Professional Documents
Culture Documents
SYSTEM
RS45-27CH, RS45-30CH, RS45-27IH, RS46-33CH,
RS46-30IH, RS46-36CH, RS46-33IH First Used
on 1537 and Up [A222]
• Always use correct blocks to prevent the unit from rolling or falling. See HOW TO PUT
THE LIFT TRUCK ON BLOCKS in the Operating Manual or the Periodic Mainte-
nance section.
• Keep the unit clean and the working area clean and orderly.
• Always use HYSTER APPROVED parts when making repairs. Replacement parts
must meet or exceed the specifications of the original equipment manufacturer.
• Make sure all nuts, bolts, snap rings, and other fastening devices are removed before
using force to remove parts.
• Always fasten a DO NOT OPERATE tag to the controls of the unit when making repairs,
or if the unit needs repairs.
• Gasoline, Liquid Petroleum Gas (LPG), Compressed Natural Gas (CNG), and Diesel fuel
are flammable. Be sure to follow the necessary safety precautions when handling these
fuels and when working on these fuel systems.
• Batteries generate flammable gas when they are being charged. Keep fire and sparks
away from the area. Make sure the area is well ventilated.
NOTE: The following symbols and words indicate safety information in this
manual:
WARNING
Indicates a condition that can cause immediate death or injury!
CAUTION
Indicates a condition that can cause property damage!
3B6 Load Limiter System Table of Contents
TABLE OF CONTENTS
General ............................................................................................................................................................... 1
Description ......................................................................................................................................................... 1
System Components........................................................................................................................................... 2
Main Unit....................................................................................................................................................... 2
Load Limiter System (Compact Display Panel)........................................................................................... 2
Compact Integrated Transducer (Boom Length and Angle Transducer) ................................................... 3
Pressure Transducers .................................................................................................................................... 3
Operation (Compact Display Panel) ................................................................................................................. 4
Display ........................................................................................................................................................... 4
Displays for the Operator.............................................................................................................................. 4
Replace and Adjust ............................................................................................................................................ 5
General ........................................................................................................................................................... 5
Main Unit....................................................................................................................................................... 5
Remove....................................................................................................................................................... 5
Install ......................................................................................................................................................... 6
Load Limiter System Display ....................................................................................................................... 6
Remove....................................................................................................................................................... 6
Install ......................................................................................................................................................... 6
Compact Integrated Transducer ................................................................................................................... 6
Remove....................................................................................................................................................... 6
Install ......................................................................................................................................................... 6
Pressure Transducers .................................................................................................................................... 6
Remove....................................................................................................................................................... 6
Install ......................................................................................................................................................... 7
Angle Potentiometer...................................................................................................................................... 7
Boom Angle Calibration............................................................................................................................ 7
Length Potentiometer.................................................................................................................................... 7
Boom Length Calibration.......................................................................................................................... 7
Diagnostics ......................................................................................................................................................... 8
Printer Options .................................................................................................................................................. 8
Troubleshooting.................................................................................................................................................. 8
HYSTER
APPROVED
PARTS
1900 SRM 1213 Description
General
This section has the description and repair proce- The instructions for the diagnostics, printer options,
dures for the 3B6 Load Limiter System components. and troubleshooting are also included in this section.
Description
The Load Limiter System is a 3B6 Load Limiter Sys- which are stored in the main unit of the Load Lim-
tem. It is an electronic load limiter system designed iter System.
to indicate the allowable lifting capacity of the Reach-
Stacker®. The display panel is shown in Figure 1 and The resulting data is displayed for the operator. If
the four main system components are shown in Fig- an overload condition is determined, the operator is
ure 2. warned with an audible and visual alarm and the hy-
draulic functions used to create the overload condi-
Each Load Limiter System is factory programmed to tions are disabled. The hydraulic functions to correct
match the specific ReachStacker to which it is at- the overload condition are still enabled.
tached. By programming the unit with the informa-
tion requested during the start up sequence, the sys- The lifted load is continuously compared with the
tem monitors and displays the following: maximum allowable load obtained from the manu-
• Actual lifted load facturer’s capacity charts, and consequently three
• Maximum admitted load possible situations can occur as follows:
• Tilting percentage • Green lamp is ON, no acoustic signal is produced.
• Operating radius of the load The lifted load is lower than 90% of the maximum
• Boom angle load.
• Boom extension • Yellow light is ON and the buzzer sounds intermit-
• Working mode tently. This is the warning situation. The signal
• Warning lights (green, yellow, red) and buzzer intervenes when the lifted load is more than 90%
and less than 100% of the maximum load.
The system continually monitors output from the • Red light is ON and buzzer sounds continuously.
pressure transducers and compact integrated trans- The lifted load exceeds the allowable load so the
ducer. It integrates the programmed inputs from the maneuvers shutdown function is activated. In
display panel switches, pressure transducers, and alarm situation, only the maneuvers allowing the
compact integrated transducer and compares this crane to go back from the danger situation are
information to the manufacturer’s capacity charts, allowed.
1
System Components 1900 SRM 1213
System Components
MAIN UNIT LOAD LIMITER SYSTEM (COMPACT
DISPLAY PANEL)
The main unit is equipped with memory for data and
program storage. There are two types of memory During operation, the system measures the angle
storage, (EPROM) for load table storage and erasable and length of the boom and the weight of the load.
type (EEPROM) for setting data storage. The main The information about the load is shown on the
unit input/output signals are self-protected against display screen above the instrument panel. The sys-
overloads and short circuits. tem has an automatic shutoff that activates when
the load moment increases beyond the factory set
limits. Load moment is a combination of the weight
2
1900 SRM 1213 System Components
of the load and its relationship to the front axle. The PRESSURE TRANSDUCERS
load moment is increased by extending or lowering
the boom and load and decreased by retracting and NOTE: The pressure reducers are exchangeable.
raising the boom and load. When a fault code occurs, it’s possible to swab
the pressure reducers and check if the fault code
COMPACT INTEGRATED TRANSDUCER changes. If the fault code changes, the pressure
(BOOM LENGTH AND ANGLE transducer must be replaced. When the fault code
remains, the problem must be found somewhere
TRANSDUCER) else.
The compacted integrated transducer is assembled The pressure transducers detect the pressure on the
on the left outside of the outer boom and contains boom lifting cylinders. Typically, the two sensors are
the components as shown in Figure 3. A drum cable required for measuring the differential pressure on
servo-winder is assembled on which a cable is wound. the main cylinders. From these values the weight
The other side of the cable is connected to the inner is calculated. These sensing devices detect the pres-
boom. A potentiometric sensor is assembled in the sure by an element, which transforms the detected
servo-winder and measures the drum rotation and pressure into a direct voltage proportional to the
therefore the boom extension. A second potentiomet- pressure. The on-board amplifier is included in the
ric sensor is positioned on the circuit board and mea- sensors itself. Any possible replacement of these
sures the absolute angle of the boom to the horizontal elements is very easy because of their compatibility.
reference. These potentiometric sensors are used by
the main computer to measure the angle/extension of
the boom.
3
Operation (Compact Display Panel) 1900 SRM 1213
By pressing the ENTER button, the display shows • L : Current extension [m or ft]
for a few seconds the measure of boom length, the • R : Radius [m or ft]
height, and the angle. See the following table. The
measure unit is in accordance with the selected unit. Page 2
LLL.L HH.H AAA.A P100 L:50 H:40
P 0 l 0 h 0
This line shows:
4
1900 SRM 1213 Replace and Adjust
Page 3 Page 5
0 XXXX 1 XXXX l
2 XXXX 3 XXXX 01234567890123
*- - - - - - - - - - - -
• 0 : Pressure transducer piston side lifting
cylinder [bit] Digital inputs. The symbol "*" indicates active input
while "-" indicates inactive input.
• 1 : Pressure transducer rod side lifting
cylinder • 0 : Cabin in retract position
• 2 : Transducer angle [bit]
Others not used.
• 3 : Transducer extension [bit]
Page 6
Page 4
O
4 XXXX 5 XXXX 01234567890123
6 XXXX 7 XXXX - - - - * *- - - - - - -
Other analog inputs (not used in this application) Digital outputs. The symbol "*" indicates active out-
put while "-" indicates inactive output.
• 4 : Analog input #4
• 4 : Cut off command
• 5 : Analog input #5
• 5 : Cut off command for minimum radius
• 6 : Analog input #6
• 7 : Analog input #7 Others not used.
5
Replace and Adjust 1900 SRM 1213
O XXXX 1 XXXX
Install
2 XXXX 3 XXXX
1. Install the Load Limiter System in the mounting
bracket.
c. Verify the boom is positioned at 0 degrees.
2. Install the two black plastic knobs on the sides of Check if value 2 is between 500 and 520,
the system and tighten. and that the value goes up when the boom
is lifted.
3. Install the connector at the rear side of the sys-
tem. d. Verify the cable length is at least 1 m (3.3 ft)
when the boom is positioned at 0 degrees.
COMPACT INTEGRATED TRANSDUCER Connect the cable when value 3 is between
30 and 60.
Remove
PRESSURE TRANSDUCERS
NOTE: The compact integrated transducer is
mounted at the left outer boom, and is attached Remove
to the inner boom with a cable.
NOTE: The pressure transducers are mounted on the
NOTE: The cable length must remain the same or bottom of the right lift cylinder.
calibration must be done by qualified personnel.
1. Place a drip pan underneath the pressure trans-
1. Remove the four screws from the top cover. ducers to catch any fluid spilled when the pres-
sure transducers are removed.
2. Remove the top cover.
2. Remove the screw at the topside of the electrical
3. Disconnect the cable from the inner boom. connector.
4. Disconnect all electrical cables from the compact 3. Remove the electrical connector from the pres-
integrated transducer and tag all connector wires sure transducer.
to aid in the installation.
6
1900 SRM 1213 Replace and Adjust
4. Remove the pressure transducer and adapter 4. When the value “Angle Min” is correct, select the
from the hydraulic block. “SET MIN” screen and press the “ENTER” but-
ton to save this value.
5. Remove the adapter from the pressure trans-
ducer. A: 00.0 t500
2. Remove the end caps from the hydraulic lines. Angle Max 60
3. Install the adapter onto the hydraulic block. 6. When the value “Angle Max” is correct, select the
“SET MAX” screen and press the “ENTER” but-
4. Install the pressure transducer onto the adapter.
ton to save this value.
5. Install the electrical connector to the pressure
A: 60.0 t690
transducer.
SET MAX 60
6. Tighten the screw at the topside of the electrical
connector.
LENGTH POTENTIOMETER
ANGLE POTENTIOMETER
Boom Length Calibration
Boom Angle Calibration NOTE: A variation of approximately ±1 m (±3 ft)
NOTE: Use this procedure to verify that the actual would indicate one wrap of cable was removed or
boom angle agrees with the angle shown on the Load added to the cable reel.
Sensing System display.
1. Select the operator display with the code typed
1. Select the operator display with the code typed and press the “INDEX” button.
and press the "INDEX" button.
*****
***** WWW.W RR.R MMM.M
WWW.W RR.R MMM.M
2. Select command “13 Boom Transd.” Confirm and
2. Select command 12 Angle Transd. Confirm and press the “ENTER” button.
press the "ENTER" button.
AAA LLL WWW
AAA LLL WWW 13 Boom Transd
12 Angle Transd
3. Fully retract the main boom. Check if the value
3. Lower the boom to a 0-degree angle. Use an angle “Boom min” is between 20 and 60. Adjust, if nec-
protractor to verify the angle of the boom. Check essary.
if the value “Angle Min” is between 500 and 520.
L: 8.8 t50
Adjust if necessary.
Boom Min 8.82
A: 00.0 t500
Angle Min 0.0
7
Troubleshooting 1900 SRM 1213
4. When the value “Boom Min” is correct, select the L: 15.8 t600
“SET MIN” screen and press the “ENTER” but-
ton to save this value. Boom Max 15.80
L: 8.8 t50 6. When the value “Boom Max” is correct, select the
SET MIN “SET MAX” screen and press the “ENTER” but-
ton to save this value.
5. Fully extend the main boom. Check if the value L: 15.8 t600
“Boom Max” is between 600 and 610. Adjust, if
necessary. Boom Max
Diagnostics
The limiter is equipped with a diagnostic part, which registers each failure of external transducers or internal
damages. When damage is registered, the limiter will put itself in a safety condition by blocking maneuvers
and, at the same time, an alarm message will be displayed.
Printer Options
See the Operators Manual for the printer options of the 3B6 Load Limiter System.
Troubleshooting
See the Operators Manual for the troubleshooting of the 3B6 Load Limiter System.
8
TECHNICAL PUBLICATIONS