Product Specification

37292D

SPM-D11 Series
Load Share Synchronizer

APPLICATIONS DESCRIPTION
· Load/var sharing
The SPM-D11 is a microprocessor-based synchronizer Protection ANSI #
designed for use on one or three-phase AC generators · Single-phase CT sensing for generator · Generator protection
equipped with Woodward or other compatible speed · Two-phase sensing of generator voltage
controls and automatic voltage regulators. The SPM-D11 · Synchronization for one
· Generator over-/undervoltage (59/27)
synchronizer provides automatic frequency, phase and
· Generator over-/underfrequency (81O/U) circuit breaker
voltage matching using either analog- or discrete output
· Generator reverse/reduced power (32R/F) · Frequency, phase, and
bias signals.
· Generator overload (32)
It combines synchronizing for one circuit breaker, load and voltage matching
power factor control or isochronous load sharing and Control outputs
generator protection. · Selectable types of
LSXR Package
· Analog bias outputs for voltage and speed control output
DESCRIPTION freely configurable for all levels (+/-1 V, +/- · Digital display of
3 V, 0 to 5 V, 0.5 to 4.5 V, +/-10 V +/-5 V, 0
Synchronizing to 20 mA, +/-20 mA, and much more
generator and bus
· Phase match or slip frequency synchronization with configurable) values
voltage matching · Speed bias output configurable as 500 Hz
· Two-phase sensing of generator and bus PWM output and adjustable voltage level
· Real power control
· Selectable operating modes like SPM-A (Run, Check, · Two raise/lower outputs configurable for
Permissive, and OFF)
· Power factor control
either speed or voltage
· Synchro-check possible · PC and front panel
· Synchronization time monitoring Operating Features configurable
· Load/var sharing · Two-line Liquid Crystal display for operation
Mains parallel operation and alarm indication · Microprocessor
· Synchroscope technology for flexible
· Real power control
· Indication of control activity and breaker and reliable operation
· True RMS power calculation state
· Generator real power setpoint by parameter (2 values) or
via 0/4 to 20 mA
· Multi-level password protection for · CE marked
parameters
· Soft unloading · Configuration directly or via PC · UL/cUL listed
· Power factor control · English or German language adjustable
· Power factor setpoint by parameter
· Power limit value with relay output
Isolated operation
· Frequency control
· Voltage control
Dead bus operation
· Closing of breaker on demand

FURTHER SPM-D SYNCHRONIZERS


· The SPM-D10 Series provides two-phase generator and bus measurement
refer to product specifications 37297 for more information
· The SPM-D10/YB Series provides three-phase generator and bus measurement
refer to product specifications 37298 for more information
SPECIFICATIONS (for more see specific manuals)
Accuracy .......................................................................................... Class 1 Relay outputs ................................................................................ isolated
Power supply 12/24 Vdc (9.5 to 32 Vdc) Contact material ............................................................................... AgCdO
Intrinsic consumption ..................................................................max. 10 W Load (GP)......................................................................2.00 Aac@250 Vac
Ambient temperature................................................................ -20 to 70 °C 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Ambient humidity...................................................... 95 %, non-condensing Pilot duty (PD) ..............................................................................................
Voltage .....................Rated /D: [1] 66/115 Vac or [4] 230/400 Vac 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Maximum value (Vmax): [1] 150 Vac or [4] 300 Vac Housing ......................................................Type APRANORM DIN 43 700
Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac Dimensions .......................................................................144×72×122 mm
Rated surge voltage: [1] 2.5 kV or [4] 4.0 kV Front cutout ............................................................ 138[+1.0]×67[+0.7] mm
Measuring frequency................................................................. 40 to 70 Hz Connection ................................................ screw/plug terminals depending
Linear measuring range up to ....................................................... 1.3×Vrated on connector 1.5 mm² or 2.5 mm²
Input resistance ................................................. [1] 0.21 MW, [4] 0.696 MW Front .................................................................................insulating surface
Max. power consumption per path ................................................ < 0.15 W Protection system .................................................. with correct installation
Current (Irated) ................................................................. [1] ../1 A, [5] ../5 A Front ................................................. IP42
Linear measuring range up to ........................................................ 3.0×Irated (sealed IP54; gasket kit = P/N 8923-1037)
Load ............................................................................................. < 0.15 VA Back ................................................. IP21
Rated short-time current (1 s) .................................[1] 50×Irated, [5] 10×Irated Weight ............................................... depending on version, approx. 800 g
Discrete inputs .............................................................................. isolated CE approval .........................tested according to applicable EN guidelines
Input range ................................................... 12/24Vdc or 18 to 250 Vac/dc Listings ......................................... UL/cUL listed (voltages up to 300 Vac)
Input resistance .................................................... approx. 6.8 kW or 68 kW

DIMENSIONS
Configuration port Configuration port Front view
35
65
72

27

Back plate mount


option (please order
brackets P/N 8923-1023)
Bottom view
108.8 50

Back view with


connecting terminals

48 25
144

50 54
136

179

01 24

SPM-D
SPM-D11
The presence of the terminal strips
depends on the Package configuration

2008-04-28 | SPM-D Dimensions spmdww-0818-ab.SKF


WIRING DIAGRAM

Frequency / Real Power Voltage / Power Factor

The socket for the PC configuration


is situated on the side of the unit.
PWM Voltage Current Voltage Current

Speed Speed Speed


Governor Governor Governor AVR AVR

PWM
GND

GND

GND

GND

GND
VA

IA

VA

IA
N/C

N/C
11 12 13 8 9 10 8 9 10 8 9 10 8 9 10 11 12 13 11 12 13

0 1 2 5 6 7 18 19 27 28 29 30 16 17 37 38 41 42 43 44 45 46 47 48
Control:
Drive

- frequency lower (f-) N.O.


SPEED / REAL POWER - voltage lower (V-)
Analog controller
Control:
- frequency higher (f+) N.O.
- voltage higher (V+)
G

VOLTAGE / POWER FACTOR


Analog controller Generator overfrequency
generator underfrequency N.C.

SPM-D11/LSXR (Synchronizing Unit) Generator overvoltage


generator undervoltage N.C.
23 24 39 40 14 15 3 4 25 26 20 21

L2
alternatively Generator voltage Reverse/reduced power
overload N.C.
L1
3

s1 (k)
Power
Generator current L1 limit value N.C.
s2 (l)

Reply: CB is open var sharing 0 to 4 Vdc


SPM-D11
Enable CB Load sharing 0 to 4 Vdc
CB

CB

SPM-D11
0 to 20 mA
N.O. Command: close CB External real power setpoint value
GND

Command: open CB
N.O. (for shutdown) Ready for operation N.O.
3

L2 Common (term. 3, 4, 5, 6)
alternatively Mains voltage or #Battery
Busbar voltage Release control or
L1 Setpoint power
All relays are open if the unit is de-energized Release isolated operation / dead bus
N.O.: The relay closes if the command is issued
or the function is fulfilled - Power supply
N.C.: The relay opens if the function is triggered
+ Power supply (refer to label for actual rating Vaux)

Reference point (terminal 29/30)


Subject to technical modifications. 2006-01-26 | SPM-D11 Wiring Diagram spmd11ww-0406-ap.SKF
FEATURES OVERVIEW
International
Woodward
PO Box 1519 SPM-D Series
Fort Collins CO, USA
80522-1519 Synchronizer SPM-D11/LSXR
1000 East Drake Road 12/24 Vdc
Fort Collins CO 80525
Ph: +1 (970) 498-3634
Fax: +1 (970) 498-3058
email: Measuring/Display
SalesPGD_NAandCA@woodward.com
Generator voltage, 2phase ü
Europe Generator current, 1phase ü
Woodward GmbH Busbar voltage, 2phase ü
Handwerkstrasse 29 Control
70565 Stuttgart, Germany
Breaker 1
Ph: +49 (0) 711 789 54-510
Fax: +49 (0) 711 789 54-101 Synchronization, 2phase ü
email: Isolated operation ü
SalesPGD_EMEA@woodward.com Mains parallel operation #1 ü
SPM-A synchronization modes ü
Distributors & Service Dead bus operation ü
Woodward has an international
network of distributors and Protection
service facilities. For your Generator: over-/undervoltage (59/27) ü
nearest representative, call the Generator: over-/underfrequency (81O/U) ü
Fort Collins plant or see the Generator: overload (32) ü
Worldwide Directory on our Generator: reverse power (32R) ü
website.
Generator: reduced power (32F) ü
Controller
www.woodward.com Discrete raise/lower: speed/load ü#2
Discrete raise/lower: voltage/power factor ü#2
Analog output: speed & load ü
Analog output: voltage & power factor ü
PMW output: speed & load ü
Active power setpoint: 0/4 to 20 mA
For more information contact:

ü
Load/var sharing ü
I/O's
Alarm relays 3
Signalling relays 3
Listings/Approvals
CE marked ü
UL/cUL listed ü
Accessories
Configuration via PC #3 ü
Manuals (for other languages please refer to the Woodward homepage)
English 37259
German GR37259
Voltage ratings
Subject to technical modifications. Power supply 12/24 Vdc
Discrete inputs 12/24 Vdc
This document is distributed for
informational purposes only. It is not Part numbers P/N
to be construed as creating or Measuring inputs 100 Vac, ../1 A 8440-1705
becoming part of any Woodward Measuring inputs 100 Vac, ../5 A 8440-1706
Governor Company contractual or Measuring inputs 400 Vac, ../5 A #4 8440-1666
warranty obligation unless expressly
#1 Additional mains decoupling relay like MFR11 required
stated in a written sales contract.
#2 Configurable to either speed/load or voltage/power factor
#3 Configuration software ‘LeoPC’ available free at Woodward.com,
We appreciate your comments
RS232 connection requires Woodward DPC cable P/N 5417-557
about the content of our
#4 All units with 400V measuring inputs can also be used for 100V system voltage
publications. Please send comments
including the document number
below to
stgt-doc@woodward.com

© Woodward

All Rights Reserved

37292D - 2012/6/Stuttgart