Professional Documents
Culture Documents
Step 7: Calculating V , bus voltage vector: Second pop-up menu is used for choosing the faulted
phase(s) or no fault conditions at the test system. Program can
(3) be run under no fault conditions by selecting the ‘‘no fault’’
option. Fault can be applied to a single phase ‘‘a’’, ‘‘b’’, ‘‘c’’,
After all these steps fault analysis part starts. or two phase ‘‘a-b’’, ‘‘a-c’’, ‘‘b-c’’, or three phase ‘‘a-b-c’’ by
selecting those options at second popup menu.
Step 8: Obtaining the location of the fault and fault
impedance data from the user interface. Third pop-up menu is used for choosing the faulted bus at
the test system. Faulted bus can be changed by selecting any
There are two different cases depending on fault bus number at the system.
impedance.
Step 9b: Calculating V from (3). Fig. 1- MATLAB GUI Based Three Phase Test System Interface
355
Fourth pop-up menu is used for changing the display either
‘‘Bus Voltages’’ or ‘‘Fault Currents’’ at specified fault Here are some results after testing the four-bus system.
location.
Case 1: Steady-State Results
Fifth pop-up menu is used for choosing fault impedance. If
the ‘‘With fault impedance’’ section selected, for entering the Bus voltages under no fault condition can be seen in Fig. 4:
fault impedance values, a new table pops up just underneath
that pop-up menu. User can change the fault impedance
values. Symmetrical or unsymmetrical faults can be tested by
changing those values.
Fig. 3 - Bus numbers and element connections for four bus test system.
1
In this case it is supposed that all of the self-impedance are
equal and mutual impedance are zero. Generally, user can
enter all the nine elements of the Z-matrix independently. Case 3: LL fault of phases ‘‘a’’ and ‘‘b’’ of second Bus
356
When the ‘‘With fault impedance’’ case is selected a new
Bus voltages under fault at phase ‘‘a - b’’ of second Bus table as shown in Fig. 8 pops up in order to enter the fault
without fault impedance can be seen in Fig. 6: impedance data. The table has the default values for fault
impedance.
Fig. 6 - Four Bus System under fault at phase “a - b” at second Bus without
fault impedance (Bus Voltages).
Fig. 9 - Four Bus System under fault at phase “a - b - c” at third Bus with
symmetrical fault impedance (Bus Voltages).
Fig. 7 - Four Bus System under fault at phase “a - b” at bus two without fault
impedance (Fault Currents).
357
Case 5: LLL fault at Bus 4 with unsymmetrical fault systems. It is user friendly and easy to use. The most
impedance important features of the interface is the testing ability of user
selected power systems under different fault conditions and
Bus voltages under fault at phase ‘‘a - b - c’’ at fourth Bus clear visualization of the results. User can get the bus
with unsymmetrical fault impedance can be seen in Fig. 11: voltages and fault currents that are the key components of
fault analysis in power systems. The behavior of the power
system under fault conditions can easily be understood after
carefully examining the results of the program.
358