NOTES :

1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT


A B C D E F G H J K L M N P SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.
58250
1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
6000 6000 3675 2375 5950 5850 6150 6000 6350 3050 2600 950 3300 ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.
1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
M1 AT SITE..
A1 B1 C1 E1 F1 G1 K1
H1 J1 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
4605

OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY


OF THE MAIN CONTRACTOR.
N2 P2
2
2395

M3
3
A3
B3 CF3
3350

P3'
N3'
20005

4
CF1
TSCL APPROVAL
CF2
2650

ASSISTANT/JUNIOR ENGINEER
L5
P5
5
M5
D5 E5
2105

ASSISTANT EXECUTIVE ENGINEER


6 D6'
M6
A6 B6 C6 E6' L6
EXECUTIVE ENGINEER
4900

7 SUPERINTENDING ENGINEER
A7 M7
B7 C7 E7 F7 G7 H7 J7 K7
ARCHITECT
STRUCTURAL EXPERT
EXCAVTION LAYOUT INFRASTRUCTURE EXPERT
TEAM LEADER
GRID LINE
EXCAVATION LINE C5A 27/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
P.C.C LINE REV. DATE ISSUED TO
DESCRIPTION OF REVISIONS
PRD CHK APD
PROJECT:
FOOTING LINE CITY LIBRARY
CLIENT: TUMKUR SMART CITY LTD.
COLUMN FOR APPROVAL
DWG. TITLE:
EXCAVTION LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-401
REV NO. SCALE:
REFER
SITE PLAN
TYPICAL DETAILS
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
A B C D E F G H J K L M N P THE WORK RELATED TO THIS DWG.
58250
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
6000 6000 3675 2375 5950 5850 6150 6000 6350 3050 2600 950 3300 LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL

100

100

100

100

100

100

100

100

100
350 375 250 375 450 450 450 450 375 100 TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
1 AT SITE..

800

800

900

800

800

800

800

800

800

800
100
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
100 500 450 450 450 375 350 PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
A1 375 B1 C1 375 E1 G1 450
F1 J1 K1 M1 OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
H1
OF THE MAIN CONTRACTOR.
4605

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
P2 NO.TSC-CLP-101-STR-DRG-400

175

425
100 200
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING
2 TO IS 456, 2010.

175
200 100

425
2395

N2 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL


350 375 CONFORMING TO IS 1786, 2008.

450
800
A3 M3
800

800
2.4 CLEAR COVER TO COLUMN REINFORCEMENT SHALL BE
3 40mm ALL ROUND.
100 375
100

100
100

450
2.5 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GRADE)
B3
3350

100 200
P3'

500

500
20005

100
200 TSCL APPROVAL

100

100
4
N3' ASSISTANT/JUNIOR ENGINEER
2650

625 801 L5
200
100 200

800

800
795
545

500
5 100 100
375 100

100
ASSISTANT EXECUTIVE ENGINEER

205
350

100

100
2105

355
D5 E5 M5 P5

100
100

100

100

100

100
350 450 650 350 351 800

225
6 525

475
500

650

650
800

800
100

350
450 375
100 100
100 L6 100

225
A6 B6 C6 D6' E6' M6 EXECUTIVE ENGINEER
4900

350 100 450 450 450 350


300 450 375
100

450 SUPERINTENDING ENGINEER

100
800

800

800

800

800

800

800

800

800
500

7
100 450 650 300 M7 100
100

100

100

100

100

100
450 450 450 450 375
100

100

B7 C7 E7 F7
A7 G7 H7 J7 K7

ARCHITECT

STRUCTURAL EXPERT
COLUMN LAYOUT
INFRASTRUCTURE EXPERT

TEAM LEADER

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD


1 DESCRIPTION OF REVISIONS
- PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
COLUMN LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-402
REV NO. SCALE:
REFER
C4A 1:100 N SITE PLAN

DATE: 28-12-2018

DETAIL 1
SCALE 1:20 -
SCHEDULE OF COLUMNS SCHEDULE OF COLUMNS
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.
SL.NO COLUMN NO COLUMN DETAILS TIES LINKS COLUMN NO COLUMN DETAILS TIES LINKS 1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
SL.NO ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
#22Ø32mm THE WORK RELATED TO THIS DWG.
1 #20Ø42mm 1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.
5
1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.
STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING
TO IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
Ø8mm@200mmC/C CONFORMING TO IS 1786, 2008.
Ø8mm@200mmC/C 2.4 CLEAR COVER TO COLUMN REINFORCEMENT SHALL BE
40mm ALL ROUND.
2.5 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GRADE)
#12Ø32mm
#16Ø32mm
2
TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
6
#2Ø25mm
ASSISTANT EXECUTIVE ENGINEER
EXECUTIVE ENGINEER
Ø8mm@200mmC/C
Ø8mm@200mmC/C #16Ø32mm
#16Ø32mm
SUPERINTENDING ENGINEER
3 7
ARCHITECT
STRUCTURAL EXPERT
INFRASTRUCTURE EXPERT
Ø8mm@200mmC/C
TEAM LEADER
#10Ø25mm Ø8mm@200mmC/C
4
#22Ø42mm
C5A ISSUED FOR APPROVAL. NPN HTM DGC
C4A 30/10/2018 ISSUED FOR APPROVAL. NPN HTM DGC
8 REV. DATE ISSUED TO PRD CHK APD
DESCRIPTION OF REVISIONS
PROJECT:
CITY LIBRARY
Ø8mm@200mmC/C CLIENT: TUMKUR SMART CITY LTD.
FOR APPROVAL
DWG. TITLE:
COLUMN DETAIL
DWG.NO. TSC-CLP-101-STR-DRG-403
REV NO. SCALE:
Ø8mm@200mmC/C REFER
SITE PLAN
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.
A B C D E F G H J K L M N P
58250 1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
6000 6000 3675 2375 5950 5850 6150 6000 6350 3050 2600 950 3300 THE WORK RELATED TO THIS DWG.
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.
1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
1 THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
M1
A1 B1 C1 E1 F1 G1 K1 AT SITE..
H1 J1
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
4605

PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND


OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.
N2 P2 STRUCTURAL NOTES :
2 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2395

2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING


TO IS 456, 2010.
M3
3 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
A3 CONFORMING TO IS 1786, 2008.
B3 CF3 2.4 CLEAR COVER TO FOOTING REINFORCEMENT SHALL BE
3350

50mm FOR TOP,BOTTOM & SIDES.


P3'
N3'
20005

4
CF1
CF2
2650

TSCL APPROVAL
L5
P5 ASSISTANT/JUNIOR ENGINEER
5
M5
D5 E5
2105

6 ASSISTANT EXECUTIVE ENGINEER


550

D6'
M6
A6 B6 C6 E6' L6
4900

EXECUTIVE ENGINEER
7
A7 M7
B7 C7 E7 F7 G7 SUPERINTENDING ENGINEER
H7 J7 K7
SCHEDULE OF FOOTINGS ARCHITECT
SL.NO GRID NO LENGTH
(A)
WIDTH THICKNESS
(B) (T)
FIRST LAYER SECOND LAYER FOOTING LAYOUT STRUCTURAL EXPERT
1 P2,P3',P5 1800 1800 450 Ø12@175mm c/c Ø12@175mm c/c
INFRASTRUCTURE EXPERT
2 M1 2000 2000 500 Ø12@150mm c/c Ø12@150mm c/c
3 A1,A6,A7,M7 2200 2200 625 Ø16@200mm c/c Ø16@200mm c/c PL(+)550
TEAM LEADER
4 A3 2400 2400 550 Ø12@150mm c/c Ø12@150mm c/c
5 E7 3400 3400 950 Ø16@250mm c/c Ø16@250mm c/c GL(+)000

(WHICHEVER IS ACHIVED EARLIER)


2800 2800 725

MIN 2M OR UPTO HARD STARTA


6 B6,B7 Ø16@200mm c/c Ø16@200mm c/c
EXCAVATION LINE
7 B1 3000 3000 700 Ø16@225mm c/c Ø16@225mm c/c
8 B3,C7 3400 3400 875 Ø16@175mm c/c Ø16@175mm c/c C5A 27/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
C4A 30/10/2018 ISSUED FOR APPROVAL. NPN HTM DGC
9 C1 4000 4000 1025 Ø16@150mm c/c Ø16@150mm c/c
REV. DATE ISSUED TO PRD CHK APD
10 C6,E1 4200 4200 1200 Ø20@200mm c/c Ø20@200mm c/c DESCRIPTION OF REVISIONS
11 K1,K7 4400 4400 1250 Ø20@200mm c/c Ø20@200mm c/c Ld PROJECT:
CITY LIBRARY
12 F1 5000 5000 1300 Ø20@200mm c/c Ø20@200mm c/c PCC 1:3:6
13 F7,H1,J1, 5200 5200 1300 Ø20@175mm c/c Ø20@175mm c/c SECTION A
- CLIENT: TUMKUR SMART CITY LTD.
14 G1 5400 5400 1350 Ø20@175mm c/c Ø20@175mm c/c FOR APPROVAL
DWG. TITLE:
15 G7,H7,J7 5600 5600 1550 Ø20@150mm c/c Ø20@150mm c/c
FOOTING LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-404
REV NO. SCALE:
REFER
SITE PLAN
FIRST LAYER
SCHEDULE OF FOOTINGS SECOND LAYER
LENGTH WIDTH THICKNESS BOTTOM TOP -
SL.NO GRID NO SIDE
(A) (B) (T) FIRST LAYER SECOND LAYER FIRST LAYER SECOND LAYER
EXCAVATION LINE
1 CF1 REF. FOOTING LAYOUT 1600 Ø20@150mm c/c Ø20@150mm c/c Ø12@200mm c/c Ø12@200mm c/c Ø12@150mm c/c
2 CF2 REF. FOOTING LAYOUT 1300 Ø20@175mm c/c Ø20@175mm c/c Ø12@200mm c/c Ø12@200mm c/c Ø12@150mm c/c
3 CF3 REF. FOOTING LAYOUT 1200 Ø20@200mm c/c Ø20@200mm c/c Ø12@200mm c/c Ø12@200mm c/c Ø12@150mm c/c
TYPICAL PLAN OF
FOOTING STEEL RF
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


A B C D E F G H J K L M N P SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
58250 NO.TSC-CLP-101-STR-DRG-400
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
6000 6000 3625 2425 5950 5850 6150 6000 6350 3050 2600 950 3300 IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
1 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
PB5 THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
PB1 (200x450) 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
4605

PB4 (200 x 450)

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER

2
2395

PB1 (200x 450) PB2 (200 x 450)


ASSISTANT EXECUTIVE ENGINEER

3
PB4 (200 x 450)
3350

PB6 (200 x 450)


EXECUTIVE ENGINEER
20005

4
2650

PB6 (200 x 450)

PB6 (200 x 450)

PB6 (200 x 450)

PB6 (200 x 450)

PB4 (200 x 450)


SUPERINTENDING ENGINEER

PB8
5
PB3 (200 x 450) PB8
2105

PB2 (200x 450) PB3 (200 x 450)


PB5
PB3 ARCHITECT

PB6 (200 x 450)


6
PB8
PB8
PB3 (200 x 450)
PB5 (200 x 450)

STRUCTURAL EXPERT
4900

INFRASTRUCTURE EXPERT

TEAM LEADER

C5A 27/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
PLINTH BEAM LAYOUT PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
PLINTH BEAM LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-405
REV NO. SCALE:
REFER
C5A 1:75 N SITE PLAN

DATE: 27-12-2018
NOTES :
A B C D E F G H J K L M N P 1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
58050 SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.
6000 6000 3675 2375 5950 5850 6150 6000 6350 3050 2600 950 3100
1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

A
-
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
1 PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.
B
-

A
-
4605

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2395

2.4 CLEAR COVER TO RETAINING WALL REINFORCEMENT SHALL


BE 25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
3
3350

B
-
20005

TSCL APPROVAL
4 ASSISTANT/JUNIOR ENGINEER
2650

5
ASSISTANT EXECUTIVE ENGINEER
2105

C EXECUTIVE ENGINEER
-
4900

7 SUPERINTENDING ENGINEER
A
-

250 PL(+)1200 ARCHITECT

STRUCTURAL EXPERT
BEAM
INFRASTRUCTURE EXPERT

GL(+)000 GL(+)000-3450(VARIES) GL(+)000


TEAM LEADER

OUTSIDE FACE OUTSIDE FACE OUTSIDE FACE

Ø12mm@200c/c Ø12mm@200c/c Ø12mm@200c/c C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC


Ø10mm@200c/c Ø10mm@200c/c Ø10mm@200c/c
3450

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
PROJECT:
250 250 CITY LIBRARY
250
CLIENT: TUMKUR SMART CITY LTD.
FOR APPROVAL
DWG. TITLE:
PL(-)3450 PL(-)3450 PL(-)3450-000(VARIES) RETAINING WALL LAYOUT
Ø10mm@200c/c Ø10mm@200c/c Ø10mm@200c/c DWG.NO. TSC-CLP-101-STR-DRG-406
REV NO. SCALE:
Ø16mm@200c/c REFER
Ø16mm@200c/c Ø16mm@200c/c
C5A 1:75 N SITE PLAN
1600

1600

1600
1400 2350 1400 2350 1400 2350 DATE: 25-11-2018
400

400

400

100 4000 100 4000 100 4000


4200 4200 4200
SECTION A SECTION B SECTION C
SCALE-1:15 - SCALE-1:15 - SCALE-1:15 -
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..

L5 M5 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS


PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :

D5 E5 D 2.1 FOR GENRAL NOTES REFER DRG


NO.TSC-CLP-101-STR-DRG-400

- 2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO


IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO RETAINING WALL REINFORCEMENT SHALL
BE 25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
B 2.5 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

- M6
L6
D6' TSCL APPROVAL
E6' ASSISTANT/JUNIOR ENGINEER

ASSISTANT EXECUTIVE ENGINEER

E
-
EXECUTIVE ENGINEER

PLAN PL(-)3450
C
-

Ø12mm@200c/c 200
SUPERINTENDING ENGINEER
Ø12mm@200c/c
PL(-)3450 2762 2150 845
Ø10mm@200c/c
Ø12mm@200c/c
1725 1900 3000
ARCHITECT
200 Ø12mm@200c/c
Ø12mm@150c/c
Ø10mm@200c/c STRUCTURAL EXPERT

1300
INFRASTRUCTURE EXPERT

Ø12mm@150c/c TEAM LEADER


1625

100 6162
6362

SECTION
SCALE 1:20
D- Ø20mm@175c/c
100 7075 P.C.C 1:3:6 C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

7275 C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD


SECTION
SCALE 1:20
B- Ø20mm@150c/c DESCRIPTION OF REVISIONS
PL(-)3450 PROJECT:
P.C.C 1:3:6
CITY LIBRARY

PL(-)3450 Ø12mm@200c/c CLIENT: TUMKUR SMART CITY LTD.


Ø12mm@200c/c FOR APPROVAL
Ø12mm@200c/c 200
Ø10mm@200c/c DWG. TITLE:
1725 2150 3245
1250 1905 2749 LIFT WALL DETAIL
200 Ø12mm@200c/c
DWG.NO. TSC-CLP-101-STR-DRG-407
Ø10mm@200c/c
Ø12mm@150c/c REV NO. SCALE:
REFER
C5A 1:100 N

1300
SITE PLAN

Ø12mm@150c/c DATE: 25-12-2018


1625

6304 100
6504

100 7525 SECTION


SCALE 1:20
E- Ø20mm@175c/c
7725 P.C.C 1:3:6
Ø20mm@150c/c
SECTION
SCALE 1:20
C- P.C.C 1:3:6
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


A B C D E F G H J K L M N P LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

58250 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)
STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
GFB1A(200x600) GFB1 (450 x750) 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.

1 A 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE


415
GFB11

THIRD OF THE SPAN


2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
GFB5 (200x600) 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
GFB6 (450 x750)

GFB7 (300 x600)


4605

TSCL APPROVAL
GFB5 (200 x 600) ASSISTANT/JUNIOR ENGINEER

2
2395

GFB11(200x600)
GFB5 (200x600)
GFB8 (600x750)
ASSISTANT EXECUTIVE ENGINEER
B

GFB11 (200 x 600)


3
415
GFB2 (200x600)

GFB10 (450x750)
3350

EXECUTIVE ENGINEER
415

GFB7 (300 x600)


20005

4 GFB5 (200 x 600)


2650

SUPERINTENDING ENGINEER
GFB12 GFB12
5
GFB5 (200 x 600)
GFB12

GFB12
2105

GFB3 (200x600)
GFB9 (750 x 750)

C ARCHITECT
6 GFB12
415
GFB12
GFB6A (200 x600)

GFB6A (200 x600)

GFB7A (200 x600)


GFB6 (300 x600)

GFB6 (300 x600)

GFB13(300x750) STRUCTURAL EXPERT


415
G
4900

INFRASTRUCTURE EXPERT

TEAM LEADER

7 D E
415 415
GFB11

GFB4 (450x750) GFB4 (450x750)


GFB5 (200x600)
GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

GFB14(200x600)

GFB13(200x600)

415
K
C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 30/10/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

SLAB SUNK BY 450 DESCRIPTION OF REVISIONS


PROJECT:
CITY LIBRARY

GROUND FLOOR BEAM LAYOUT


415

CLIENT: TUMKUR SMART CITY LTD.


415

J
H

FOR APPROVAL
DWG. TITLE:
GROUND FLOOR BEAM LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-408
REV NO. SCALE:
REFER
C5A 1:100 N SITE PLAN

DATE: 25-12-2018
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.
A B C D E F G H J K L M N P
58250 1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
1B18 (300 x750) PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF

1B19
1B1A(200x600)

1B19
THE SAID WORK.
1B1 (450 x750)
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
1 A TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
416 AT SITE..

1B17
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
1B5 (200x600) OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
4605

1B6 (300 x600)

1B7 (300 x600)


OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
1B5 (200 x 600) 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
2 IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
2395

1B5 (200x600)

1B17(200x600)
CONFORMING TO IS 1786, 2008.

1B8 (450x750)
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25

3 B OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.

1B17 (200 x 600)


416 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
1B2 (2000x600) THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
3350

1B11 (600x750)

1B12 (450x750)

1B13 (450x750)
SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
416

1B7 (450 x750)


20005

TSCL APPROVAL
4 1B5 (200 x 600) ASSISTANT/JUNIOR ENGINEER
2650

1B14 1B15
5
ASSISTANT EXECUTIVE ENGINEER
1B5 (200 x 600)
2105

1B3 (200x600)

1B14

1B14
1B9 (750 x 750)
6 C 1B14
416
1B14
1B6A (300 x600)

1B6A (200 x600)

1B7A (200 x600)


1B6 (300 x600)

1B6 (300 x600)

EXECUTIVE ENGINEER
416
G
4900

SUPERINTENDING ENGINEER

7 D E
416 416
1B4A (200x600) 1B4 (450x750)
1B19

1B19

1B19
ARCHITECT
1B5 (200x600)
STRUCTURAL EXPERT
1B18 (300x600)

416
M
416
416

416

416
J
H

N
INFRASTRUCTURE EXPERT

K
SLAB SUNK BY 450
INTERMEDIATE FLOOR BEAM LAYOUT TEAM LEADER

C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC


#6Ø25mm #6Ø25mm
REV. DATE ISSUED TO PRD CHK APD
400 400
#6Ø25mm DESCRIPTION OF REVISIONS
300 300 PROJECT:
450 #3Ø16mm #3Ø25mm+
#2Ø20mm #2Ø16mm CITY LIBRARY
200 #3Ø25mm
200
#3Ø20mm #3Ø25mm CLIENT: TUMKUR SMART CITY LTD.
4L-12mmØ@ 4L-12mmØ@ FOR APPROVAL
150mmc/c 125mmc/c
DWG. TITLE: INTERMEDIATE FLOOR
900

#2Ø16mm #6Ø10mm #6Ø10mm 2L-8mmØ@ 2L-10mmØ@


225mmc/c 225mmc/c BEAM LAYOUT
750

750

750
2L-8mmØ@ DWG.NO. TSC-CLP-101-STR-DRG-409
600

2L-8mmØ@
600

900

125mmc/c 4L-10mmØ@
200mmc/c REV NO. SCALE:
200mmc/c REFER

#2Ø25mm
C5A 1:100 N SITE PLAN

DATE: 25-12-2018
#3Ø20mm+
#3Ø20mm #2Ø12mm #3Ø16mm #3Ø16mm
#6Ø32mm #6Ø32mm+#2Ø25mm
#6Ø20mm

DETAILS OF 1B5 DETAILS OF 1B6 DETAILS OF 1B14 DETAILS OF 1B17 DETAILS OF 1B15 DETAILS OF 1B18 DETAILS OF 1B19
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
B OF THE MAIN CONTRACTOR.
A C D E F G H J K L M N P
58250 STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
2B1A (200 x600) 2B1 (450 x750) IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
1 A CONFORMING TO IS 1786, 2008.
417 2B16
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
2B7 (200x600)
2B10 (300 x600)

2B11 (300 x600)


THIRD OF THE SPAN
4605

2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR


SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
2B7 (200 x 600)
TSCL APPROVAL
2 ASSISTANT/JUNIOR ENGINEER
2395

2B7 (200x600)

2B16(200x600)
2B12 (450x750)
3 B

2B16 (200 x 600)


417 ASSISTANT EXECUTIVE ENGINEER
2B2 (200x600)
3350

2B15 (450x750)
417
N

417

2B11 (450 x750)


20005

4 2B7 (200 x 600) EXECUTIVE ENGINEER


2650

2B9 2B9
5
SUPERINTENDING ENGINEER
2B7 (200 x 600)
2105

2B3 (200x600)

2B9
2B9

C 2B13 (750 x 750)


6 2B9
417 2B9
2B10A (200 x600)

2B10A (200 x600)

2B11A (200 x600)


2B10 (300 x600)

1B8(300x750) ARCHITECT
417
G
4900

STRUCTURAL EXPERT

INFRASTRUCTURE EXPERT

7 D E
417 2B4 (200x600) 419
2B4 (450x750) TEAM LEADER

2B17
2B17

2B17

2B17

2B17

2B17
2B5A (200x600) 2B5 (300x750)
2B5 (300x750)

FIRST FLOOR BEAM LAYOUT


417
417

C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

417
J
H
417

K
M

C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC


SLAB SUNK BY 450 REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
FIRST FLOOR BEAM LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-410
REV NO. SCALE:
REFER
C5A 1:100 N SITE PLAN

DATE: 25-11-2018
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
A B C D E F G H J K L M N P 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
58250
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
3B1A (200 x600) 3B1 (450 x750) CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25

1 A OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.


417 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
3B16

THIRD OF THE SPAN


2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
3B7 (200x600)
3B10 (300 x600)

3B11 (300 x600)


4605

2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

TSCL APPROVAL
3B7 (200 x 600) ASSISTANT/JUNIOR ENGINEER

2
2395

3B7 (200x600)

3B16(200x600)
3B12 (450x750)
ASSISTANT EXECUTIVE ENGINEER
3 B

3B16 (200 x 600)


417
3B2 (200x600)
3350

3B15 (450x750)
417
N

417

EXECUTIVE ENGINEER
3B11 (450 x750)
20005

4 3B7 (200 x 600)


2650

SUPERINTENDING ENGINEER
3B9 3B9
5
3B7 (200 x 600)
2105

3B3 (200x600)

3B9
3B9

3B13 (750 x 750)

6 C 3B9 ARCHITECT
417 3B9
3B10A (200 x600)

3B10A (200 x600)

3B11A (200 x600)

3B8(300x750)
417

STRUCTURAL EXPERT
3B10 (300 x600)

3B10 (300 x600)


4900

INFRASTRUCTURE EXPERT

D E TEAM LEADER
7
417 3B4 (200x600) 419
3B4 (450x750)

3B17
3B17

3B17

3B17

3B17
2B5A (200x600) 3B5 (300x750)
3B5 (300x750)
C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

SECOND FLOOR BEAM LAYOUT C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
417
417

417
J
H
417

REV. DATE ISSUED TO PRD CHK APD

K
M

DESCRIPTION OF REVISIONS
SLAB SUNK BY 450 PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
SECOND FLOOR BEAM LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-412
REV NO. SCALE:
REFER
C5A 1:100 N SITE PLAN

DATE: 27-12-2018
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

B STRUCTURAL NOTES :
A C D E F G H J K L M N P 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
58250 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
6000 6000 3625 2425 5950 5850 6150 6000 6350 3100 2550 950 3300 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.

4B1A (200 x600) 4B1 (450 x750) 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
1 A THIRD OF THE SPAN
419 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
4B16

SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
4B10 (450 x750)

4B11 (450 x750)


4605

4B7 (200x600)
TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
4B7 (200 x 600)

2
2395

4B16(200x600)
ASSISTANT EXECUTIVE ENGINEER
4B12 (450x750)

3 B

4B16 (200 x 600)


419
4B2 (450x750)
3350

4B15 (450x750)
EXECUTIVE ENGINEER
419

4B11 (450 x750)


20005

4 4B7 (200 x 600)


2650

SUPERINTENDING ENGINEER

4B9 4B9
5
4B7 (200 x 600)
2105

4B9
4B3 (450x750)
4B9

ARCHITECT
4B13 (750 x 750)

6 C 4B9
419 4B9
4B10A(200 x600)

4B10A(200 x600)

4B10A(200 x600)

STRUCTURAL EXPERT
4B10(300 x600)

4B10(300 x600)
419
G
4900

INFRASTRUCTURE EXPERT

TEAM LEADER

7 D E
419 419
4B4A (200x600)
4B17

4B17

4B17

4B4 (450x750)

419
4B5 (300x750)

K
C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

THIRD FLOOR BEAM LAYOUT REV. DATE ISSUED TO PRD CHK APD
419
419

J
H

SLAB SUNK BY 450 DESCRIPTION OF REVISIONS


PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
THIRD FLOOR BEAM LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-412
REV NO. SCALE:
REFER
C5A 1:100 N SITE PLAN

DATE: 27-12-2018
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
A B C D E F G H J K L M N P 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
58250 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
TB1A (200 x600) TB1 (450 x750) THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
1 A 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
420
TB16

TSCL APPROVAL
TB10 (450 x750)

TB11 (450 x750)

ASSISTANT/JUNIOR ENGINEER
4605

TB7 (200x600)

TB7 (200 x 600)

2 ASSISTANT EXECUTIVE ENGINEER


2395

TB16(200x600)
TB12 (450x750)

3 B

TB16 (200 x 600)


420 EXECUTIVE ENGINEER
TB2 (450x750)
3350

TB15 (450x750)
420

TB11 (450 x750)


20005

4 TB7 (200 x 600) SUPERINTENDING ENGINEER


2650

TB9 4B9
5
ARCHITECT
TB7 (200 x 600)
2105

TB9
TB3 (450x750)
TB9

TB13 (750 x 750)

C STRUCTURAL EXPERT
6 TB9
420 TB9
TB10A (200 x600)

TB10A( 200 x600)

TB11A (200 x600)


TB10 (300 x600)

TB10 (300 x600)

INFRASTRUCTURE EXPERT
420
G
4900

TEAM LEADER

7 D E
420 420
TB4 (200x600)
TB17

TB17

TB17

TB17

TB4 (450x750)
C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

420
TB5 (300x750)

K
REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
SLAB SUNK BY 450
TERRACE FLOOR BEAM LAYOUT
420

PROJECT:
420

J
H

CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
TERRACE FLOOR BEAM LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-414
REV NO. SCALE:
REFER
C5A 1:100 N SITE PLAN

DATE: 27-12-2018
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
A B C D E F G H J K L M N P SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


58250 ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
1 THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
4605

1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS


PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

MB1 STRUCTURAL NOTES :


2 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2395

2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO


IS 456, 2010.

MB1
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
3 CONFORMING TO IS 1786, 2008.

MB1
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
3350

2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE


THIRD OF THE SPAN
MB1 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
20005

MB1
SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
4

MB1
2650

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
MB2 MB1
5
MB1
2105

MB1

MB1
MB2

MB2
ASSISTANT EXECUTIVE ENGINEER
6 MB2 MB1
MB2 MB2
4900

MB2

MB2
EXECUTIVE ENGINEER

7
MB2 SUPERINTENDING ENGINEER
MB2

MB2

ARCHITECT

MUMTY FLOOR BEAM LAYOUT STRUCTURAL EXPERT

INFRASTRUCTURE EXPERT

TEAM LEADER

200 200
#3Ø25mm #3Ø25mm
C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD


2L-8mmØ@ 2L-8mmØ@
450

450

180mmc/c 180mmc/c DESCRIPTION OF REVISIONS


PROJECT:
CITY LIBRARY

#2Ø20mm #2Ø20mm+ CLIENT: TUMKUR SMART CITY LTD.


#1Ø12mm FOR APPROVAL
DWG. TITLE:

DETAILS OF MFB1 DETAILS OF MFB2 MUMTY FLOOR BEAM LAYOUT


SCALE-1:15 SCALE-1:15 DWG.NO. TSC-CLP-101-STR-DRG-414
REV NO. SCALE:
REFER
C5A 1:100 N SITE PLAN

DATE: 27-12-2018
NOTES :
A B C E F G H J K M 1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


1000 1000 1000 1000 2000
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
5275 5250 5300 5125 4950 5250 5100 5525 4925 PREPARATION OF SHOP DWGS.

AA
1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME

-
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
GFB1 LONGITUDINAL SECTION A
408 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
#6Ø25mm #6Ø32mm #6Ø25mm TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
450 450 450
A B C D 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
A B C 300 PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
#3Ø25mm
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
900 900 900 900 OF THE MAIN CONTRACTOR.
EXT#3Ø25mm EXT #6Ø25mm EXT #6Ø25mm
900
4L-10mmØ@ EXT#2Ø25mm
STRUCTURAL NOTES :

750
750

750
150mmc/c
4L-12mmØ@ 4L-10mmØ@ 2.1 FOR GENRAL NOTES REFER DRG
2L-10mmØ@

600
180mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 2L-10mmØ@200mmc/c 150mmc/c
200mmc/c NO.TSC-CLP-101-STR-DRG-400
EXT #4Ø25mm 4L-12mmØ@180mmc/c 4L-12mmØ@180mmc/c 5200 4900 3175 #2Ø12mm
#2Ø25mm+ 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
5275 5725
IS 456, 2010.

CA
CC
1Ø16mm

-
-
BB
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL

-
GFB3 LONGITUDINAL SECTION C GFB13 LONGITUDINAL SECTION C CONFORMING TO IS 1786, 2008.
408 408 #3Ø25mm
GFB2 LONGITUDINAL SECTION B 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
#6Ø25mm 408 #6Ø25mm+
#4Ø20mm
#6Ø20mm
SECTION CA OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.

SECTION CC SCALE-1:20 -
SECTION AA #6Ø25mm SECTION BB 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
SCALE-1:20 - SCALE-1:20 - SCALE-1:20 - 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
450
A B C E F G H J K M SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

900 900 EXT #4Ø25mm 900 1200 900 900 900 900 1200 1200 900 TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER

750
4L-10mmØ@
4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c
#4Ø25mm
5200 4900 5125 4950 5250 5100 5525 4925

DD
DD

-
-

ASSISTANT EXECUTIVE ENGINEER


GFB4 LONGITUDINAL SECTION D #6Ø25mm GFB4 LONGITUDINAL SECTION E
408 #6Ø25mm 408
450
#6Ø32mm
SECTION DD 600
SCALE-1:20 -
3 1 6 3 7 6 3 1
EXT #5Ø25mm EXECUTIVE ENGINEER

1500 1500
750

900 900 EXT #5Ø32mm


4L-12mmØ@
180mmc/c

750
#2Ø16mm 4L-12mmØ@180mmc/c 4L-12mmØ@
4L-12mmØ@180mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 125mmc/c
8805 4L-12mmØ@125mmc/c
5400
SUPERINTENDING ENGINEER
3450 7905 6000

FF
-
FF
-

HH-
#4Ø20mm
GFB7 LONGITUDINAL SECTION F GFB7 LONGITUDINAL SECTION G GFB8 LONGITUDINAL SECTION H
408 SECTION FF 408 408 #7Ø25mm
SCALE-1:20 - ARCHITECT
SECTION HH
SCALE-1:20 -
#6Ø25mm
7 5 #8Ø32mm
STRUCTURAL EXPERT
750 7 6 5 3 1 450

1200 1200
2500 900
INFRASTRUCTURE EXPERT

EXT #4Ø25mm
EXT #6Ø32mm
4L-12mmØ@125mmc/c TEAM LEADER

750
750

4L-12mmØ@ 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c


3400 2100 125mmc/c 4L-10mmØ@
3750 1905 4750 5750 200mmc/c
JJ

#6Ø32mm #2Ø20mm
-

KK
-
GFB9 LONGITUDINAL SECTION J GFB10 LONGITUDINAL SECTION K
408 408
#7Ø32mm #6Ø25mm
C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
SECTION JJ SECTION KK
SCALE-1:20 - C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
SCALE-1:20 -
REV. DATE ISSUED TO PRD CHK APD
#11Ø25mm DESCRIPTION OF REVISIONS
400
#6Ø25mm PROJECT:
CITY LIBRARY
450
CLIENT: TUMKUR SMART CITY LTD.
200 200
#3Ø25mm #3Ø25mm FOR APPROVAL
4L-10mmØ@ DWG. TITLE:
#2Ø16mm 125mmc/c GROUND FLOOR BEAM DETAIL
900

#2Ø12mm #6Ø10mm #2Ø16mm DWG.NO. TSC-CLP-101-STR-DRG-415


750

2L-8mmØ@ 4L-8mmØ@ 2L-8mmØ@ REV NO. SCALE:


600

600

180mmc/c REFER
125mmc/c
#2Ø16mm
150mmc/c C5A 1:100 N SITE PLAN

#1Ø12mm DATE: 27-12-2018

#3Ø20mm #3Ø25mm
#10Ø25mm
#6Ø20mm

DETAILS OF GFB5 DETAILS OF GFB6 DETAILS OF GFB12 DETAILS OF GFB11


SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

A B C E F G H J K M 1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.
900 1200 900 900 1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
1200 PREPARATION OF SHOP DWGS.

4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@100mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
5275 5250 5300 5125 4950 5250 5100 5525 4925 SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.

AA
#6Ø25mm

-
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL

#6Ø32mm #6Ø32mm
1B1 LONGITUDINAL SECTION A 450 TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
409
450 450 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
A B C D EXT #3Ø25mm OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
A B C OF THE MAIN CONTRACTOR.

750
EXT #7Ø25mm EXT #4Ø25mm
4L-10mmØ@
900 900
180mmc/c
STRUCTURAL NOTES :
900
750

2.1 FOR GENRAL NOTES REFER DRG

750
4L-12mmØ@
4L-12mmØ@ NO.TSC-CLP-101-STR-DRG-400
125mmc/c
180mmc/c
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
EXT #2Ø25mm 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c IS 456, 2010.
4L-12mmØ@180mmc/c 4L-12mmØ@180mmc/c 5200 4900 3175
5275 5725 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL

CC
CONFORMING TO IS 1786, 2008.

-
BB
#6Ø20mm

-
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
1B3 LONGITUDINAL SECTION C SECTION CC OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
#6Ø25mm
1B2 LONGITUDINAL SECTION B #6Ø32mm
#9Ø20mm 409
SCALE-1:20 - 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
409
SECTION AA 450 SECTION BB THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SCALE-1:20 - SCALE-1:20 - SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
A B C E F G H J K M
EXT #6Ø25mm
TSCL APPROVAL
900 900 900

750
900 900 900 1500 1500
4L-12mmØ@ ASSISTANT/JUNIOR ENGINEER
125mmc/c
#2Ø25mm 1200

4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c


5200 4900 5125 4950 5250 5100 5525 4925

DD
DD

-
-

ASSISTANT EXECUTIVE ENGINEER


#6Ø25mm #6Ø32mm
1B4 LONGITUDINAL SECTION D 1B4 LONGITUDINAL SECTION E 450
409 SECTION DD 409
#6Ø25mm SCALE-1:20 -
3 1 450 6 3 7 6 3 1
EXT #4Ø25mm EXECUTIVE ENGINEER

900 900 900 900 1200

750
EXT #4Ø25mm
4L-12mmØ@
180mmc/c
1000
EXT #3Ø20mm
750

4L-10mmØ@125mmc/c
4L-10mmØ@
4L-10mmØ@125mmc/c 125mmc/c 8805 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c
5400 3450 7905 6000 SUPERINTENDING ENGINEER
#2Ø12mm FF -
FF -

HH -
#6Ø25mm #6Ø16mm
1B7 LONGITUDINAL SECTION F 1B7 LONGITUDINAL SECTION G 1B8 LONGITUDINAL SECTION H 450
#6Ø20mm
450
409 409 409
#4Ø20mm SECTION HH
SCALE-1:20 - ARCHITECT
SECTION FF
SCALE-1:20 - EXT #2Ø25mm+
7 5 7 6 5 3 1 #1Ø16mm
4L-8mmØ@
STRUCTURAL EXPERT

750
150mmc/c

750
4L-8mmØ@
225mmc/c
1200 #6Ø32mm 1200 900 900 1200
EXT #2Ø25mm+ #4Ø25mm
750 #1Ø16mm INFRASTRUCTURE EXPERT
1200 2000
4L-8mmØ@150mmc/c
4L-10mmØ@150mmc/c 4L-8mmØ@225mmc/c 4L-8mmØ@225mmc/c 4L-8mmØ@225mmc/c 6865

LL
TEAM LEADER

-
3400 2100 3750 1905 4750 5750
#6Ø25mm 1B10 LONGITUDINAL SECTION L
JJ

KK
#6Ø25mm
-

EXT #2Ø25mm

-
409
SECTION KK SECTION LL
750

4L-10mmØ@
1B13 LONGITUDINAL SECTION K SCALE-1:20 - SCALE-1:20 -
1B9 LONGITUDINAL SECTION J 150mmc/c
EXT #6Ø25mm 409 #4Ø25mm
409 #8Ø32mm 450
600

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC


EXT#2Ø25mm
7 #8Ø32mm 1 C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
EXT #2Ø32mm+ 4L-8mmØ@

750
#2Ø25mm 225mmc/c
SECTION JJ 4L-10mmØ@
900
REV. DATE ISSUED TO PRD CHK APD
750

2500
SCALE-1:20 - 2500
225mmc/c
DESCRIPTION OF REVISIONS
EXT #2Ø25mm PROJECT:
10000
4L-8mmØ@225mmc/c CITY LIBRARY
4L-10mmØ@225mmc/c 6175

PP -
20205
MM

#4Ø25mm+ CLIENT: TUMKUR SMART CITY LTD.


-

#8Ø32mm 1B16 LONGITUDINAL SECTION P SECTION PP


#2Ø12mm
FOR APPROVAL
1B11 LONGITUDINAL SECTION M 409
409 SECTION MM SCALE-1:20 -
SCALE-1:20 - DWG. TITLE: INTERMEADATE FLOOR
BEAM DETAIL
DWG.NO. TSC-CLP-101-STR-DRG-416
7 1 #6Ø32mm
REV NO. SCALE:
450 REFER
1200 1200
C5A 1:100 N SITE PLAN

EXT #3Ø25mm
DATE: 28-12-2018
4L-8mmØ@
4L-8mmØ@180mmc/c
750

180mmc/c
18405
NN -

1B12 LONGITUDINAL SECTION N


409

#4Ø25mm+
#2Ø16mm
SECTION NN
SCALE-1:20 -
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
A B C E F G H J K M SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.
1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
5275 5250 5300 5125 4950 5250 5100 5525 4925 PREPARATION OF SHOP DWGS.
1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
-

#6Ø25mm #4Ø32mm+ #6Ø25mm SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
450
#2Ø25mm
#4Ø25mm THE SAID WORK.
450 450
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
300 TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
A B C D
A B C EXT #4Ø25mm
EXT #3Ø25mm 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
4L-10mmØ@
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
200mmc/c OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
750
750

750
900 2L-8mmØ@
900 4L-10mmØ@ 4L-8mmØ@ 125mmc/c OF THE MAIN CONTRACTOR.
150mmc/c 150mmc/c

750
#2Ø20mm STRUCTURAL NOTES :
4L-8mmØ@150mmc/c 4L-8mmØ@150mmc/c 2L-8mmØ@125mmc/c 2.1 FOR GENRAL NOTES REFER DRG
4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 5200 4900 3175
#2Ø20mm NO.TSC-CLP-101-STR-DRG-400
5275 5725 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
-

-
-

#8Ø25mm #4Ø25mm+ #6Ø20mm #4Ø25mm 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
#2Ø16mm
CONFORMING TO IS 1786, 2008.
#6Ø32mm
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
450
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
A B C EXT #3Ø25mm E F G H J K M SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
750

4L-12mmØ@
125mmc/c 900 900 900 900
TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c
5200 4900 5125 4950 5250 5100 5525 4925
-

-
#4Ø32mm+
#2Ø16mm
ASSISTANT EXECUTIVE ENGINEER
#6Ø25mm #6Ø32mm
450 450
3 1 EXT #3Ø25mm
6 3 7 6 3 1 EXT #4Ø25mm EXECUTIVE ENGINEER
750

750
4L-10mmØ@ 4L-12mmØ@
900 900 150mmc/c 900 900 150mmc/c
4L-10mmØ@150mmc/c
4L-10mmØ@150mmc/c 8805 4L-12mmØ@150mmc/c 4L-12mmØ@150mmc/c 4L-12mmØ@150mmc/c SUPERINTENDING ENGINEER
5400 3450 7905 6000

-
-

#4Ø20mm+ #3Ø32mm+

-
#2Ø16mm #2Ø25mm
ARCHITECT
#6Ø32mm+#2Ø25mm
#5Ø25mm #6Ø20mm
750
450 450 STRUCTURAL EXPERT
7 5 7 6 5 3 1 INFRASTRUCTURE EXPERT
EXT #3Ø25mm
4L-12mmØ@ 4L-8mmØ@
4L-8mmØ@
750

900 250mmc/c 150mmc/c


200mmc/c

750

750
900 900 900 900
TEAM LEADER
#2Ø25mm
4L-12mmØ@250mmc/c 4L-8mmØ@200mmc/c 4L-8mmØ@200mmc/c 4L-8mmØ@200mmc/c 4L-10mmØ@200mmc/c
3400 2100 3750 1905 4750 5750 6865

-
-

-
#8Ø32mm
#8Ø25mm #6Ø32mm
C5A 25/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
7 6 3 1 REV. DATE ISSUED TO PRD CHK APD
1200
DESCRIPTION OF REVISIONS
#4Ø25mm 900 900 1200 PROJECT:
450 #6Ø25mm CITY LIBRARY
400
4L-8mmØ@200mmc/c
4L-8mmØ@250mmc/c
#3Ø20mm
6175 4L-8mmØ@250mmc/c
EXT#2Ø25mm 3300 5400 300 CLIENT: TUMKUR SMART CITY LTD.
-

300 #4Ø25mm FOR APPROVAL

-
4L-8mmØ@
200mmc/c #2Ø20mm
750 200 200 DWG. TITLE:
#3Ø25mm #2Ø25mm+ SECOND FLOOR BEAM DETAIL
4L-12mmØ@ #1Ø16mm
#5Ø25mm 150mmc/c
DWG.NO. TSC-CLP-101-STR-DRG-417
2L-8mmØ@
450
2L-8mmØ@ REV NO. SCALE:

900
200mmc/c #2Ø16mm #6Ø10mm #2Ø16mm REFER
#4Ø25mm+ 225mmc/c

750
SITE PLAN

750
#2Ø12mm
2L-8mmØ@ 2L-8mmØ@

600

600
EXT #3Ø16mm
150mmc/c 200mmc/c

750
4L-8mmØ@ #2Ø16mm
250mmc/c #2Ø25mm
#3Ø20mm #2Ø25mm+ #4Ø25mm
#3Ø16mm
#1Ø22mm
#3Ø25mm+ #6Ø32mm
#2Ø16mm
DETAILS OF 2B5 DETAILS OF 2B7 DETAILS OF 2B9 DETAILS OF 2B16 DETAILS OF 2B17
NOTES :
A B C E F G H J K M 1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.
450

750
4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 4L-10mmØ@200mmc/c 1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
5275 5250 5300 5125 4950 5250 5100 5525 4925 LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
SECTION AA
SCALE-1:20
PREPARATION OF SHOP DWGS.

AA-
1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
3B1 LONGITUDINAL SECTION A SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
#6Ø25mm #4Ø32mm+ 410 #6Ø25mm THE SAID WORK.
#2Ø25mm
450 450 450 #4Ø25mm 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
300 TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
A B C D AT SITE..
A B C
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
EXT #4Ø25mm
EXT #3Ø25mm PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
900
4L-10mmØ@ 900 OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY

750
750

200mmc/c

750
2L-8mmØ@ OF THE MAIN CONTRACTOR.
4L-10mmØ@ 4L-8mmØ@ 125mmc/c
150mmc/c 150mmc/c

750
#2Ø20mm 4L-8mmØ@150mmc/c 4L-8mmØ@150mmc/c 2L-8mmØ@125mmc/c STRUCTURAL NOTES :
4L-10mmØ@150mmc/c 4L-10mmØ@150mmc/c 5200 4900 3175 2.1 FOR GENRAL NOTES REFER DRG
5275 5725 NO.TSC-CLP-101-STR-DRG-400
#2Ø20mm

CA
CC-

-
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO

BB -
IS 456, 2010.
3B3 LONGITUDINAL SECTION C 3B8 LONGITUDINAL SECTION C
#8Ø25mm 3B2 LONGITUDINAL SECTION B #4Ø25mm+ 410 410 #6Ø20mm #4Ø25mm
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
410 #2Ø16mm
SECTION AA #6Ø32mm SECTION BB SECTION CC SECTION CA 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
SCALE-1:20 - 450
SCALE-1:20 - SCALE-1:20 - SCALE-1:20 - OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
A B C E F G H J K M 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
EXT #3Ø25mm 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
900 900 900 900

750
4L-12mmØ@
125mmc/c TSCL APPROVAL
4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c ASSISTANT/JUNIOR ENGINEER
4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c
5200 4900 5125 4950 5250 5100 5525 4925
DD

DD
-

-
3B4 LONGITUDINAL SECTION D #4Ø32mm+ 3B4 LONGITUDINAL SECTION E
410 #2Ø16mm
410 ASSISTANT EXECUTIVE ENGINEER
#6Ø25mm
SECTION DD #6Ø32mm
450 SCALE-1:20 - 450

3 1 EXT #3Ø25mm
6 3 7 6 3 1
EXT #4Ø25mm EXECUTIVE ENGINEER
750

750
900 900 900 900
4L-10mmØ@ 4L-12mmØ@
150mmc/c 150mmc/c

4L-10mmØ@150mmc/c
4L-10mmØ@150mmc/c 8805 4L-12mmØ@150mmc/c 4L-12mmØ@150mmc/c 4L-12mmØ@150mmc/c
5400 3450 7905 6000 SUPERINTENDING ENGINEER

FF -
FF -

HH
-
#4Ø20mm+ #3Ø32mm+
3B11 LONGITUDINAL SECTION F #2Ø16mm 3B11 LONGITUDINAL SECTION G 3B12 LONGITUDINAL SECTION H #2Ø25mm
410 SECTION FF 410 410 SECTION HH
SCALE-1:20 - SCALE-1:20 -
#6Ø32mm+#2Ø25mm
ARCHITECT
750
#5Ø25mm #6Ø20mm
450 450 STRUCTURAL EXPERT

7 5 7 6 5 3 1
INFRASTRUCTURE EXPERT
4L-12mmØ@
EXT #3Ø25mm
750

250mmc/c
900 900 900 900 900 4L-8mmØ@
4L-8mmØ@
150mmc/c

750
200mmc/c

750
TEAM LEADER

4L-12mmØ@250mmc/c 4L-8mmØ@200mmc/c 4L-8mmØ@200mmc/c 4L-8mmØ@200mmc/c 4L-10mmØ@200mmc/c #2Ø25mm

3400 2100 3750 1905 4750 5750 6865

LL-
KK
JJ -

-
#8Ø32mm 3B14 LONGITUDINAL SECTION L
410
JJ 3B15 LONGITUDINAL SECTION K
3B13 LONGITUDINAL SECTION J SECTION 410 #8Ø25mm #6Ø32mm
410 SCALE-1:20 - SECTION KK SECTION LL C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
SCALE-1:20 - SCALE-1:20 - C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
7 6 3 1
#4Ø25mm REV. DATE ISSUED TO PRD CHK APD
1200 450
900 900 1200 DESCRIPTION OF REVISIONS
PROJECT:
4L-8mmØ@200mmc/c EXT#2Ø25mm CITY LIBRARY
4L-8mmØ@250mmc/c 4L-8mmØ@250mmc/c
6175 400
PP

4L-8mmØ@ 3300 5400 #3Ø20mm


-

MM

MM

200mmc/c
750

CLIENT: TUMKUR SMART CITY LTD.


-

3B6 LONGITUDINAL SECTION P 3B10 LONGITUDINAL SECTION M 3B10 LONGITUDINAL SECTION N 300 FOR APPROVAL
410 410 410
#2Ø20mm DWG. TITLE:
200 200
#3Ø25mm #2Ø25mm+ SECOND FLOOR BEAM DETAIL
#1Ø16mm
#4Ø25mm+ #5Ø25mm
4L-12mmØ@ DWG.NO. TSC-CLP-101-STR-DRG-418
#2Ø12mm 150mmc/c
SECTION PP 450
2L-8mmØ@ REV NO. SCALE:

900
SCALE-1:20 - #2Ø16mm #2Ø16mm REFER
#6Ø10mm
200mmc/c
C5A 1:100 N SITE PLAN
750

2L-8mmØ@ 2L-8mmØ@
600

600
EXT #3Ø16mm
150mmc/c 200mmc/c
DATE: 28-12-2018
750

4L-8mmØ@
250mmc/c
#2Ø25mm

#3Ø20mm #2Ø25mm+
#3Ø16mm
#3Ø25mm+ #1Ø22mm
#2Ø16mm #6Ø32mm
SECTION MM
DETAILS OF 2B5 DETAILS OF 2B7 DETAILS OF 2B9 DETAILS OF 2B16
SCALE-1:20 -

SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15


NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
A B C E F G H J K M SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


900 ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
5275 5250 5300 5125 4950 5250 5100 5525 4925 PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME

AA
-
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
#6Ø25mm 4B1 LONGITUDINAL
#4Ø32mm+ SECTION A #6Ø25mm THE SAID WORK.
450 450
#2Ø25mm
412 450 #3Ø25mm+ 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
#1Ø12mm
300
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
A B C 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
EXT #4Ø25mm
EXT #3Ø25mm PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
4L-10mmØ@ OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
900

750
750

200mmc/c

750
900 2L-8mmØ@ OF THE MAIN CONTRACTOR.
4L-10mmØ@ 4L-8mmØ@ 200mmc/c
150mmc/c 150mmc/c

750
#2Ø20mm
STRUCTURAL NOTES :
4L-8mmØ@150mmc/c 4L-8mmØ@150mmc/c 2L-8mmØ@200mmc/c 2.1 FOR GENRAL NOTES REFER DRG
4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c
5200 5050 3025 NO.TSC-CLP-101-STR-DRG-400
5275 5725
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO

CA
CC
IS 456, 2010.

-
BB-
#8Ø25mm #4Ø25mm+ 4B3 LONGITUDINAL SECTION C 4B8 LONGITUDINAL SECTION C #6Ø20mm #4Ø25mm
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
4B2 LONGITUDINAL SECTION B #2Ø16mm 412 412 CONFORMING TO IS 1786, 2008.
SECTION AA 412 #6Ø25mm SECTION BB SECTION CC SECTION CA 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
SCALE-1:20 - 450 SCALE-1:20 - SCALE-1:20 - SCALE-1:20 - OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
A B C E F G H J K M 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
EXT #2Ø20mm
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
900 900

750
4L-10mmØ@
180mmc/c TSCL APPROVAL
EXT #2Ø20mm ASSISTANT/JUNIOR ENGINEER
4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c
5200 4900 5125 4950 5250 5100 5525 4925

DD
DD

-
-

#6Ø25mm
4B4 LONGITUDINAL SECTION D 4B4 LONGITUDINAL SECTION E ASSISTANT EXECUTIVE ENGINEER
412 #4Ø25mm
SECTION DD 412 #6Ø25mm
450 SCALE-1:20 - 450

EXT #3Ø25mm+
3 1 #1Ø16mm 6 3 7 6 3 1 EXT #3Ø16mm
EXT #6Ø25mm EXECUTIVE ENGINEER

-
750
-

900 900 4L-10mmØ@ 900 900

750
150mmc/c 4L-12mmØ@
180mmc/c
4L-10mmØ@150mmc/c
4L-10mmØ@150mmc/c 8805 4L-10mmØ@125mmc/c 4L-10mmØ@125mmc/c 4L-10mmØ@125mmc/c
5400 3450 7905 6000
SUPERINTENDING ENGINEER

FF
-
FF -

HH
#4Ø20mm

-
4B11 LONGITUDINAL SECTION F 4B11 LONGITUDINAL SECTION G 4B12 LONGITUDINAL SECTION H #4Ø25mm+

412 SECTION FF 412 412


#2Ø16mm
SCALE-1:20 - SECTION HH
#7Ø25mm SCALE-1:20 - ARCHITECT
750
7 5 7 6 5 3 1 #5Ø25mm
#5Ø16mm
450 STRUCTURAL EXPERT
450
900
900
EXT #3Ø25mm INFRASTRUCTURE EXPERT
750

6L-12mmØ@ EXT #3Ø25mm


4L-12mmØ@125mmc/c 225mmc/c
EXT #5Ø20mm 4L-8mmØ@225mmc/c 4L-8mmØ@225mmc/c 4L-8mmØ@225mmc/c 4L-12mmØ@200mmc/c
4L-8mmØ@

750
3400 2100 4L-12mmØ@ TEAM LEADER

750
3750 1905 4750 5750 225mmc/c 6865
200mmc/c

LL
-
JJ -

EXT #1Ø20mm
4B14 LONGITUDINAL SECTION L

KK-
EXT #3Ø25mm
412
4B13 LONGITUDINAL SECTION J 4B15 LONGITUDINAL SECTION K
412 #6Ø32mm 412

SECTION JJ
SCALE-1:20 - #5Ø25mm
#5Ø32mm
C5A 27/12/2018
SECTION KK SECTION LL
ISSUED FOR APPROVAL. NPN HTM DGC
SCALE-1:20 - SCALE-1:20 - C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

#10Ø25mm DESCRIPTION OF REVISIONS


#3Ø20mm 400 PROJECT:
#6Ø25mm #5Ø25mm
1200 450 300 CITY LIBRARY
300 450 #4Ø25mm

200 200 CLIENT: TUMKUR SMART CITY LTD.


4L-8mmØ@200mmc/c #3Ø25mm #2Ø25mm+
6175
EXT#2Ø25mm #1Ø12mm 4L-12mmØ@
FOR APPROVAL
150mmc/c DWG. TITLE:
PP
-

4L-8mmØ@
750

200mmc/c 2L-8mmØ@

900
4B6 LONGITUDINAL SECTION P 225mmc/c #2Ø16mm #2Ø16mm 2L-8mmØ@
225mmc/c
THIRD FLOOR BEAM DETAIL
750

750

750
412 4L-8mmØ@
2L-8mmØ@ 2L-8mmØ@ DWG.NO. TSC-CLP-101-STR-DRG-419
600

600

225mmc/c
150mmc/c 225mmc/c
REV NO. SCALE:
#2Ø20mm #2Ø16mm REFER
#4Ø25mm+
#2Ø12mm
C4A 1:75 N SITE PLAN

SECTION PP DATE: 20-11-2018


SCALE-1:20 - #3Ø16mm #2Ø20mm+ #3Ø20mm #4Ø25mm
#1Ø12mm #10Ø25mm
#5Ø16mm

DETAILS OF 4B5 DETAILS OF 4B7 DETAILS OF 4B10 DETAILS OF 4B16 DETAILS OF 4B17 DETAILS OF 4B9
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
A B C E F G H J K M SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


900 ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &

750
4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
5275 5250 5300 5125 4950 5250 5100 5525 4925 PREPARATION OF SHOP DWGS.
#5Ø25mm
1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME

AA
-
450 #3Ø25mm+ SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
TB1 LONGITUDINAL
#6Ø25mm SECTION A #1Ø12mm THE SAID WORK.
450 413 300
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
EXT #3Ø25mm AT SITE..
A B C 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS

750
EXT #6Ø25mm 2L-8mmØ@ PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
4L-8mmØ@
150mmc/c 200mmc/c OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
900

750
900 OF THE MAIN CONTRACTOR.

750
4L-10mmØ@
180mmc/c
STRUCTURAL NOTES :
4L-8mmØ@150mmc/c 4L-8mmØ@150mmc/c 2L-8mmØ@200mmc/c 2.1 FOR GENRAL NOTES REFER DRG
4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c
5200 5050 3025 NO.TSC-CLP-101-STR-DRG-400
5275 5725
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
#3Ø25mm+ #4Ø25mm

CA
CC
IS 456, 2010.

-
BB
#2Ø16mm

-
#5Ø25mm TB3 LONGITUDINAL SECTION C TB8 LONGITUDINAL SECTION C SECTION CC SECTION CA 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
TB2 LONGITUDINAL SECTION B 413 413 SCALE-1:20 - SCALE-1:20 - CONFORMING TO IS 1786, 2008.
413 SECTION BB 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
#6Ø25mm
SCALE-1:20 - OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
450
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
A B C E F G H J K M 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
EXT #2Ø20mm 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
900 900

750
4L-10mmØ@
180mmc/c
TSCL APPROVAL
EXT #2Ø20mm ASSISTANT/JUNIOR ENGINEER
4L-10mmØ@180mmc/c 4L-10mmØ@180mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c 4L-12mmØ@125mmc/c
5200 4900 5125 4950 5250 5100 5525 4925

DD
DD

-
-

TB4 LONGITUDINAL SECTION D #6Ø25mm


TB4 LONGITUDINAL SECTION E ASSISTANT EXECUTIVE ENGINEER
413 413
#4Ø25mm SECTION DD #6Ø25mm
450 SCALE-1:20 - 450

3 1 6
EXT #3Ø25mm+ 3 7 6 3 1 EXT #3Ø16mm
#1Ø16mm
EXT #6Ø25mm EXECUTIVE ENGINEER

-
-

750

900 900 900 900

750
4L-10mmØ@
150mmc/c 4L-12mmØ@
180mmc/c
4L-10mmØ@150mmc/c
4L-10mmØ@150mmc/c 8805 4L-10mmØ@125mmc/c 4L-10mmØ@125mmc/c 4L-10mmØ@125mmc/c
5400 3450 7905 6000 SUPERINTENDING ENGINEER

FF
-
FF -

HH
#4Ø20mm

-
TB11 LONGITUDINAL SECTION F SECTION FF TB11 LONGITUDINAL SECTION G TB12 LONGITUDINAL SECTION H #4Ø25mm+
#2Ø16mm
413 413 413
SCALE-1:20 - SECTION HH
SCALE-1:20 - ARCHITECT
#7Ø25mm
750
7 5 7 6 5 3 1 #5Ø25mm
#5Ø16mm
450
450
STRUCTURAL EXPERT
900
900
INFRASTRUCTURE EXPERT
EXT #3Ø25mm
EXT #3Ø25mm
750

4L-12mmØ@125mmc/c 6L-12mmØ@
225mmc/c 4L-8mmØ@225mmc/c 4L-8mmØ@225mmc/c 4L-8mmØ@225mmc/c 4L-8mmØ@ 4L-12mmØ@200mmc/c

750
4L-12mmØ@

750
3400 2100 EXT #5Ø20mm 3750 1905 4750 5750 225mmc/c 6865 200mmc/c
TEAM LEADER

LL
-
EXT #1Ø20mm
JJ -

TB14 LONGITUDINAL SECTION L EXT #3Ø25mm

KK-
413
TB13 LONGITUDINAL SECTION J TB15 LONGITUDINAL SECTION K
413 413
#6Ø32mm

SECTION JJ #5Ø25mm
#5Ø32mm
SCALE-1:20 - SECTION KK SECTION LL C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
SCALE-1:20 - SCALE-1:20 - C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
#10Ø25mm PROJECT:
#6Ø25mm #3Ø20mm 400
450
#5Ø25mm CITY LIBRARY
1200 300
300 450 #4Ø25mm
CLIENT: TUMKUR SMART CITY LTD.
200 200
4L-8mmØ@200mmc/c EXT#2Ø25mm #3Ø25mm #2Ø25mm+ FOR APPROVAL
6175 #1Ø12mm 4L-12mmØ@
4L-8mmØ@ DWG. TITLE:
750
PP

150mmc/c
-

200mmc/c
2L-8mmØ@ TERRACE FLOOR BEAM DETAIL

900
2L-8mmØ@
TB6 LONGITUDINAL SECTION P 225mmc/c #2Ø16mm #2Ø16mm
225mmc/c
750

750

750
413 4L-8mmØ@
DWG.NO. TSC-CLP-101-STR-DRG-420
2L-8mmØ@ 2L-8mmØ@
600

600

150mmc/c 225mmc/c 225mmc/c REV NO. SCALE:


REFER
#4Ø25mm+
#2Ø12mm
#2Ø20mm #2Ø16mm
C4A 1:100 N SITE PLAN

SECTION PP DATE: 20-11-2018


SCALE-1:20 - #2Ø20mm+
#3Ø16mm #3Ø20mm #4Ø25mm
#1Ø12mm #10Ø25mm
#5Ø16mm

DETAILS OF TB5 DETAILS OF TB7 DETAILS OF TB10 DETAILS OF TB16 DETAILS OF 4B17 DETAILS OF TB9
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.
1 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
4605

TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION


AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
GFBW2 PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.
2
STRUCTURAL NOTES :
2395

2.1 FOR GENRAL NOTES REFER DRG


NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
3 IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
3350

2.4 CLEAR COVER TO SLAB REINFORCEMENT SHALL BE 20


OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
20005

THIRD OF THE SPAN


4 2.6 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
2.8 BEAM DEPTH INDICATED IS INCLUSIVE OF SLAB THICKNESS.
GFBW4 SLAB NOT SHOWN FOR CLARITY IN SECTIONS AT DETAILS.
2650

GFBW1
S2 TSCL APPROVAL
5 ASSISTANT/JUNIOR ENGINEER
2105

6
ASSISTANT EXECUTIVE ENGINEER
4900

EXECUTIVE ENGINEER

7
GFBW3
SUPERINTENDING ENGINEER

ARCHITECT
#3Ø36mm+
#3Ø32mm #9Ø25mm #3Ø32mm #5Ø25mm
300 300 300 300 STRUCTURAL EXPERT

INFRASTRUCTURE EXPERT

#2Ø20mm
#1Ø32mm+ TEAM LEADER
#2Ø25mm #2Ø16mm
750

750

750

750
4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@
180mmc/c 180mmc/c 180mmc/c 225mmc/c

#3Ø25mm #3Ø25mm #3Ø32mm


C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD


150 150 150 150 DESCRIPTION OF REVISIONS
#2Ø25mm #2Ø25mm #2Ø36mm #5Ø25mm PROJECT:
CITY LIBRARY

DETAILS OF GFBW1 DETAILS OF GFBW2 DETAILS OF GFBW3 DETAILS OF GFBW4 CLIENT: TUMKUR SMART CITY LTD.
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 FOR APPROVAL
Ø8mm@200 c/c Ø8mm@200 c/c DWG. TITLE: GROUND FLOOR WAFFLE
125

1302 300 BEAM/SLAB DETAIL


DWG.NO. TSC-CLP-101-STR-DRG-421
SLABREINFORCEMENTDETAILS REV NO. SCALE:
REFER
720 Ø10mm@200mmc/c
C5A 1:100 N SITE PLAN
750

750

S2 DATE: 28-12-2018
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays
150
TYPICAL SLAB REINFORCEMENT DETAIL
SCALE 1:20
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
A B C D E F G H J K L M N P THE WORK RELATED TO THIS DWG.
58250 1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 PREPARATION OF SHOP DWGS.
1BW5 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.
4605

STRUCTRAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
1BW2 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2395

2.4 CLEAR COVER TO SLAB REINFORCEMENT SHALL BE 20


OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
3 THIRD OF THE SPAN
2.6 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
1BW4 2.8 BEAM DEPTH INDICATED IS INCLUSIVE OF SLAB THICKNESS.
3350

SLAB NOT SHOWN FOR CLARITY IN SECTIONS AT DETAILS.


20005

TSCL APPROVAL
4 ASSISTANT/JUNIOR ENGINEER
2650

1BW1
S2
5 1BW6 ASSISTANT EXECUTIVE ENGINEER
2105

EXECUTIVE ENGINEER
4900

1BW7
SUPERINTENDING ENGINEER

ARCHITECT

STRUCTURAL EXPERT
1BW5
1BW3 INTERMEDIATE FLOOR WAFFLE BEAM LAYOUT INFRASTRUCTURE EXPERT

TEAM LEADER
#3Ø32mm
#5Ø25mm #3Ø32mm #5Ø25mm #8Ø25mm #5Ø25mm #9Ø25mm #5Ø25mm
300 300 300 300 300 300 300 300

#1Ø25mm+
#1Ø20mm
#4Ø25mm #3Ø25mm #2Ø25mm+
#2Ø20mm #3Ø25mm #1Ø20mm
750

750

750

750

750

750

750

750
4L-8mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-8mmØ@ 4L-10mmØ@ 4L-10mmØ@
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
180mmc/c 180mmc/c 150mmc/c 180mmc/c 150mmc/c 150mmc/c 180mmc/c 150mmc/c
C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
#2Ø20mm #3Ø25mm #3Ø20mm #3Ø20mm #3Ø25mm #2Ø20mm
REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
150 150 150 150 150 150 150 150 PROJECT:
#2Ø25mm
#2Ø25mm #2Ø25mm #2Ø25mm #2Ø25mm #2Ø25mm #2Ø25mm #2Ø25mm
CITY LIBRARY
DETAILS OF 1BW1 DETAILS OF 1BW1 DETAILS OF 1BW2 DETAILS OF 1BW3 DETAILS OF 1BW4 DETAILS OF 1BW5 DETAILS OF 1BW6 DETAILS OF 1BW7
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 CLIENT: TUMKUR SMART CITY LTD.
FOR APPROVAL
DWG. TITLE: INTERMEDIATE FLOOR
WAFFLE BEAM/SLAB DETAIL
SLABREINFORCEMENTDETAILS DWG.NO. TSC-CLP-101-STR-DRG-422
Ø8mm@200 c/c Ø8mm@200 c/c Ø10mm@200mmc/c
125

REV NO. SCALE:


1302 300 S2 REFER
BothWays C5A 1:100 N SITE PLAN

TORSIONCORNER Ø8mm@200mmc/c DATE: 28-12-2018


720 BothWays
750

750

150
TYPICAL SLAB REINFORCEMENT DETAIL
SCALE 1:20
B NOTES :
A C D E F G H J K L M N P 1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.
58250
1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.
2BW5
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
1 LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
4605

THE SAID WORK.


2BW5 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
2BW2 2BW5
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
2 OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
2BW4 OF THE MAIN CONTRACTOR.
2395

STRUCTRAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
3 NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
3350

2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL


CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO SLAB REINFORCEMENT SHALL BE 20
20005

OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.


4 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
2650

2.8 BEAM DEPTH INDICATED IS INCLUSIVE OF SLAB THICKNESS.


2BW1 2BW7 S2 SLAB NOT SHOWN FOR CLARITY IN SECTIONS AT DETAILS.

5
TSCL APPROVAL
2105

ASSISTANT/JUNIOR ENGINEER

ASSISTANT EXECUTIVE ENGINEER


4900

2BW5

EXECUTIVE ENGINEER
7
2BW5

2BW6 SUPERINTENDING ENGINEER

2BW3
FIRST FLOOR WAFFLE BEAM LAYOUT
#3Ø32mm #3Ø32mm
#5Ø25mm #5Ø25mm #8Ø25mm #5Ø25mm #3Ø25mm+
300 300 300 300 300 300 300 #1Ø20mm ARCHITECT

STRUCTURAL EXPERT

#2Ø16mm
#4Ø25mm #4Ø25mm #4Ø25mm #2Ø20mm INFRASTRUCTURE EXPERT
750

750

750

750

750

750

750
4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-8mmØ@
TEAM LEADER
180mmc/c 150mmc/c 180mmc/c 180mmc/c 150mmc/c 180mmc/c 200mmc/c

#2Ø20mm
#3Ø20mm #3Ø25mm #3Ø20mm #3Ø25mm #4Ø25mm

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC


150 150 150 150 150 150 150 C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

#2Ø20mm #2Ø25mm #5Ø25mm #2Ø20mm #2Ø25mm #2Ø25mm #4Ø25mm REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
DETAILS OF 2BW1 DETAILS OF 2BW2 DETAILS OF 2BW3 DETAILS OF 2BW4 DETAILS OF 2BW5 DETAILS OF 2BW6 DETAILS OF 2BW7 PROJECT:
CITY LIBRARY
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
CLIENT: TUMKUR SMART CITY LTD.
FOR APPROVAL
DWG. TITLE: FIRST FLOOR WAFFLE
SLABREINFORCEMENTDETAILS BEAM / SLAB DETAIL
Ø8mm@200 c/c Ø8mm@200 c/c DWG.NO. TSC-CLP-101-STR-DRG-423
125

1302 300 Ø10mm@200mmc/c


S2 REV NO. SCALE:
REFER
BothWays C5A 1:100 N SITE PLAN

TORSIONCORNER Ø8mm@200mmc/c DATE: 28-12-2018


720 BothWays
750

750

150
TYPICAL SLAB REINFORCEMENT DETAIL
SCALE 1:20
NOTES :
A B C D E F G H J K L M N P 1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

58250 1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 THE WORK RELATED TO THIS DWG.

3BW5 1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
1 PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
4605
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
3BW5 TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
3BW2 3BW5 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
2 OF THE MAIN CONTRACTOR.
3BW4
2395

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
3 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
#3Ø25mm+
IS 456, 2010.
#1Ø20mm

2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL


3350

4L-8mmØ@
200mmc/c

CONFORMING TO IS 1786, 2008.


#4Ø25mm

DETAILS OF 3BW7

2.4 CLEAR COVER TO SLAB REINFORCEMENT SHALL BE 20


OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
20005

2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE


4 THIRD OF THE SPAN
2.6 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
2.8 BEAM DEPTH INDICATED IS INCLUSIVE OF SLAB THICKNESS.
2650

SLAB NOT SHOWN FOR CLARITY IN SECTIONS AT DETAILS.


3BW1 3BW7 S2
5 TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
2105

ASSISTANT EXECUTIVE ENGINEER


4900

3BW5

EXECUTIVE ENGINEER

7
3BW5
SUPERINTENDING ENGINEER
3BW6
3BW3
SECOND FLOOR WAFFLE BEAM LAYOUT
ARCHITECT

300
STRUCTURAL EXPERT
#3Ø25mm #3Ø32mm #3Ø32mm
#5Ø25mm #5Ø25mm #5Ø25mm #8Ø25mm #5Ø25mm #3Ø25mm+
300 300 300 300 300 300 300 300 #1Ø20mm
INFRASTRUCTURE EXPERT

#2Ø16mm
#3Ø20mm #4Ø25mm #4Ø25mm #4Ø25mm #2Ø20mm TEAM LEADER
750

4L-8mmØ@
750

750

750

750

750

750

750

750
4L-8mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-8mmØ@
180mmc/c 180mmc/c 180mmc/c 150mmc/c 180mmc/c 180mmc/c 150mmc/c 180mmc/c 200mmc/c

#2Ø20mm
#2Ø12mm #3Ø20mm #3Ø25mm #3Ø20mm #3Ø25mm #4Ø25mm
150

150 150 150 150 150 150 150 150 C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
#4Ø25mm #2Ø25mm #2Ø20mm #2Ø25mm #5Ø25mm #2Ø20mm #2Ø25mm #2Ø25mm #4Ø25mm
C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

DETAILS OF 2BW9 DETAILS OF 2BW1 DETAILS OF 3BW1 DETAILS OF 3BW2 DETAILS OF 3BW3 DETAILS OF 3BW4 DETAILS OF 3BW5 DETAILS OF 3BW6 DETAILS OF 3BW7 REV. DATE ISSUED TO PRD CHK APD
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
DESCRIPTION OF REVISIONS
PROJECT:
CITY LIBRARY
SLABREINFORCEMENTDETAILS
CLIENT: TUMKUR SMART CITY LTD.

S2 Ø10mm@200mmc/c FOR APPROVAL


BothWays DWG. TITLE: SECOND FLOOR WAFFLE
Ø8mm@200 c/c Ø8mm@200 c/c Ø8mm@200mmc/c BEAM / SLAB DETAIL
125

1302 300 TORSIONCORNER DWG.NO. TSC-CLP-101-STR-DRG-424


BothWays REV NO. SCALE:
REFER

720
C5A 1:100 N SITE PLAN

DATE: 28-12-2018
750

750

150
TYPICAL SLAB REINFORCEMENT DETAIL
SCALE 1:20
NOTES :
A B C D E F G H J K L M N P 1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

58250 1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
4BW5 PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


1 SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
4605

AT SITE..
4BW5 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
4BW2 OF THE MAIN CONTRACTOR.

2 2.1 FOR GENRAL NOTES REFER DRG


4BW4
3BW4 NO.TSC-CLP-101-STR-DRG-400
2395

2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO


IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
3 CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO SLAB REINFORCEMENT SHALL BE 20
4BW5 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
3350

2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE


THIRD OF THE SPAN
20005

2.6 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)


2.8 BEAM DEPTH INDICATED IS INCLUSIVE OF SLAB THICKNESS.
4 SLAB NOT SHOWN FOR CLARITY IN SECTIONS AT DETAILS.

4BW6
2650

4BW1 TSCL APPROVAL


S2 ASSISTANT/JUNIOR ENGINEER
5
2105

6 ASSISTANT EXECUTIVE ENGINEER


4900

4BW5
EXECUTIVE ENGINEER

7
4BW5 SUPERINTENDING ENGINEER

4BW3
THIRD FLOOR WAFFLE BEAM LAYOUT ARCHITECT

#4Ø25mm #3Ø25mm+
#8Ø25mm #8Ø25mm+ #9Ø25mm #5Ø25mm #5Ø25mm STRUCTURAL EXPERT
#2Ø12mm
300 300 300 #1Ø20mm 300 300 300 300
INFRASTRUCTURE EXPERT

#2Ø16mm TEAM LEADER


750

750

750

750

750

750

750
4L-8mmØ@ 4L-8mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-8mmØ@
200mmc/c 180mmc/c 180mmc/c 180mmc/c 180mmc/c 150mmc/c 200mmc/c

#3Ø25mm #3Ø25mm #3Ø25mm #3Ø25mm C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 04/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
150 150 150 150 150 150 150 PROJECT:
#2Ø20mm #2Ø25mm #2Ø25mm #7Ø25mm #2Ø25mm #2Ø25mm #4Ø25mm CITY LIBRARY

DETAILS OF 4BW1 DETAILS OF 4BW1 DETAILS OF 4BW2 DETAILS OF 4BW3 DETAILS OF 4BW4 DETAILS OF 4BW5 DETAILS OF 4BW6 CLIENT: TUMKUR SMART CITY LTD.
FOR APPROVAL
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
DWG. TITLE: THIRD FLOOR RAFFLE
BEAM LAYOUT
Ø8mm@200 c/c Ø8mm@200 c/c DWG.NO. TSC-CLP-101-STR-DRG-407
125

1302 300 SLABREINFORCEMENTDETAILS REV NO. SCALE:


REFER

Ø10mm@200mmc/c
C5A 1:100 N SITE PLAN

S2 DATE: 28-12-2018
720 BothWays
750

750

TORSIONCORNER Ø8mm@200mmc/c
BothWays

150
TYPICAL SLAB REINFORCEMENT DETAIL
SCALE 1:20
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.
A B C D E F G H J K L M N P
1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
58250 PREPARATION OF SHOP DWGS.

6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME
SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TBW5 TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.
4605

TBW5 2.1 FOR GENRAL NOTES REFER DRG


NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
TBW2 IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
2 CONFORMING TO IS 1786, 2008.
TBW4 2.4 CLEAR COVER TO SLAB REINFORCEMENT SHALL BE 20
2395

OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.


2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
3 2.6 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
2.8 BEAM DEPTH INDICATED IS INCLUSIVE OF SLAB THICKNESS.
TBW5 SLAB NOT SHOWN FOR CLARITY IN SECTIONS AT DETAILS.
3350
20005

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
4
TBW6
2650

TBW1
S2
5 ASSISTANT EXECUTIVE ENGINEER
2105

6
EXECUTIVE ENGINEER
4900

TBW5
SUPERINTENDING ENGINEER

7
TBW5
ARCHITECT

#4Ø25mm TBW3 #3Ø25mm+


STRUCTURAL EXPERT

300 300
#8Ø25mm
300
#8Ø25mm+
#1Ø20mm
TERRACE
300
FLOOR WAFFLE300BEAM
#9Ø25mm LAYOUT
#5Ø25mm
300
#5Ø25mm
300
#2Ø12mm
INFRASTRUCTURE EXPERT

TEAM LEADER

#2Ø16mm
750

750

750

750

750

750

750
4L-8mmØ@ 4L-8mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-10mmØ@ 4L-8mmØ@
200mmc/c 180mmc/c 180mmc/c 180mmc/c 180mmc/c 150mmc/c 200mmc/c
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

#3Ø25mm #3Ø25mm #3Ø25mm #3Ø25mm C4A 04/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
PROJECT:
150 150 150 150 150 150 150 CITY LIBRARY
#2Ø20mm #2Ø25mm #2Ø25mm #7Ø25mm #2Ø25mm #2Ø25mm #4Ø25mm
CLIENT: TUMKUR SMART CITY LTD.

DETAILS OF 4BW1 DETAILS OF TBW1 DETAILS OF TBW2 DETAILS OF TBW3 DETAILS OF TBW4 DETAILS OF TBW5 DETAILS OF TBW6 FOR APPROVAL
DWG. TITLE: TERRACE FLOOR RAFFLE
SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15 SCALE-1:15
BEAM LAYOUT
Ø8mm@200 c/c Ø8mm@200 c/c DWG.NO. TSC-CLP-101-STR-DRG-407
125

1302 300 REV NO. SCALE:


REFER
SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

S2 Ø10mm@200mmc/c DATE: 28-12-2018


720 BothWays
750

750

TORSIONCORNER Ø8mm@200mmc/c
BothWays
150
TYPICAL SLAB REINFORCEMENT DETAIL
SCALE 1:20
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


A B C D E F G H J K L M N P LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

58250 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
1 OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

2.1 FOR GENRAL NOTES REFER DRG


4605

NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.

2 2.4 CLEAR COVER TO SLAB REINFORCEMENT SHALL BE 20


OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2395

2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE


THIRD OF THE SPAN
2.6 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

S3
3350

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
20005

4
2650

ASSISTANT EXECUTIVE ENGINEER

5
2105

6 EXECUTIVE ENGINEER
4900

SUPERINTENDING ENGINEER
S3

7
ARCHITECT

STRUCTURAL EXPERT

INFRASTRUCTURE EXPERT

MUMTY FLOOR SLAB LAYOUT


TEAM LEADER

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 04/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

SLABREINFORCEMENTDETAILS REV. DATE ISSUED TO

DESCRIPTION OF REVISIONS
PRD CHK APD

S3 Ø10mm@200mmc/c PROJECT:
CITY LIBRARY
BothWays CLIENT: TUMKUR SMART CITY LTD.

TORSIONCORNER Ø8mm@200mmc/c FOR APPROVAL


DWG. TITLE: MUMTY FLOOR SLAB
BothWays LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-407
REV NO. SCALE:
REFER
C5A 1:100 N SITE PLAN

DATE: 28-12-2018
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

C F 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME

- 20 21 22 23 24 25 26 27 28 29 30 - SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF


THE SAID WORK.
49 50 51 52 53 54 55 56 57 58 59 60 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
19 48 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
18 47 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
17 46 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
16 45 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
15 44 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
43 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
14 SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER

13 12 11 10 9 8 7 6 5 4 3 2 1 42 41 40 39 38 37 36 35 34 33 32 ASSISTANT EXECUTIVE ENGINEER


A D
- -

EXECUTIVE ENGINEER

PART PLAN AT GROUND LEVEL


B

PART PLAN AT BASEMENT FLOOR

E
-

-
SUPERINTENDING ENGINEER

PL(+)1200 0 500
120 EL(+)5550 0 500
7 30
31
100 60
395 59 ARCHITECT
29 58
5 300 57
300 27
28 402 150 56 STRUCTURAL EXPERT
150 26 55
1800

25

1800
54
0 INFRASTRUCTURE EXPERT
GL(+)000 120 23
24 175 53
0 52
22 100 175
150 500 21 0
51
TEAM LEADER
2000 150 50 50 SECTION F
EL(-)600 20 SECTION C EL(+)3750 2000 49
-
-
Ø16MM @200MMC/C Ø16MM @200MMC/C

EL(+)3750 2 750 500 2425 C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
201 48
0 2425 C4A 20/11/2018
750 5 0
ISSUED FOR APPROVAL. NPN HTM DGC
EL(-)600 2 47
201 19
18 750 45
46 REV. DATE ISSUED TO PRD CHK APD
900

750
17 150 500 44 DESCRIPTION OF REVISIONS
16
900

PROJECT:
500 EL(+)2850 2425 43 175
150 15 CITY LIBRARY
2425 14
EL(-)1500 175
SECTION E CLIENT: TUMKUR SMART CITY LTD.
Ø16MM @200MMC/C
SECTION B
Ø12MM @125MMC/C
- FOR APPROVAL

150 2000
- 150
DWG. TITLE:
INSIDE STAIRCASE DETAIL
500 120 2000
EL(-)1500 0 EL(+)2850 500 100
13 42 0 DWG.NO. TSC-CLP-101-STR-DRG-428
12 41
11 436 369 REV NO. SCALE:
0 40 0 REFER
Ø16MM @200MMC/C
10
9 Ø16MM @200MMC/C
39 300
38 150 C5A 1:25 N SITE PLAN
8 37 DATE: 28-12-2018
1650

Ø16MM @200MMC/C 7 Ø16MM @200MMC/C 36


1950

6 35 100
175 120 0
5 0 175 34
4 33 500
Ø8MM @200MMC/C 3 Ø8MM @200MMC/C
500 PL(+)1200 32
2
PL(-)3450 1
SECTION D
SECTION A -
- GROUND FLOOR
BASEMENT FLOOR CROSS SECTION OF STAIRCASE
CROSS SECTION OF STAIRCASE
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


J M SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
- 77 78 79 80
- THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
76 81 82 100 101 102 103 104 105 106 107 108 109 110 111 TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
99 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
75 98 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
74 97 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
73 96 2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
72 95 2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
71 94 SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
70
TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
93

69 68 67 66 65 64 63 62 61 60 92 91 90 89 88 87 86 85 84 83 ASSISTANT EXECUTIVE ENGINEER


G L
- -
EXECUTIVE ENGINEER

PART PLAN AT INTERMEDIATE FLOOR PART PLAN AT FIRST FLOOR


H

K
-

-
SUPERINTENDING ENGINEER

EL(+)13200 0 500
100 111
ARCHITECT
110
109
5
402 300 107
108 STRUCTURAL EXPERT
150 106

1800
105 INFRASTRUCTURE EXPERT
2
EL(+)8850 201 750 500 82
2075 EL(+)12900 104 175
0 103
81 100 102 TEAM LEADER
80 150 0 0 101
750 79 5 SECTION M
-
900

EL(+)11400 2000 100


150 500 78
77
EL(+)7950 2000 175
SECTION J
- Ø16MM @200MMC/C
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
Ø16MM @200MMC/C EL(+)11400 2 750 500 2425
201 99 C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
2 750 500 2425
EL(+)7950 201 76
98 REV. DATE ISSUED TO PRD CHK APD

75 750 96
97
DESCRIPTION OF REVISIONS
900

74 0 0
750 73
150 5 95 PROJECT:
900

EL(+)10500 2425 94 175


150 2425 500 72 CITY LIBRARY
71
EL(+)7050 175
CLIENT: TUMKUR SMART CITY LTD.
SECTION L FOR APPROVAL
Ø16MM @200MMC/C
SECTION H
-
Ø16MM @200MMC/C
- DWG. TITLE:
INSIDE STAIRCASE DETAIL
150 2000
EL(+)7050
500 100 150 2000 DWG.NO. TSC-CLP-101-STR-DRG-429
70 0 500 100
EL(+)10500
69 335 93 0 REV NO. SCALE:
68 4 REFER

Ø16MM @200MMC/C
67 300
66 150
92
91
90 300
369
0 C5A 1:25 N SITE PLAN

65 Ø16MM @200MMC/C 150 DATE: 28-12-2018


1500

100 89
Ø16MM @200MMC/C 64 0 88
1650

175 63 Ø16MM @200MMC/C 87


62 500 86 100
0
61 175 85
EL(+)5550 1100
Ø8MM @200MMC/C 84 500
EL(+)8850 Ø8MM @200MMC/C 83
SECTION G
- SECTION K
INTERMEDIATE FLOOR
FIRST FLOOR
-
CROSS SECTION OF STAIRCASE
CROSS SECTION OF STAIRCASE
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
Q TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
- AT SITE..
129 130 131 132 133 134 135 136 137 138 139 140 1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
128 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
127 CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
126 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
125 THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
124 SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

123
TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER

122
ASSISTANT EXECUTIVE ENGINEER

121 120 119 118 117 116 115 114 113 112
P
- EXECUTIVE ENGINEER

SUPERINTENDING ENGINEER

PART PLAN AT SECOND FLOOR


N
-

EL(+)17550 0 500 EL(+)21900 0 500


100 140 100 169 ARCHITECT
139 168
138 167
5 5 300 166
402 300 136
137 402 150
STRUCTURAL EXPERT
165
150 135 164
INFRASTRUCTURE EXPERT
1800

1800
134 163
133 175 162 175
0 132 0 161
100 131 100 160 TEAM LEADER
150 500 130 SECTION Q 150 500 159 SECTION T
EL(+)15750 2000 129
- EL(+)20100 2000 158
-
Ø16MM @200MMC/C Ø16MM @200MMC/C
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
EL(+)15750 2 750 500 2425 EL(+)20100 2 750 500 2425
201 128 201 157 C4A 20/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC
127 156 REV. DATE ISSUED TO PRD CHK APD

750 125
126
750 154
155
DESCRIPTION OF REVISIONS
900

900

150 500 124 150 500 153 PROJECT:


EL(+)14850 2425 123 175 EL(+)19200 2425 152 175 CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


SECTION P SECTION S FOR APPROVAL
Ø16MM @200MMC/C

150
- 150
Ø16MM @200MMC/C
- DWG. TITLE:
2000 2000 INSIDE STAIRCASE DETAIL
EL(+)14850 500 100 EL(+)19200 500 100
122 0 151 0
121 369 150 369
DWG.NO. TSC-CLP-101-STR-DRG-430
120 0 149 0
119 300 148 300
REV NO. SCALE:
REFER
150 150
Ø16MM @200MMC/C 118
117
Ø16MM @200MMC/C 147
146 C5A 1:25 N SITE PLAN
1650

1650

Ø16MM @200MMC/C 116 Ø16MM @200MMC/C 145


175 115 100 144 100 DATE: 28-12-2018
0 0
114 175 143
113 500 142 500
EL(+)13200 Ø8MM @200MMC/C 112 EL(+)17550 Ø8MM @200MMC/C 141

SECTION N SECTION R
- -
SECOND FLOOR THIRD FLOOR
CROSS SECTION OF STAIRCASE CROSS SECTION OF STAIRCASE
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT

3' 2
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

3' 2 1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT
ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

N N 1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 60 59 58 57 56 55 54 53 52 51 50 49 48 47 46
B F PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY

- - OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 32 33 34 35 36 37 38 39 40 41 42 43 44 45 THIRD OF THE SPAN
A E 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR

- - SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

TSCL APPROVAL

P P ASSISTANT/JUNIOR ENGINEER

PART PLAN AT GROUND FLOOR


PART PLAN AT BASEMENT FLOOR ASSISTANT EXECUTIVE ENGINEER

500 PL(+)1200
500 120 EL(+)5550
31 120 60 0
0 59
30
EXECUTIVE ENGINEER
29 58
28 57 441
27
415 56 5
2
26 55
25 54 SUPERINTENDING ENGINEER
24 GL(+)000 53

2250
2250
23 52
Ø16MM @200MMC/C 22 Ø8MM @200MMC/C 51 120
21 120 50
175 0 0
20 49 ARCHITECT
19 500 48 500
18 1300 47
Ø8MM @200MMC/C 17 Ø16MM @200MMC/C 46 1350 STRUCTURAL EXPERT
EL(-)1050 EL(+)3300

SECTION B SECTION F INFRASTRUCTURE EXPERT

-
Ø16MM @200MMC/C
1BS1 - Ø16MM @200MMC/C
1BS3
TEAM LEADER

0 500 1350
120 45
EL(+)3300

1300 44
0 500 EL(-)1050
408
2 43 Ø16MM @200MMC/C
120 16 42
1BS3
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
15 41
14 40
C4A 30/10/2018 ISSUED FOR APPROVAL. NPN HTM DGC
1BS1
8 13 39 REV. DATE ISSUED TO PRD CHK APD
447 12 Ø16MM @200MMC/C Ø8MM @200MMC/C

2100
38 DESCRIPTION OF REVISIONS
11 37
0 PROJECT:
10 120 36 175 CITY LIBRARY
9
2250

35
8
7
Ø8MM @200MMC/C
500 34 CLIENT: TUMKUR SMART CITY LTD.
33
0 6 FOR APPROVAL
120 5
32 Ø16MM @200MMC/C
PL(+)1200
DWG. TITLE:
4 OUT SIDE STAIRCASE DETAIL
500
3 Ø16MM @200MMC/C SECTION E
1
2 EL(-)3450 - DWG.NO. TSC-CLP-101-STR-DRG-431
GROUND FLOOR REV NO. SCALE:
REFER

CROSS SECTION OF STAIRCASE C5A 1:25 N SITE PLAN

DATE: 28-12-2018

SECTION A
-
BASEMENT FLOOR
CROSS SECTION OF STAIRCASE
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

3' 2 3' 2 1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &
LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.

N N 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL


TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

82 81 80 79 78 77 76 75 74 73 72 111110 109 108 107 106 105 104 103 102 101100 99 98 97
D H STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
- - NO.TSC-CLP-101-STR-DRG-400
2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
61 62 63 64 65 66 67 68 69 70 71 83 84 85 86 87 88 89 90 91 92 93 94 95 96
C G TSCL APPROVAL
- - ASSISTANT/JUNIOR ENGINEER

P P ASSISTANT EXECUTIVE ENGINEER

PART PLAN AT FIRST FLOOR


PART PLAN AT INTERMEDIATE FLOOR
500 120 EL(+)13200
EXECUTIVE ENGINEER
111 0
110
109
108
107
420 SUPERINTENDING ENGINEER
9
500 106
82
100 EL(+)8850
105
0
81 320 104

2250
80 7 103
ARCHITECT
79 Ø8MM @200MMC/C 102 120
78 101 0
77 175 100 STRUCTURAL EXPERT

1650
76 100 99 500
75 0 98 INFRASTRUCTURE EXPERT
Ø16MM @200MMC/C Ø16MM @200MMC/C 97 1350
175 74 500 EL(+)10950
73 SECTION H
Ø8MM @200MMC/C
72 1850 EL(+)7200 - Ø12MM @125MMC/C
TEAM LEADER

1BS4

SECTION D Ø16MM @200MMC/C

- 1BS2
0 500 1350
120 96
EL(+)10950
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC
95
C4A 30/10/2018
2 94 Ø12MM @125MMC/C ISSUED FOR APPROVAL. NPN HTM DGC
1850 408 1BS4
1 00
0 500 71
EL(+)7200 93 REV. DATE ISSUED TO PRD CHK APD

92 DESCRIPTION OF REVISIONS
3 20 7 70 91 PROJECT:
69 Ø16MM @200MMC/C
90
1BS2 Ø8MM @200MMC/C CITY LIBRARY
68

2100
89
67 88
0
66 120 87
CLIENT: TUMKUR SMART CITY LTD.
1650

65 175 FOR APPROVAL


00 0 Ø8MM @200MMC/C 86
1 64
63 500 85 DWG. TITLE:
OUTSIDE STAIRCASE DETAIL
0 175 84
5 0 62 83 Ø12MM @125MMC/C
EL(+)8850
61 Ø16MM @200MMC/C EL(+)5550
DWG.NO. TSC-CLP-101-STR-DRG-432
REV NO. SCALE:
SECTION G REFER

- C5A 1:25 N SITE PLAN


SECTION C FIRTS FLOOR
- CROSS SECTION OF STAIRCASE
DATE: 28-12-2018
INTERMEDIATE FLOOR
CROSS SECTION OF STAIRCASE
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT

3' 2 ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF


THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL

N TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION


AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
140 139 138 137 136 135 134 133 132 131130 129 128 127 126
H 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400

- 2.2. GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO


IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO BEAM REINFORCEMENT SHALL BE 25
OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

112 113 114 115 116 117 118 119 120 121122 123 124 125
TSCL APPROVAL
G ASSISTANT/JUNIOR ENGINEER
-

P ASSISTANT EXECUTIVE ENGINEER

PART PLAN AT SECOND FLOOR


EXECUTIVE ENGINEER

500 120 EL(+)17550


500 120 EL(+)21900
140 0 169 0 SUPERINTENDING ENGINEER
139 168
138 167
137 166
136
420 165
420
9 9
135 164 ARCHITECT
134 163
133 162

2250

2250
STRUCTURAL EXPERT
132 161
Ø8MM @200MMC/C 131 120 Ø8MM @200MMC/C 160 120
130 159 INFRASTRUCTURE EXPERT
175 0 0
129 175 158
128 500 157 500 TEAM LEADER
127 156
Ø16MM @200MMC/C 126 1350 Ø16MM @125MMC/C 155 1350
EL(+)15300 EL(+)19650
SECTION K SECTION M
- Ø12MM @125MMC/C
- Ø16MM @125MMC/C
1BS5 1BS6
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

500 500
C4A 20/11/2018 NPN HTM DGC
0 1350 0 1350 ISSUED FOR APPROVAL.

120 125
EL(+)15300
120 154
EL(+)19650 REV. DATE ISSUED TO PRD CHK APD

124 153 DESCRIPTION OF REVISIONS


2 123 Ø16MM @125MMC/C 2 152 Ø12MM @125MMC/C PROJECT:
408 122
1BS5 408 151
1BS6
CITY LIBRARY
121 150
120 149 CLIENT: TUMKUR SMART CITY LTD.
119 Ø8MM @200MMC/C
148 Ø8MM @200MMC/C FOR APPROVAL
2100

2100
118 147
DWG. TITLE:
0 117 0 146
120 116 120 145
OUTSIDE STAIRCASE DETAIL
115 SECTION J 144 TSC-CLP-101-STR-DRG-433
500
113
114
175
- 500
142
143
175 DWG.NO.

REV NO. SCALE:


REFER

111
112 Ø16MM @200MMC/C
EL(+)13200 141 Ø16MM @200MMC/C

SECTION L
EL(+)17550 C5A 1:25 N SITE PLAN

SECOND FLOOR - DATE: 28-12-2018

CROSS SECTION OF STAIRCASE THIRD FLOOR


CROSS SECTION OF STAIRCASE
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
A B C D E F G H J K L M N P 1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
58250
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
1 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
4605

2 ASSISTANT EXECUTIVE ENGINEER


2395

3
EXECUTIVE ENGINEER
3350
20005

4 SUPERINTENDING ENGINEER
2650

S2
5 ARCHITECT
2105

STRUCTURAL EXPERT
6
INFRASTRUCTURE EXPERT
4900

TEAM LEADER

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
GROUND FLOOR SLAB LAYOUT GROUND FLOOR SLAB LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-434
REV NO. SCALE:
REFER

SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

DATE: 28-12-2018
S3 Ø10mm@200mmc/c
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

A B C D E F G H J K L M N P STRUCTURAL NOTES :
58250 2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
1 THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
4605

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER

2
2395

ASSISTANT EXECUTIVE ENGINEER

3
3350

EXECUTIVE ENGINEER
20005

4
2650

SUPERINTENDING ENGINEER
S2
5
2105

ARCHITECT
6
STRUCTURAL EXPERT
4900

INFRASTRUCTURE EXPERT

TEAM LEADER

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

INTERMEDIATE FLOOR WAFFLE BEAM AND SLAB LAYOUT PROJECT:


DESCRIPTION OF REVISIONS

CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
INTERMEDIATE FLOOR WAFFLE BEAM AND
SLAB LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-435
REV NO. SCALE:
REFER

SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

DATE: 28-12-2018
S3 Ø10mm@200mmc/c
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
B CONFORMING TO IS 1786, 2008.
A C D E F G H J K L M N P
2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
58250
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
1
TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
4605

ASSISTANT EXECUTIVE ENGINEER

2
2395

EXECUTIVE ENGINEER
3
3350
20005

SUPERINTENDING ENGINEER
4
2650

2BW8 S2
ARCHITECT
5
2105

STRUCTURAL EXPERT

6
INFRASTRUCTURE EXPERT

TEAM LEADER
4900

7
C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
FIRST FLOOR WAFFLE BEAM AND SLAB LAYOUT PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
FIRST FLOOR WAFFLE BEAM AND SLAB LAYOUT

DWG.NO. TSC-CLP-101-STR-DRG-436
REV NO. SCALE:
REFER

SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

DATE: 28-12-2018
S3 Ø10mm@200mmc/c
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
B IS 456, 2010.
A C D E F G H J K L M N P
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
58250
2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
1 SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

TSCL APPROVAL
4605

ASSISTANT/JUNIOR ENGINEER

2 ASSISTANT EXECUTIVE ENGINEER


2395

3
EXECUTIVE ENGINEER
3350
20005

4 SUPERINTENDING ENGINEER
2650

2BW8 S2
5
ARCHITECT
2105

6 STRUCTURAL EXPERT

INFRASTRUCTURE EXPERT
4900

TEAM LEADER

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
SECOND FLOOR WAFFLE BEAM AND SLAB LAYOUT PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
SECOND FLOOR WAFFLE BEAM AND
SLAB LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-437
REV NO. SCALE:
REFER

SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

DATE: 28-12-2018
S3 Ø10mm@200mmc/c
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
A B C D E F G H J K L M N P 2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.

58250 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL


CONFORMING TO IS 1786, 2008.
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
1 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
4605

ASSISTANT EXECUTIVE ENGINEER


2
3BW4
4BW4
2395

3
EXECUTIVE ENGINEER
3350
20005

4 SUPERINTENDING ENGINEER

4BW7
2650

S2
5 ARCHITECT
2105

STRUCTURAL EXPERT
6
INFRASTRUCTURE EXPERT
4900

TEAM LEADER

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
THIRD FLOOR WAFFLE BEAM AND SLAB LAYOUT PROJECT:
CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
THIRD FLOOR WAFFLE BEAM AND
SLAB LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-438
REV NO. SCALE:
REFER

SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

DATE: 28-12-2018
S3 Ø10mm@200mmc/c
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
A B C D E F G H J K L M N P 2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
IS 456, 2010.
58250 2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
CONFORMING TO IS 1786, 2008.
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
1 2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)

TSCL APPROVAL
4605

ASSISTANT/JUNIOR ENGINEER

2 ASSISTANT EXECUTIVE ENGINEER


3BW4
4BW4
2395

3
EXECUTIVE ENGINEER
3350
20005

4 SUPERINTENDING ENGINEER

4BW7
2650

S2
5
ARCHITECT
2105

STRUCTURAL EXPERT
6

INFRASTRUCTURE EXPERT
4900

TEAM LEADER

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

TERRACE FLOOR WAFFLE BEAM AND SLAB LAYOUT PROJECT:


DESCRIPTION OF REVISIONS

CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
TERRACE FLOOR WAFFLE BEAM AND
SLAB LAYOUT
DWG.NO. TSC-CLP-101-STR-DRG-439
REV NO. SCALE:
REFER

SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

DATE: 28-12-2018
S3 Ø10mm@200mmc/c
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays
NOTES :
1.1 ALL DIMENSIONS & LEVELS ARE IN MM. (U.N.O). DO NOT
SCALE DWG. FOLLOW WRITTEN DIMENSIONS ONLY.

1.2 REFER THIS DWG. ALONG WITH THE OTHER RELEVANT


ARCH., STRUCTURAL, & SERVICES DWGS, BEFORE START OF
THE WORK RELATED TO THIS DWG.

1.3 THE CONTRACTOR(S) SHALL VERIFY ALL DIMENSIONS, &


LEVELS ON SITE BEFORE COMMENCING ANY WORK OR
PREPARATION OF SHOP DWGS.

1.4 IF ANY ERRORS/ AMBIGUITIES ARE NOTICED, THE SAME


SHALL BE RESOLVED WITH THE PMC BEFORE EXECUTION OF
THE SAID WORK.
1.5 ALL RCC/STRUCTURAL WORK SHALL BE EXECUTED - FULL
TIME - STRICTLY UNDER COMPETENT TECHNICAL SUPERVISION
AT SITE..
1.6 SITE CO-ORDINATION WITH THE SERVICES SUCH AS
PLUMBING, FIRE FIGHTING, HVAC, ELECTRICAL ETC. AND
OTHER SPECIALIZED VENDOR'S IS THE SOLE RESPONSIBILITY
OF THE MAIN CONTRACTOR.

STRUCTURAL NOTES :
2.1 FOR GENRAL NOTES REFER DRG
NO.TSC-CLP-101-STR-DRG-400
2.2 GRADE OF CONCRETE MIX SHALL BE M40 CONFORMING TO
A B C D E F G H J K L M N P IS 456, 2010.
2.3 REINFORCEMENT SHALL BE HIGH STRENGTH Fe 500 STEEL
58250 CONFORMING TO IS 1786, 2008.
2.4 CLEAR COVER TO PLINTH BEAM REINFORCEMENT SHALL BE
6000 6000 3675 2375 5950 5850 6150 6000 6350 3100 2550 950 3300 25 OR DIAMETER OF THE BAR WHICHEVER IS HIGHER.
2.5 TOP REINFORCEMENT SHALL BE LAPPED IN THE MIDDLE
THIRD OF THE SPAN
2.6 BOTTOM REINFORCEMENT SHALL BE LAPPED NEAR
SUPPORT
2.7 MINIMUM LAP LENGTH SHALL BE 36d(FOR M40 GARDE)
1
TSCL APPROVAL
ASSISTANT/JUNIOR ENGINEER
4605

ASSISTANT EXECUTIVE ENGINEER


2
2395

3 EXECUTIVE ENGINEER

S3
3350
20005

SUPERINTENDING ENGINEER
4
2650

5 ARCHITECT
2105

STRUCTURAL EXPERT

6
INFRASTRUCTURE EXPERT
4900

TEAM LEADER

S3

C5A 28/12/2018 ISSUED FOR APPROVAL. NPN HTM DGC

C4A 22/11/2018 ISSUED FOR APPROVAL. NPN HTM DGC

REV. DATE ISSUED TO PRD CHK APD

DESCRIPTION OF REVISIONS
PROJECT:
MUMTY FLOOR SLAB LAYOUT CITY LIBRARY

CLIENT: TUMKUR SMART CITY LTD.


FOR APPROVAL
DWG. TITLE:
MUMTY FLOOR SLAB DETAIL
DWG.NO. TSC-CLP-101-STR-DRG-440
REV NO. SCALE:
REFER

SLABREINFORCEMENTDETAILS C5A 1:100 N SITE PLAN

DATE: 28-12-2018
S3 Ø10mm@200mmc/c
BothWays
TORSIONCORNER Ø8mm@200mmc/c
BothWays