You are on page 1of 1

OTTV CALCULATION (OFFICE)

CORRECTION FACTOR
SOLAR ABSORBTION

U-VALUE FOR WALL

OVERALL THERMAL
WINDOW TO WALL
SOLID WALL AREA

COEFFICIENT EXT.

TRANSFER VALUE
COEFFICIENT OF

(SC = SC1 X SC2)


WINDOW AREA

FENESTRATION

FENESTRATION
ORIENTATION
U-VALUE FOR

COEFFICIENT
FAÇADE (A)

SHADING

SHADING

SHADING
SHADING
CONSTANT

RATIO

A X OTTV
1-WWR

(Uw)
(Aw)

(Uf)
(Af)

(α)
ELEVATION

M² M² M² α WWR (W/m²K) (W/m²K) (CF) SC1 SC2 SC (W/m²)


NORTH WALL 2450 0 2450 15 0.88 1.0 0.0 2.87 N/A N/A N/A N/A N/A 0.00 0
HEAT CONDUCTION
THROUGH WALL

SOUTH WALL 1764 1059 705 15 0.88 0.7 0.3 2.87 N/A N/A N/A N/A N/A 12.66 22,339
EAST WALL 1747 1130 617 15 0.88 0.5 0.5 2.87 N/A N/A N/A N/A N/A 17.20 30,046
WEST WALL 1 844 403 441 15 0.88 1.1 -0.1 2.87 N/A N/A N/A N/A N/A -3.57 -3,015
WEST WALL 2 923 635 288 15 0.88 0.5 0.5 2.87 N/A N/A N/A N/A N/A 20.70 19,108
SUB-TOTAL 7728 3227 4501 15 X α X (1-WWR) Uw 68,478
NORTH WALL 2450 0 2450 6 N/A 1.0 0.0 N/A 2.57 N/A N/A N/A N/A 15.42 37,779
THROUGH WINDOW
HEAT CONDUCTION

SOUTH WALL 1764 1059 705 6 N/A 0.7 0.3 N/A 3.00 N/A N/A N/A N/A 11.98 21,138
EAST WALL 1747 1130 617 6 N/A 0.5 0.5 N/A 2.57 N/A N/A N/A N/A 8.42 14,709
WEST WALL 1 844 403 441 6 N/A 1.1 -0.1 N/A 2.57 N/A N/A N/A N/A 16.87 14,242
WEST WALL 2 923 635 288 6 N/A 0.5 0.5 N/A 3.00 N/A N/A N/A N/A 8.16 7,535
SUB-TOTAL 7728 3227 4501 6 X WWR X Uf 95,403
NORTH WALL 2450 0 2450 194 N/A 1.0 N/A N/A N/A 0.9 0.51 1 0.51 89.05 218,163
THROUGH WINDOW
SOLAR HEAT GAIN

SOUTH WALL 1764 1059 705 194 N/A 0.7 N/A N/A N/A 0.92 0.28 1 0.28 33.27 58,687
EAST WALL 1747 1130 617 194 N/A 0.5 N/A N/A N/A 1.23 0.51 1 0.51 66.45 116,085
WEST WALL 1 844 403 441 194 N/A 1.1 N/A N/A N/A 0.94 0.51 1 0.51 101.77 85,897
WEST WALL 2 923 635 288 194 N/A 0.5 N/A N/A N/A 0.94 0.28 1 0.28 23.16 21,375
SUB-TOTAL 7728 3227 4501 194 X CF X WWR X SC 500,206
FAÇADE AREA 7728 OVERALL BUIDING OTTV 85.93 664,087

OTTV CALCULATION (FACTORY)

CORRECTION FACTOR
SOLAR ABSORBTION

U-VALUE FOR WALL

OVERALL THERMAL
WINDOW TO WALL
SOLID WALL AREA

COEFFICIENT EXT.

TRANSFER VALUE
COEFFICIENT OF

(SC = SC1 X SC2)


WINDOW AREA

FENESTRATION

FENESTRATION
ORIENTATION
U-VALUE FOR

COEFFICIENT
SHADING

SHADING

SHADING
SHADING
FAÇADE

CONSTANT

RATIO

A X OTTV
(Uw)
(Aw)

1-WWR

(Uf)
(Af)

(α)

ELEVATION

M² M² M² α WWR (W/m²K) (W/m²K) (CF) SC1 SC2 SC (W/m²)


NORTH WALL 691 691 0 15 0.88 0.0 1.0 2.87 N/A N/A N/A N/A N/A 37.88 26,178
THROUGH WALL
CONDUCTION

SOUTH WALL 1134 1059 75 15 0.88 0.1 0.9 2.87 N/A N/A N/A N/A N/A 35.20 39,918
HEAT

EAST WALL 843 650 193 15 0.88 0.3 0.7 2.87 N/A N/A N/A N/A N/A 26.64 22,454
WEST WALL 1281 1281 0 15 0.88 0.0 1.0 2.87 N/A N/A N/A N/A N/A 37.88 48,529
SUB-TOTAL 3949 3681 268 15 X α X (1-WWR) Uw 137,079
NORTH WALL 691 691 0 6 N/A 0.0 1.0 N/A 3.00 N/A N/A N/A N/A 0.00 0
CONDUCTION

SOUTH WALL 1134 1059 75 6 N/A 0.1 0.9 N/A 3.00 N/A N/A N/A N/A 1.27 1,446
THROUGH
WINDOW
HEAT

EAST WALL 843 650 193 6 N/A 0.3 0.7 N/A 3.00 N/A N/A N/A N/A 5.34 4,506
WEST WALL 1281 1281 0 6 N/A 0.0 1.0 N/A 3.00 N/A N/A N/A N/A 0.00 0
SUB-TOTAL 3949 3681 268 6 X WWR X Uf 5,951
NORTH WALL 691 691 0 194 N/A 0.0 N/A N/A N/A 0.9 0.28 1 0.28 0.00 0
SOLAR HEAT GAIN

SOUTH WALL 1134 1059 75 194 N/A 0.1 N/A N/A N/A 0.92 0.28 1 0.28 3.54 4,014
THROUGH
WINDOW

EAST WALL 843 650 193 194 N/A 0.3 N/A N/A N/A 1.23 0.28 1 0.28 19.84 16,724
WEST WALL 1281 1281 0 194 N/A 0.0 N/A N/A N/A 0.94 0.28 1 0.28 0.00 0
SUB-TOTAL 3949 3681 268 194 X CF X WWR X SC 20,737
FAÇADE AREA 3949 OVERALL BUIDING OTTV 41.47 163,767