spring
Cam Cam

Arc Nozzle
Ratchet
Ratchet Moving arcing Puffer Fixed
contact cylinder finger
Closing
Closing spring
spring

LeverLever Ratchet
Ratchet wheelwheel

Closing-holding
Closing-holding
2. Spring Operating Mechanism latchlatch

Trip-holding
Trip-holding Closing
Closing trigger
trigger
The design of the spring operated mechanism provides the high performance the closing
latchlatch spring. The lever is rotated clockwise, compressing the trip spring
required for reliable operation. The lever engaged with the locking device, by torque from the cam (Fig.2). Closing
Closing coil coil
which is released when the trip coil is energized, is rotated counterclockwise
As soon as the closing sequence is completed, the closing spring is charged
interrupter
interrupter
by the trip spring (Fig.1). openopen
coil coil
by the ratchet linked to the motor (Fig.3).
Trip trigger
Trip trigger
The cam and the ratchet wheel engaged with the locking device, which is
released when the closing coil is energized, are rotated counterclockwise by Fig1.Fig1. Closed
Closed position
position
(closing
(closing spring
spring charged)
charged)

Trip spring
Cam

Ratchet
Closing spring

Lever Ratchet wheel

Closing-holding
latch

Trip-holding Closing trigger


latch
Closing coil

interrupter
open coil
Trip trigger

Fig1. Closed position Fig2.Fig2.


Open Open position
position Fig3.Fig3. Closed
Closed position
position
(closing spring charged) (closing
(closing spring
spring charged)
charged) (closing
(closing spring
spring discharged)
discharged)

6 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

3. Hydromechanical Operating Mechanism for


Circuit Breakers
The hydromechanical mechanism is built with its functional parts linked by
integrated modules. To keep the operation as relaible as possible, “O”-rings
are used at sealing points, disc-type springs are used to store energy, and two
sets of respectively independent opening control valves are incorporated into
Hydro-mechanical
the design. This mechanism mechanism
can be operated either in single phase or in three
phase electrically, and can be gang-operated in Hydro-mechanical
three phase mechanically. mechanism

1. Low pressure oil tank


Hydro-mechanical mechanism 2. Oil lever indicator
1. Low pressure oil tank
3. Operating piston rod
2. Oil lever indicator
4. High pressure oil tank
3. Operating piston rod
5. Piston for charge
4. High pressure oil tank
6. Support ring
7. Disk spring 1. Low pressure oil tank 5. Piston for charge
8. Auxiliary switch 6. Support ring
2. Oil lever indicator
7. Disk spring
9. Oil-filling hole 3. Operating piston rod
8. Auxiliary switch
10. Throttle of close 4. High pressure oil tank
11. Electro-magnetic valve for close 9. Oil-filling hole
5. Piston for charge
12. Electro-magentic valve for open 10. Throttle of close
6. Support ring
13. Throttle of open 7. Disk spring 11. Electro-magnetic valve for close
14. Oil drainage valve8. Auxiliary switch 12. Electro-magentic valve for open
15. Energy-store motor 13. Throttle of open
9. Oil-filling hole 14. Oil drainage valve
16. Oil pump 10. Throttle of close 15. Energy-store motor
17. Pressure release valve
11. Electro-magnetic valve for close
16. Oil pump
18. Spring position switch
12. Electro-magentic valve for open
17. Pressure release valve
13. Throttle of open
14. Oil drainage valve 18. Spring position switch
15. Energy-store motor
16. Oil pump
17. Pressure release valve
a. Uncharged, b. Charged, c. Charged, 18. Spring position switch
open position open position closed position
a. Uncharged, b. Charged, c. Charged,
open position open position closed position

1. Low pressure oil tank


2. Oil lever
High indicator
pressure oil a. Uncharged,
Low pressure oil b. Charged, c. Charged,
3. Operating piston rod open position open position closed position
4. High pressure oil tank High pressure oil Low pressure oil
5. Piston for charge
6. Support ring
7. Disk spring
8. Auxiliary switch High pressure oil Low pressure oil
9. Oil-filling hole
10. Throttle of close
11. Electro-magnetic valve for close
12. Electro-magentic valve for open
13. Throttle of open
14. Oil drainage valve
15. Energy-store motor
16. Oil pump
17. Pressure release valve
18. Spring position switch

550kV Dead Tank SF6 Circuit Breaker

GEDigitalEnergy.com 7
72.5Dead Tank
– 800kV Circuit Breakers
DeadTank Circuit — 72.5–800kV
Breakers

Innovative Facilities and Rigorous Quality Processes

XD|GE’s technology portfolio is built in state-of-the-art manufacturing and Advanced Test Facilities
testing facilities with robust quality processes which provide customers with
XIHARI®, the Xi’an High Voltage Apparatus Research Institute, is an integral
products that meet the critical and demanding reliability and environmental
part of the XD|GE alliance. XIHARI has extensive testing capabilities at its
challenges of transmission applications.
facility sites, which include a: High Power Laboratory, High Voltage Laboratory,
Artificial Climate Laboratory, EMC Laboratory, and an Operational Test Circuit
for HVDC Thyristor Valves.
Manufacturing Excellence
XD|GE designs a broad range of switchgear in five specialized production The testing hall meets all of the requirements of ISO/IEC® 17025 and houses
facilities including machining, surface treatment, insulating, housing and some of the largest test equipment in the world, providing the capacity to
casting. test primary equipment as large as 1,100kV AC. The High Voltage Apparatus
Laboratory in XIHARI is a government authorized national high-voltage
Additionally, there are two specialized facilities that produce both the spring apparatus quality supervision and inspection test center. It is an independent
and hydromechanical operating mechanisms. third-party laboratory for type tests, routine tests, performance tests and
Final production is completed in three workshop assembly lines that total certificate tests for high-voltage apparatus. The testing facilities at XIHARI
more than 50,000 square meters. Components such as aluminum enclosures, also include an extension environmental laboratory. Testing capabilities here
cast resin insulators, current and voltage transformers, and operating include high altitude testing, high humidity testing, and temperature testing
mechanisms are manufactured by XD|GE through a completely integrated from -70° C up to +150° C.
manufacturing model.

The switchgear facilities are ISO® 9001 certified, ISO 14001 certified for
environmental management systems, as well as OSHA® 18001 certified for
health and safety management systems.

Exceptional Quality
A focus on quality is an ongoing strategic initiative for XD|GE and that is
evident throughout the manufacturing environment. The quality process
begins with an incoming inspection of all materials to ensure the best possible
inputs before manufacturing begins.

Throughout the production and assembly process, there are multiple


checkpoints, including both visual inspections as well as stopped flow
inspections, all performed to documented test plans. The production facilities
follow strict non-conforming procedures to identify, control and avoid the
use and delivery of non-conforming products. Each production facility has
developed strict environmental standards, including controls of cleanliness,
temperature and humidity, and has controls in place to monitor and manage
to the established standards.

In addition, XD|GE has a dedicated measurment and inspection department


with a certified full time inspector in each of its manufacturing sites. The
measuring and inspection department provides a secondary cross-inspection
for all work in process, as well as finished products, ensuring a high level of
quality is achieved throughout the manufacturing process. First Pass Yield
and Cost of Quality data is maintained and analyzed, per product family,
in order to drive continual product and process improvements and higher
product reliability.

From raw materials acquisition and inspection to finished product, XD|GE’s


breakers are designed to meet rigid quality processes so the installed product
provides the highest level of reliability.

8 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

Support and Service

Global Project Engineering Services


XD|GE is dedicated to helping its customers reach their system objectives
and provides a suite of professional services to assist the successful
deployment and maintainance of XD|GE products and solutions globally.
From design to implementation to post-sales support, a team of technical
and business experts are available to help customers effectively use the
capabilities and product domain knowledge that are available from XD|GE.

This support infrastructure covers the entire life cycle of the product.
From the coordination of transportation logistics to the completion of site
acceptance testing and warranty service, the highly qualified XD|GE team is
available throughout the implementation.

To ensure a high quality of service to meet the needs of each unique


application, XD|GE has a global field service team of highly experienced and
dedicated individuals. Coupled with a vast network of high voltage power
equipment domain experts, XD|GE is able to support a broad range of
applications in various environments.

Finally, XD|GE offers a 24x7 global support service to address and direct any
customer application and field questions.

Specialized Installation and Commissioning


• Logistics including coordination of ocean and inland transportation
• Installation services include receiving, rigging, unloading and labor
(mechanical and electrical)
• Test commissioning
• Site acceptance testing

Post-Sales and Installation Support


• 24x7 global customer service
• Emergency response hotline
• Several customer support access points available to ensure timely
support (telephone, e-mail, fax, or web)
• Global spare parts reserve
• A global network of maintenance and repair facilities

4800kV/720 kJ Impulse Voltage Generator &


±2000kV 30mA DC Voltage Generator

GEDigitalEnergy.com 9
Dead Tank Circuit Breakers — 72.5–800kV

Primary Plus

Pre-Engineering Secondary Equipment


Primary Plus, XD|GE’s supplemental offering to its primary equipment, is a pre-engineered, factory
installed solution set that allows utilities to reduce the time and labor associated with substation
construction and commissioning. Primary Plus uses technologies and methodologies familiar to
existing resources and skill sets.

• Digitized primary equipment for replacing labor-intensive, individually terminated copper wires
• Electrical protection solutions to monitor and react to fault conditions
• Secure and ruggedized communications infrastructure devices including wireless radios, fiber optic multiplexers
and Ethernet switches

Digitized Substation

MultilinTM HardFiber System Key Benefits


• Using the Multilin HardFiber system, XD|GE • Saves up to 50% of Protection & Control
can deliver primary equipment with digital labor costs
communications. The Multilin HardFiber system • Eliminates the majority of copper wiring to better utilize resources for the design,
digitizes analog signals from primary assets utilizing building, commissioning, and maintenance of power system protection and control
IEC 61850 communications, reducing total life
costs of protection and control through labor and • Robust and simple architecture for deploying IEC 61850 process bus
resource optimization. • Improves employee safety by leaving potentially dangerous high-energy signals
• This factory-installed solution reduces the amount in the switchyard
of labor-intensive, individually terminated copper • Reduces the chances for operational mistakes made during isolation and
wire connections with pre-terminated copper and restoration after routine maintenance
fiber optic cables with standard physical interfaces • Built as an extension of the Multilin Universal Relay (UR) family of products,
and open digital communications. suitable for a wide array of protection applications
• Rugged, hardened, and secure switchyard interface enabling
NERC/CIP compliance

Electrical Protection & Control

Advanced Relays for Primary Key Benefits


Substation Equipment • Advanced circuit breaker monitoring
and control in a single platform
Primary Plus utilizes the Multilin C60 Breaker
Protection system or Multilin F60 Feeder Protection • Complete IEC 61850 Process Bus solution providing resource optimization
system to provide primary protection of critical substation and minimizing total protection & control lifecycle costs
equipment. Multilin relays are substation hardened • Modular hardware architecture allow for device configuration
devices that provide comprehensive protection, control, flexibility, meeting the needs of most circuit breaker applications
automation, and monitoring of high voltage substation
• Advanced fault and disturbance recording, including internal device health
circuit breakers. With fast, deterministic execution of
monitoring, eliminating the need for external devices and maximizing asset life
programmable automation logic, extensive I/O options,
and integrated high-speed peer-to-peer communications, • Robust network security enabling critical infrastructure
Multilin protection devices can receive and execute Protection and NERC/CIP compliance
commands and at a fraction of the cost when compared • Advanced automation capabilities for customized protection and control systems
to a traditional hard-wired configuration.
• Simplified system integration and access to information through the use of multiple
communication options and protocols, including native support for IEC 61850

10 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

Dimensions and Foundation


72.5kV SF6 Breaker

LW24-72.5
LW24-72.5

2115
2530 10° 10°
2320
1160

30° 30°

1360

3650
2806
2363

Grounding
2×4-M10 Terminal
981

32
56
885

300

32
120 920 120 56
1280
M20

85
1280
500

500
920

150
392

280

80
400
940

16
R6

All measurements
are in millimeters (mm)

GEDigitalEnergy.com 11
Dead Tank Circuit Breakers — 72.5–800kV

126-145kV SF6 Breaker

LW24-126
LW24-126/LW24-145

2030
251 1560 3200
1510 1510
C

2 800
N1 10
M
2-

40

14
40
3820

22x2.4

4-ф
100
370

102
225
45
530

45 30

1750
1530
1000

2*4-M10

1070
1670
2300
3820
3900
1000

50
175
175

180 34
1000 1300 610

6-ø12 180
120x200
120
1500 200
120
1000
500 500
38 120 R7
50 1205
100

250 100
650

2070
1300
1800

85 50
(865)

R7
650

200
100

630
250

38
610

220
100
280

250

370

12 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

252kV SF6 Breaker

LW24-252
outline and foundation drawing
LW24-252
3000 - 4000 3000 - 4000
(2860)

P1 P2

(5165)

(2511)

591
1220

1320
Phase A Phase B Phase C
P1 P1 P1
t22 Aluminum 9-φ18
Alloy Plate A-A

45 45
2860

145
.5
R9

A A
45 45 45

Terminal Pad Grounding Block


800 800

P2
10

P2 P2
10

800


10

924

Cement
A-A Foundation
70

Anchor Bolt
320 M30*800 Grounding
E E E
Position (2 places)
245
1220

220
1380
1380

A
245

A E E 320 C E
300

500

All measurements
145 C
are in millimeters (mm)

373

GEDigitalEnergy.com 13
Dead Tank Circuit Breakers — 72.5–800kV

363kV SF6 Breaker


LW23-363/ Y
363kV DTB with single-breaker
LW23-363
4000-5000 4000-5000

873

510
700
920

(3463)
6534

1500

(1438)

14 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

363kV SF6 Breaker


LW13-363/Y
Outline Drawing of 363kV DTB
with double-breakers

LW13A-363

5000 5000

2180
2200

200
1000
1120

5
84

800
4620

1100

2500
7300

Anchor Bolt
3325

M30X800
80
1800

800

820

All measurements
are in millimeters (mm)
125

GEDigitalEnergy.com 15
Dead Tank Circuit Breakers — 72.5–800kV
LW13A-550/Y
550kV DTB
Outline Drawing

550kV SF6 Breaker

LW13A-550
Phase A
Phase C Phase B
8000 8000

80

2450
I

2850
(1000)
(1180)

800
5
R=84

80

1100
0
30
0
1500

6190
8395

Anchor Bolt
M30X1000
1000 105

1000
2150

3195

1600

150
All measurements
125
800 are in millimeters (mm)

16 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

800kV SF6 Breaker

LW13-800
General Assembly Drawing LW13-800 DTB

10249
11000 11000
7607

4681

12966
13146
12108
3000
3820

560

2000

3820
3864
4239
Grounding Ground
1680

LCP
Block
800

630

500
1460
500

1580 4523
190

5620

P1 P1 P1

Terminal Pad
36

LCP 9-Ø24 65 65 65

R900
65 65
220

Aluminum
Alloy Plate

P2 P2 P2

Size of
Grounding Block

Copper Soldering
70*70
70
40

70

15 100
15

130

GEDigitalEnergy.com 17
Dead Tank Circuit Breakers — 72.5–800kV

Technical Specifications

Main Technical Data of 72.5kV-800kV Dead Tank Circuit Breaker*


PRODUCT TYPE LW24-72.5 LW24-126 LW24- 145 LW24-252 LW23-363 LW13A-363 LW13A-550 LW13-800
1. Electrical Parameters
1. 1 Rated voltage (kV) 72.5 126 145 252 363 363 550 800
1. 2 Rated frequency (Hz) 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
3150/4000/ 3150/4000/
1. 3 Rated continuous current (A) 3150 3150 3150 4000 5000 5000
5000
1. 4 Rated short circuit
40 40 31.5/40 50/63 50 50/63 50/63 50/63
breaking current (kA)
1. 5 Making current (kA) 100 100 80 125 125 125/160 135/171 135/171

1. 6 Rated peak withstand current (kA) 100 100 80 125 125 125/160 135/171 135/171

1. 7 Specific creepage distance (mm/kV) 25/31 25/31 25/31 25/31 25/31 25/31 25 25

1. 8 Short line fault breaking current (kA) 36/30 36/30 28.35/23.63 45/37.5 45/37.5(50kA); 56.7/47.25(63kA)

1. 9 Out of phase breaking current (kA) 10 10 7.875 12.5 12.5(50kA)/15.75(63kA)

1. 10 Rated short-time power-frequence


withstand voltage (kV): To earth 160 230 275 460 510 510 740 960
1. 11 Rated lightning impulse withstand
voltage (kV): To earth 350 550 650 1050 1300 1300 1675 2100
1.12 Last pole to clear factor 1.5 1.5 1.5 1.3 1.3 1.3 1.3 1.3
1.13 Rated short-time withstand
duration(s) 4 4 3 3 3 3 3 3

PRODUCT TYPE LW24-72.5 LW24-126 LW24- 145 LW24-252 LW23-363 LW13A-363 LW13A-550 LW13-800
2. Mechanical Parameters
Spring/ Spring/ Spring/
2. 1 Type of mechanism Spring Spring Spring Hydro-mechanical
Hydro-mechanical Hydro-mechanical Hydro-mechanical
2. 2 Mechanical endurance (times) ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000 ≥ 5000
2. 3 Rated operating sequence O-0.3s-CO-180s-CO
2. 4 Close time (ms) ≤100 ≤100 ≤100 ≤110 ≤100 ≤100 ≤100 ≤100
2. 5 Open time (ms) ≤30 ≤30 ≤30 ≤30 ≤20 ≤20 ≤20 ≤20
2. 6 Breaking time (ms) ≤60 ≤60 ≤60 ≤60 ≤40 ≤40 ≤40 ≤40
2. 7 Close-open time (ms) 40-50 40-50 40-50 50-70 40-50 40-50 40-50 40-50
2. 8 Operating asynchronism (ms)
Between poles ≤2 ≤3 ≤3 ≤3 ≤3 ≤3
Open ≤4 ≤4 ≤5 ≤4 ≤4 ≤5
Close
2. 9 Operating asynchronism (ms)
Across break ≤2 ≤2 ≤2 ≤2
Open ≤3 ≤3 ≤3 ≤3
Close
2. 10 Number of breaks per pole 1 1 1 1 1 2 2/1 2
2. 11 Three phase operation/
3p 3p 3p 3p/1p 1p 1p 1p 1p
single phase
2. 12 Rated SF6 gas pressure (Mpa) 0.4/0.5 0.5 0.5 0.6 0.5 0.5 0.5/0.6 0.6
2. 13 Leakage of SF6 gas per year (%) ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5 ≤0.5
2. 14 Weight (kg) 1550 3400 3400 9000 10000 18000 18000/15000 60000

* Additional products available - see product


ordering page for complete listing.

18 GEDigitalEnergy.com
Dead Tank Circuit Breakers — 72.5–800kV

Ordering

LW * - * / * * - *
SF6 Circuit Breaker
Outdoor LW
Design Sequence No. 24
13/ 13A
23
Rated Voltage 72.5
126
145
252
363
550
800
Operating System:
T: Spring Mechanism T
Y: Hydro-mechanical Mechanism Y
Rated Current (A) 1250
2000
3150
4000
5000
Rated Interrupting Current (kA) 31.5
40
50
63

Dead Tank Circuit Breaker Product Line Dead Tank Circuit Breaker Product Line
With Spring Mechanism: With Hydro-mechanical Mechanism:

LW24-72.5/T1250-31.5 LW24-252/Y4000-63

LW24-72.5/T2000-31.5 LW23-363/Y3150-50
LW24-72.5/T2500-31.5 LW23-363/Y4000-50
LW24-72.5/T3150-40 LW13A-363/Y3150-50
LW24-126/T3150-40 LW13A-363/Y4000-50
LW24-145/T3150-31.5 LW13A-363/Y5000-50
LW24-145/T3150-40 LW13A-363/Y3150-63
LW24-252/T4000-50 LW13A-363/Y4000-63
LW13A-363/Y5000-63
LW13A-550/Y5000-63
LW13-800/Y5000-63

Ordering Notes: Please provide the following information when ordering:

1. Type, description of product, and type of mechanism. Toll Free: 1.877.605.6777


2. Rated voltage, rated current, short circuit breaking current.
Direct: 678.844.3777
3. Current ratio, accuracy class and quantity, rated output capacity.
gedigitalenergy@ge.com
4. Pollution class: class III or class IV.
5. Control voltage of mechanism: DC220V or DC110V.
2018 Powers Ferry Road,
6. Voltage of energy-store motor: AC380V or AC/DC 220V or AC/DC 110V.
Atlanta, GA 30339

GEDigitalEnergy.com 19
GEDigitalEnergy.com

Digital Energy
Toll Free: 1.877.605.6777
Direct: 678-844-6777
gedigitalenergy@ge.com

2018 Powers Ferry Road, Atlanta, GA 30339

GE, the GE monogram, Primary Plus and Multilin are trademarks of the General Electric Company.

XD Electric is a registered trademark of China XD Electric Group. XIHARI is a registered trademark


of the Xi’an High Voltage Apparatus Research Institute Co., Ltd. IEC is a registered trademark
of Commission Electrotechnique Internationale. IEEE is a registered trademark of the Institute
of Electrical Electronics Engineers, Inc. ISO is a registered trademark of the International

g
Organization for Standardization. OSHA is a registered trademark of the U.S. Department of
Labor. KEMA is a registered trademark of DNV.

GE Digital Energy reserves the right to make changes to specifications of products described at
any time without notice and without obligation to notify any person of such changes.

Copyright 2013, General Electric Company.

GEA-12723B(E)
English
131220

You might also like