SPM-D11 Series: Load Share Synchronizer
SPM-D11 Series: Load Share Synchronizer
37292D
SPM-D11 Series
Load Share Synchronizer
APPLICATIONS DESCRIPTION
· Load/var sharing
The SPM-D11 is a microprocessor-based synchronizer Protection ANSI #
designed for use on one or three-phase AC generators · Single-phase CT sensing for generator · Generator protection
equipped with Woodward or other compatible speed · Two-phase sensing of generator voltage
controls and automatic voltage regulators. The SPM-D11 · Synchronization for one
· Generator over-/undervoltage (59/27)
synchronizer provides automatic frequency, phase and
· Generator over-/underfrequency (81O/U) circuit breaker
voltage matching using either analog- or discrete output
· Generator reverse/reduced power (32R/F) · Frequency, phase, and
bias signals.
· Generator overload (32)
It combines synchronizing for one circuit breaker, load and voltage matching
power factor control or isochronous load sharing and Control outputs
generator protection. · Selectable types of
LSXR Package
· Analog bias outputs for voltage and speed control output
DESCRIPTION freely configurable for all levels (+/-1 V, +/- · Digital display of
3 V, 0 to 5 V, 0.5 to 4.5 V, +/-10 V +/-5 V, 0
Synchronizing to 20 mA, +/-20 mA, and much more
generator and bus
· Phase match or slip frequency synchronization with configurable) values
voltage matching · Speed bias output configurable as 500 Hz
· Two-phase sensing of generator and bus PWM output and adjustable voltage level
· Real power control
· Selectable operating modes like SPM-A (Run, Check, · Two raise/lower outputs configurable for
Permissive, and OFF)
· Power factor control
either speed or voltage
· Synchro-check possible · PC and front panel
· Synchronization time monitoring Operating Features configurable
· Load/var sharing · Two-line Liquid Crystal display for operation
Mains parallel operation and alarm indication · Microprocessor
· Synchroscope technology for flexible
· Real power control
· Indication of control activity and breaker and reliable operation
· True RMS power calculation state
· Generator real power setpoint by parameter (2 values) or
via 0/4 to 20 mA
· Multi-level password protection for · CE marked
parameters
· Soft unloading · Configuration directly or via PC · UL/cUL listed
· Power factor control · English or German language adjustable
· Power factor setpoint by parameter
· Power limit value with relay output
Isolated operation
· Frequency control
· Voltage control
Dead bus operation
· Closing of breaker on demand
DIMENSIONS
Configuration port Configuration port Front view
35
65
72
27
48 25
144
50 54
136
179
01 24
SPM-D
SPM-D11
The presence of the terminal strips
depends on the Package configuration
PWM
GND
GND
GND
GND
GND
VA
IA
VA
IA
N/C
N/C
11 12 13 8 9 10 8 9 10 8 9 10 8 9 10 11 12 13 11 12 13
0 1 2 5 6 7 18 19 27 28 29 30 16 17 37 38 41 42 43 44 45 46 47 48
Control:
Drive
L2
alternatively Generator voltage Reverse/reduced power
overload N.C.
L1
3
s1 (k)
Power
Generator current L1 limit value N.C.
s2 (l)
CB
SPM-D11
0 to 20 mA
N.O. Command: close CB External real power setpoint value
GND
Command: open CB
N.O. (for shutdown) Ready for operation N.O.
3
L2 Common (term. 3, 4, 5, 6)
alternatively Mains voltage or #Battery
Busbar voltage Release control or
L1 Setpoint power
All relays are open if the unit is de-energized Release isolated operation / dead bus
N.O.: The relay closes if the command is issued
or the function is fulfilled - Power supply
N.C.: The relay opens if the function is triggered
+ Power supply (refer to label for actual rating Vaux)
ü
Load/var sharing ü
I/O's
Alarm relays 3
Signalling relays 3
Listings/Approvals
CE marked ü
UL/cUL listed ü
Accessories
Configuration via PC #3 ü
Manuals (for other languages please refer to the Woodward homepage)
English 37259
German GR37259
Voltage ratings
Subject to technical modifications. Power supply 12/24 Vdc
Discrete inputs 12/24 Vdc
This document is distributed for
informational purposes only. It is not Part numbers P/N
to be construed as creating or Measuring inputs 100 Vac, ../1 A 8440-1705
becoming part of any Woodward Measuring inputs 100 Vac, ../5 A 8440-1706
Governor Company contractual or Measuring inputs 400 Vac, ../5 A #4 8440-1666
warranty obligation unless expressly
#1 Additional mains decoupling relay like MFR11 required
stated in a written sales contract.
#2 Configurable to either speed/load or voltage/power factor
#3 Configuration software ‘LeoPC’ available free at Woodward.com,
We appreciate your comments
RS232 connection requires Woodward DPC cable P/N 5417-557
about the content of our
#4 All units with 400V measuring inputs can also be used for 100V system voltage
publications. Please send comments
including the document number
below to
stgt-doc@woodward.com
© Woodward
37292D - 2012/6/Stuttgart