Overview Features
An extensive range of interfaces are available • Soft addressed
to support the Cooper range of UL intelligent • Integral short circuit isolator
• Single address
addressable control panels, providing
• Suitable for monitoring:
solutions for most design requirements. - Flow switches
- Non fire inputs
The UL micro single channel input unit - Auxillary panels
(ULMCIM) is a single input, soft addressed micro • Optional variant:
interface, incorporating integral short circuit - ULMCIM-C
isolators. It is extremely compact and therefore
ideal for incorporation into other equipment.
Benefits
It is designed for applications requiring the • Quick and simple to install
monitoring of a set of normally open, volt free • No hard addressing required
contacts such as sprinkler system flow (Plug and play)
switches, auxiliary panel fire/fault signals as well • Compact size
as non fire input signals such as flow valve open
contacts, generator start up, fire door closed
etc.
Optional Variant
51
CFS0077-UL-C_Layout 1 12/01/2012 11:44 Page 52
180mm
Standard Connections
130mm
22K
mounting details.
2. Connect the unit according to standard
connections. Loop Out
3. Up to 3 units can be fitted inside a micro Addressable
Loop
module box unit.
5K6
Operation 5K6
22K
Note:
1. The end of line resistor provided must always be fitted, even if the input is unused.
2. Monitored inputs can detect open or short circuit faults.
3. Recommended loop cable type: FIRETUF, FP200, MICC.
Product Codes
Code Description
ULMCIM Micro Single Channel Input Unit (recognised as input unit)
ULMCIM-C Micro Single Channel Input Unit (recognised as pull station)
ULBU Micro Module Box Unit (empty box)