Professional Documents
Culture Documents
for the
with
AL: N
ECCN: N
Statistical product number: 49019900
Notes/FAQ´s (frequently Asked Questions):
With load-dependent field weakening you must pay attention to the input of output
hyperbole characteristic (P527-P538). The output hyperbole characteristic must be either
normalised to the device current or the current of the SIMOREG DC MASTER 6RA70 (to
the T300/pcd 4) must be scaled to the motor current. (module hoisting gear)
When semi-automatic mode is selected, the master switch enters the maximum speed
setpoint. Depending on the speed setpoint polarity the position setpoint 1 or position
setpoint 2 is selected.
A positive speed setpoint needs a position setpoint1, which is larger than the actual
position, to approach the target position.
A negative speed setpoint needs a position setpoint2, which is smaller than the actual
position, to approach the target position.
(module hoisting gear, holding gear, slewing gear and traversing gear)
s
Changes
Version Date Changes
V1.10 01.07.99
V1.11 01.11.99 - Type transformation of parameter (H171-H174): Nominal pulse
number for 100 % position (H171, H173 transformed; H172, H174
deleted)
V1.20 01.01.01 - Parameter for factory setting added
- Max. process data of the communication board have been in-
creased to 16 process data words
- „free“ process data has been connected with the basic drive /
communication board
- Allocation of digital inputs and digital outputs has been changed for
commissioning purposes
- Allocation of the alarm display has been changed
NOTES
This documentation describes the software implementation of the closed-loop technology control
of crane drives.
The installation, connection and commissioning of the equipment and modules is not described
here. These are provided in sufficient detail in the Instruction Manual of the equipment.
The information on danger, warning notes and cautionary measures should also be taken from
the appropriate Instruction Manuals of the devices.
Further, it is assumed that the equipment is installed, commissioned and serviced by suitably
trained and qualified personnel, who are both knowledgeable about the product itself as well as
the particular industry sector.
This document also doesn't describe basic and simpler functions related with crane drives.
No part of this publication may be reproduced or transmitted in any form or by any means, elec-
tronic or mechanical, including photocopy, recording, or any information storage and retrieval
system, without permission in writing from the publisher.
STRUCTURE
Presently, SIMOREG DC-MASTER 6RA70 devices are being used for the closed-loop control of DC
crane drives and SIMOVERT MASTER DRIVES CUVC for AC drives.
In order to implement the technological closed-loop control tasks and functions, in almost all cases, it is
necessary to use an additional T300 technology processor in the units mentioned above.
The T300 is a freely-configurable technology processor with analog and digital inputs and outputs, two
connections for pulse encoders, serial interfaces etc. On the plant/system side, these connections are
routed to the SE300 terminal block. This is connected to the T300 technology module using screened
round cables. (For this application, only the pulse encoder connections, the analog inputs and outputs
and the serial interfaces are used. The digital inputs and outputs are only used for commissioning pur-
poses.)
The sub-modules (Eproms, program memory modules) for the T300 are programmed with the STRUC
programming language from SIMADYN D. However, these are not required for this particular applica-
tion.
The T300 technology module is used in the electronics box of the drive converter units as option board
(slot 2). Module T300 is shown on Page 9, the installation on Page 8 as well as a connection example
on page 16.
For the various crane drive types, the necessary and frequently required closed-loop control structures
and functions required for these drives, are combined in drive-specific software modules. These are
listed in the table on Page 10 together with the functions which have been implemented.
If other functions are required, which are not listed in the table on the next page, then these must be
implemented as custom software.
With the software, the open-loop- and closed-loop control tasks are clearly separated. These are exe-
cuted in the systems which have been designed for these purposes, i.e. the implementation of all of the
open-loop control functions in the SIMATIC as well as implementation of all closed-loop control func-
tions which are distributed in the drive control system.
Digital interlocking, e.g. controlling contactors, generating enable signals for the drive must therefore
be implemented in the higher-level open-loop control system. Only the drive-specific closed-loop con-
trol circuits and functions are implemented in the freely-programmable technology modules.
The closed-loop technology control is realized in the technology modules. However, the closed-loop
speed control and the closed-loop current control in the basic drives are fully utilized.
The complete control (control words and setpoint-actual values) of the drive converters is realized via
this interface. (The communication board CBP/CBP2 has to be inserted in slot G via the adaption
board ADB (slot 3)).
The essential signals from the automation system to the drives are four 16-bit control words as well as
the setpoints for the speeds and the position setpoint for a closed-loop position control.
The communications between the technology module and a basic drive is realized through a DPR (dual
port Ram).
The setpoint is entered from the master switch via ET200, SIMATIC and Profibus to the drive unit.
The position actual values must be sensed for the closed-loop position control of a drive. In many
cases, this can be realized using the speed encoder is mounted on the motor.
For the grab position control of a grab crane or for the closed-loop synchronous control of two drives, it
is necessary to sense the position actual values of both drives. This can also be realized using the
pulse encoder, mounted on the motor for the speed actual values.
The pulse encoder signals for the speed actual value sensing are fed to the basic drives and for the
position actual value sensing, to the technology module. It is also possible to mount additional pulse
encoders on the cable drum.
The necessary parameters are defined as technology parameters and these can be set and changed.
They are set via the basic drive operator panel. It is also possible to parameterize the units (basic drive
and technology module) using the SIMOVIS service tool. (The database of the T300 technology mod-
ule is included in delivery.)
An overview of the concept is shown in the following block diagram using as an example, the holding-
and closing gear of a grab crane. The block diagram is also valid for an individual drive or a master-
slave drive.
control words
n** status words
n*
s*
ET ET ET
CB CB
peer to peer
TB n*, i* TB
master switch
HW and SW
GG GG
1 2 3 4 5 6 7 8
Memory module
for slot in T300
X132 (RS232)
Peer-to-peer-
connection X133 (RS485)
(to other T300
units, to the SCB2 X134 (RS485)
or SIMOREG
6RA24)
X136
SC58 SC60
Length of
1 the round 1
cables: 2 m
Hoisting gear
► Load-depending field weakening ► Position sensing with synchronization (of the position)
► Heavy load operation (reduced setpoint) ► Closed-loop position control (for automatic- or
► Jogging manual operation)
► Ramp-function generator changeover for field- ► Non-linear master switch setpoint
weakening and heavy loads ► Pre-limit switch
► Changeover to synchronous operation control with ► Start pulse
one-only (manual) setting of the position difference ► Monitoring functions
(slave operation) ► Current distribution monitoring
► Braking with constant distance
Holding gear
► Constant field weakening (efficiency) ► Slack rope control
► Heavy load operation (reduced setpoint) ► Position sensing with synchronization (of the position)
► Closed-loop position control (for automation- or
► Non-linear master switch setpoint
manual operation)
► Pre-limit switch
► Jogging
► Start pulse
► Ramp-function generator changeover for ► Monitoring functions
heavy loads
Closing gear
► Grab adjustment ► Grab position sensing
► Start pulse ► Closed-loop grab position control
► Current equalization control with polyp grab ► Jogging
operation ► Monitoring functions
► Changeover to synchronous operation control with
one-only (manual) setting of the position difference
(slave operation))
Slewing gear
► Non-linear master switch setpoint ► Position sensing with synchronization (of the position)
► Closed-loop position control (for automatic or ► Pre-limit switch
manual operation) ► Monitoring functions
► Jogging ► Influencing the ramp-function generator dependent
► Working angle-dependent accelerating time on the system deviation
► Working angle-dependent slewing speed
Traversing gear, master
► Non-linear master switch setpoint ► Position sensing with synchronization (of the position)
► Closed-loop position control (for automation- or ► Pre-limit switch
manual operation) ► Monitoring functions
► Jogging ► Current distribution monitoring
► Changeover to synchronous operation control with
one-only (manual) setting of the position difference
(slave operation)
Traversing gear, slave
► Current distribution monitoring ► Jogging
► Closed-loop synchronous operation control with ► Position sensing with synchronization (of the position)
offset as position difference ► Monitoring functions
The communications between these two systems is implemented via Profibus SINEC L2-DP.
This serial peripheral SINEC L2-DP bus system is optimized for extremely fast cyclic master-slave
operation. In this case, the drives are always operated as slaves; the higher-level system has the
master function, which in this case is the SIMATIC.
The net data structure with which a DP master can access the drives is described in the following text.
The SINEC L2-DP transfers the net data with the SRD utility (Send and Request with Data). This
means, that net data are always transferred via the bus, both from the master to the slave as well as in
return telegrams from the slave to the master.
The master formulates a task, the slave processes this task and formulates the appropriate response.
There is precisely one task in each telegram from the master to the slave; there is precisely one re-
sponse in each telegram from the slave to the master.
The length and structure of the net data are permanently specified, and are known as Parameter Proc-
ess data Objects (PPO).
Five types are defined to transfer net data (PPO), with which process data, i.e. control words, status
words, setpoints and actual values can be simultaneously transferred, also parameters from the mas-
ter to the slave and vice versa.
1
In the following application, only PPO type 5 is used.
The PPOs are sub-divided into two areas: PKW (parameter identification value)
PZD (process data)
The PKW area allows parameter values to be read and written into and parameter descriptions and
texts read. Every drive parameter can be visualized or changed via this mechanism.
The PZD area contains all of the necessary signals which are required for process control. These in-
clude control words and setpoints from the automation to the drive and status words and actual values
from the drive to the automation system.
The advantage in this case is that in a telegram, both the cyclically required process data can be
transferred, and it is also possible to simultaneously access parameters (reading/writing).
1
Cyclical data can be freely-configured by using the communication board CBP2 with the Engineering
Tool DriveES (no PPO-type). There are up to 16 process data words configurable. Independent from
the amount of process data a parameter area (PKW) is configurable. So you are not dependent on the
5 predetermined PPO types.
System connector
Fixing screw
LED (green)
LED (yellow)
LED (red)
Fixing srcew
PKW PZD
PZD1 PZD2
IND PWE STW1 HSW PZD3 PZD4 PZD5 PZD6 PZD7 PZD8 PZD9 PZD10
ZSW1 HIW
1st 2nd 3rd 4th 1st 2nd 3rd 4th 5th 6th 7th 8th 9th 10th
PPO1
PPO2
PPO3
PPO4
PPO5
The data transfer within the "slave modules", i.e. between the drive converter and CB, is realized using
internal SIEMENS data transfer mechanisms, the so-called device response. The data is transferred
between the communications module and drive converter via the DUAL PORT RAM (DPR).
Data transfer between the communications module CB and the basic drive is realized via a dual port
RAM coupling (DPR). Both sides, CB and basic drive can access the memory of the dual port RAM
writing and reading. The dual port RAM chip is provided on the CB.
If an additional TB technology module is provided, then this is switched between the CB and the basic
drive. In this case, the dual port RAM of the CB is the interface to the TB and dual port RAM on the TB
is the interface to the basic drive (configuration TB-CB basic drive).
The initialization data transferred between CB and the basic drive is not influenced by the TB, i.e. the
technology module copies the data from its dual port RAM one-to-one into the dual port RAM of the CB
and vice versa. The function must be appropriately configured in the TB.
16 pieces of process data can be transferred in both directions between the TB and basic drive.
This communications connection is generally used for master-slave drives, where the master setpoint
for the slave drive(s) is (are) entered from the master drive.
This is also the case for holding- and closing gears of a grab crane where the speed setpoint for the
closing gear and the current setpoint for the current equalization control is transferred to the closing
gear via this coupling.
This coupling is realized using a fast peer-to-peer connection between the technology modules.
A maximum of 5 PZD data words can be transferred in both directions via this interface.
peer
to
peer
T300 5 unit 2
words
1 2 3 4 5 6 7 8
control word 1
IG
control word technology 1
setpoints
ET200 ET200
functions functions
n* n* ML
2
PROFIBUS i*
SINEC L2 DP
M
technological
control
nist
∆n
1 i* T
nist
monitoring
acknowledge monitoring
sist acknowledge
nist nist
status word 1
status word 2
1 2 3 4 5 6 7 8
1.8 basic signal characteristics and structure of the closed-loop control I&S IT PS Erl 35 01.01.01 V 1.2 page 16
s
1.9 Connecting-up diagram for the T300
2 pulse encoder inputs
+24 V +24 V
Fine HTL-signal level, max.
pulse Input frequency 400 kHz
Coarse
Zero- +15 V Zero-
+15 V Input current per channel:
pulse pulse
pulse 90° 0° 90° 0° 4 mA
X5.538 537535 533 531 540 539 548 547 545 543 541 549
+15V X133
Pulse encoder Pulse encoder
detection 1 detection 2
6
X5
Serial interface 1
7
501 e.g. for service,
+ A RS485, 2-wire
+10
- V 502 - 8
start-up with PC/PG
D
T/Rx+
503
+ A 9
+10
- V 504 - D T/Rx- Either RS232 or RS485
10
505 interface useable!
+ A X132
+10
- V 506 - D RxD 1
TTL
7 analog inputs 507 RxD 2
Differential inputs + A RS232
+10
- V 508 - D 3
11 bits + sign
10 V/ k 4
511
+ A 5
+10
- V 512 - D X134
513 RS485, 4-wire
+ A Tx+ 13
+10 V 514 -
Micro-
- D
processor Tx- 14
515 Serial interface 2
A
CPU:
+ Rx+ 11 (peer-to-peer)
+10
- V 516 - D 80C186
20 MHz Rx- 12
X6
15
+24 V 610
+ 11 bit + VZ X5
601 D 509
602 A
510
603
8 binary inputs D
604 519
24 V DC A
(input current 605 520
4 analog outputs
8 mA typical) 606
D 521
11 bits + sign
607 + 10 V / 10 mA.
A
608 522
D 523
+24 V 630
A
524
+
611 X6
639 +24 V
612
Slot for 631
613 memory
8 binary inputs 632
614 module, e.g.
24 V DC MS 300 633 8 binary outputs
(input current 615
634 24 V DC / max. 100 mA
8 mA typical) 616 Base load 40 mA for
635
617 external P24 infeed which
636
can also come from
618 637 the basic unit
638
640
VZ = sign
In order to establish error-free communications and functionality between SIMATIC and the drive unit,
the following parameter settings must be made in the basic drive of the converter or inverter. Depend-
ing on the selected BICO data set, these settings are made in index 1 or 2. These are:
P576.1 or 2 = 3300
P577.1 or 2 = 3301
P578.1 or 2 = 3302
P579.1 or 2 = 3303
P580.1 or 2 = 3304
P581.1 or 2 = 3305
P582.1 or 2 = 3306
P583.1 or 2 = 3307
P584.1 or 2 = 3308
P585.1 or 2 = 3309
P586.1 or 2 = 3310
P587.1 or 2 = 3311
P588.1 or 2 = 3312
P589.1 or 2 = 3313
P590.1 or 2 = 3314
P591.1 or 2 = 3315
Otherwise, the parameters which are not to be controlled from the SIMATIC, should be left in the
factory setting.
The remaining available process data can be connected and used individually.
2
The start pulse has to be parameterized just for hoisting gear, holding gear and closing gear (mod-
ules 1-3) because it is only relevant for these gears
Introduction and overview V1.20 19 01.01.2001
Copyright © Siemens AG All Rights Reserved
s
1.10.2 SIMOREG DC MASTER 6RA70
The remaining available process data can be individually connected and used.
3
The start pulse has to be parameterized just for hoisting gear, holding gear and closing gear (mod-
ules 1-3) because it is only relevant for these gears
Introduction and overview V1.20 21 01.01.2001
Copyright © Siemens AG All Rights Reserved
Technology software module
for the
STRUCTURE
2.1 Jogging
Using this function, the drive can be moved with small speed setpoint intervals. This is required, for
example, to attach the cable to the hoisting gear.
ramp-function
generator speed controller
0
1
jogging
setpoint
command jogging
direction 1
command jogging
direction 2
command jogging
direction 1
command jogging t
direction 2
jogging setpoint
direction 1
jogging setpoint t
direction 2
1 2 3 4 5 6 7 8
jogging
speed controller
n* i*
nist
selection
enable start
pulse
1 2 3 4 5 6 7 8
start pulse
This function continually monitors the speed setpoint and speed actual value, which, when the system
is operating correctly, must approximately correspond with one another.
This monitoring function responds, for example, if the closed-loop control goes to its current limit due
to an overload or a stalled drive, as the speed actual value can no longer follow the speed setpoint.
However, if the setpoint is less than the response difference, then there is a no signal output if the ac-
tual value is missing. This fault is detected using the interrupted tachometer monitoring function of the
basic drives.
This function can be used for speed-actual-actual monitoring if a drive is equipped with a speed actual
value- and position actual value encoder.
If a drive has, in addition to a pulse encoder for the speed actual value, also a pulse encoder for the
position actual value, which is not mounted to the motor, but for example, to the drum, then monitoring
can be realized by evaluating the speeds supplied from both encoders. For instance, this can be used
to monitor the gearboxes or couplings for two rigidly coupled drives.
This monitoring function represents a software centrifugal switch. Using this monitoring function, a
signal can be generated when a selectable speed is exceeded.
Values of between 110-150% of the maximum permissible operating speed are set for these over-
speed protective devices. When an overspeed monitoring function responds, appropriate shutdown
mechanisms can be initiated.
This function monitors the speed and responds if the selected limit is fallen below.
This signal is mainly used to close the brake. It is also used, for example, in the hoisting gear module
to calculate the supplementary speed setpoint for load-dependent field weakening.
actual speed
signal to status word
value from
+ (technology) bit 4
basic unit -
actual speed
value from
technology board
(NAV)
closed-loop control monitoring
overspeed monitoring
actual speed
signal to status word
value from
(technology) bit 2
basic unit
1 2 3 4 5 6 7 8
monitorings
This function is required for the closed-loop grab position (travel) control.
The prerequisite for the closed-loop grab travel control (positioning) or the closed-loop position syn-
chronous control for the holding- and closing units (e.g. for traversing operation) is that the actual posi-
tion values of the holding- and closing gear have to be sensed (for grab operation, a grab actual value
position).
It is not possible to sense the grab opening position directly at the grab, but is approximately deter-
mined by measuring the cable length difference (holding cable minus the closing cable). This cable
length difference is in turn proportional to the number of revolutions of the cable drum holding gear (or
motor holding gear) minus the number of revolutions of the cable drum, closing gear (or motor closing
gear). This measurement is technologically precise in spite of the elasticity and cable sag.
The position actual value of the holding- and closing gear is measured (or the grab opening travel) in
almost all cases using the speed encoder, mounted at the motor (a pulse encoder must be used, an
analog tachometer is not adequate).
The T300 technology module has, in the form of its terminal module pulse encoder sensing inputs 1
and 2, which can be read-in from a block at the same time.
The pulse encoder signals are connected to the basic drive for the speed actual value sensing and to
the technology module for position actual value sensing.
For a closed-loop synchronous position control of the holding- and closing gear, the position actual
value difference sensing can also be used if it is sufficient that the position difference, which the sys-
tem should control, is set manually once.
The actual (required) position difference actual value when closed-loop synchronous operation control
is selected with “grab closed" must be saved as setpoint. The closed-loop synchronous operation con-
trol is operated with this as setpoint until it is cancelled again.
For closed-loop grab position controls as well as for closed-loop synchronous operation control of
holding- and closing gears, the position actual values of both drives must be sensed in the closing
gear. This can also be implemented using the pulse encoder, mounted at the motor, which is used to
sense the speed actual values.
The pulse encoder signals are routed to the basic drive for speed actual value sensing and to the tech-
nology module of the second drive for position actual value sensing.
The position actual value of a drive must always be connected to pulse encoder sensing input 1 and
that of the master drive to pulse encoder sensing 2 (for the slave).
In order to adjust the grab when changing grabs, the master switch is directly entered as setpoint and
the required end positions for grab open and closed, is approached, closed-loop speed controlled. The
actual values at the end positions, open and closed, are then saved as setpoints at the push of a but-
ton. When the master switch is moved to open or close the grab, the associated signal is switched to
the position controller as setpoint.
setpoints setpoints
n* n*
i* i*
nist nist
M T M T
T T
1 2 3 4 5 6 7 8
hardware- and software structure for position- and synchronization control I&S IT PS Erl 35 01.01.01 V 1.2 page: 8
s
2.9 Close-loop grab position control
This closed-loop control ensures that the closing operation, when required, is executed at the maxi-
mum speed, and is optimally positioned in the "closed" or "opened" end positions.
The demand for higher material handling performance has meant that crane drives must approach the
specified target as quickly as possible.
State-of-the-art grab cranes with high closing speeds have closing gear equipped with closed-loop
position control, which is effective both in the automatic- as well as in the manual modes.
The closed-loop grab position control ensures that the closing operation, when required, is executed at
the maximum speed, and the grab is optimally braked and positioned in the grab open and grab closed
end positions.
For the closed-loop grab position control, the end points for grab open and grab closed are approached
as quickly as possible corresponding to the principle of the previously described closed-loop position
control. The grab, for example, reaches the precise position closed, without the grab gripping edges
hitting each other.
Also in the manual mode, the closed-loop position control makes it far easier for the crane driver, as
the closing gear drive is precisely and automatically stopped in the grab open and grab closed end
positions by the software.
By applying the position equations and taking into account the limiting conditions, it can be determined
that this is possible using the square-root equation.
v = 2⋅a⋅s
By implementing this equation, the drive can approach a specified point as quickly as possible, closed-
loop position controlled.
The closed-loop position control specifies the setpoint for the closed-loop speed controller. If the drive
comes in the direction of the target point, then from a calculated initiation point, the speed setpoint is
reduced as a function of the position. The position actual value is available from a pulse encoder. The
target for the end points (position setpoint) are manually saved at the start of a grab change and
switched-in, dependent on the direction requested from the master switch.
The generated setpoint must then be normalized to the rated speed of the closing gear for closing and
opening.
speed setpoint
0% 0
to basic unit
speed
1
setpoint
setpoint
enable
(S7)
x
y>x
0% y
master switch
polarity
0%
setpoint grab open 0 MIN 0
1
+ 1
pulse
T encoder
∆s
evaluation x
y>x
0% y
command grab open ∆s=0
1 2 3 4 5 6 7 8
signal flow chart grab position control closing gear I&S IT PS Erl 35 01.01.01 V 1.2 page: 10
s
2.10 Closed-loop synchronous operation control for holiding- and closing gear of grab
cranes
This function is required if holding- and closing gear, which normally operate individually and essen-
tially independent of one another in the closed-loop speed controlled mode, must operate in synchro-
nism for specific operating cases.
For grab cranes, which can also be used for multi-function operation (container-, traversing- or normal
hook operation), depending on the application and design of the mechanical system, it may be neces-
sary that the holding- and closing gear operate in synchronism.
For this operating case, it is necessary to have closed-loop synchronous position control between the
holding- and closing gear. When positioning to accept loads the drives first operate individually, and
then can be changed over at any position to closed-loop synchronous operation control.
When the holding- and closing gear operate in synchronism, the closing gear follows the holding gear,
closed-loop position controlled with the position difference setpoint to be saved, from the closed grab
position.
The actual position difference actual value must then be saved as setpoint with the grab closed com-
mand. The closed-loop synchronous control is then operated with this as setpoint..
The drives which are operated separately in the closed-loop speed controlled mode, also in this oper-
ating case, are then coupled through the closed-loop control using a closed-loop synchronous control-
ler in the slave drive. They must then operate with position synchronism, even if the load is unevenly
distributed
The closed-loop synchronous operation controller is superimposed on the closed-loop speed control of
the slave drive. The inputs of the closed-loop synchronous operation controller are the saved position
difference actual value as setpoint and the actual position difference actual value as actual value. The
synchronous controller output acts as supplementary setpoint on the setpoint input of the slave drive
speed controller.
When closed-loop synchronous operation control is activated, and a position difference develops be-
tween the drives, then the slave drive receives a supplementary speed setpoint via the synchronous
operation controller. The drive is operated with an increased or decreased speed setpoint, until the
position difference is again zero. The supplementary setpoint (the intervention of the supplementary
setpoint from the synchronous operation controller) should in this case be a maximum of 20% to 30%
of the max. drive speed.
speed setpoint to
0% 0 basic unit i*
speed setpoint (S7) 1
setpoint
position setpoint (S7) enable (S7)
actual position
value
position synchronization
value (S7) pulse s1
encoder
T evaluation
peer to peer
synchronize
closing gear
n-controller
speed setpoint to
speed setpoint (S7) 0% 0 basic unit i*
0 1
1
>0% setpoint
selection enable (S7)
synchronism
0%
setpoint grab open 0
(S7)
1
∆s=0 selection
command grab
open (S7) synchronism
enable (S7)
synchronization
controller (S7)
1 2 3 4 5 6 7 8
signal flow chart synchronization control holding and closing gear overview I&S IT PS Erl 35 01.01.01 V 1.2 page: 12
holding gear n-controller
speed setpoint to
0% 0 basic unit i*
speed setpoint (S7) 1
setpoint
position setpoint (S7) enable (S7)
position synchronization
value (S7) pulse
s1
encoder
evaluation
T
enable slack-rope
controller (S7)
speed setpoint current setpoint
synchronize
selection
grab change
(S7)
n-controller
>0%
scaling
setpoint
nominal selection
0% enable (S7)
setpoint grab open speed synchronism
0
1 (S7)
signal flow chart holding and closing gear overview I&S IT PS Erl 35 01.01.01 V 1.2 page: 13
s
2.11 Current equalization controller with polyp grab operation
When raising and lowering the load with the grab closed, the tension levels in the holding- and closing
cable should be approximately equal. The required hoisting power is then optimally distributed over
both hoisting motors This demand is fulfilled by using a closed-loop equalization control between the
two drives.
The current setpoints, generated from the speed controllers of the hoisting gear are compared, and
their difference is added to the speed setpoint of the closing gear via a controller.
The highest cable torque is obtained when the grab has almost closed. The selected closed-loop posi-
tion control is falsified by the unavoidable cable expansion, i.e. the closing operation is automatically
ended before the grab has completely closed.
This "fault" is also corrected by enabling the closed-loop current equalization control when the grab
closed message is received.
For grab cranes, which are also used for multi-functional operation (container-, traversing- or hook
operation) it may be necessary to activate the closed-loop current equalization controller depending on
the application and the mechanical design.
With this operating mode, the grab generally requires a higher tension in the closing cable than in the
holding cable. The current distribution can be unsymmetrically divided with the required ratio by using
additional circuitry in the closed-loop current equalization control.
This is required, for example, when loading scrap, tree trunks and other large objects. Using polyp
grabs, these objects are held with the grab not completely closed at the grab points.
In order that the load doesn't slip from the grab, the largest possible closing force should be applied.
The closed-loop current equalization controller is used to ensure that the load distribution is non-
symmetrical.
Haltewerk (HW)
n-Regler HW i-Regler HW
i*HW
n*HW M
Schließwerk (SW)
n-Regler SW i-Regler SW
i*SW
n*SW M
Stromausgleichregler
n*Zusatz
1 2 3 4 5 6 7 8
Übersicht Stromausgleichregler
current
equalization
controller
i*HW
nzusatz
to speed
setpoint
K3 closing gear
enable current
equalization
controller
i*SW 0
1
p-droop function
selection
polyp grab
K1
K2
1 2 3 4 5 6 7 8
STRUCTURE
This application of the T300 is provided for 16 receive and send process data from or to the Communi-
cation Board. The process data words 11-16 could only be configured and used with the Engineering
Tool DriveES and the Communication Board CBP2. The following tables show the allocation of the
process data words. Further on the tables show the goal or source of the process data words, i.e. the
connection of the process data (T300, base unit CU or Communication Board CB).
This application of the T300 is provided for 16 receive and send process data from or to the base unit.
The process data, which aren’t used in this application, are connected between the base unit and the
Communication Board. The following tables show the allocation of the process data words. Further on
the tables show the goal or source of the process data words, i.e. the connection of the process data
(T300, base unit CU or Communication Board CB).
The allocation of the control words for the technology board in this application are appropriately the
following tables. The tables show the level (high- (H) or low-active (L)) of the commands. A description
of each control bit follows the tables.
A high-signal sets the speed setpoint to the base unit to the value, parameterized via the parameter
H333. Either additional to the speed setpoint from holding gear (H323 = 0) or separate (H323 = 1). The
setpoint should be for example positive for the direction 1. A low-signal doesn’t select a speed setpoint
for jogging.
A high-signal sets the speed setpoint to the base unit to the value, parameterized via the parameter
H332. Either additional to the speed setpoint from holding gear (H323 = 0) or separate (H323 = 1). The
setpoint should be for example negative for the direction 2 (reverse to direction 1). “Command jogging
direction 1” has priority, if “command jogging direction 1” and “command jogging direction 2” are set
together (high). A low-signal doesn’t select a speed setpoint for jogging.
A high-signal enables the start pulse. At selected start pulse (H453 = 0), the set value (H448) or the
value via automation system decays with the decay time (H451) after low-high level change of the sig-
nal.
A high-signal enables the difference between position difference setpoint and actual position differ-
ence. So the calculation of the position-dependent, additional speed setpoint is possible and necessary
to close and open the grab. A low-signal sets the speed setpoint to 0%.
A high-signal enables the synchronization controller. The position difference value must be saved via
the command “grab closed save”, before the release. A low-signal disables the synchronization con-
troller.
After a grab change, a high-signal sets first the position difference value to 0 when the grab is open.
After a grab change and saved position difference for the position grab open, a high-signal saves the
actual position difference when the grab is closed.
A high-signal selects synchronism. The speed setpoint is set via peer-to-peer-coupling from master
drive. This control is only relevant for slave drives.
Bit 17: selection polyp grab (H „polyp grab mode“ / L „no polyp grab mode“)
A high-signal selects the polyp operation mode for current equalization controller.
A high-signal enables the current equalization controller. A low-signal locks the current equalization
controller.
Bit 19: selection grab change (H „grab change“ / L „no grab change“)
A high-signal selects grab change, i.e. the grab position control isn’t working and the speed setpoint is
setting via PCD2 from automation system. Either additional to the speed setpoint from holding gear
(H323 = 0) or separate (H323 = 1). The grab position control work with a low-signal again.
The allocation of the control words 1 and 2 are appropriately the operating instruction of the base unit
(6SE70 or 6RA70). The following tables show the level (high- (H) or low-active (L)) of the commands. A
description of each control bit you find in the operating instruction of the base unit.
control word 1
Bit 0 OFF1 (L) EIN
Bit 1 OFF2 (L) AUS2
Bit 2 OFF3 (L) AUS3
Bit 3 inverter enable (H) FWR
Bit 4 ramp-function generator enable (H) FHG
Bit 5 ramp-function generator start (H) SHG
Bit 6 setpoint enable (H) FWN
Bit 7 acknowledge (↑) QUITT
Bit 8 jogging bit 0 (H) TIPP1
Bit 9 jogging bit 1 (H) TIPP2
Bit 10 control requested (H) FAG
Bit 11 clockwise phase sequence enable (H) RDF
Bit 12 counter-clockwise phase sequence enable (H) LDF
Bit 13 motorized potentiometer raise (H) MOPOH
Bit 14 motorized potentiometer lower (H) MOPOT
Bit 15 external fault 1 (L) STOEX1
control word 2
Bit 16 selection function data set bit 0 (H) ANW FDS0
Bit 17 selection function data set bit 1 (H) ANW FDS1
Bit 18 selection motor data set bit 0 (H) ANW MDS0
Bit 19 selection motor data set bit 1 (H) ANW MDS1
Bit 20 select fixed setpoint bit 0 (H) ANW FSW0
Bit 21 select fixed setpoint bit 1 (H) ANW FSW1
Bit 22 synchronizing enable (H) FSYN
Bit 23 enable flying restart (H) FFANG
Bit 24 enable droop, speed controller (H) FSTAT
Bit 25 enable speed controller (H) FDREH
Bit 26 external fault 2 (L) STOEX2
Bit 27 master drive (speed control) (L) LEIT
Bit 28 external alarm 1 (L) WARNEX1
Bit 29 external alarm 2 (L) WARNEX2
Bit 30 select BICO data set 1 (L) ANW BICO
Bit 31 no MC checkback signal (L) HS RUECK
The allocation of the status word of the technology board in this application is appropriately the follow-
ing table. The table shows the level (high- (H) or low-active (L)) of the signals. A description of each
status bit follow the table.
A low-signal shows a configuring error of the encoder. The bit is just reset to high-level via the ac-
knowledge command.
Bit 1: signal speed setpoint-actual value difference saved (H „no speed setpoint-actual value
difference saved“ / L „speed setpoint-actual value difference saved“)
A low-signal shows a deviation of the actual speed compared to the speed setpoint, which is larger
than the value parameterized via H456/H457. A larger deviation is saved and the bit is just reset to
high-level via the acknowledge command.
A low-signal shows, if the actual speed is greater than the limit parameterized via H459/H460. A
greater actual speed is saved and the bit is just reset to high-level via the acknowledge command.
A high-signal shows a deviation of the actual speed compared to speed 0, which is larger than the
value parameterized via H461/H462.
A low-signal shows a deviation of the actual speed (T300) compared to the actual speed from the base
unit, which is larger than the value parameterized via H466/H467. A larger deviation is saved and the
bit is just reset to high-level via the acknowledge command.
Bit 5: signal fault coupling T300 to base unit (H „no fault“ / L „fault“)
A low-signal shows an error between the coupling T300 / base unit. The bit is just reset to high-level via
the acknowledge command.
A low-signal shows an error between the coupling T300 / automation system (Communication Board).
The bit is just reset to high-level via the acknowledge command.
A low-signal shows an error between peer-to-peer-coupling. The bit is just reset to high-level via the
acknowledge command.
Bit 10: signal grab open (H „grab open“ / L „grab not open“)
A high-signal shows the opened grab, within the parameterized limit (H256/H257).
Bit 11: signal grab closed (H „grab closed“ / L „grab not closed“)
The allocation of the status words 1 and 2 are appropriately the operating instruction of the base unit
(6SE70 or 6RA70). The following tables show the level (high- (H) or low-active (L)) of the signals. A
description of each status bit you find in the operating instruction of the base unit.
status word 1
Bit 0 signal ready to switch on (H) EINBE
Bit 1 signal ready (H) BETRBE
Bit 2 signal run (H) BETRIEB
Bit 3 signal fault (H) STOERUNG
Bit 4 signal OFF2 (L) KEINAUS2
Bit 5 signal OFF3 (L) KEINAUS3
Bit 6 signal switch-on inhibit (H) EINSPERR
Bit 7 signal alarm (H) WARNUNG
Bit 8 signal setpoint-actual value deviation (L) KEINWXAB
Bit 9 signal PcD control requested (H) FAGGEF
Bit 10 signal comparison value reached (H) VGWER
Bit 11 signal low voltage fault (H) STOEUSP
Bit 12 signal request to energize main contactor (H) HSANGEST
Bit 13 signal ramp-function generator active (H) HLGAKT
Bit 14 signal positive speed setpoint (H) RECHTDF
Bit 15 signal kin. buf./ flex. response active (H) KIPAK
status word 2
Bit 16 signal flying restart or excitation active (H) FANGAK
Bit 17 signal synchronism reached (H) SYNCER
Bit 18 signal overspeed (L) KEIUED
Bit 19 signal external fault 1 (H) STOEEX1
Bit 20 signal external fault 2 (H) STOEEX2
Bit 21 signal external alarm (H) WARNEX
Bit 22 signal converter overload alarm (H) WARNI2T
Bit 23 signal converter overtemperature fault (H) STOEUTMP
Bit 24 signal converter overtemperature alarm (H) WARNUTMP
Bit 25 signal motor overtemperature alarm (H) WARNMTMP
Bit 26 signal motor overtemperature fault (H) STOEMTMP
Bit 27 reserve
Bit 28 signal motor pulled out/blocked fault (H) STOEMBLK
Bit 29 signal bypass contactor energized (H) UEBSAN
Bit 30 signal synchronizing error (H) FBSYN
Bit 31 signal pre-charging active (H) VORLAK
d 065 EGG10.Y1 status word 1 from base unit CU Type: V2 page 5/2
d 066 EGG10.Y2 actual speed value from base unit CU Type: N2 page 5/2
d 067 EGG10.Y3 status word 2 from base unit CU Type: V2 page 5/2
d 068 EGG10.Y4 current setpoint from base unit CU Type: N2 page 5/2
d 069 EGG10.Y5 setpoint-actual value difference from CU Type: N2 page 5/2
d 070 EGG10.Y6 PCD 6 from base unit (to CB connected) Type: N2 page 5/2
d 071 EGG10.Y7 PCD 7 from base unit (to CB connected) Type: N2 page 5/2
d 072 EGG10.Y8 PCD 8 from base unit (to CB connected) Type: N2 page 5/2
d 073 EGG100.Y1 PCD 9 from base unit (to CB connected) Type: N2 page 5/2
d 074 EGG100.Y2 PCD 10 from base unit (to CB connected) Type: N2 page 5/2
d 075 EGG100.Y3 PCD 11 from base unit (to CB connected) Type: N2 page 5/2
d 076 EGG100.Y4 PCD 12 from base unit (to CB connected) Type: N2 page 5/2
d 077 EGG100.Y5 PCD 13 from base unit (to CB connected) Type: N2 page 5/2
d 078 EGG100.Y6 PCD 14 from base unit (to CB connected) Type: N2 page 5/2
d 079 EGG100.Y7 PCD 15 from base unit (to CB connected) Type: N2 page 5/2
d 080 EGG100.Y8 PCD 16 from base unit (to CB connected) Type: N2 page 5/2
d 081 EGG20.Y status word 1 to CB Type: V2 page 5/6
Type: N2
evaluation actual speed value from base unit
H 082 EGG30.X2 Min: -200% 100 % page 5/3
CU Max: 199,9%
d 083 EGG40.Y status word 2 to CB Type: V2 page 5/6
Type: N2
H 084 EGG50.X2 evaluation current setpoint from base unit CU Min: -200% 100 % page 5/3
Max: 199,9%
Type: N2
evaluation setpoint-actual value difference from
H 085 EGG60.X2 Min: -200% 100 % page 5/3
CU Max: 199,9%
Type: N2
H 086 EGG70.X2 evaluation PCD 6 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 087 EGG80.X2 evaluation PCD 7 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 088 EGG90.X2 evaluation PCD 8 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 089 EGG110.X2 evaluation PCD 9 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 090 EGG120.X2 evaluation PCD 10 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 091 EGG130.X2 evaluation PCD 11 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 092 EGG140.X2 evaluation PCD 12 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 093 EGG150.X2 evaluation PCD 13 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
Type: N2
H 094 EGG160.X2 evaluation PCD 14 from base unit Min: -200% 100 % page 5/3
(to CB connected) Max: 199,9%
analog inputs
Type: N2
H 133 AE20.X2 evaluation analog input A Min: -200% 100 % page 7/2
(terminal SE 300 X5/501,502) Max: 199,9%
Type: N2
H 134 AE50.X2 evaluation analog input B Min: -200% 100 % page 7/2
(terminal SE 300 X5/503,504) Max: 199,9%
Type: N2
H 135 AE80.X2 evaluation analog input C Min: -200% 100 % page 7/2
(terminal SE 300 X5/505,506) Max: 199,9%
Type: N2
H 136 AE110.X2 evaluation analog input A Min: -200% 100 % page 7/2
(terminal SE 300 X5/507,508) Max: 199,9%
Type: N2
H 137 AE30.X2 offset analog input A Min: -200% 0% page 7/3
Max: 199,9%
Type: N2
H 138 AE60.X2 offset analog input B Min: -200% 0% page 7/3
Max: 199,9%
Type: N2
H 139 AE90.X2 offset analog input C Min: -200% 0% page 7/3
Max: 199,9%
Type: N2
H 140 AE120.X2 offset analog input D Min: -200% 0% page 7/3
Max: 199,9%
d 141 AE30.Y analog input A after evaluation and offset Type: N2 page 7/3
d 142 AE60.Y analog input B after evaluation and offset Type: N2 page 7/3
d 143 AE90.Y analog input C after evaluation and offset Type: N2 page 7/3
d 144 AE120.Y analog input D after evaluation and offset Type: N2 page 7/3
d 187 ERX520.Y actual speed value from position encoder Type: N2 page 9/7
(track 1)
setpoint preparation
Type: B1
H 205 W10.I selection source for speed setpoint Min: 0 0 page 10/1
(0 = from CB / 1 = from analog input 1) Max: 1
position control
d 252 WR50.Y position difference setpoint for grab close Typ: N2 page 10/2
d 253 WR55.Y position difference setpoint for grab Typ: N2 page 10/3
Typ: N2
H 256 WR70.L setting value for signal grab open Min: -200% page 10/4
Max: 199,9%
Typ: N2
H 257 WR70.HY setting value hysteresis for signal grab open Min: -200% page 10/4
Max: 199,9%
Typ: N2
H 258 WR90.L setting value for signal grab closed Min: -200% page 10/3
Max: 199,9%
Typ: N2
H 259 WR90.HY setting value hysteresis for signal grab closed Min: -200% page 10/3
Max: 199,9%
position difference between setpoint-actual
d 262 WR35.Y Type: N2 page 11/3
value
initiation point position control Type: E2
H 263 WR110.KP (set the position difference, at which the speed will be less Min: -256 12 page 11/3
than the max. speed (100%) => ramp-down from 100% starts) Max: 255
d 264 WR110.Y output position controller (following: 2a∆s(scaled)) Type: N2 page 11/3
initiation point root function Type: E2
H 265 WR150.KP (sets the gradient of the line function and so the point of Min: -256 2 page 11/4
changeover from root function to line function) Max: 255
synchronization controller
Typ: N2
H 287 GLR75.LU upper limit synchronization controller Min: -200% 5% page/10/3
(max. additional positive setpoint of synchronization controller) Max: 199,9%
lower limit synchronization controller Typ: N2
H 288 GLR75.LL (max. additional negative setpoint of synchronization control- Min: -200% - 5% page 10/3
ler) Max: 199,9%
Typ: E2
H 289 GLR75.KP gain KP synchronization controller Min: -256 1 page 10/3
Max: 255
Type: R2
H 306 GLR100.T filtering time for controller output Min: 10ms 500 ms page 10/4
Max:163840ms
changeover
d 310 W420.Y speed setpoint after position control Type: N2 page 10/5
Typ: N2
H 320 W940.X2 adaption setpoint to base speed Min: -200% 50% page 11/2
Max: 199,9%
speed setpoint for position/synchronization
d 322 W960.Y Typ: N2 page 11/3
control
release for disable speed setpoint (master) at Typ: B1
H 323 W960.I2 jogging mode (at selected jogging mode: 0 = additive Min: 0 0 page 11/3
speed setpoint from Master / 1 = no additive speed setpoint Max: 1
from Master)
release for disable speed setpoint (master) ati Typ: B1
H 324 W970.I2 grab change (at selected grab change: 0 = additive speed Min: 0 0 page 11/3
setpoint from Master / 1 = no additive speed setpoint from Max: 1
Master)
d 330 W470.Y speed setpoint after selection (no) synchronism Type: N2 page 10/7
d 331 W460.Y speed setpoint after selection (no) jogging Type: N2 page 10/6
Type: N2
H 332 W440.X1 jogging setpoint direction 2 (negative direction) Min: -200% -10 % page 10/4
Max: 199,9%
ramp-function generator
Type: N2
H 374 W630.LU upper setpoint limit at RFG Min: -200% 100 % page 10/7
(upper speed limit at ramp-function generator output) Max: 199,9%
Type: N2
H 375 W630.LL lower setpoint limit at RFG Min: -200% -100 % page 10/8
(lower speed limit at ramp-function generator output) Max: 199,9%
Typ: R2
H 376 W630.TU ramp-up time Min: 10ms 4000 ms page 11/6
Max:163840ms
Typ: R2
H 377 W630.TD ramp-down time Min: 10ms 4000 ms page 11/6
Max:163840ms
d 428 SAR135.Y effective current setpoint for SAR (holding gear) Typ: N2 page 11/5
d 429 SAR145.Y effective current setpoint for SAR (closing gear) Typ: N2 page 11/5
Typ: E2
P-gain for P-droop current equalization
H 431 SAR150.KP Min: -256 5 page 11/6
controller (SAR) Max: 255
d 432 SAR150.Y output P-droop current equalization contr. Typ: N2 page 11/7
evaluation for P-droop current equalization Typ: N2
H 433 SAR160.X2 Min: -200% 5% page 11/4
controller (SAR) Max: 199,9%
d 434 SAR 160.Y2 effective P-droop Typ: N2 page 11/5
Typ: E2
H 436 SAR170.KP P-gain current equalization controller Min: -256 3 page 11/5
Max: 255
Typ: R2
H 437 SAR170.TN integral time current equalization controller Min: 10ms 2000 ms page 11/5
Max:163840ms
d 439 SAR170.Y output value current equalization controller Typ: N2 page 11/6
Typ: R2
H 440 SAR180.T
filtering time for output value current equaliza- Min: 10ms 50 ms page 11/6
tion controller (SAR) Max:163840ms
evaluation additional setpoint from current Typ: N2
H 441 SAR190.X2 Min: -200% 10 % page 11/7
equalization controller SAR Max: 199,9%
d 442 SAR195.Y effective additional setpoint from SAR Typ: N2 page 11/7
d 444 W810.Y effective additional speed setpoint (closing Typ: N2 page 11/7
gear)
start pulse
Type: B1
H 445 STI05.I selection source for load-dependent start pulse Min: 0 0 page 15/2
(0 = from CB / 1 = from analog input 4) Max: 1
monitorings
Type: R2
H 455 UEB20.T filtering time setpoint-actual value difference Min: 20ms 2000 ms page 14/6
Max:327680ms
Type: N2
setting value for signal setpoint-actual value
H 456 UEB30.M Min: -200% 10 % page 14/6
difference Max: 199,9%
Type: N2
hysteresis for signal setpoint-actual value dif-
H 457 UEB30.HY Min: -200% 1% page 14/6
ference Max: 199,9%
Type: R2
H 458 UEB60.T filtering time actual speed value Min: 20ms 20 ms page 14/6
Max:327680ms
Type: N2
H 459 UEB70.M setting value for signal overspeed Min: -200% 110 % page 14/6
Max: 199,9%
Type: N2
H 460 UEB70.HY hysteresis for signal overspeed Min: -200% 2% page 14/6
Max: 199,9%
Type: N2
H 461 UEB90.M setting value for zero speed signal Min: -200% 5% page 14/6
Max: 199,9%
Type: N2
H 462 UEB90.HY hysteresis for zero speed signal Min: -200% 1% page 14/6
Max: 199,9%
Type: R2
filtering time speed actual-actual value differ-
H 465 UEB130.T Min: 20ms 2000 ms page 14/2
ence Max:327680ms
Type: N2
H 466 UEB140.M setting value for stopping nact- nact -difference Min: -200% 15 % page 14/3
Max: 199,9%
Type: N2
H 467 UEB140.HY hysteresis for stopping nact – nact -difference Min: -200% 1% page 14/3
Max: 199,9%
general
analog outputs
Type: O2
H 960 AA10.XCS control input multiplexer for analog output H Min: 0 1 page 7/5
Max: 32767
Type: O2
H 961 AA50.XCS control input multiplexer for analog output J Min: 0 1 page 7/5
Max: 32767
Type: O2
H 962 AA90.XCS control input multiplexer for analog output K Min: 0 1 page 7/5
Max: 32767
Type: O2
H 963 AA130.XCS control input multiplexer for analog output L Min: 0 1 page 7/5
Max: 32767
d 964 AA10.Y actual output value AO H Type: N2 page 7/6
d 965 AA50.Y actual output value AO J Type: N2 page 7/6
d 966 AA90.Y actual output value AO K Type: N2 page 7/6
The faults (and alarms) generated from the technology board T300 are send to the base unit. The base
unit shut down the drive with the fault message. This configured system of the T300 saves the faults.
So the faults generated from the T300 cannot acknowledge via base unit. The technology faults must
be acknowledged via bit 7 of control word 1, when the inverter release (control word 1 bit 4) isn´t high
(s. function plans)
speed setpoint
jogging from holding
setpoint gear
0% 0
synchronization
1
+
controller
-
command grab 0% 0
y=x
closed (S7) y 1
x
selection
synchronism
enable (S7)
increments from synchronization
pulse
closing gear controller (S7)
encoder
evalua- actual position difference value
increments from current equalization
holding gear
tion
controller
current setpoint
holding gear
command grab current setpoint
open (S7) closing gear
enable current
equalization
controller
T300 X134 CU
receive peer
to peer from
holding gear
1 2 3 4 5 6 7 8
020
005
5 control word 2 (technology) 0
1
STEU_TB2 [3/5]
[2/5] NSTTB2
006
0
6 PZD6_Empf PZD6_Emp [6/4]
021
CB X135 007 100%
022
DUAL 7 PZD7_Empf PZD7_Emp [6/4]
PORT connected to base
008 100%
RAM 023 unit CU
CB → TB 8 PCD8_Empf PZD8_Emp [6/4]
009 100%
024
9 PCD9_Empf PZD9_Emp [6/4]
010 100%
025
10 start pulse STI [13/1]
011 100%
026
11 PCD11_Empf PZD11_Emp [6/4]
012 100%
027
12 PCD12_Empf PZD12_Emp [6/4]
013 100%
028 parameter:
13 PCD13_Empf PZD13_Emp [6/4] connected to base
unit CU
014 100% xxx : display parameter
029 (only usable with DriveES
14 PCD14_Empf PZD14_Emp [6/4] (no PPO-type))
015 100%
030 xxx : setting parameter
15 PCD15_Empf PZD15_Emp [6/4]
016 100%
031
16 PCD16_Empf PZD16_Emp [6/4] [7/5]
100%
032
FES5 [12/1]
1 2 3 4 5 6 7 8
block diagram: closing gear - receive from CB I&S IT PS Erl 35 01.01.01 V 1.2 page: 1/14
terminal PIN T300 PIN T300 terminal
0 0
SE300 X6 X136 X136 SE300 X6
0 1
0 2 binary output 1
1 binary input 1 [10/4] 21
601 inverter enable 3 MGG signal grap closed 631
ramp-function generator enable 4
2 binary input 2 0 5 binary output 2 22
602 [10/4] MGO signal grap open 632
setpoint enable 6
acknowledge 7
binary input 3 NSTEU1 [1/6] binary output 3 23
603
3 0 8 [12/8] MXNGS overspeed 633
0 9
1 10 binary output 4
4 binary input 4 [12/8] MXN0
24
604 0 11 speed = 0 634
0 12
5 binary input 5 0 13 binary output 5 25
605 [12/4] FIGNSS speed actual-actual value differ. 635
0 14
0 15
6 binary input 6 binary output 6 26
606 [12/3] FKGERS fault coupling T300 to base unit 636
14 binary input 12
614 0 16
selection polyp grab 17
15 binary input 13 enable current equalization contr. 18
615
selection grab change 19
0 20
16 binary input 14
616 0 21
0 22
17 binary input 15 0 23
617 NSTTB2 [1/6]
0 24
0 25
18 binary input 16 0 26
618
0 27 the operation via binary inputs or
0 28 outputs isn´t intented with this
19
24V + 619 P24 extern 0 29 application.
- 0 30 the binary inputs or outputs are only
20
0 31 to simplify the commissioning etc..
620 M24 extern
1 2 3 4 5 6 7 8
block diagram: closing gear - simulation control words I&S IT PS Erl 35 01.01.01 V 1.2 page: 2/14
0 OFF1 (L) EIN 0 command jogging direction 1 (H) KTA [11/2]
1 OFF2 (L) AUS2 1 command jogging direction 2 (H) KTB [11/2]
2 OFF3 (L) AUS3 2 enable start pulse (H) FST [13/4] [13/5]
3 inverter enable (H) FWR [14/5] 3
033 4 ramp-function generator enable (H) FHG [11/6]
036 4
5 ramp-function generator start (H) SHG 5
6 setpoint enable (H) FWN [11/5] 6
7 acknowledge (↑) QUITT [14/5] 7 enable position control (H) FRS [10/4]
[1/7] STEU1 [1/7] STEU_TB1
8 jogging bit 0 (H) TIPP1 8 enable synchronization controller (H) FGR [10/4]
9 jogging bit 1 (H) TIPP2 9
10 control requested (H) FAG 10 command grab open save (H) KGO [9/2]
11 clockwise phase sequence enable (H) RDF 11 command grab closed save (H) KGG [10/1]
12 counter-clockwise phase sequence enable (H) LDF 12 selection synchronism (H) AGL [11/5] [11/6]
13 motorized potentiometer raise (H) MOPOH 13
14 motorized potentiometer lower (H) MOPOT 14
15 external fault 1 (L) STOEX1 15
1 2 3 4 5 6 7 8
block diagram: closing gear - control words I&S IT PS Erl 35 01.01.01 V 1.2 page: 3/14
send to CB
081
[5/5] ZUST1 status word 1 1
881
[9/7] FIGS signal fault encoder (L) 0
[12/8] MXNDS signal speed setpoint-actual value diff. saved (L) 1 [5/5] XNGG actual speed value 2
[12/8] MXNGS signal overspeed saved (L) 2
[12/8] MXNO signal speed = 0 (H) 3 100% 083
849
[12/4] FIGNSS signal fault speed actual-actual value differ. (L) 4 [5/5] ZUST2 status word 2 3
[12/3] FKGERS signal fault coupling T300 to base unit (L) 5
[12/3] FKS5S signal fault coupling to automation system (L) 6 883
7
status word (technology) 4
8
[12/3] FKPPS signal fault coupling peer to peer (L) 9
[10/4] MGO signal grap open (H) 10
[10/4] MGG signal grap closed (H) 11 0% 5
12
13 885
14 [5/5] PZD6_Send PZD 6_Send 6
15
886 X135 CB
[5/5] PZD7_Send PCD 7_Send 7 DUAL
PORT
887 RAM
[5/5] PZD8_Send PCD 8_Send 8 TB → CB
888
[5/5] PZD9_Send PCD 9_Send 9
889
[5/5] PZD10_Send PCD 10_Send 10
890
connected from
base unit CU [5/5] PZD11_Send PCD 11_Send 11
891
[5/5] PZD12_Send PCD 12_Send 12
892
[5/5] PZD13_Send PCD 13_Send 13
only usable with DriveES 893
(no PPO-type)
[5/5] PZD14_Send PCD 14_Send 14
894
[5/5] PZD15_Send PCD 15_Send 15
895
[5/5] PZD16_Send PCD 16_Send 16
FSS5 [12/1]
1 2 3 4 5 6 7 8
block diagram: closing gear - send to CB I&S IT PS Erl 35 01.01.01 V 1.2 page: 4/14
receive from CU
065
1 status word 1 ZUST1 [4/4]
066
2 actual speed value XNGG [4/4] [7/5] [12/1]
[12/5] 0 signal ready to switch on (H) EINBE
067 100% 1 signal ready (H) BETRBE
082
3 status word 2 ZUST2 [4/4] 2 signal run (H) BETRIEB
3 signal fault (H) STOERUNG
068 4 signal OFF2 (L) KEINAUS2
081
5 signal OFF3 (L) KEINAUS3
4 current setpoint WIGG [7/5] [11/1] 6 signal switch-on inhibit (H) EINSPERR
7 signal alarm (H) WARNUNG
069 100%
084 8 signal setpoint-actual value deviation (L) KEINWXAB
5 setpoint-actual value differ. ENGG [12/5] 9 signal PcD control requested (H) FAGGEF
10 signal comparison value reached (H) VGWER
070 100% 11 signal low voltage fault (H) STOEUSP
085
6 PCD 6_Send PZD6_Send [4/4] 12 signal request to energize main contactor (H) HSANGEST
13 signal ramp-function generator active (H) HLGAKT
071 100% 14 signal positive speed setpoint (H) RECHTDF
086 15 signal kin. buffering / flex. response active (H) KIPAK
7 PCD 7_Send PZD7_Send [4/4]
072 100%
087
CU X137
8 PCD 8_Send PZD8_Send [4/4]
DUAL
PORT 073 100%
RAM 088
CU → TB 9 PCD 9_Send PZD9_Send [4/4]
074 100%
089
10 PCD 10_Send PZD10_Send [4/3] 16 signal flying restart or excitation active (H) FANGAK
17 signal synchronism reached (H) SYNCER
075 100% 18 signal overspeed (L) KEIUED
090 19 signal external fault 1 (H) STOEEX1
11 PCD 11_Send PZD11_Send [4/4] 20 signal external fault 2 (H) STOEEX2
083
076 100% 21 signal external alarm (H) WARNEX
091 22 signal converter overload alarm (H) WARNI2T
12 PCD 12_Send PZD12_Send [4/4] 23 signal converter overtemperature fault (H) STOEUTMP
077 100% 24 signal converter overtemperature alarm (H) WARNUTMP
092 25 signal motor overtemperature alarm (H) WARNMTMP
13 PCD 13_Send PZD13_Send [4/4] 26 signal motor overtemperature fault (H) STOEMTMP
078 nur nutzbar mit DriveES 27 reserve
100%
093 (kein PPO-Typ) 28 signal motor pulled out / blocked fault (H) STOEMBLK
14 PCD 14_Send PZD14_Send [4/4] 29 signal bypass contactor energized (H) UEBSAN
079 100% 30 signal synchronizing error (H) FBSYN
094 31 signal pre-charging active (H) VORLAK
15 PCD 15_Send PZD15_Send [4/4] [7/5]
080 100%
095 durchverbunden
16 PCD 16_Send PZD16_Send [4/4] [7/5] zum Communication Board CB
100%
096
FEGG [12/1]
1 2 3 4 5 6 7 8
block diagram: closing gear - receive from CU I&S IT PS Erl 35 01.01.01 V 1.2 page: 5/14
send to CU
033
[1/7] STEU1 control word 1 1
945
[11/8] WNGG speed setpoint 2
100% 035
913
[1/5] STEU2 control word 2 3
947
[13/6] WST setpoint start pulse 4
100%
915
0% 5
949
[1/5] PZD6_Emp PCD 6_Empf 6
950
[1/5] PZD7_Emp PCD 7_Empf 7
connected from
communication board CB 951 X137 CU
[1/5] PZD8_Emp PCD 8_Empf 8 DUAL
PORT
952 RAM
TB → CU
[1/5] PZD9_Emp PCD 9_Empf 9
0% 10
954
[1/5] PZD11_Emp PCD 11_Empf 11
955
[1/5] PZD12_Emp PCD 12_Empf 12
956
958
[1/5] PZD15_Emp PCD 15_Empf 15
959
[1/5] PZD16_Emp PCD 16_Empf 16
FSGG [12/1]
1 2 3 4 5 6 7 8
block diagram: closing gear - send to CU I&S IT PS Erl 35 01.01.01 V 1.2 page: 6/14
terminal PIN T300 PIN T300 terminal
SE300 X5 X131 X131 SE300 X5
[11/8] WNGG
-10V...+10V 133 137 141 964 968 972 -10V...+10V
[1/5] PZD16E
100% 0% [11/7] WNNHG 0% 100%
501 input 1+ [11/4] WNUTI output 1
A D 509
1
input 1-
D
AE1 [7/5] [10/3] [11/6] WNSWF MUX A
9
[5/5] PZD15S
134 138 142 965 969 973
0%
100% 0% 0% 0% 100%
503 input 2+ 0% output 2
A D 519
3
input 2-
D
AE2 [7/5] [5/5] XNGG MUX A
17
[11/5] WIHW
135 139 143 966 970 974
[11/5] WISW
100% 0% 0% 0% 100%
505 input 3+ 0% output 3
A D 521
5
input 3-
D
AE3 [7/5] 0% MUX A
19
506 6 [10/4] ES
0% GND
18 522
[7/4] AE3
962
1
[5/5] PZD16S
136 140 144 967 971 975
[10/3] WS
100% 0% [10/4] WNMS 0% 100%
507 input 4+ 0% output 4
A D 523
7
input 4-
D
AE4 [7/5] [13/1] [13/6] WST MUX A
20
1 2 3 4 5 6 7 8
block diagram: closing gear - AI + AO I&S IT PS Erl 35 01.01.01 V 1.2 page: 7/14
receive peer to peer
145
WNMA
1 WNMA [11/4]
146
WIMA
2 WIMA [7/5] [11/1]
X134
3
+Rx
1
TB
-Rx
2
4
FEPP [12/1]
1 2 3 4 5 6 7 8
block diagram: closing gear - receive peer to peer I&S IT PS Erl 35 01.01.01 V 1.2 page: 8/14
185 187
pulse encoder 1
pulse encoder input 1 100%
0H0000 XNTB
165 IT1 Y1 XNTB [7/5] [12/1]
500 40ms
167 PR1 186
1000
169 RS1
2000000
171 RP1
0H0000
175 CW1
pulse encoder 2
pulse encoder input 2
0H0000
166 IT2
500
168 PR2
1000
170 RS2
2000000
173 RP2
0H0000
176 CW2
pulse encoder 1 + 2
[3/7] KGO RD
0
SYNDP
≥1 SD
179 0%
WSSYNDP
0 XSD12
y=x 1
SVD YDP XSD12 [7/5] [10/1]
y
x FIG
OFC S
QN FIGS [4/1]
[14/8] RESET R
182
1 INIT
0
≥1 NOT
1s T 0
1 2 3 4 5 6 7 8
block diagram: closing gear - actual position sensing I&S IT PS Erl 35 01.01.01 V 1.2 page: 9/14
SWGRSCHL
X QU
+ - 0% M
5% MGG [4/1] [2/6]
258 L
1%
259 HY QL
SWGROEF
[3/7] KGG X QU
+ - 0% M
1% MGO [4/1] [2/6]
256 L
0,2%
257 HY QL
1 0 LLMS
1
-100%
0 LUMS
1
100%
1 2 3 4 5 6 7 8
block diagram: closing gear - speed setpoint channel I&S IT PS Erl 35 01.01.01 V 1.2 page: 10/14
428
[7/5]
[8/3] WIMA 0
WIHW
W
1
0%
20 ms 100% X1 439 441
420
[7/5]
0 X2 10%
421 WISW
100% LU
-100% LL
3 50ms
436 KP 440
[5/5] WIGG 2000ms
0 437 TN
1 0
0% 0% 199% 1 0 HI
20 ms 100% -/+ 100%
422 EN
0 423
APO 429 W
[3/7] FRA
[3/7] WNSA
434 [7/5]
0% X 432
100%
5
431 KP EN
425
-199% 0% 5% 0
433 442
100%
427
374 375
320 322 331 100% -100%
334
50% 382 444
[7/5] LU LL
[10/8] WNUGW 0 0% 0 WNSWF
WNN
1 WNUTI 0 1 WNGG [6/4] [7/5]
WNTI 1 376 TU WNNHG
[7/5] 4000ms [7/5]
330 377 TD EN
4000ms
FWN
AGL [3/4]
[3/7] FHG
-10% [3/4]
332 0 [8/3] WNMA 0
10% 1 1
307
333 0%
[3/7] KTA
KTI [10/4] WNGL 0% 0
≥1
[3/7] KTB
323
0 & 500ms
1
306
≥1
[3/7] AGW AGL
324
0 & 307 [3/7]
1 2 3 4 5 6 7 8
block diagram: closing gear - current equalization controller I&S IT PS Erl 35 01.01.01 V 1.2 page: 11/14
communication monitoring
overspeed monitoring
intern FKS5
[1/2] FES5 fault coupling to Communication Board CB [14/1]
[4/7]
intern
FSS5
FKOP
& RESET
S
R
QN FKS5S [4/1] [14/1] [5/5] XNGG X QU
MXNG
S
QN MXNGS [4/1] [2/6]
[14/8] RESET R
20ms 110%
458 459 M [14/8]
2%
460 HY QL
FIGNS 5%
[5/5] XNGG X QU S 461 M
+ QN FIGNSS [4/1] [2/6] [14/1]
- 2000ms 15%
RESET R
1%
465 466 M [14/8] 462 HY QL MXN0 [4/1] [2/6]
XNTB
[9/7] 1%
467 HY QL
1 2 3 4 5 6 7 8
block diagram: closing gear - monitorings I&S IT PS Erl 35 01.05.02 V 1.21 page: 12/14
start pulse
1 2 3 4 5 6 7 8
block diagram: closing gear - start pulse I&S IT PS Erl 35 01.01.01 V 1.2 page: 13/14
send faults and alarms to base unit CU
fault messages:
[3/4] QUITT
≥1
[12/7] MXND 0
[12/7] MXNG 1
0 2
0 3 1
0 4 ≥1 NOT QUI_IN [14/3]
827 0
0 5 10s T 0
0 6
0 7 NQI_IN
base unit CU
0 8
829
& alarms 97-112 [14/2]
0 9 0HFFFF
0 10
0 11 factory setting
0 12
0 13 with change of parameter H832 from 0 to 1 the technology parameter (1000-
0 14 1999/ d-,H-Parameter) are reset. Therefore the power is to switch off and on.
0 15 After that the technology parameter are reset.
1 2 3 4 5 6 7 8
block diagram: closing gear - general I&S IT PS Erl 35 01.01.01 V 1.2 page: 14/14