CACP Configuration and Control Program
for Multiblock Programming Application:
ACS800-MD SUPPLY-SECTIONS
with Fieldbus control
by PROFIBUS DP
User's Manual
Overview This chapter describes the purpose, contents and the intended audience of
this manual. It also explains the terms used in this manual and lists related
publications.
5. DI5 EM_STOP_PB_PRESSED = 0
Î Warning AP “EmStpPB+R” (CDP312)
this signal contains: Emergency Stop Push Button is pressed and / or Emergency Stop Relay
is OFF see also Ext2_DI3
6. DI6 Q30+Q31_DC-DISCONNECTOR_OK = 1
Î Warning AP “Q30+31FLT” (CDP312)
7. DIIL S11_IN_LOCAL_ON = 1
Î Warning AP “S11_OFF” (CDP312)
8. EXT1_DI1_FUNDAMENTAL_INTERLOCK, Interlock = 0
Î Warning AP “Fund_IL” (CDP312)
this signal must be used as HW interlock, respective to switch OFF the supply-unit from
REMOTE
9. EXT1_DI2 Q1.1-POS_NET_ON =1
Î Fault AP “Q1.1.FLT” (CDP312)
this fault-message appears, if switch-on or switch-off Q1.1 doesn’t finish within an adjustable
time, see chapter 6.
12. EXT2_DI2_FUSES_SWITCHES_OK = 1
Î Warning AP “FuseTripd” (CDP312)
Signal “OLPT” is sent to OCS by SWS-bit00
this INPUT collects aux. contacts of fuse-switches (OLPT)
13. EXT2_DI3_EMERGENCY_STOP_PB_OR_RELAY_OFF = 0
Î Warning AP “EmStpPB+R” (CDP312)
this signal contains: Emergency Stop Push Button is pressed and / or Emergency Stop Relay
is OFF see also DI5
14. EXT3_DI1_F1.1_NET_VOLT_PRESENT = 1
this signal shows that the net voltage is present at Q1.1 input-terminals.
(see single-line diagram)
15. EXT3_DI2_F1.2_EMERG_VOLT_PRESENT = 1
this signal shows that the emergency voltage is present at Q1.2 input-terminals.
(see single-line diagram)
16. EXT3_DI3_F1.3_INPUT_VOLT_PRESENT = 1
this signal shows that the voltage in front off Q1 is present at Q1 input-terminals.
(see single-line diagram)
Digital Outputs
1. DO1_REM_ON_RELEASE = 1
2. DO2_REM_ON_PULSE = 0_1_0
3. DO3_REM_RESET_PULSE = 0_1_0
4. EXT1_DO1_Q1.1_ON_CMD = 1
5. EXT1_DO2_Q1.1_OFF_CMD = 1
6. EXT2_DO1_Q1.2_ON_CMD = 1
7. EXT2_DO2_Q1.2_OFF_CMD = 1
8. EXT3_DO1_LED_FAULT = 1
9. EXT3_DO2_LED_READY = 1
Profibus DP Control signals from OCS to Drive by PROFIBUS for each supply-unit:
ControlWord CWS as per description in Serial Interface (Profibus)
Overview ACS800 Multi Drive Systems 3BHS267977.
Before You The purpose of this manual is to provide you with the necessary
Multiblock Programming Application: ACS800-MD SUPPLY-SECTIONS
1-3 with Fieldbus control by PROFIBUS DP
Chapter 1 - Introduction and Related Documents
Start information to load and set the parameters into the supply-unit.
This to provide the function of the ACS800-MD SUPPLY-SECTIONS with
Fieldbus control by PROFIBUS DP
Read through this manual before beginning with start-up the supply-unit.
The installation and commissioning instructions given in the Hardware
Manual (the appropriate manual is delivered with the unit) must also be
read before proceeding.
Study carefully the Safety Instructions before attempting any work on, or
with, the unit.
Supply-section:
1 0 3 1 1 1 (1)
Solution
Table 1: Required Hardware depending on Options (Don't forget always CACP-Software needed on RMIO board)
RMIO-01/02 - board
Terminal block X20
In this Application program, 1 VREF- Ref. voltage –10 VDC
max 10mA
Analogue input AI2 and AI3 are used 2 GND
section. The scaling Parameters are 1 VREF+ Ref. voltage +10 VDC
max 10mA
indicated in the table beside. 2 GND
3 AI 1 + AI 1 NOT USED
Analogue output AO1and AO2 are not 4 AI 1 - -10...0…+10V Scaling Par: 13.01 + 13.02
used. 5 AI 2 + AI 2 DSU-Phase-Current u1.1
Scaling Par: 13.03 + 13.04
The digital inputs have the function as 6 AI 2 - 0..1mA = 0..1000 = 0..100%
AI 3 DSU-Phase-Current u1.2
mentioned in the table beside. 7 AI 3 +
Scaling Par: 13.05 + 13.06
8 AI 3 - 0..1mA = 0..1000 = 0..100%
Relay outputs have the function as 9 AO 1 + AO 1 NOT USED
seen in table beside. 10 AO 1 - 0…20mA Scaling Par: 15.01 + 15.02
11 AO 2 + AO 2 NOT USED
External Power Supply for RMIO 12 AO 2 - 0…20mA Scaling Par: 15.03 + 15.04
board is needed if e.g. Profibus Terminalblock X22
module still has to be powered when 1 DI 1 DSU Fault (ALARM only)
the AC-power to the ACS800 is 2 DI 2 DSU Running
switched off 3 DI 3 DSU Overtemp (ALARM only)
ÎCommunication is still on. 4 DI 4 EARTH_FAULT (ALARM only)
1 RO 1 RELAY OUPUT 1
DSU-
2 RO 1
RemoteOnRelease
3 RO 1 Set by Drive-AP
Terminal block X26
1 RO 2 RELAY OUPUT 2
DSU-
2 RO 2
RemoteOnPulse
3 RO 2 Set by Drive-AP
Terminal block X27
1 RO 3
RELAY OUPUT 3
2 RO 3 DSU-RemoteReset
Set by Drive-AP
3 RO 3
RDIO-01 - board
Terminal block
In this Application program, X11
1 DI1A FUNDAMENTAL_INTERLOCK
2 DI1B Interlocked = 0
Terminal block
Digital inputs have the function as mentioned in X12
DI1 is calvanically isolated from DI2+DI3
Terminal block
X21
1 R1NC
RELAY OUPUT 1
HW-switches settings: AIMA-Slot1 2 R1CM
Q1.1 – On Cmd = 1
Node ID selector (S1): 5 3 R1NO
RDIO-01 - board
Terminal block
In this Application program, X11
1 DI1A
Q1 – MCB – Off = 1
2 DI1B
Digital inputs have the function as mentioned in Terminal block
DI1 is calvanically isolated from DI2+DI3
X12
the table beside. 1 DI2A FUSES_ON = 1
2 DI2B (SWS-OLPT)
Relay outputs have the function as seen in 3 DI3A EMERGENCY_STOP_RELAY_OFF = 1
table beside. 4 DI3B (connected only in supply-unit which has Emerg-Stop-Relay)
Terminal block
X21
1 R1NC
HW-switches settings: AIMA-Slot2 2 R1CM
RELAY OUPUT 1
Q1.2 – On Cmd = 1
Node ID selector (S1): 6 3 R1NO
Configuration switch (S2): 1,2,3 = ON Terminal block
4 = OFF X22
1 R2NC
RELAY OUPUT 2
Technical data see RDIO-01 Digital I/O 2 R2CM Q1.2 – Off Cmd = 1
3 R2NO
Extension User’s Manual (3AFE64485733,
[English]).
Figure 2.2 ACS800-MD SUPPLY-SECTION:
nd
2 RDIO-01 I/O connections
RDIO-01 - board
Terminal block
In this Application program, X11
1 DI1A
F1.1 – NetsupplyVoltagePresent = 1
2 DI1B
Digital inputs have the function as mentioned in Terminal block
DI1 is calvanically isolated from DI2+DI3
X12
the table beside. 1 DI2A
F1.2 – EmergencyVoltagePresent = 1
2 DI2B
Relay outputs have the function as seen in 3 DI3A
table beside. 4 DI3B
F1.3 – InputVoltagePresent = 1
Terminal block
X21
1 R1NC
HW-switches settings: AIMA-Slot3 2 R1CM
RELAY OUPUT 1
LED Fault = 1
Node ID selector (S1): 7 3 R1NO
Configuration switch (S2): 1,2,3 = ON Terminal block
4 = OFF X22
Hardware connections
The Hardware connections in detail are depending on the chosen Variation.
And can be seen in the project specific Hardware drawings.
No special features
For detailed procedure see Chapter 5 Loading Drive Application by DriveAP 2.x.
4. Set the parameters for communication to the overriding system according to site needs.
See Chapter 7 Remote control (Profibus DP).
2. Make a New Backup Package of the already commissioned data’s with sequence:
FileÎSystem SoftwareÎNewÎBackup Package
4. Select the desired Drive (with single drive connected only one possible), then press
Backup Button, the backup takes about 3 minutes.
3 min
Give the Backup Package the drives name in the next window, then press the Save
Button
6. After few seconds, download finished then answer following question with yes
CDP312 Panel
Recommended ACS800-MD SUPPLY-SECTIONS
actual values
Modifications by Drive-Ap2.x
ACS800-MD SUPPLY-SECTIONS
(or DriveWindow)
In Application program (potential adjustments during commissioning)
BLOCK_1 AI2_OFFSET_CORRECTION
10ms 1/5 Set ADD2-input to negative value of PAR - [5.02], if DSU is switched OFF
ADD-BLOCK-Input: ADD2 See also Drive-AP 10ms 1/5
BLOCK_2 AI3_OFFSET_CORRECTION
10ms 1/5 Set ADD2-input to negative value of PAR - [5.03], if DSU is switched OFF
ADD-BLOCK-Input: ADD2 See also Drive-AP 10ms 1/5
BLOCK_7 WARNING_LEVEL_ASYMMETRIC_CURR (Alarm only signal)
10ms 1/5 Scaling 100 = 10.0%
Compare-BLOCK-Input: I2 Default setting C100 = 10%
BLOCK_11 WARNING_LEVEL_OVERLOAD_CURR (Alarm only signal)
10ms 1/5 Scaling 1000 = 100%
Compare-BLOCK-Input: I2 Default setting C999 = 99.9%
DC_REFERENCE_VOLTAGE_TRICKY_DISPLAY
BLOCK_21 (Indication in top right REF raw on CDP312, used to have a reasonable value on CDP312,
10ms 5/5 set the value to ACT DC-voltage shown in INU’s CDP312)
WR-I_BLOCK-Input: IN Scaling 100 = 100V
Default setting C1097 = 1097V
BLOCK_1 + BLOCK_2 TD defines the time between Q1.1-off-cmd and Q1.2-on-cmd,
100ms 2/5 respective the time between Q1.2-off-cmd and Q1.1-on-cmd.
TOFF-BLOCK-Input: TD Default setting = 1000ms for both.
BLOCK_33
TD defines the time for the “DSU-RemoteOnPulse” by DO2 (RMIO)
100ms 4/5
Default setting = 2000ms
TOFF-BLOCK-Input: TD
TD defines the maximal time for opening/closing Q1.1,
BLOCK_14 + BLOCK_15
respective the maximal time for opening/closing Q1.2.
500ms 5/5
Default setting = 5000ms = 5sec for both.
TOFF-BLOCK-Input: TD
After time elapsed: Fault message to OCS is generated.
BLOCK_16 TD defines the time-delay for warning message on CDP312-panel:
500ms 5/5 “NoSuppVlt” no supply voltage present not from net- and not from emergency-supply.
TOFF-BLOCK-Input: TD Default setting = 3000ms = 3sec
Following parameters in group 53 are application specific, for the rest is still valid the basic
Firmware Manual:
ACS 600 / ACS800 Multi Block Programming Application 7.1x 3AFE64773984.
Group name:
53 USER PARAMETERS in ACS800-MD SUPPLY-SECTIONS
This parameter group consists of Application specific parameters.
NUMERIC 1
01
Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 60 Integer scaling: 1 = 1s
NUMERIC 2
02 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
NUMERIC 3
03 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 1 Integer scaling:
NUMERIC 4
04 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
NUMERIC 5
05 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
NUMERIC 6
06 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
NUMERIC 7
07 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
NUMERIC 8
08 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
NUMERIC 9
09 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
NUMERIC 10
10 Description: User's numeric parameter for Multi Block Programming purposes used as:
Index:
Not used
unit: type: l Min: -8388608 Max: 8388607 Def: 0 Integer scaling:
Group name:
53 USER PARAMETERS in ACS800-MD SUPPLY-SECTIONS
STRING 1
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
11 Drive-AP AC-DISCONNECTOR Q1.1 SWITCHING FAULT, DOES NOT SWITCH TO CORRECT
Index: 500ms (5/5) POSITION WITHIN DEFINED TIME SETTING (SEE TABLE 6 Q1.1 Fault Delay)
Î FAULT AP “Q1.1.FLT”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 1 Integer scaling: -
STRING 2
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
12 Drive-AP AC-DISCONNECTOR Q1.2 SWITCHING FAULT, DOES NOT SWITCH TO CORRECT
Index: 500ms (5/5) POSITION WITHIN DEFINED TIME SETTING (SEE TABLE 6 Q1.2 Fault Delay)
Î FAULT AP “Q1.2.FLT”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 2 Integer scaling: -
STRING 3
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
13 Drive-AP NO POWER SUPPLY PRESENT AT AC-DISCONNECTORS INPUTS, BOTH NET-SUPPLY
Index: 500ms (5/5) AND EMERGENCY SUPPLY (DIESEL) ARE OFF
Î WARNING AP “NoSuppVlt”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 3 Integer scaling: -
STRING 4
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
14 Drive-AP DSU IS TRIPPED BY FAULT, DETAILED FAULT MESSAGE CAN BE SEEN FROM DSU-
Index: 100ms (5/5) DSSB-BOARD EXPLANATIONS ACCORDING DSU-MANUAL
Î WARNING AP “DSU-FLT”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 4 Integer scaling: -
STRING 5
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
15 Drive-AP EMERGENCY_STOP_PUSH-BUTTON_PRESSED DI5=0 and / or
Index: 100ms (5/5) EMERGENCY_STOP_RELAY_OFF EXT2DI3=1 (ALARM=0)
Î WARNING AP “EmStpPB+R”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 5 Integer scaling: -
STRING 6
16 Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
Index: Drive-AP DC-DISCONNECTOR SWITCHES EITHER Q30 OR Q31 IN WRONG POSITION
100ms (5/5) Î WARNING AP “Q30+31FLT”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 6 Integer scaling: -
STRING 7
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
17 Drive-AP S11 IN DSU-CABINET-DOOR HAS TO BE IN POSITION 1, TO ENABLE REMOTE
Index: 100ms (5/5) OPERATION OF THE SUPPLY UNIT
Î WARNING AP “S11-OFF=0”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 7 Integer scaling: -
STRING 8
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
18 Drive-AP NO INPUT VOLTAGE AT MCB Q1 PRESENT, MESSAGE APPEARS DURING CHANGE-
Index: 100ms (5/5) OVER FROM (Q1.1) NET- TO (Q1.2) EMERG- SUPPLY OR IN REVERSE ORDER.
Î WARNING AP “InpVltOFF”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 8 Integer scaling: -
STRING 9
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
19 Drive-AP FUNDAMENTAL INTERLOCK INPUT EXT1 DI1 (ALARM=0), THIS SIGNAL IS BY-PASSED
Index: 20ms (5/5) IN CASE OF CDP312 PANEL IS SWITCHED TO LOCAL-MODE (LOC).
Î WARNING AP “Fund-IL”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 9 Integer scaling: -
Group name:
53 USER PARAMETERS in ACS800-MD SUPPLY-SECTIONS
STRING 10
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
20 Drive-AP THIS ALARM-ONLY SIGNAL APPEARS IF THE CURRENTS FROM THE DIODE-BRIDGES
Index: 20ms (5/5) ARE HAVING A DIFFERENCE > 10% OF NOMINAL CURRENT.
Î WARNING AP “AsymmCURR”
unit: type: S Min: 0 chars Max: 9 chars Def: Message10 Integer scaling: -
STRING 11
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
Drive-AP FIELDBUS COMMUNICATION SUPERVISION.
21 20ms (5/5) Message is generated only in REM control mode for information at CDP312 Panel.
Index: To switch on DSU without Fieldbus-communication, select LOC-mode at CDP312 Panel, the
message FB_ComOFF disappears and then switch on the DSU by impulse of S11 switch at
DSU-cabinets door.
Î WARNING AP “FB_ComOFF”
unit: type: S Min: 0 chars Max: 9 chars Def: Message11 Integer scaling: -
STRING 12
22 Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
Index: Drive-AP EARTH FAULT ALARM INPUT DI4 (ALARM=1)
100ms (5/5) Î WARNING AP “Earth-FLT”
unit: type: S Min: 0 chars Max: 9 chars Def: Message12 Integer scaling: -
STRING 13
23 Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
Index: Drive-AP DSU OVERTEMPERATURE WARNING OCCURED, (ALARM only)
100ms (5/5) Î WARNING AP “DsuOvrTmp”
unit: type: S Min: 0 chars Max: 9 chars Def: Message 13 Integer scaling: -
STRING 14
Description: User's ASCII string type of parameter for the alarm or fault text definition of EVENT block.
24 Drive-AP THIS ALARM-ONLY SIGNAL APPEARS IF THE CURRENT OF THE DIODE-SUPPLY-UNIT
Index: 20ms (5/5) IS > 99.9% OF NOMINAL CURRENT.
Î WARNING AP “OverlCURR”
unit: type: S Min: 0 chars Max: 9 chars Def: Message14 Integer scaling: -