Professional Documents
Culture Documents
Although hollow brick infills, widely used as partition walls, are considered as non-structural members,
experimental studies revealed that hollow brick infills have favourable effects on strength and stiffness
of structures. In this work, analytical studies were conducted to investigate the hollow brick infill
behaviour, in which infills were modeled by diagonal compression struts. Results were compared with
experimental ones obtained from tests of one-bay, one or two story reinforced concrete (RC) frames,
tested under both vertical and reversed-cyclic lateral loads simulating earthquake. Test frames have
intentionally been constructed poorly to reflect the most common deficiencies encountered in Turkey
such as strong beam-weak column connections, insufficient confinement, low-grade concrete, poor
workmanship and insufficient lap-splice length. Experimental studies shows that hollow brick infills
increased both strength and stiffness of RC frames. Analytical studies conducted, shows that hollow
brick infills could adequately be modeled by diagonal compression struts.
Key words: Reinforced concrete, strength, stiffness, hollow brick infill, diagonal compression strut and reversed-
cyclic lateral load.
INTRODUCTION
Filling reinforced concrete (RC) frames with clay tile This is the most probable reason for hollow brick infills
serving as partitions are very common, especially in not being considered as “structural” members during the
Turkey. In structural design process, such infills are structural design process, resulting with inaccurate
considered as “nonstructural” members. Structure is solutions. With this approach, natural period of building,
assumed to carry horizontal loads only by the frame earthquake load transferred to each beam and column,
elements. However, it is apparent from geometrical short column mechanisms that can occur and the failure
considerations that infills also resist loads and impede mode of building under an earthquake loading can not be
deformations compatible with infilled frame action. evaluated precisely. Since the behaviour is nonlinear and
Analytical and experimental studies shows that infilled closely related to the interaction conditions between
frames have greater strength and stiffness compared to frame and infill, analytical studies should be revised and
bare frames. Due to changes in stiffness and mass, supported by experimental data. Earthquake regulations
dynamic characteristics of the building also change. of many countries (Israel, Costa Rica, France, Algeria,
Understanding the behaviour of infilled frames and being European Union, Colombia, Phillipines, etc.) recommend
capable of making a satisfactory modeling of infills during to take the effect of infill walls into account during the
structural design process will help engineers to have design process (Kaplan, 2008).
more realistic and economical solutions. Behaviour of In the experimental part of the present study, one and
infilled frames under seismic loading is complicated. two-story RC frames were tested. In two-story frames,
lateral load was applied at a greater height resulting in
more turning effect whereas compressive and shear
stresses are more dominant in one-story frames. By this
*Corresponding author. E-mail: memetbaran@gmail.com. Tel: way, hollow brick infill behaviour can be analyzed under
++ (90) (318) 357 42 42 – 1254. Fax: ++ (90) (318) 357 24 59 tensile stresses as well as compressive and shear stresses.
1982 Int. J. Phys. Sci.
bricks (with void ratio of 0.52) covered with a scaled layer of plaster. connections at both ends to eliminate any accidental eccentricity
Ordinary cement-lime mortar was used for the plaster, reflecting the mainly in vertical direction and tolerating a small rotation in
usual practice. Hollow brick and infilling method is shown in Figure horizontal direction normal to testing plane. Lateral load was
2. Ordinary workmanship was intentionally employed in wall applied on a spreader beam at one-third of its span to ensure that
construction and plaster application. For the same reason, mild the lateral load at second floor level always remains twice as the
steel plain bars were used as longitudinal steel in both test frames. lateral load at first floor level. A very rigid external steel ‘guide
Typical properties of reinforcing bars used in this study and average frame’ attached to the universal base, was used to prevent any out-
compressive strength values for frame concrete and plaster of-plane deformations. During the tests, increasing load cycles were
determined on testing day are listed in Table 1. applied up to the capacity of frame and beyond that, deformation
controlled loading was performed with increasing displacement
cycles. Load histories of all test frames are given in Figure 4.
Loading and supporting system
In Figure 3, general views of the test set-up for two and one-story Deformation measurement system
test frames are given, respectively. As can be seen in Figure 3,
tests were performed in front of a reaction wall. Frames were All deformations were measured by displacement transducers;
subjected to reversed cyclic lateral loading resembling seismic using either linear variable differential transformers (LVDTs) or
effects. The quasi-static test loading consisted of reversed cyclic electronically recordable dial gages (DGs) as shown in Figure 3.
lateral loading besides constant vertical load applied on both Sway displacements were measured both at first and second floor
columns. The axial load on columns was provided by steel cables levels. Infill wall shear deformations were determined on the basis
post-tensioned by hydraulic jacks. of displacement measurements along the diagonals. Displacement
Reversed cyclic lateral loading was applied by using a double measurements taken at the bottom of both columns were meant for
acting hydraulic jack. The lateral loading system had pin computation of rotations of the entire frame. They also provided
1984 Int. J. Phys. Sci.
Axial load Column Lap-splice Long. Reinf. Trans. Reinf. Frame concrete Brick laying Plaster
Test frame No. of floors
N/No steel length (MPa) (MPa) (MPa) mortar (MPa) (MPa)
SP1 0.11 2 Cont. - 365 271 12.7 - -
SP2 0.11 2 Cont. - 365 271 13.3 3.4 -
SP3 0.11 2 Cont. - 365 271 12.7 8.4 8.2
SP4 0.19 2 Cont. - 330 220 16.6 6.5 6.5
SP5 0.30 2 Lapped 20 φ 330 220 8.6 3.5 3.5
SP6 0.10 2 Cont. - 405 268 15.0 23.1(1) -
SP7 0.25 1 Cont. - 330 220 15.6 6.1 6.1
SP8 0.13 1 Cont. - 405 268 10.7 5.2 5.2
SP9 0.13 1 Lapped 20 φ 330 220 9.7 4.9 4.9
(1)
Compressive Strength of RC Infil.
200 200
150 150
Lateral Load (kN)
-150 -150
SP1 SP2
-200 -200
200 250
200
150
150
Lateral Load (kN)
100
66.6 62.2 100 76.8 72.5
56.7 69.4
46.6 40.5 49.2 59.1 50.3
50 36.5 28.0 22.3 50 39.5 32.7
16.5 17.0
0.0 0
0 0
24.6 16.8 17.3
21.7 -50 39.8 43.0 37.0
-50 32.9 61.6 60.6 55.9
43.6 53.5 50.2 69.5
63.6 66.5 -100 78.8
-100
-150
-150 -200
SP3 SP4
-200 -250
180.5
189.7
170.4
180.2
200
160.1
200
153.0
151.0
141.5
130.9
120.5
109.3
150 150
101.3
95.4
90.7
83.3
79.3
Lateral Load (kN)
70.9
100 100
60.3
0.0
0 0
20.3
-50 40.3 33.9 -50
49.5 59.4 53.9
60.3
64.9
70.0
69.5 71.9
82.7
-100
88.9
-100
94.0
97.5
98.1
111.7
120.2
129.1
131.5
-150 -150
141.2
SP5
150.3
SP6
153.9
161.3
171.0
180.8
-200
189.4
-200
Cycles Cycles
200
150
Lateral Load (kN)
-150
SP7
-200
200 200
150 150
Lateral Load (kN)
100 100
65.5
56.0
59.2
49.5
42.9
39.4
34.2
31.3
31.0
29.5
31.3
25.8
25.5
23.2
0 0.0
0
0.0
19.9
28.8 18.7
21.1
29.6
30.1
30.1
21.7
24.0
-50
41.1
39.3 -50
41.1
37.1
48.7
50.1
48.4
58.5
59.6 62.3
60.8
-100 -100
-150 -150
SP8 SP9
-200 -200
Cycles Cycles
Maximum lateral 1st story drift ratio 2nd story drift ratio Initial stiffness Energy dissipation
Test frame Ratio(1) Ductility
load (kN) at peak δ1/h at Peak (δδ2-δ
δ1)/h (kN/mm) (kJ)
SP1 14.5 1.00 0.0160 0.0076 1.7 2.1 4.7
SP2 50.3 3.47 0.0113 0.0062 24.4 5.9 5.9
SP3 66.6 4.59 0.0043 0.0032 21.4 4.5 2.8
SP4 76.8 5.30 0.0042 0.0033 43.5 6.4 4.9
SP5 74.2 5.12 0.0035 0.0021 59.1 4.6 7.4
SP6 189.7 13.08 0.0079 0.0069 125.3 21.5 4.8
SP7 86.6 1.00 0.0036 - 95.8 5.7 10.0
SP8 62.3 0.72 0.0065 - 59.4 6.0 3.5
SP9 65.5 0.76 0.0053 - 59.9 8.6 5.3
(1)
The ratio of Maximum lateral load to that of the reference frame.
data for monitoring the critical column section the RC infilled frame behaviour which forms an upper expected, major damage took place in the first story infill
deformations; steel yielding in the tension side column, bound. As expected, this specimen behaved as a wall for all two-story test frames. In addition, first story drift
concrete crushing in the compression side column etc. monolithic cantilever where failure took place at foundation ratio values were higher than that of second story at
level with column bases in terms of yielding of the steel in ultimate load level for all test frames.
the tension side column and concrete crushing and One-story test frames SP7, SP8 and SP9 had drift ratios
buckling of longitudinal steel in the compression side of 0.36, 0.65 and 0.53%, respectively. The value for test
EXPERIMENTAL RESULTS
column. frame SP7 was less when compared to the other two,
Test of SP5 Specimen was terminated since the since this frame had continuous column longitudinal bars
Behaviour of test specimens diagonal crack just below the first story beam – left column together with higher axial column loads. Drift ratios were
joint turned out to be a shear failure and the column broke 0.42 and 0.43% for the test frames SP4 and SP3, which
One being bare and one hollow brick infilled (Sevil et al., off due to low concrete strength of the frame. Story Drift were the equivalent pairs for test frames SP7 and SP8,
2010), one being RC infilled (Baran et al., 2009) and six Ratio is a term which is frequently used in the earthquake having drift ratios of 0.36 and 0.65% respectively.
plastered hollow brick infilled frames (Sevil., 2010; Baran engineering as a measure of non-structural damage and to Equivalent pairs had all the variables same except the
and Tankut, 2009; Okuyucu and Tankut, 2009) were tested control second order effects. First and second story drift number of stories that test frames had. As expected, first
under vertical and quasi-static lateral loading simulating ratio values of the test frames at ultimate load levels are story drift ratio value for test frame SP3 was greater than
earthquake effect. Except from the bare and RC infilled, all given in Table 2 and lateral load-first story drift ratio curves that of test frame SP4 and value for test frame SP8 was
frames exhibited typical masonry infilled frame behaviour for the test frames are given in Figure 5. According to the greater than that of test frame SP7 since higher axial load
characterized by: Rather rigid and linearly elastic behaviour story drift ratio curves, hollow brick infill walls and made the infills and frames much stiffer.
at the initial stages, relatively high capacity resulting from plastering increased lateral strength and stiffness. Bare According to the Turkish Seismic Code (2006),
infill wall contribution and rapid strength degradation and test frame SP1 reached 1.60% lateral drift at ultimate load. maximum story drift index is limited to 0.0035 in the elastic
very rapid stiffness degradation upon infill wall crushing. This ratio was 1.13% for test frame SP2, with non- analysis of the structure whereas, it is specified as 0.010
This expected behaviour was concluded by a typical plastered hollow brick infills. As expected, test frames SP3, for inelastic analysis. On the other hand, according to
failure accompanied by excessive permanent first story SP4 and SP5 with plastered hollow brick infills reached clause 1630.10 of UBC (Uniform Building Code, 1997), the
sway deformations. It is important to note here that story drift ratios of 0.43, 0.42 and 0.35% values maximum story drift index is limited to 0.025 for the
although not plastered at both sides, test frame SP2 also respectively. structures with a fundamental period less than 0.7 s and
exhibited typical masonry infilled frame behaviour. It was Test frame SP6, with RC infills, had a drift ratio of 0.79% 0.020 for the structures with a fundamental period greater
tested to observe effects of plaster application on infilled at its ultimate load which was lower than that of test frame than 0.7 s. Hollow brick infilling reduces the amount of
frame behaviour. Test frame SP6 was tested to observe SP1 but higher than masonry infilled specimens. As deformations as compared to bare test frame SP1.
Baran and Sevil 1987
100 100
75
SP1 SP2 75
Lateral Load (kN)
50 50
25 25
0 0
-25 -25
-50 -50
-75 -75
-100 -100
100
-0.080 -0.060 -0.040 -0.020 0.000 0.020 0.040 0.060 0.080
-0.080 -0.060 -0.040 -0.020 0.000 0.020 0.040 0.060 0.080100
75
SP3 SP4 75
Lateral Load (kN)
50 50
25 25
0 0
-25 -25
-50 -50
-75 -75
-100 -100
100-0.080 -0.060 -0.040 -0.020 0.000 0.020 0.040 0.060 0.080 200
SP5 175
75
SP6 150
125
Lateral Load (kN)
50 100
75
25 50
25
0 0
-25
-25 -50
-75
-50 -100
-125
-75 -150
-175
-100 -200
100 100
SP7 SP8 75
75
Lateral Load (kN)
50 50
25 25
0 0
-25 -25
-50 -50
-75 -75
-100 -100
100-0.080 -0.060 -0.040 -0.020 0.000 0.020 0.040 0.060 0.080-0.080 -0.060 -0.040 -0.020 0.000 0.020 0.040 0.060 0.080100
75
SP9 SP9 75
Lateral Load (kN)
50 50
25 25
0 0
-25 -25
-50 -50
-75 -75
-100 -100
-0.080 -0.060 -0.040 -0.020 0.000 0.020 0.040 0.060 0.080 -0.080 -0.060 -0.040 -0.020 0.000 0.020 0.040 0.060 0.080
Figure 6. Envelope load-displacement curves (for two-story and one-story test frames).
ultimate displacement is defined as the top story level loads (nearly 25% of column axial load capacity) showed
displacement at which the lateral load dropped to 85% of more ductile behaviour than two-story test frame SP3 and
the maximum applied load at post peak region. The yield one-story test frame SP8, respectively which had lower
displacement was described with a secant drawn starting column axial loads (nearly 10% of column axial load
from the origin and passing from the point on which capacity). This situation can be owing to the more
lateral load is 70% of the maximum applied load. This dominant compressive and shear stresses in one-story
secant line was extended up to the horizontal line drawn frames and more efficient behaviour of the infill, which
from the maximum load and corresponding displacement can be positively influenced by the confining effect of
was accepted as yield displacement (Sezen and Moehle, compressive forces. Although test frame SP5 had two-
2004; Sevil, 2010). The calculated ductility values are stories, it showed more ductile behaviour than one-story
listed in Table 2. As it can be observed, one-story test test frame SP9 which had lower column axial load. It
frames SP7 and SP8 showed more ductile behaviour should be noted here that, test frame SP2, which had
than equivalent two-story test frames SP4 and SP3, non-plastered hollow bricks, showed more ductile
respectively. In addition, two-story test frame SP4 and behaviour than bare test frame SP1 and RC infilled test
one-story test frame SP7, which had higher column axial frame SP6.
1990 Int. J. Phys. Sci.
ANALYTICAL STUDIES been conducted for nearly fifty years. During his studies,
Polyakov observed diagonal cracks in the center region
Infill wall modeling of the infill, seperation over a finite length of the beam
and the column between the frame member and the infill
Beginning with the first study conducted by Polyakov at the unloaded corners and full contact between them
(1957), analytical and experimental studies on infills have adjacent to two opposite loaded corners. In the 1960’s,
Baran and Sevil 1991
Smith (1962, 1966, 1967, 1968) and Smith and Carter contact between them remains adjacent to two opposite
(1969) modeled the infill walls as equivalent diagonal corners. At this stage, a line drawn from one loaded
compression struts. In the 1970’s (Mainstone and Weeks, corner to the other represents the direction of the
1970; Mainstone, 1974; Klingner and Bertero, 1978) in principal compression. Therefore, the panel transfers
the 1990’s (Paulay and Priestley, 1992; Angel et al., compression along this line. In fact, it can be assumed
1994; Saneinejad and Hobbs, 1995) and in the early that the infill behaves as a diagonal strut and the
2000’s (Al-Chaar, 2002; El-Dakhakhni et al., 2003) structure can be analyzed with equivalent struts replacing
conducted analytical and experimental studies on the infill the infills, as shown in Figure 8. A diagonal compression
walls and contribute to better understanding of the infilled strut can adequately represent load transfer mechanism
frame behaviour.Results obtained by Smith and Carter observed from the experiments and conducted finite
(1969) showed similarity to experimental results obtained element analysis. Here α and β are the interaction
by Mainstone (1974) and Al-Chaar (2002). distribution parameters as presented in Figure 8. In the
In their studies, Smith and Carter (1969) assumed that case of infills with masonry materials, Equations 1 and 2
the frame and the infill are not bonded together. When are proposed by FEMA (1998) for the determination of
the load is applied, the frame and the infill seperates over the mechanical and the geometrical properties of the
a finite length of the beam and the column and the equivalent diagonal strut;
1992 Int. J. Phys. Sci.
finfill-90 =
(f brick ⋅ t brick + f plaster⋅ t plaster)
relating Einfill-θ to f infill-θ and Einfill-90 to f infill-90, since the infill
wall is anisotropic. The assumption that compressive
(t brick + t plaster)
(3) strength of the infill varies according to the angle of
loading was investigated by Hamid and Drysdale (1980)
and a value of f infill-θ = 0.7f infill-90 was suggested by Seah
(1998). The orthotropic model for the infill given by El-
Einfill-90 =
(E brick ⋅ t brick + Eplaster⋅ t plaster) Dakhakhni et al. (2003) is illustrated in Figure 8.
(4)
(t brick + t plaster) Nonlinear finite element analysis conducted by
Saneinejad and Hobbs (1995) suggested that the secant
stiffness of the infilled frames at the peak load to be half
Ebrick is the Young’s modulus of the infill material. the initial stiffness. This suggestion might be adapted to
the calculation of the Young’s modulus at peak load, Einfill-
Binici and Ozcebe (2006) proposed its value to be p = 0.5Einfill-θ.
varying between 500 to 1500 times the compressive A trilinear relation stress-strain diagram for concrete
strength of the infill. Hollow bricks used in the infills of the masonry infill is suggested by El-Dakhakhni et al. (2003)
test frames were loaded in the direction of (Duvarci, instead of the parabolic one as shown in Figure 9.
2003) and perpendicular to the holes and the results are Accordingly, this approximation is simpler and more
given in Table 3. practical for analysis. Accepting the strain ε2 equal to the
Since the infill is diagonally compressed when the strain ε1, using an average value of Einfill-0 and Einfill-90 for
infilled frame is loaded laterally, El-Dakhakhni et al. modulus of elasticity and accepting f infill-θ = 0.6finfill-90 yield
(2003) made a justifiable assumption that the properties satisfactory estimations for the deformation capacity of
in the diagonal direction are the governing material the equivalent compression strut. Hence, a stress-strain
properties. Plastered hollow brick infills are anisotropic. diagram as shown in Figure 10 for the equivalent
At this point, another assumption is made by considering compression strut modeling the plastered hollow brick
the anisotropic infill as orthotropic. Since the infill of the infill wall, was used in the analytical studies. Test results
test frames behave as it is under compression, Equation showed that axial load applied on the frames increased
5 derived by using constitutive relations of orthotropic the push over capacity of the specimens. Therefore, axial
plates and axes transformation matrix, can be used to load should have effect on the ultimate load carrying
Baran and Sevil 1993
Z
Figure 9. Simplified stress-strain diagram of concrete.
Figure 10. Stress-strain diagram for the compression strut modelıng plastered hollow brick infill.
capacity of the strut and should be taken into 30% of column’s axial load capacity was applied during
account.The ultimate load carrying capacity and the yield the tests. Taking the ultimate strain of the equivalent
deformation of the strut were calculated by using compression strut as εu = 0.018 yields satisfactory results
Equation (6) in analytical studies.
Tile no. Failure load (kN) Compressive strength (Net area) Compressive strength (Gross area)
49.87 17.71 8.50
can be decreased proportional to the square root of structures under lateral loads. In the push-over analysis,
lapped-splice length of the steel. Since the lapped-splice a load pattern is selected first and applied to the structure
length at the floor levels were 20 φ, the reduced yield in incremental steps. The computer program accepts
stress of the longitudinal steel, fy′ can be calculated using axial load-moment interaction curve or just yield moment
Equation (9) given by Canbay and Frosch (2005): values of the members. In the present study, interaction
curves were used for columns whereas just yield moment
values were used for the beams idealizing beam
20φ behaviour as elasto-plastic. Lapped-splices in the column
f y′ ≅ f y ⋅ = 0.7071 ⋅ f y (8)
40φ longitudinal steels (if exist) were taken into account.
Analytical model of the test frames is given in Figure 11.
It is assumed that the equivalent compression struts were
Push-over analysis hinge-connected to the frames at both ends.
100 100
SP2 SP3
75 75
50 50
25 25
0 0
-25 -25
-50 -50
-75 -75
-100 -100
50 50
25 25
0 0
-25 -25
-50 -50
-75
Analytical -75
Experimental
-100 -100
-40 -30 -20 -10 0 10 20 30 40 -40 -30 -20 -10 0 10 20 30 40
2nd Storey Level Displacement (mm) 2nd Storey Level Displacement (mm)
Figure 12. Comparison of analytical and experimental load-displacement curves (two-story).
push-over analysis (Baran et al., 2010) made by the limited data obtained from tests of RC frames and
proposed analytical method, where plastered hollow brick analytical studies conducted. The plastered hollow brick
infills modeled by equivalent diagonal compression struts, infills, used as partition walls, increased both strength
gave safe and sound results in estimating the ultimate and stiffness of frames. In the test of frames with
load capacities of the test frames. With the proposed masonry infills, the increase in strength was nearly 6
method, the deviation in the estimation of the ultimate times as compared to the bare frame for both frame
load carrying capacities of the test frames stated in ± types. This increase in initial stiffness was nearly 20 and
about 10% range of the experimental values. In addition, 30 times for two and one-story test frames, respectively.
post-peak portions (descending portions) of the push- For RC infilled frame, the increase in strength and initial
over curves were adequately simulated by the proposed stiffness was nearly 15 and 60 times as compared to the
method. However, initial stiffness values of the infilled bare frame. This proved the effectiveness of the method
test frames could not be estimated within acceptable in improving the overall seismic structural performance.
closeness for all test frames. This can be owing to the Application of plaster on both sides of the hollow brick
quality of the workmanship in the hollow brick infill wall infill increased lateral load carrying capacity of the frame.
and plastering of the specimen which played an important The increase was nearly 3.5 times as compared to the
role in the displacement history in early cycles. Since the bare frame. For both types of frame, one of the main
proposed method is for hollow brick infilled RC frames, difference is the application level of loading. In two-story
push-over analysis for bare test frame SP1 and RC frames, the lateral load was applied at a greater height
infilled test frame SP6 were not conducted. and therefore moment arm is greater resulting in more
overturning effect. Therefore, more tensile stress occurs
at the tension side column of two-story frames. However,
Conclusions compressive and shear stresses are more dominant in
one-story frames. This is the most possible reason for
The conclusions presented below are based on the higher initial stiffness of one-story frames.
1996 Int. J. Phys. Sci.
100 100
SP7 SP7
75 75
25 25
0 0
-25 -25
-50 -50
-75 -75
-100 -100
100 -40 -30 -20 -10 0 10 20 30 40 -40 -30 -20 -10 0 10 20 30 40 100
SP8 SP9
75 75
Lateral Load (kN)
50
25 25
0 0
-25 -25
-50 -50
Experimental
-100 -100
-40 -30 -20 -10 0 10 20 30 40 -40 -30 -20 -10 0 10 20 30 40
1st Storey Level Displacement (mm) 1st Storey Level Displacement (mm)
Table 4. Comparison of experimental response curves with the analytical push-over curves.
Two-story and one-story equivalent test frames showed lateral load capacity to the frame. This phenomenon was
very similar behaviour, especially lateral load capacities taken into account in calculating the ultimate load
of equivalent pairs were close. Presence of inadequate carrying capacity of a compression strut modeling the
(20 bar diameter) lapped-splices on column longitudinal plastered hollow brick infill.
steels did not seem to adversely affect the infill The proposed equivalent diagonal compression strut
effectiveness significantly, if the column axial load was modeling showed good correlation with the test results. In
not less than 20% of its axial load capacity. Hence, bond the structural design process, equivalent diagonal
problems due to lapped-splices on column steels would compression struts modeling the plastered hollow brick
not be critical in the cases when the axial load level on infills can easily be added to the existing frame model of
the columns are not very low. Independent from the the buildings. By this way, considerable amount of time
presence of lapped-splice in steel, lower axial load on and work might be saved by the use of this method which
columns created a negative effect on the lateral strength. enables the quick determination of the ultimate load
Hence, it can be concluded that higher column axial carrying capacities of the frames with plastered hollow
loads made the infills stronger which provided higher brick infills.
Baran and Sevil 1997
Lıst of symbols
Technical University, Ankara, Turkey. Sevil T (2010). Seismic Strengthening of Masonry Infilled R/C Frames
El-Dakhakhni WW, Elgaaly M, Hamid AA (2003). Three-Strut Model for with Steel Fiber Reinforcement. Ph D Thesis, Middle East Technical
Concrete Masonry-Infilled Steel Frames. J. Struct. Eng., pp. 177-185, University, Ankara, Turkey.
February. Sevil T, Baran M, Canbay E (2010). Investigation of the Effects of
Federal Emergency Management Agency (FEMA) (1998). Evaluation of Hollow Brick Infills on the Behavior of Reinforced Concrete Framed
Earthquake Damaged Concrete and Masonry Wall Buildings, FEMA Structures; Experimental and Analytical Studies. International Journal
306. of Research and Development, Accepted for Publication.
Hamid AA, Drysdale RG (1980). Concrete Masonry under Combined Sezen H, Moehle JP (2004). Shear Strength Model for Lightly
Shear and Compression Along the Mortar Joints. ACI J., 77: 314-320. Reinforced Concrete Columns. J. Struct. Eng. ASCE, 130: 1692-
Kaplan SA (2008). Dolgu Duvarlarin Betonarme Taşiyici Sistem 1703.
Performansina Etkisi. Türkiye Mühendislik Haberleri, 452-2008/6. Smith BS (1962). Lateral Stiffness of Infilled Frames. ASCE J. Struct.
Klingner RE, Bertero V (1978). Earthquake Resistance of Infilled Div., 88: 183-199.
Frames. J. Struct. Division ASCE, 104, June. Smith BS (1966). Behaviour of Square Infilled Frames. ASCE J. Struct.
Mainstone RJ, Weeks GA (1970). The Influence of Bounding Frame on Div., 92, ST. 1.
the Racking Stiffness and Strength of Brick Walls. 2nd International Smith BS (1967). Methods for Predicting the Lateral Stiffness and
BrickMasonry Conference held at Watford, England, pp. 165-171. Strength of Multi-Storey Infilled Frames. Build. Sci., 2: 247-257.
Mainstone RJ (1974). Suplementary Note on the Stifness and Strengths Smith BS (1968). Model Test Results of Vertical and Horizontal Loading
of Infilled Frames. Building Research Station UK, Current Paper of Infilled Specimens. ACI J. August, pp. 618-624.
13/74, February. Smith BS, Carter CA (1969). Method of Analysis for Infilled Frames.
Okuyucu D, Tankut (2009). Effect of Panel Concrete Strength on Proc. ICE., pp. 44: 31-48.
Seismic Performance of RC Frames Strengthened by Precast Turkish Seismic Code (2006). Ministry of Public Work and Settlement,
Concrete Panels. WCCE-ECCE-TCCE Joint Conference: earthquake Government of Republic of Turkey, Ankara.
& tsunamı held at Istanbul, Turkey, IMO Publication Nr.: E/09/03, Uniform Building Code (1997). 5360 Workman Mill Road, Whittier,
June 22-24. California 90601-2298, USA.
Paulay T, Priestley MJN (1992). Seismic Design of Reinforced Concrete
and Masonry Buildings, New York, John Wiley.
Polyakov SV (1957). Masonry in Framed Buildings; An Investigation into
the Strength and Stiffness of Masonry Infilling (English Translation),
Moscow.
Saneinejad A, Hobbs B (1995). Inelastic Design of Infilled Frames. J.
Struct. Eng., 121(4): 634-650.
Seah CK (1998). Universal Approach for the Analysis and Design of
Masonry-Infilled Frame Structures. Ph D Thesis, University of New
Brunswick, Fredericton (NB), Canada.