Professional Documents
Culture Documents
The detailed procedures for high-speed cyclic loading test and the used in building frames in Singapore to high-frequency
authors’ first-hand experience during the tests of reinforced concrete excitations, and to qualitatively and quantitatively evaluate
beam-column connections subjected to cyclic displacements at the influence of loading rate in the overall damage of the
frequencies as high as 20 Hz are documented in this paper. It is beam-column subassemblies. Altogether, eight full-scale RC
necessary to give special attention to the quality of the instruments
to successfully perform high-speed data acquisition. Problems beam-column joint specimens were fabricated, and cyclic
faced in different phases of the high-speed tests that are not common loading tests ranging from slow pseudo-dynamic tests to
in pseudo-dynamic tests are highlighted. The applicability of some high-speed dynamic tests were conducted in the laboratory
basic criteria established for quasistatic and seismic performance in of the National Center for Research on Earthquake Engineering
gauging the high-speed dynamic performance is also discussed. (NCREE) in Taiwan. As the objective of this paper is to
Unlike in pseudo-dynamic tests, the inertia force contributed share the high-speed test experience and to inform researchers
significantly to the readings of load cells integrated with the actuators of the special considerations needed for similar tests, test
that apply the high-speed displacement cycles. The shear capacity
execution and typical results of only two specimens subjected
of the tested joints was higher than that computed with the
empirical equation in seismic design codes. to the representative high-speed loading are discussed herein.
Tso-Chien Pan is Professor and Director of the Protective Technology Research Center,
School of Civil and Environmental Engineering, Nanyang Technological University,
Singapore. He received his BSCE from the National Cheng-Kung University, Taiwan,
and his MSCE and PhD from the University of California at Berkeley, Calif. His
research interests include dynamic response of structures, damage assessment of
structures, and seismic isolation and energy dissipation.
Note that the column main bars and the beam bars at the bottom
are discontinuous and are overlapped just adjacent to the joint.
The average compressive strength of the concrete taken
from standard compression tests was respectively 31.7 and
33.8 MPa for the two specimens. Moreover, the average
Fig. 1—Geometrical and reinforcement details of specimens
yield strengths of 32, 25, and 10 mm-diameter bars measured
(dimensions in mm).
from standard axial tension tests were 538.0, 537.6, and
363.7 MPa, respectively. Similarly, the ultimate tensile
strengths of these reinforcing bars were 677.3, 675.3, and
571.5 MPa, respectively. Using these material properties,
section analyses were carried out to predict the failure mode
of the connections. The computations revealed that both
specimens are of strong-beam weak-column type, and the
story shear forces required to fail the column are 264.6 and
269.3 kN, respectively. The corresponding joint shear stresses
computed assuming a perfect bond are 10.7 and 10.9 MPa
for the two specimens. On the other hand, the empirical
equation for allowable shear stress in ductile beam-column
joints recommended by the ACI-ASCE seismic design code
(ACI 352.R-91) yields 7.0 and 7.3 MPa, respectively. A similar
provision in the New Zealand Standards (NZS3101-95)
yields 6.3 and 6.8 MPa, respectively. These allowable values
are substantially lower than the joint shear stress induced at
the column failure indicating that the specimens may undergo Fig. 2—Schematic illustration of test setup (dimensions in mm).
joint shear failure before the formation of plastic hinges in
the columns. and Aoyama 1985; Beres et al. 1992) that use pin joints for
all four supports. Because of the additional moment at the
Test setup base, the proposed setup would be statically determinate if
To simulate the seismic action, two different loading both the forces at the beam tip loading points and the column
methods are commonly found in references reporting similar top are measured. Hence, an actuator integrated with a load cell
beam-column joint tests. Some researchers have applied the and an LVDT was used to measure the horizontal reaction and
cyclic displacements at the column top while clamping the displacement at the column top, in addition to the measurements
beam tips (Carlos and James 2001; Otani, Kitayama, and of applied axial load and the reactions at the beam tips.
Aoyama 1985). The others have applied the cyclic displacements The test setup is schematically illustrated in Fig. 2. Although
at the beam tips while restraining the movement of the column the height and length of the specimens were 3.7 and 5.4 m,
ends (Oka and Shiohara 1992; Filiatrault, Pineau, and Houde respectively, the effective height of the column is 3.2 m
1995; Beres et al. 1992). As the authors found no specific reason (distance between the centerlines of the supports at the top
to prefer one arrangement over the other, the latter method and the bottom) and the effective length of the beam is 6.0 m
was adopted in this test series, that is, the cyclic drifts would (distance between the centerlines of the actuators at the right
be applied through the beam tips rather than through the column and the left) owing to the connection details. These values
top because it would impose lesser disturbance on the axial were used for the conversion between absolute displacements
load value and mechanism. Hence, each end plate of the and story drift angle, and also for the capacity predictions.
beam was pinned to a vertical dynamic actuator, which was
equipped with an internal linear variable differential transformer Intended displacement history
(LVDT) type and a load cell to measure the displacement and Note the word intended in the subtitle, which is intentionally
force at the loading point. Although the column top was used because the authors were not sure whether the actuators
connected to a universal pin joint, the column was clamped would be able to exactly follow the desired displacement history,
to the rig at the base, thus restricting the rotation and inducing a especially during the higher-speed displacement reversals.
moment here. The setup adopted in the current test series is The two specimens were subjected to two different sets of
hence different from the usual test setups (Hakuto, Park, and loading histories, namely normal dynamic (ND) and high
Tanaka 2000; Oka and Shiohara 1992; Filiatrault, Pineau, dynamic (HD). As the specimen type discussed here was
and Houde 1995; Carlos and James 2001; Otani, Kitayama, identified C4 in the overall experimental plan, the two
Fig. 6—(a) Relationship between load and displacement at actuator in C4ND test; and (b)
story shear force versus story drift relationship for Specimen C4ND.
Fig. 8—(a) Output displacement history at loading actuator in C4ND test; (b) accelera-
tion history derived from output displacement; and (c) actuator forces versus displace-
ment relationship after correction for inertia force.
Fig. 9—Plot of data recorded by test software in C4ND test: (a) relationship between load
and displacement at actuator in C4ND test; and (b) story shear force versus story drift
relationship for Specimen C4ND.
through the data logger and test software were respectively significant even during the small-displacement cycles. This
188.4 and 206.5 kN, and the actuator force and the average is because the induced inertia force is proportional to the
displacement at this instant were 55.5 kN and 47.3 mm in the loading rate in mm/s rather than to the cyclic frequency in
data logger records and 31.9 kN and 50.3 mm in the test Hz. Because of a constant frequency in the C4ND test, the
software records. loading rate increased gradually with the amplitude of the
Although the correct values of the forces and displacements displacement cycles, and so did the inertia force. In contrast, the
at the peak could be restored from the test software records, combination of decreasing frequency and increasing amplitude
corresponding values received from the other sensors that in the C4HD test kept the loading rate (mm/s) within a certain
were connected only to the data logger may not have been range, and hence the inertia force was not much different
accurate. Note that this discrepancy would have gone unnoticed during the small and large displacement cycles.
if the test software did not inherently record some of the The story shear force versus story drift relationship is
channels or if the data logger records were not crosschecked. shown in Fig. 12(b). Note that the curves presented in Fig. 12
In quasistatic tests, this is not a problem as the displacement are plotted from the data recorded through the data logger that
cycles are applied very slowly, and the undulations, if any, did not filter any high-frequency components. Consequently,
would never exceed 10 Hz. The authors were fortunate to some undulations in the loops and sharp reversals can be clearly
discover it after the first test because the effect would be identified in the curves. The data recorded through the test
more severe for the second test where the loading frequency software were almost exactly the same as the data logger
is higher than the filter frequency. This default filtering records. The maximum values of the load and displacement at
provision was hence deactivated during the second test to the peaks of different cycles recorded by the test software and the
retrieve the correct values of the measured parameters at the data logger were also equal. This corroborated the argument
peak of each displacement cycle through the data logger. presented earlier that the difference in the data recorded from the
two sources was due to the high-frequency signal filtering
Performance of Specimen C4HD mechanism set as default in the data logger. Owing to the very
The conditions of both faces of the joint after the emergence high sampling frequency, the response showed undesired
of the first crack, after completion of 2.5% radian story drift undulations that created difficulties in processing the data and
cycles, and at the end of the test are shown in Fig. 11. As locating the maximum load, which did not always appear at the
shown in the photographs, the first pair of diagonal cracks peak displacement. It is hence recommended to retrieve data at a
were seen after 0.5% radian story drift (±15 mm) cycles were lower sampling rate that can capture the prominent frequency
applied. Concrete cover spalling had already started at both components with reasonable accuracy.
faces after 2.5% radian story drift cycles. At this stage, the
first pair of diagonal cracks had opened significantly, while Comparison between C4ND and C4HD test results
the other cracks remained thin. Cracks in the joint faces The earlier prediction that the joint is weaker than the
extended beyond the joint-column interface, and more flexural members is supported by the damage concentration in the
cracks could be observed in the columns than in the beams. joint panels, which eventually led to the termination of loading
A big piece of concrete had even spalled off from beneath the in both tests. Both specimens could withstand 2.5% radian
joint front face. In addition to the cracks in the joint faces and story drift (±75 mm) cycles without showing any alarming
members, vertical cracks along the joint-beam interfaces sign of failure. The high-speed small-amplitude cycles did
could also be seen. This might be due to the alternate opening not cause any visible damage. Both specimens exhibited
and closure at the joint corners. The specimen deteriorated significant pinching behavior, and a gradual degradation of the
quickly on further loading, and the test was terminated after story shear force could be observed in the post-peak region, that
3% radian story drift (±90 mm) cycles had been applied. At is, especially after 2% radian story drift angle (±60 mm). The
the final stage, concrete cover spalled off from both faces of the maximum story shear force observed in the test was 206.5 kN for
joint, thus exposing the main reinforcing bars inside the joint. Specimen C4ND and 230.9 kN for Specimen C4HD. This more
The relationship between force and displacement measured than 10% increase in the capacity of Specimen C4HD might be
by the integrated load cell and LVDT in one of the loading attributed to the strain rate effect, that is, the increase of
actuators is plotted in Fig. 12(a). As explained earlier, the concrete strength due to a faster loading speed. Computation
load cell reading decreases at the positive and negative assuming a perfect bond showed that the horizontal joint shear
peaks of each displacement cycle. Nevertheless, unlike in stress corresponding to the maximum story shear force is 8.3
Specimen C4ND, the sudden drop in Specimen C4HD is MPa in C4ND and 9.3 MPa in C4HD, which is 20 to 40%