Professional Documents
Culture Documents
163 Guide For SF6 Gas Mixtures PDF
163 Guide For SF6 Gas Mixtures PDF
August 2000
Draft 7 (SC23 Final)
CIGRE WG 23.02
TASK FORCE 01
March 2000
SUMMARY
The present applications of SF6 mixtures in electrical power equipment are determined by
the forces driving their use: technical – avoiding SF6 liquefaction in circuit breakers,
financial – reducing capital expenses on SF6, and environmental – reducing the quantity
of SF6 to reduce emissions of SF6 to the atmosphere. This guide addresses the issues of
using an SF6 mixture, where SF6 is diluted by one other gas, typically nitrogen or CF4,
added at a concentration in the range of 5 to 90%. The practical application of SF6
mixtures in electrical equipment requires an understanding of their performance, both
environmental and functional, as well as methods and equipment for handling gas
mixtures.
The environmental impact of SF6 as a greenhouse gas is reviewed as the first step in
comparing the environmental performance of an application using undiluted SF6 with the
same application using an SF6 mixture. The basis for the comparison is a method for an
environmental Life Cycle Assessment. The comparison illustrates that mixtures with
nitrogen reduce the environmental impact, whereas mixtures with CF4 have no advantage
over undiluted SF6.
Handling SF6 mixtures entails both new and used mixtures of gases, and criteria for
safety, emissions, reuse, transport, and ultimately disposal. In most respects, the technical
definitions and criteria are the same as for undiluted SF6. The important new requirement
is to control the composition of the gas mixture, i.e. the concentration of SF6. Devices for
dynamic mixing of the gases while filling are preferable to diffusive mixing after filling.
Removal and storage of an SF6 mixture intended for reuse requires care to prevent partial
separation by liquefaction of the SF6. A gas mixture that will not be reused can be treated
to recover the SF6 by commercial methods, such as membrane separation and selective
sorption, as well as cryogenic condensation. If reclamation or separation is not feasible,
then disposal of an SF6 mixture by burning in an environmentally acceptable process may
be the only option.
1
1. INTRODUCTION
4. FUNCTIONAL PERFORMANCE
4.1 Insulation
4.2 Interruption in switchgear
4.3 Fault arcing
4.4 Gas deterioration
4.5 Leakage
4.6 Summary
7. CONCLUSIONS
8. REFERENCES
2
1. INTRODUCTION
SF6 has, however, been identified as a strong man-made greenhouse gas with
a high global warming potential and a long atmospheric lifetime of the order
of 3000 years [1]. Extensive research to find environmentally preferable
substitute gases for SF6 has been without success (e.g. [2]). It has also been
shown that it is difficult to substitute another gas for SF 6 without increasing
the total environmental impact of the equipment [3].
2. Diluting SF6 with a “synergistic” admixture gas such that the SF6
controls the insulation performance of the mixture more than in
proportion to its concentration.
There are two further motivations for using SF6 diluted in a gas mixture: to
reduce the cost of the gas required for equipment, and to prevent liquefaction
in equipment in cold climates. For the latter case, the partial pressure of the
SF6 is reduced to below its vapour pressure for the lowest ambient
temperature expected in a mixture with a non-condensing gas.
This document reviews the main aspects of SF6 mixtures for use in electric
power equipment, namely,
3
- the past, present and possibly future applications of SF6 mixtures in
electric power transmission and distribution equipment,
In this document, the only applications considered are those in which only
one admixture gas is purposely added at a significant concentration, typically
in the range 5 to 90%. The following issues are not treated :-
- mixtures of SF6 with contaminants that have already been treated in the
CIGRE Recycling Guide [4]),
The only admixture gases that are considered in detail are nitrogen and CF 4,
both of which are already in practical use.
The driving forces to use SF6 mixtures in electrical power equipment are as
follows:-
In the past the only driving force for using SF6 mixtures has been the need to
reduce its partial pressure at low ambient temperatures to avoid SF6
liquefaction. As admixture gases, both nitrogen and CF4 are in use; each has
a sufficiently low boiling point so as not to liquefy down to the lowest
ambient temperatures and up to the highest filling pressures of interest
(typically -50 oC and 500 kPa). Whereas nitrogen is environmentally neutral,
CF4 may be considered objectionable as it is also a strong greenhouse gas.
However, it should be noted that CF4 is a major by-product of various
industrial processes such as aluminium smelting and fluorochemistry from
which it is emitted at a rate of more than 10 000 tons/y [5]. The emission
from cold climate circuit breakers by leakage and handling is estimated to be
at least three orders of magnitude lower, hence insignificant.
5
Fig.2.1: SF6 liquefaction temperature Tliq as a function of SF6 concentration
in a mixture for 4 total pressures 100, 400, 600, and 800 kPa. Calculated
from the SF6 vapour pressure curve.
One of the drivers for mixing SF6 with other gases is to reduce the
environmental impact of the mixture by reducing the quantity of SF6 in use.
Clearly, the best choices for admixture gases are ones that have less impact
on the environment than SF6. One measure of the impact of a gas is its
6
global warming potential (GWP), a parameter that combines the greenhouse
effect of a gas on a molecular basis with its atmospheric lifetime. SF6 has
the largest GWP of all gases analysed to date, and CF4 also has a large
GWP. On the other hand, nitrogen is a major component of the atmosphere
and has no global warming potential. Therefore, there is practically no
environmental advantage to replacing SF6 with CF4, but there is an
advantage with nitrogen.
(2) Define the “horizon” of the study, e.g. which of its life cycle phases
(such as manufacturing, transport, erection, operation, decommissioning
and scrapping) are considered, which material production, energy
generation and transport scenarios are assumed, which types of
environmental impact are assessed, and which methodological approach
is to be applied.
7
(3) Establish a life cycle inventory (LCI) that quantifies all relevant
material and energy flows into the system and all emissions and waste
flows out of it, e.g:-
(a) the materials required and energies consumed to produce the
equipment, such as SF6, conductor and enclosure metals, insulator
materials, materials for support constructions and civil works,
materials for control equipment etc…
(b) the emissions and waste caused by producing these materials and by
the manufacturing processes,
(c) the energy losses in the equipment during its operational lifecycle
(for gas insulated equipment mainly ohmic losses in conductor and
enclosure), and
(d) the energy losses and emissions associated with the
decommissioning, scrapping and recycling of the equipment at its
end of life.
(4) The Life Cycle Impact Assessment (LCIA) phase derives from the LCI
data the corresponding environmental impacts such as emissions relevant
to climate. All impact data are quantitatively aggregated in units of
primary fuels consumed and the associated CO2 emitted so that a total
global warming potential (GWP) can be assigned.
(5) The Life Cycle Interpretation phase combines the LCI and LCIA data
to derive conclusions and recommendations in the framework of the
horizon of the study.
where (E/p)cr,o is the pressure reduced critical field of undiluted SF 6 and f()
is a dimensionless correction function characterising the insulation synergy
of the gas mixture (see Fig. 4.1).
Firstly, the SF6 inventory contained in the equipment is reduced by the factor
/f( This inventory is the relevant quantity for handling losses and
accidental releases. Secondly, the leakage rate of SF6 through sealings and
other small porosities is driven by the partial pressure of the SF6. It is thus
proportional to pmix, so that it is reduced, with respect to undiluted SF6
insulation, by the factor
*
(Note: Some care is required even with this simple approach as increasing pressure may make the equipment
more susceptible to defect failure.)
9
i.e. by the same factor as the inventory Eq. 3. Thus, provided that the
handling efficiency of the SF6 mixtures is the same as for undiluted SF6, both
handling and leakage losses of SF6 from the system are reduced by the factor
/f( As this factor increases slightly more than proportionally with one
arrives at the following conclusions:-
(1) Diluting SF6 in a mixture can reduce SF6 emissions, e.g. an SF6
concentration of 10% can reduce the SF6 emissions by about 85%.
The above statements are only valid if the mixture is handled with the same
efficiency as undiluted SF6.
3.4 Summary
4.1 Insulation
0.9 SF6-N2
0.8
0.7 SF6-CF4
0.6
f
0.5
0.4
0.3
0.2
0.1
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Fig. 4.1 Normalised dielectric strength functions f() of SF6 mixtures with
nitrogen and with CF4 as a function of the SF6 volume concentration .
It is seen that:-
(1) The insulation performance of SF6 mixtures with nitrogen and with
CF4 is always lower than that of undiluted SF6.
11
(2) SF6 with a high percentage of admixed nitrogen (~ 80 – 95%)
exhibits a strong insulation synergy, i.e. an influence of the SF6
greater than in proportion to its concentration.
At equal gas pressure, N2/SF6 mixtures are less sensitive to defects than
undiluted SF6. The relative reduction of the dielectric strength by particles is
approximately related to the reduction of the critical field [14,16,17].
12
It can thus be concluded that:-
Gas insulated lines (GIL) are expected to become one of the major
applications of SF6 / Nitrogen mixtures in the future. As they exhibit some
specific features due to their extended length, their insulation co-ordination
and testing will be briefly discussed. This topic is being treated in the CIGRE
GIL Joint Working Group SC 33/21/23. Some ideas have already been
published in Ref. 21.
The type test shall be carried out on a portion of GIL around 20 m long. It
gives a guarantee of the insulation levels (U w) based on 20 m of GIL for the
3 standard test voltage waveforms AC, LI and SI.
The on-site test shall be performed on portions of GIL from 300 to 1000 m
length with the 3 standard shapes AC, LI and SI but at levels (U ES) lower
than those of the type test. It is proposed to apply UES = 0,8 Uw
During the on-site test the voltage enhancement within the GIL during LI-
testing has to be considered. It is proposed to apply only an AC-test as
recommended in Ref. 6 with a test level UES (AC) = 0,8x0,5xLIWL followed
by a PD test.
For example, oscillating impulse voltages can be applied [22]. For a GIL
length of 1000 m a front duration of 30 s has to be realised by a sufficient
coil inductance to obtain equal crest voltages in the whole GIL. In the case of
a front duration of 10 ms, as often used in GIS, there are deviations of more
than 10 % along the GIL.
For cold climate applications in which the SF6 partial pressure is reduced to
prevent liquefaction of the gas, a derating of the short-circuit interruption
performance results, which is illustrated by the data in Table 4.1 for the case
of a 145 kV circuit-breaker.
To realise operating temperatures that are even lower than those shown in
Table 4.1 (e.g. -50°C) and to compensate the derating at least in part, SF 6/N2
and SF6/CF4.are usually admixed. Table 4.2 shows the performance
improvement obtained in this way at various test duties.
Table 4.1: Example for the influence of the SF6 gas pressure on the
interruption performance of a high-voltage circuit-breaker
14
Pure nitrogen or low SF6 partial pressures result in an extreme derating of the
interruption performance [23,24] due to the much reduced arc cooling
efficiency and dielectric strength, with the consequence that such mixtures
cannot be efficiently used in circuit breakers that were originally designed
for undiluted SF6.
Internal arcs within SF6-insulated equipment are normally the severest fault
condition. They are caused by a short-circuit between the live parts of the
equipment and the grounded enclosure. The fault current can reach several
tens of kA with durations of several 100 ms. The arc in the enclosure causes
a rise of pressure which eventually leads to the bursting of the rupture
diaphragms provided for that very purpose and, in extreme cases, even burn-
through of the enclosure.
15
The pressure rise p scales with the arc energy
ui dt introduced into the
enclosure divided by the enclosure volume V.
p = ( –1)
ui dt /V (5)
Here, is the adiabatic exponent of the gas which is 1.4 for nitrogen, 1.07 for
SF6 and correspondingly takes intermediate values in mixtures. The voltage u
developed by an internal arc depends, among other parameters, on the
enclosure geometry, the gas, the current and the used materials. It is
empirically found to range between 0.8 and 1.4 kV, depending on the
enclosure design, which determines the arc-length. Fig.4.2 shows the
pressure rise according to Eq. 5. This relation is used to dimension the
mechanical strength of the enclosure for a given internal arc current and
arcing-time.
In reality the pressure rise is measured to be lower than the one predicted by
Eq. 5 and Fig. 4.2. The main reasons are that part of the arc energy is taken
up by the enclosure and that the specific heat of the SF6 starts to depend on
the temperature above about 1600 K. The first effect increases with
increasing surface area and with higher temperatures of the heated gas. A
detailed calculation procedure is described in Ref. 25. Fig. 4.3 shows the
result of the calculation together with measured values and with the limiting
curve according to Eq. 5 for reference. It is seen that at low energy input the
deviation is relatively small. For higher energy input the influence increases
and the dependence of the pressure rise on energy is no longer linear.
9
8 100% N2 / 0% SF 6
pressure in enclosure in MPa
0
0 5 10 15 20 25
W/Vol. in MJ/m³
Fig. 4.2: Pressure rise as a function of arc-energy per unit volume (filling
pressure 700 kPa, energy dissipation neglected)
16
5
3.5
3
with energy-dissipation
2.5
0.5
0
0 5 10 15 20 25
W/Vol. in MJ/m³
Fig. 4.3: Pressure rise as a function of arc-energy per unit volume starting
from a filling pressure of 700 kPa. Gas mixture 80% N2 / 20% SF6. Current
50 kA and Volume V = 650 l. Broken curve: without energy-dissipation;
solid curve: with energy dissipation, crosses: measured values.
During equipment operation and gas handling the gas mixture may be
subject to various deterioration processes that affect its functional
performance once certain levels are exceeded. The major contaminants, their
origins and their deteriorating effects on the functionality of the equipment in
SF6-N2 mixtures are summarised in Table 4.4.
Humidity has the same effect in mixtures as in undiluted SF6. When its
concentration becomes so high that water vapour can condense on insulator
surfaces, electrolytically conducting surface layers are created and lead to
surface flashover. Humidity control in SF6 mixtures should therefore be the
same as in undiluted SF6 [4, 26].
18
Table 4.3: Major contaminants, origins and deteriorating effects in SF6-N2
mixtures.
19
might be generated. As the discussion here is restricted to the admixture
gases nitrogen N2 and CF4, and as CF4 is already a common decomposition
product in undiluted SF6, it is sufficient to discuss nitrogen as a new reaction
partner.
4.5 Leakage
From a functional point of view the leakage of both SF 6 and admixture gas is
important. According to IEC 60694, leakage of equipment has to be less than
1% p.a. Modern equipment shows values clearly smaller than 0.5% p.a., on
the order of 0.2% p.a.. Although the leakage flow of each gaseous
component of the mixture is proportional to its partial pressure, this fact does
not play a significant part during equipment operation because of the very
low leakage rates.
20
Other than the recalibration of SF6 density monitors, there are no practical
consequences for gas monitoring and service intervals of equipment filled
with SF6 mixtures.
For topping up, i.e. for filling in small gas quantities, pre-mixed gas should
be used.
4.6 Summary
Fault arcing in an SF6 mixture will result in a greater pressure rise than in
undiluted SF6, for the same conditions. Apart from the temporary pressure
rise, there will also be decomposition products. The major decomposition
products in SF6 mixtures are the same as in undiluted SF6, and the total
production tends to decrease with decreasing SF6 content.
SF6 mixtures are available for use in electric power equipment in premixed
form supplied by gas suppliers (“new” SF 6 mixture), as component gases
(“new” gases) in separate containers from which they have to be mixed on-
site by an adequate mixing procedure, as a mixture that has been previously
recovered from equipment, purified and checked to be suited for reuse.
21
As in the case of undiluted SF6, it should be noted that:-
In the following, the terminology for handling and recycling used SF6
mixtures will be used, in line with the CIGRE SF6 Recycling Guide [4], see
Table 5.1.
Prior to handling, the gas has to be assigned to one of three categories for
used gas mixtures, which define the handling modalities and personnel
protection measures.
Non-arced gas is gas from equipment for which it is known that no arcing
has occurred. Such gas does not constitute a toxic hazard, and personnel
protection measures are not required.
Heavily arced gas that has experienced internal arcing or circuit breaker
failure requires handling by personnel wearing gloves, safety goggles,
protective overalls and respirators.
Thus:-
The safety measures defined for undiluted SF6 cover those for SF6
mixtures.
Gas mixture handling operations on-site include evacuation of the air from
the equipment prior to filling it with the gas mixture, recovering the gas from
the equipment, its reclaiming (purification), subsequent quality checking,
intermediate storage and, finally, reuse on-site or off-site. The totality of
these functions are provided by devices which are referred to as reclaimers.
Devices which are only capable of recovering the mixture, without purifying
it, will be referred to as recoverers.
After having been processed by the reclaimer the gas mixture has to undergo
a quality check, as a result of which it can be assigned to one of the two
reuse categories “suited for reuse” or “not suited for reuse” in electric power
22
equipment. The criteria for this assignment are limit contamination levels
(see Section 5.3).
Gas that is not suited for reuse requires transportation to a site where further
treatment is possible. For this purpose it has to be assigned to a transport
category. Two transport categories are proposed, “non-toxic” and “toxic and
corrosive”, based on limit contamination levels of toxic and corrosive
decomposition products (see Section 5.3).
23
Table 5.1. Summary of technical terms used in recycling SF6 – N2 mixtures
Recovery
Evacuation
Filling
Purification Reclaim
Gas Storage ing
handling Quality check
operations Composition Recycling
correction
Reuse
Transportation
Further treatment off-
site
- N2-SF6 separation
- Final disposal
The gas mixture handling devices mentioned above are subdivided into the
following categories:
24
- Mixing and composition control devices which serve to produce the
mixture from the component gases or to correct the composition of an
already existing mixture,
- Reclaimers which can recover a gas mixture from equipment, purify it,
check its quality for reuse and refill it into equipment,
The main characteristics of the above devices are summarised in Table 5.2.
Details are described in Sections 6.2 – 6.7.
25
1)
As for undiluted SF6, see CIGRE SF6 Recycling Guide
2)
1 mbar is recommended and feasible with modern equipment
3)
To be specified for specific gas volume V and connecting piping (length and diameter)
4)
In this case, the ratio of residual recovery pressure to filling pressure (see Section 5.2).
The key environmental criterion for all gas handling processes is the gas
release rate associated with a gas handling operation cycle. It is defined as
the ratio
This rate measures the care with which the gas is handled. A benchmark
value for is 1%, given by standard handling technology of undiluted SF6
[4].
Reuse criteria have already been defined for undiluted SF6 in the CIGRE SF6
Recycling Guide [4] and are now in the process of being implemented in the
international standard IEC 60480 [10]. The values proposed in the CIGRE
SF6 Recycling Guide have been used to specify analogous figures for SF 6
mixtures. The results are summarised in Table 5.3 and Fig. 5.1. They are
expressed in terms of volume concentrations referred to the total gas mixture.
Except for the concentration of non-reactive gases, the reuse criteria remain
identical with those for undiluted SF 6. For the admixture gases N2 and CF4,
the reuse criterion has to be re-formulated as these gases are now intended
components of the mixture. Instead of specifying a limit concentration of
these components it is practical to specify limits for the SF6 concentration.
It is proposed that:-
26
Table 5.3: Reuse criteria for SF6 mixtures based on the corresponding
criteria for undiluted SF6 as proposed in the CIGRE SF6 Recycling Guide.
Figure 5.1: Humidity criteria for the reuse of SF6 mixtures: Maximum
admissible humidity concentrations as a function of the total filling pressure.
Solid curve: threshold above which condensation of humidity results in
insulation degradation (Dew point = -5 oC). Dotted curve: maximum
27
admissible concentration for reuse proposed in [4] (Dew point = -15 oC).
Broken curve: requirement for new SF6 [33].
As with SF6, the transport criteria for SF6 mixtures have to be established
according to the concentration of toxic and corrosive decomposition products
as these are the only components that determine the health hazard associated
with the gas mixture.
The resulting transport criteria are summarised in Table 5.4. Note that the
ADR classification refers to Europe. Outside Europe the local transport
authorities should be consulted.
Also, note that the transport classification for used SF6 mixtures that meet the
reuse criteria specified in Section 5.3 are the same as for unused mixtures.
1) Based on present ADR regulations which refer to Europe. In any case we recommend
to confirm the packaging and labelling requirements with the local transport
authorities.
2) Regulation for liquefied gas adopted as worst case
It is expected that most of the gas mixtures recovered from electric power
equipment can be purified and corrected for reuse on-site if appropriate
reclaimers are available.
5.4 Summary
The technical terms for handling SF6 mixtures are in line with the
terminology described in the CIGRE SF6 Recycling Guide for used SF6. As
a result, the safety measures defined for undiluted SF6 also correspond to
SF6 mixtures. The key environmental criterion for all gas handling processes
is the gas release rate: the benchmark value for standard handling of SF6 is
1%.
The criteria for reuse of SF6 mixtures are based on the limit concentrations of
contaminants. These are similar to the values for undiluted SF6 except that
the admixture gas is now an intentional component and so must have a
concentration appropriate to the application. Most of the gas mixtures
recovered from electrical equipment should be capable of being treated on
site for reuse.
Mixing and composition control devices serve to mix SF6 with other gases
from separate reservoirs (e.g. cylinders) in the desired proportion or to
correct the SF6 concentration of an available mixture to the desired value.
For small equipment volumes, gases from separate reservoirs can be mixed
manually by filling to the designated SF 6 partial pressure and then topping-
up with the admixture gas to the desired total pressure. The composition of a
mixture already contained in equipment can be corrected by adding one or
the other component gas. When using these procedures, the gas cannot be
considered as sufficiently mixed until after a waiting period, a characteristic
mixing time tmix. An upper limit for this time is the time for diffusive mixing,
the slowest mixing process which is approximately
29
tmix = L2/D (7)
where L is the longest segment length of the enclosure and D [m2/s] is the
mutual diffusivity of the mixed gases. D is given approximately by the
relation
D = k/p (8)
In extended structures such as large GIS and GIL, tmix may be unacceptably
long due to the large segment length L of the equipment. In this case a
dynamic mixing device is required to mix the component gases, or to correct
the mixture composition, before they pass through the inlet valve to the
equipment. Such devices are commercially available for SF6-N2 mixtures
[32,33]. They use microprocessor regulated proportional valves and
temperature control, and can be programmed to the desired mixture
composition and filling pressure. They can process both component gases
and mixtures.
As gas filling into power equipment is not associated with losses to the
atmosphere the associated loss rate is practically zero, unless handling
errors occur.
30
The sequence in which the gas quality check measurements should be carried
out to minimise working time is shown in Fig. 6.1. The figure also indicates
the gas category assignment as a result of the measurements.
When the reclaimed mixture complies with the criteria for reuse with respect
to reactive decomposition products and humidity, a non-compliance of the
SF6 concentration is not a reason to discard it. If adequate means to correct
the composition are available (see section 6.5,) the mixture can be rendered
reusable by correcting the composition upon refilling the equipment.
Transport
as:
Not suited React. < 50 ppmv
for decomp . non-
reuse prod. (SO2+SOF2 toxic
equival.)
toxic
and
corrosive
Fig. 6.1: Optimal sequence of gas quality check measurements and gas
category assignment for SF6 mixtures.
6.3 Recoverers
Recoverers are devices that only serve to remove gas mixtures from power
equipment and to store it in transportable form, e.g. in cylinders, so that it
can be transported off-site for further treatment. Recoverers only require a
pre-filter to protect the compressor from excessive dust and corrosive
decomposition products. They are able to recover the gas mixture down to a
residual recovery pressure of less than 5 kPa.
Recoverers have the advantage of relatively low investment and service costs
and only require modest operation expertise. By using a recoverer, the more
complicated processes of gas purification and gas quality checking are
delegated to an adequately equipped SF6 service centre off-site.
31
The components of a recoverer (valves, piping, pre-filter, compressor,
controls etc.) can be obtained from suppliers of SF6 recycling equipment who
can also assemble them into a system.
The second essential performance parameter is the loss rate of the recovery
process, which is the ratio of the residual recovery pressure to the filling
pressure of the equipment:
= prec/ pf (9)
The residual recovery pressure prec is thus the key figure determining the
environmental efficiency of the recoverer.
Recoverers that have been designed for undiluted SF6 can, in principle, also
be used for recovering SF6 mixtures. Nevertheless, because of the different
adiabatic exponent of the mixture, the maximal compression pressure and the
storage volume may have to be re-rated to avoid compressor failure.
32
Dilute SF6 mixtures, e.g. 10 % SF6, must not be compressed beyond 2 MPa
at an ambient temperature of 20 oC.
Mixtures with 50% SF6 must not be compressed to more than 4 MPa at an
ambient temperature of 20 oC.
20
Maximal storage pressure pcomp [MPa]
15 o
+20 C
o
0 C
10 o
-20 C
0
0 50 100
SF6 concentration [% ]
The most convenient pressure containers for SF6 mixtures are standard
compressed gas cylinders of the nitrogen type. Their major advantages are:-
- low cost
- compactness
- transportability
- low risk when large quantities of gas have to be stored (the cylinders can
be connected by manifold tubing to form stationary or truck-mounted
cylinder batteries).
33
Larger storage tanks can also be used if they are suited for the desired
storage pressure and comply with storage and/or transport regulations.
34
6.5 Reclaimers
The basic structure of a mixture reclaimer is shown in Fig. 6.3. Its main
elements are a vacuum pump to evacuate the air from the equipment prior to
filling it with SF6, a compressor or compressor set to recover the SF 6 mixture
from the equipment and compress it into a storage container, a dust filter to
remove solid particles from the recovered gas, a gas/humidity filter to
remove reactive gaseous decomposition products and humidity, and a storage
tank for the purified gas. An additional pre-filter can be inserted at the input
of the reclaimer when “heavily arced” gas has to be processed. Note that the
gas mixture should never be compressed into the reclaimer tank to a pressure
at which the SF6 will start to liquefy.
SF6 - N2 recover
EQUIPMENT PREFILTER
SF6 N2 STORAGE
Fig. 6.3: Basic structure of an SF6 mixture reclaimer, shown with nitrogen as
the admixture gas.
Reclaimers for undiluted SF6 have been developed through the last three
decades and are commercially available for all application ranges in T&D
35
equipment. Reclaimers for SF6 mixtures are commercially available too.
Within certain limitations, reclaimers designed for undiluted SF 6 can be
retrofitted to be used for SF6 mixtures.
Table 6.1: Basic physical principles for separating SF6 from mixtures.
No experience,
Sorption Selective sorption though commercial
devices are
available.
Experienced
a) Membrane technology,
separation Commercial devices
available.
Diffusion Highly developed
for military
applications,
b) Thermodiffusion especially isotope
c) Gas centrifuges separation.
SF6 condensation
36
The separation of SF6 by condensation and extraction of the condensate may
be an effective separation process particularly when sufficiently high
compression pressures and/or low cooling temperatures are used. In this
process, however, the gas phase above the liquefied SF6 still contains an
appreciable amount of SF6, which determines the loss rate of the separation
process.
It is seen that almost 20 MPa are required to start SF6 condensation from a
10% SF6 mixture at ambient temperature 20 oC whereas 4 MPa are sufficient
to start condensation from a 50 % SF6 mixture at ambient temperature.
However, the start of condensation does not mean that all the SF6 condenses.
The fraction of the SF6 that actually condenses increases with increasing
compression pressure and with decreasing cooling temperature. A further
important feature of the process is that the SF6 condensate is only liquid
down to the melting point of SF6, which is Tm = - 51 oC (broken line in Fig.
6.4). Below this temperature the SF6 condenses in solid form as “SF6 snow”,
the extraction of which may pose considerable practical problems.
Reference (43) treats the cases of SF6-N2 mixtures containing 50% SF6 or
more, and discusses the factors limiting the efficiency of its separation and
how it can be improved.
37
10000 100 20
10
solid liquid
1000 10
gaseous 1
100 1
0.1
10 0.1
1 0.01
-100 -50 0 50
temperature T [ C]
Fig. 6.4: Vapour pressure curve of SF6. Pressure scale on the left side refers
to undiluted SF6 or to the SF6 partial pressure. Pressure scales on the right
refer to the total pressure of a 10 % and a 50 % SF6 mixture. Left of the
broken line (melting temperature) SF6 condenses in solid form.
The vapour pressure curve pv(Tc) gives the SF6 partial pressure in the gas
above the liquid phase and thus quantifies the SF6 concentration res that
remains in the gas phase:-
As the SF6 quantity contained in the gas phase is proportional to res pcomp
It is seen that the loss rate decreases with the cooling temperature Tc and with
increasing compression pressure pcompr and initial SF6 concentration of the
mixture.
Fig. 6.5 shows a plot of the loss rate as a function of the cooling
temperature Tc for compression pressures pcomp of 5 and 20 Mpa and for a
38
50% (solid curves) and a 10 % SF6 mixture (broken curves). It is seen that
the benchmark value of = 1% can only be reached at cooling temperatures
Tc below the melting point Tm of SF6. This would entail a high cooling cost
and, in addition, create the problem of extracting SF6 as “SF6 snow” .
Practical limit values for the loss rate can be obtained by assuming a cooling
temperature of Tc = -40 oC, which can be reached with standard refrigeration
devices and allows the extraction of SF6 as a liquid. At this temperature, the
vapour pressure of SF6 is pv (Tc = -40 oC)= 350 kPa. The loss rates for
compression pressures of 5 and 20 Mpa are shown in Table 6.2.
39
10%, 50 bar 10%, 200 bar 50%, 50 bar
release rate [%] 100
10
1
-60 -50 -40 -30 -20 -10 0 10 20 30 40 50 60
cooling temperature [ C]
Fig. 6.5: SF6 loss rate as a function of the cooling temperature Tc for the
compression/SF6 liquefaction separation process for mixtures with = 10 %
and 50 % SF6 and for compression pressures pcomp of 5 MPa and 20 MPa.
Selective sorption
Membrane separation
These processes are used for separating uranium isotopes and would
certainly be effective for separating SF6 from nitrogen as these two gases
differ greatly in molecular weight, but there is presently no practical
experience for this application. Due to their military applications, these
methods are not easily available.
Combined processes.
Gas mixtures containing environmentally critical gases such as SF6 and CF4
eventually have to be destroyed when they cannot be rendered reusable or
when they are no longer needed. This destruction has to occur in an
environmentally acceptable way; i.e. these gases have to be transformed into
environmentally benign substances. For the destruction of SF 6, a typical
chemical process is the reaction
where CaO is lime, CaF2 is fluorspar and CaSO4 is gypsum, all of which are
environmentally benign materials. Similar reactions are available for the
destruction of CF4.
Chemisorption of SF6
In this concept, the gas mixture is brought in contact with a substance that is
capable of reacting with SF6 to form products with much lower or no
environmental impact. From the chemical literature it is known that SF6 and
CF4 are thermodynamically unstable at sufficiently high temperatures and
can react with a number of metals and metal oxides. Some such reactions
were studied in Ref. 39 for SF6. It was shown that activation temperatures
above 500 °C were required to obtain sufficiently high reaction rates.
As with metal oxides, SF6 and CF4 can also react with metals. As an
example, it has been shown that SF 6 decomposes very slowly at copper
surfaces above 250 oC [40]. It is not clear if this process is a chemical
reaction with the metal or if catalysis is also involved.
42
6.8 Commercial equipment and services
6.9 Summary
Devices for mixing and controlling gas composition are required for
handling SF6 in mixtures. Filling electrical equipment with premixed gases
or by dynamic mixing of component gases is preferable to filling with
undiluted gases which relies on diffusive mixing in the equipment.
Care should be taken to store SF6 mixtures intended for reuse so that the SF6
does not condense thereby partially separating the mixture. The maximum
storage pressure without liquefaction is a function of the ambient
temperature and the SF6 concentration, essentially the vapour pressure of
SF6.
43
membrane separation is probably the most promising and efficient
technology for arbitrary SF6 concentrations.
44
7. CONCLUSIONS
(1) The main rationale for using SF6 mixtures, aside from low temperature
applications and lower gas costs, is the reduction of the environmental
impact by reducing SF6 emissions. The degree of environmental impact
reduction obtainable by using SF 6 mixtures instead of undiluted SF6 has
to be quantified by environmental life cycle analysis (LCA) according
to the Standard ISO 14040.
(2) The established handling and recycling technology for undiluted SF6,
which has been commercially available for a few decades, can normally
not be directly used to handle the SF6 mixtures discussed in this
document.
(4) Some of the existing handling equipment for undiluted SF6 can be
upgraded to handle SF6 mixtures within the above restricted concept.
(5) SF6 can be separated from mixtures by various processes and process
combinations. Corresponding equipment with low loss rate is now
becoming commercially available.
45
8. REFERENCES
[1] Radiative Forcing of Climate Change", the 1994 report of the scientific
assessment working group of IPCC, p.28.
[7] X. Waymel “Low SF6 concentration SF6/N2 mixtures for GIL”, 8th
Internat. Sympos. on Gaseous Dielectrics, Virginia Beach 1998,
Plenum, 345-351
[8] Koch, H., “Future aspects of gas insulated transmission line (GIL)
applications”, CIGRE SC23.99 (COLL) IWD, Zurich 1999
[9] CIGRE WG 23-10, “ SF6 and the global atmosphere”, ELECTRA 164
(1996) 121-130
46
[13] Boeck, W., Pfeiffer, W.: "Conduction and Breakdown in Gases".
Wiley Encyclopaedia of Electrical and Electronics Engineering, J.G:
Webster ed., (1999)
[16] Imano, A.M.; Schurer, R.; Feser, K.: “The Influence of a Conducting
Particle on a Spacer on the Insulation Properties in SF6/N2 Mixtures”,
ISH 1999, London, paper 3.233.
[17] Diessner, A.; Finkel, M.; Grund, A.; Kynast, E.: “Dielectric Properties
of N2/SF6 Mixtures for Use in GIS or GIL”, ISH 1999, London, paper
3.67.
[18] Graf, R.; Boeck, W.: “Statistical Breakdown Behaviour of N2-SF6 Gas
Mixtures under LI Stress”, ISH 1999, London, paper 3.96.
[19] Schöffner, G.; Boeck, W.: “PD Measurements in N2-SF6 Gas Mixtures
With the UHF Method”, ISH 1999, London, paper 5.86.
[22] Diessner,A.; Koch, H., Kynast, E.; Schelle, A.: “Progress in High
Voltage Testing of Gas Insulated Transmission Lines”. 10th ISH
Montreal 1997, Vol.4, pp.41-43
.
[23] Grant.D.M.etal “Comparative interruption studies of gas blast arcs in
SF6-N2 and SF6-He mixtures”, 4th International conference on gas
discharges and their applications, Proc. Pp48-51.
49
Le CIGRÉ a apporté le plus grand soin à la réalisation de cette brochure thématique numérique afin de vous
fournir une information complète et fiable.
Cependant, le CIGRÉ ne pourra en aucun cas être tenu responsable des préjudices ou dommages de quelque
nature que ce soit pouvant résulter d’une mauvaise utilisation des informations contenues dans cette brochure.
Copyright © 2000
Toute reproduction, même partielle, par quelque procédé que ce soit, est interdite sans autorisation préalable.
Cette interdiction ne peut s’appliquer à l’utilisateur personne physique ayant acheté ce document pour
l’impression dudit document à des fins strictement personnelles.
Pour toute utilisation collective, prière de nous contacter à sales-meetings@cigre.org
The greatest care has been taken by CIGRE to produce this digital technical brochure so as to provide you with
full and reliable information.
However, CIGRE could in any case be held responsible for any damage resulting from any misuse of the
information contained therein.
Published by CIGRE
21, rue d’Artois
FR-75 008 PARIS
Tel : +33 1 53 89 12 90
Fax : +33 1 53 89 12 99
Copyright © 2000
All rights of circulation, translation and reproduction reserved for all countries.
No part of this publication may be produced or transmitted, in any form or by any means, without prior
permission of the publisher. This measure will not apply in the case of printing off of this document by any
individual having purchased it for personal purposes.
For any collective use, please contact us at sales-meetings@cigre.org