Feeder Protection and Control Ref615 Ansi: Product Guide
Feeder Protection and Control Ref615 Ansi: Product Guide
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB Inc. ABB
Inc. assumes no responsibility for any errors that may appear in this document.
Copyright © 2008-2011 ABB
All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 3
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
4 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 5
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Load 50
PQ-15
Prof. BF-1
50N
51N-1 50N-1 50N-2 50N-3 BF-1
1
REF
(Low Z)
SEF2 HIZ2
6 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Bus A
3
3 3 (1)
(1) (2)
50
49F-1 51P-1 50P-1 50P-2 46-1 37-1 PQ-12 50
BF-1 49F-1 51P-1 50P-1 50P-2 46-1 37-1 PQ-12
BF-1
52
51G 50G-1
50N
(1)
51N-1 50N-1 50N-2 51G 50G-1
BF-1 50N
51N-1 50N-1 50N-2
BF-1
Δ
50N
51N-2 50N-4 50N-5
AFD-
1
1
AFD-
2
1
AFD-
3
1
BF-2
Y 51N-2 50N-4 50N-5
50N
52 52 AFD- AFD- AFD- BF-2
(1) (2) 1
1
2
1
3
1
52
49F-2 51P-2 50P-4 50P-5 46-2 37-2 PQ-22
50 (2)
BF-2
50
49F-2 51P-2 50P-4 50P-5 46-2 37-2 PQ-22
BF-2
(2)
1
Available with Arc Flash Detection option 3
2
Available with Power Quality option
1
Available with Arc Flash Detection option
2
Available with Power Quality option
a) b)
Figure 2. Protection functions overview for standard configuration B applied to a) main feeder protection and b) bus and transformer backup
protection
Υ or Δ
3
REF615 V4.0 ANSI
Load
51P-1 50P-1 50P-2 50P-3 46-1
3 Prof.
50N
51N-1 50N-1 50N-2 50N-3 BF-1
27-26 81-26
1
67/ 67/ 67/ REF 81LSH
32N-16 59-16
51N6 50N-16 50N-26 (Low Z) -26
50G 81LSH
51G1 50G-11 50G-21 50G-31 59-26
52 BF-1
1
-26
ABB 7
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Υ or Δ Δ
3
REF615 V4.0 ANSI
Load
51P-1 50P-1 50P-2 50P-3 46-1 59G
3 Prof.
50N
51N-1 50N-1 50N-2 50N-3 BF-1
27-2 81-2
1
67/ 67/ 67/ REF 81LSH
32N-1 59-1
51N 50N-1 50N-2 (Low Z) -1
50G 81LSH
51G1 50G-11 50G-21 50G-31 59-2
52 BF-1
1
-2
Bus A Υ
or (1)
Υ or Δ
REF615 V4.0 ANSI (1) Δ REF615 V4.0 ANSI
3
3
24-1 27-1 47-1 59-1 60-1 3 24-1 27-1 47-1 59-1 60-1
3 59N- 3 (1)
(1) 1 (2) 59N-1
50
49F-1 51P-1 50P-1 50P-2 46-1 37-1 PQ-12 32P-1 50
BF-1 49F-1 51P-1 50P-1 50P-2 46-1 37-1 PQ-12 32P-1
BF-1
52
51G 50G-1
50N
(1)
51N-1 50N-1 50N-2 32N-1 51G 50G-1
BF-1 50N
51N-1 50N-1 50N-2 32N-1
BF-1
Δ
50N
51N-2 50N-4 50N-5 32N-2
AFD-
1
1
AFD-
2
1
AFD-
3
1
BF-2
Y 51N-2 50N-4 50N-5 32N-2
50N
52 52 AFD- AFD- AFD- BF-2
(1) (2) 1
1
2
1
3
1
52
49F-2 51P-2 50P-4 50P-5 46-2 37-2 PQ-22 32P-2
50 (2)
BF-2
59N- 50
49F-2 51P-2 50P-4 50P-5 46-2 37-2 PQ-22 32P-2
2 BF-2
27-2 47-2 59-2 60-2 59N-2
(2)
(2)
27-2 47-2 59-2 60-2
1
Available with Arc Flash Detection option 3
2 3
Available with Power Quality option
1
Available with Arc Flash Detection option
2
3 Available with Power Quality option
Υ
or (2)
Δ
a) b)
Figure 5. Protection functions overview for standard configuration E applied to a) main feeder protection and b) bus and transformer backup
protection
8 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
The REF615 ANSI IED offers users maximum E: Non-directional phase and ground overcurrent,
flexibility of application with five standard voltage and power directional protection, control and
configurations A – E. Each configuration allows users power system metering for two breakers
convenient ordering selections to perfectly match
available analog inputs (AI) and binary inputs and In addition to protection, control and metering,
outputs (I/O) required in their distribution feeder each configuration includes many features standard
protection and control designs. All configurations for comprehensive utility and industrial distribution
include the customer programmable phase and ground feeder schemes including graphical user-programmable
CT and, where applicable, VT secondary nominal logic, digital fault (waveform), sequence of events
settings plus wide protection setting ranges that (SOE) and fault recording, monitoring, load profile
increase the REF615 flexibility of application and and advanced Ethernet communications supporting
eliminate need for multiple different feeder relay order IEC61850-8 with GOOSE (peer-to-peer) messaging
codes. Here are the descriptions of each of the five and DNP3.0 Level 2+ and Modbus protocols over
configurations available: TCP/IP. Valuable options include reclosing, serial
communications supporting DNP3.0 Level 2+
A: Non-directional overcurrent protection, control and Modbus protocols, Power Quality, Spanish or
and metering for single breaker Portuguese menu/WebHMI language, Arc Flash
Detection safety feature and ABB’s unique feeder
B: Non-directional overcurrent protection, control Cable Fault Detection (CFD).
and metering for two breakers
Costly bus differential protection and bus transfer
C: Directional current-based, voltage and frequency control schemes due to dedicated CTs, I/O wiring
protection, control and power system metering for one and special communication cables are now affordable
breaker with the 615 series relays’ standard Ethernet
communications. Using peer-to-peer communications
via IEC-61850’s GOOSE messaging affords
integration of high-speed monitoring and control
applications.
ABB 9
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
REF
615
52
REF
615
52
REF REF
615 615
52 52
F1 Fn
IEC 61850
a) b)
REF
3 615
HS
52
1
Δ
REF
615
Y
3
1
LS
52
52
REF
615
52
REF REF
615 615
52 52 52 52
F1 F2 Fn-1 Fn
IEC 61850
REF
615
52
REF
615
52
REF REF
615 615
52 52
F1 Fn
IEC 61850
REF
615
52
REF
615
52
REF REF
615 615
52 52
DG DG
F1 Fn
IEC 61850
52
REF
615
52
REF REF
615 615
52 52 52 52
F1 F2 Fn-1 Fn
IEC 61850
REF REF
615 615
52 52
REF REF
615 615
52 52
T T
52 52 52 52
DG DG DG DG
F1 Fn F1 Fn
IEC 61850 IEC 61850
Figure 12. Peer-to-peer ‘open (cold) bus transfer’ control and high-speed bus overcurrent protection using IEC61850 GOOSE messaging
REF REF
615 615
52 52
REF REF
615 615
52 52
T T
52 52 52 52
DG DG DG DG
F1 Fn F1 Fn
IEC 61850 IEC 61850
Figure 13. Peer-to-peer ‘closed (hot) bus transfer’ control and high-speed bus overcurrent protection using IEC61850 GOOSE messaging
ABB 13
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
14 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB
MicroSCADA
IEC 60870-5-104
COM600 COM600
Web HMI Web HMI
COM600 COM600
Binary signal
transfer
Fibre optic LD
REF615 RET615 RED615 communication RED615 RET615 REF615
Figure 14. Utility distribution network example using 615 series IEDs, Station Automation COM600 and MicroSCADA Pro
ABB
System 800xA
OPC
COM600 COM600
Web HMI Web HMI
COM600 COM600
Binary signal
transfer
Fibre optic LD
REF615 RET615 REM615 RED615 communication RED615 REM615 RET615 REF615
Figure 15. Industrial distribution network example using 615 series IEDs, Station Automation COM600 and System 800xA
ABB 15
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
16 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
13. Self-diagnostics
ABB 17
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
18 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
To protect the IED from unauthorized access and to • Two NO outputs with trip circuit monitoring
maintain information integrity, the IED is provided • One Form C output
with a four-level, role-based authentication system with • One Form C self-check alarm output
administrator programmable individual passwords • Additional binary inputs and outputs optional
for the viewer, operator, engineer and administrator • High-speed outputs (1 ms operate time) optional
level. The access control applies to the frontpanel user
interface, the web-browser based user interface and the
PCM600 tool.
ABB 19
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
22. Communications unrelated data traffic. The Ethernet ring solution supports
the connection of up to 30 ABB 615 series relays. If more
than 30 IEDs are to be connected, it is recommended that
The relay (IED) supports a range of communication proto- the network is split into several rings with no more than
cols including IEC 61850, Modbus® and DNP3.0 Level 2. 30 IEDs per ring. The self-healing Ethernet ring solution
Operational information and controls are available through avoids single point of failure concerns and improves the
these protocols. Certain communication functionality, e.g., reliability of the communication. The solution can be
horizontal communication between relays, is only enabled applied for the Ethernet-based IEC 61850, Modbus and
by the IEC 61850 communication protocol. DNP3.0 Level 2 protocols.
The IEC 61850 communication implementation sup- All communication connectors, except for the front port
ports all monitoring and control functions. Additionally, connector, are placed on integrated optional communica-
parameter settings, disturbance recordings and fault records tion modules. The IED can be connected to Ethernet-based
can be accessed using the IEC 61850 protocol. Disturbance communication systems via the RJ-45 connector (100Base-
recordings are available to any Ethernet-based application TX) or the fiber-optic LC connector (100Base-FX). If
in the standard COMTRADE file format. The IED sup- connection to a serial bus is required, the 10-pin RS-485
ports simultaneous event reporting to five different clients screw-terminal or the fiber-optic ST connector can be used.
on the communication network bus.
Modbus implementation supports RTU, ASCII and TCP
The IED can send binary signals to other IEDs (so called modes. Besides standard Modbus functionality, the IED
horizontal communication) using the IEC 61850-8-1 supports retrieval of time-stamped events, changing the ac-
GOOSE (Generic Object Oriented Substation Event) tive setting group and uploading of the latest fault records.
profile. Binary GOOSE messaging can, e.g., be employed If a Modbus TCP connection is used, five clients can be
for protection and interlocking-based protection schemes. connected to the IED simultaneously. Further, Modbus
The relay meets the GOOSE performance requirements serial and Modbus TCP can be used in parallel, and if
for tripping applications in distribution substations, as required both IEC 61850 and Modbus protocols can be
defined by the IEC 61850 standard. Also, the IED supports run simultaneously.
the sending and receiving of analog values using GOOSE
messaging. Analog GOOSE messaging enables fast transfer DNP3.0 Level 2 supports both serial and TCP modes for
of analog measurement values over the network bus, thus connection to one master. Additionally, changing of the
facilitating, for example, sharing of RTD input values, such active setting group is supported.
as surrounding temperature values, to other IED applica-
tions. When the IED uses the RS-485 bus for the serial com-
munication, both two- and four wire connections are
The IED offers an optional second Ethernet bus to enable supported. Termination and pull-up/down resistors can
the creation of a self-healing Ethernet ring topology. The be configured with jumpers on the communication card so
IED communication module options include both galvanic external resistors are not needed.
and fiber-optic Ethernet combinations. The communica-
tion module including one fiber-optic LC port and two The IED supports the following time synchronization
galvanic RJ-45 ports is used when the ring between the methods with a time-stamping resolution of 1 ms:
IEDs is built using CAT5 STP cables. The LC port can in
this case be used for connecting the IED to communication Ethernet-based:
ports outside the switchgear. The communication module • SNTP (Simple Network Time Protocol) – primary and
including three RJ-45 ports is used when the whole substa- secondary SNTP servers supported
tion network bus is based on CAT5 STP cabling.
With special time synchronization wiring:
The self-healing Ethernet ring solution enables a cost-effec- • IRIG-B (Inter-Range Instrumentation Group
tive communication ring solution controlled by a managed - Time Code Format B)
switch with rapid spanning tree protocol (RSTP) support
to be created. The managed switch controls the consistency In addition, the IED supports time synchronization via the
of the loop, routes the data and corrects the data flow in following serial communication protocols:
case of a communication disturbance. The IEDs in the • Modbus
ring topology act as unmanaged switches forwarding • DNP3.0 Level 2
ABB 21
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Client A Client B
Network
Network
22 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 23
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 12. Signal outputs (SO) on X120 and X130 [Typical operation time: 5...8 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous carry 5A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit time 1 A/0.25 A/0.15 A
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load 10 mA at 5 V AC/DC
24 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 13. Self-diagnostics alarm signal output (SO) [Typical operation time: 5...8 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5A
Make and carry for 3.0 s 10 A
Make and carry 0.5 s 15 A
Breaking capacity when the control-circuit time 1 A/0.25 A/0.15 A
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load 10 mA at 5 V AC/DC
Table 14. Double-pole power output (PO) relays with TCM [Typical operation time: 8...11 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8A
Make and carry for 3.0 s 15 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time 5 A/3 A/1 A
constant L/R<40 ms, at 48/110/220 V DC (two
contacts connected in series)
Minimum contact load 100 mA at 24 V AC/DC
Trip-circuit monitoring (TCM):
• Control voltage range 20...250 V AC/DC
• Current drain through the monitoring circuit ~1.5 mA
• Minimum voltage over the TCM contact 20 V AC/DC (15...20 V)
Table 15. Single-pole power output (PO) relays [Typical operation time: 8...11 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 8A
Make and carry for 3.0 s 15 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time 5 A/3 A/1 A
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load 100 mA at 24 V AC/DC
ABB 25
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 16. Double-pole signal output (SO1) on X100 [Typical operation time: 8...11 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 5A
Make and carry for 3.0 s 15 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time 1 A/0.25 A/0.15 A
constant L/R<40 ms, at 48/110/220 V DC
Minimum contact load 100 mA at 24 V AC/DC
Table 17. High-speed output (HSO) devices [Typical operation time: 1 ms]
Description Value
Rated voltage 250 V AC/DC
Continuous contact carry 6A
Make and carry for 3.0 s 15 A
Make and carry 0.5 s 30 A
Breaking capacity when the control-circuit time 5A/3A/1A
constant L/R<40 ms, at 48/110/220 V DC
26 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 21. Lens sensor and optical fibre for arc protection
Description Value
Fiber-optic cable including lens 1.5 m, 3.0 m or 5.0 m
Normal service temperature range of the lens -40...+100°C
Maximum service temperature range of the +140°C
lens, max 1 h
Minimum permissible bending radius of the 100 mm
connection fibre
Table 22. Degree of protection of flush-mounted relay
Description Value
Front side IP 54
Rear side, connection terminals IP 20
Table 23. Environmental conditions
Description Value
Operating temperature range -25 C to +55° C
Short-term operating temperature range -40 C to +85° C (<16 h) 1) 2)
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude Up to 6561 ft (2000 m)
Transport and storage temperature range -40...+85ºC
1)
Degradation in MTBF and LHMI performance outside continuous operating temperature range
2)
For relays with an LC communications interface, the maximum operating temperature is +70° C
28 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 29
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Protection functions
30 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 32. Three-phase non-directional overcurrent protection (50P, 51P) main settings
Parameter Function Value (Range) Step
Pickup value 51P 0.05...5.00 x In 0.01
50P-1, 50P-2 0.10...40.00 x In 0.01
50P-3 1.00...40.00 x In 0.01
Time multiplier 51P 0.05...15.0 0.05
50P-1, 50P-2 0.05...15.00 0.05
Definite time delay 51P 40...200000 ms 10
50P-1, 50P-2 40...200000 ms 10
50P-3 20...200000 ms 10
1)
Operating curve type 51P Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
14, 15, 17, 18, 19
50P-1, 50P-2 Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
50P-3 Definite time
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
ABB 31
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 34. Three-phase directional overcurrent protection (67/51P, 67/50P) main settings
Parameter Function Value (Range) Step
Pickup value 67/51P 0.05...5.00 x In 0.01
67/50P-1, 67/50P-2 0.10...40.00 x In 0.01
Time multiplier 67/51P, 67/50P-1, 67/50P-2 0.05...15.00 0.05
Definite time delay 67/51P, 67/50P-1, 67/50P-2 40...200000 ms 10
Directional mode 67/51P, 67/50P-1, 67/50P-2 1 = Non-directional
2 = Forward
3 = Reverse
Characteristic angle 67/51P, 67/50P-1, 67/50P-2 -179...180 degrees 1
1)
Operating curve type 67/51P Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
14, 15, 17, 18, 19
67/50P-1, 67/50P-2 Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
32 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 35. Non-directional ground fault protection (51N, 51G, 50N, 50G, SEF)
Characteristic Value
Pickup Depending on the frequency of the current
accuracy measured: fn ±2Hz
51N, 51G, SEF ±1.5% of the set value or ±0.002 x In
50N-1, 50N-2, 50G-1, 50G-2 ±1.5% of set value or ±0.002 x In
and (at currents in the range of 0.1…10 x In)
50N-3, 50G-3 ±5.0% of the set value
(at currents in the range of 10…40 x In)
Pickup time 1) 2) Minimum Typical Maximum
50N-3, 50G-3:
IFault = 2 x set Pickup value 15 ms 16 ms 17 ms
IFault = 10 x set Pickup value 12 ms 13 ms 14 ms
50N-1, 50N-2, 50G-1, 50G-2 and
51N, 51G, SEF: 23 ms 25 ms 28 ms
IFault = 2 x set Pickup value
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 30 ms
Trip time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Trip time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)
Suppression of harmonics RMS: No suppression
DFT: -50dB at f =
n x fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1) Measurement mode = default (depends on stage), current before fault = 0.0 x In, fn = 50 Hz, earth-fault current with nominal frequency
injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Pickup value = 2.5 x In, Pickup value multiples in range of 1.5 to 20
Table 36. Non-directional ground fault protection (51N, 51G, 50N, 50G) main settings
Parameter Function Value (Range) Step
Pickup value 51N/51G 0.010...5.000 x In 0.005
50N-1, 50N-2, 50G-1, 50G-2 0.10...40.00 x In 0.01
50N-3, 50G-3 1.00...40.00 x In 0.01
Time multiplier 51N/51G 0.05...15.00 0.05
50N-1, 50N-2, 50G-1, 50G-2 0.05...15.00 0.05
Definite time delay 51N/51G 40...200000 ms 10
50N-1, 50N-2, 50G-1, 50G-2 40...200000 ms 10
50N-3, 50G-3 20...200000 ms 10
1)
Operating curve type 51N/51G Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
14, 15, 17, 18, 19
50N-1, 50N-2, 50G-1, 50G-2 Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
50N-3, 50G-3 Definite time
1)
For further reference please refer to the Operating characteristics table at the end of the Technical data chapter
ABB 33
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
34 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 38. Directional ground fault protection (67/51N, 67/50N) main settings
Parameter Function Value (Range) Step
Pickup value 67/51N 0.010...5.000 x In 0.005
67/50N-1, 67/50N-2 0.10...40.00 x In 0.01
Directional mode 67/51N, 67N/ 50N-1 and 1=Non-directional
67/50N-2 2=Forward
3=Reverse
Time multiplier 67/51N 0.05...15.00 0.05
67/50N-1, 67/50N-2 0.05...15.00 0.05
Definite time delay 67/51N 60...200000 ms 10
67/50N-1, 67/50N-2 60...200000 ms 10
1)
Operating curve type 67/51N Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13,
14, 15, 17, 18, 19
67/50N-1, 67/50N-2 Definite or inverse time
Curve type: 1, 3, 5, 15, 17
Operation mode 67/51N, 67/50N-1 1=Phase angle
and 2=I0Sin
67/50N-2 3=I0Cos
4=Phase angle 80
5=Phase angle 88
ABB 35
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 40. Three-phase non-directional long time overcurrent protection (51LT) main settings
Parameter Function Value (Range) Step
Pickup value 51LT 0.05 - 5.00 x In 0.01
Time multiplier 51LT 0.10...15.001 0.01
1
Definite time delay 51LT 0.020...200.00 s 0.001
Operating curve type 51LT Definite or inverse-time curve
type: 6, 7, 14, 15, 17
1
Embedded 10x factor in time multiplier to achieve ‘very long-time’ curve characteristic
36 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 37
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
38 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 39
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 56. Circuit breaker failure protection (50BF, 50NBF, 50GBF) main settings
Parameter Function Value (Range) Step
Current value 50BF, 50NBF, 50GBF 0.05...1.00 x In 0.05
(Operating phase current)
Current value Res 50BF, 50NBF, 50GBF 0.05...1.00 x In 0.05
(Operating residual current)
CB failure mode 50BF, 50NBF, 50GBF 1=Current
(Operating mode of function) 2=Breaker status
3=Both
CB fail trip mode 50BF, 50NBF, 50GBF 1=Off
2=Without check
3=Current check
Retrip time 50BF, 50NBF, 50GBF 0...60000 ms 10
CB failure delay 50BF, 50NBF, 50GBF 0...60000 ms 10
CB fault delay 50BF, 50NBF, 50GBF 0...60000 ms 10
40 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 41
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
42 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 43
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Table 65. Restricted earth fault, low impedance (REF) main settings
Parameter Function Value (Range) Step
Trip value REF 5...50 % 1
Restraint mode REF None -
2nd harmonic
Pickup value 2.H REF 10...50 % 1
Minimum trip time REF 40...300000 ms 1
Operation REF Off
On
Table 66. Single-phase undercurrent protection (37)
Characteristic Value
Pickup Accuracy Depending on the frequency of the current
measured: fn ±2Hz
±1.5% of the set value or ±0.002 x In
Pickup time Typical < 55 ms
Reset time < 40 ms
Reset ratio Typical 1.04
Retardation time < 35 ms
Trip time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Table 67. Single-phase undercurrent protection (37) main settings
Parameter Function Value (Range) Step
Pickup value 37 0.01...1.00 x In 0.01
Current block value 37 0.01...0.50 x In 0.01
Definite time delay 37 400...600000 ms 10
Operation 37 Off
On
44 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Control functions
Voltage change:
Typical < 40 ms
Reset time < 50 ms
Reset ratio Typical 0.96
Retardation time < 35 ms
Trip time accuracy in definite-time mode ± 1.0% of the set value or + 20 ms
Trip time accuracy in inverse-time mode ± 5.0% of the theoretical value or + 50 ms
1) Results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
ABB 45
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
46 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 47
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
48 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Measurement functions
Table 85. Three-phase and single-phase power and energy (P, SP, E, SE)
Characteristic Value
Measurement accuracy At all three currents in range 0.10…1.20 x In
At all three voltages in range 0.50…1.15 x Vn
At the frequency fn ±1Hz
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71
±1.5% for power (S,P and Q)
±0.015 for power factor
±1.5% for energy
Suppression of harmonics DFT: -50dB at f = n x fn, where n = 2, 3, 4, 5,…
Table 87. Power quality sag (dip), swell, interruption measurements (PQSS)
Characteristic Value
Pickup accuracy ±1.5% of the set value or ±0.2% of the reference voltage
Reset ratio Typical 0.96 (Swell), 1.04 (Sag (dip), Interruption)
Supervision functions
50 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 51
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
24. Display
The relay’s local HMI includes a large LCD screen The large display offers increased front-panel usability
standard. The large LCD display offers full front-panel with less menu scrolling and improved information
user-interface functionality with menu navigation and overview than with smaller LCD screens. The large
menu views. display is well-suited for all relay installations providing
an easy viewing interface.
52 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Figure 18: Flush mounting Figure 19: Semi-flush mounting Figure 20: Semi-flush with a 25º tilt
ABB 53
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
27. Selection and side of the draw-out unit as well as inside the case.
The order number consists of a string of alphanumeric
ordering data characters generated from the hardware and software
modules of the relay.
The relay type and serial number label identifies Use the ordering key information in Fig. 10 to generate
t h e p r o t e c t i o n r e l a y. T h e l a b e l i s p l a c e d the order number when ordering complete protection
above the HMI on the upper part of the draw- relays.
out unit. An order number label is placed on the
REF615 ANSI Order Codes
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Notes
Ex: HAFCCBCBNBE1BAN1XE H A F C C B C B N B E 1 B A N 1 X E
Digit Description
1) Product Series H: 615 (Tiger including case) H
2) Standard A: ANSI A
3) Main Application F: Feeder protection and control F
4) Functional Application A: Non-directional phase and ground
A
overcurrent protection for single breaker
B: Non-directional phase and ground
B
overcurrent protection for two breakers
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
54 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
Example code: H A F D D A D A F F E 1 B A N 1 X E
Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
Code
ABB 55
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
56 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 57
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
$
%
&
5()$16, ;
;
%, 9DX[
%,
6(/) &+(&.$/$50
%,
32
%,
,$
3
32
6
,%
6
3
,& 62
,*
62
$ % &
32
7&0
;
32
%,
7&0
%,
;
%,
62
%,
%, 62
%,
62
%,
%, 62
;
%,
%,
%,
%, ;
%, +62
%,
+62
%,
%, +62
;
%,
;
%,
62
%,
%, 62
%,
62
%,
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
Figure 21. Terminal diagram for REF615 standard configuration A with options
58 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
$
%
&
;
5()$16, ;
,$ 9DX[
,%
6(/) &+(&.$/$50
,&
,$ 32
3
6
,%
6
3
32
,&
,*
62
3
6
62
6
3
32
7&0
3
6
;
32
6
3
%,
7&0
%,
;
%,
62
%,
D
E
F
%, 62
%,
62
%,
%, 62
;
%,
%,
%,
%, ;
%, +62
%,
+62
%,
%, +62
;
%,
;
%,
62
%,
%, 62
%,
62
%,
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
Figure 22. Terminal diagram for REF615 standard configuration B with options
ABB 59
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
$
%
&
$
1
Q
D 5()$16,
; ;
9$ 9DX[
9% 6(/) &+(&.$/$50
9&
32
,$
3
6
,%
6 32
3
,&
,*
62
$ % &
62
32
7&0
;
32
%,
7&0
%,
;
%,
62
%,
%, 62
%,
62
%,
%, 62
;
%,
%,
%,
%,
;
%, +62
%,
+62
%,
%, +62
;
%,
;
%,
62
%,
%, 62
%,
62
%,
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
Figure 23. Terminal diagram for REF615 standard configuration C with options
60 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
$
%
&
$
Q
1
5()$16,
; ;
D GD GQ %,
9DX[
%,
6(/) &+(&.$/$50
%,
32
%,
,$
3
32
6
,%
6
3
,& 62
,*
62
;
%, 32
%,
% $ 7&0
E D
%,
32
%,
$ % & 7&0
96
9$
9%
9&
9*
;
%,
%,
;
%,
62
%,
%, 62
%,
62
%,
%, 62
;
%,
%,
%,
%,
;
%, +62
%,
+62
%,
%, +62
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
Figure 24. Terminal diagram for REF615 standard configuration D with options
ABB 61
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
$
%
&
$
1
Q 5()$16, ;
;
D ,$ 9DX[
,%
6(/) &+(&.$/$50
,&
3
6
,$ 32
3
6
,%
32
,&
,*
3
6
62
6 ;
3
%, 62
%,
32
3
6
%,
6
3 7&0
9$
32
9%
9& 7&0
9$
9%
D 9&
Q
1 ;
$ %,
D
E %,
F
;
%,
62
%,
%, 62
%,
62
%,
%, 62
;
%,
%,
%,
%, ;
%, +62
%,
+62
%,
%, +62
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
;
/LJKWVHQVRULQSXW
Figure 25. Terminal diagram for REF615 standard configuration E with options
62 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
31. Certificates
KEMA has issued an IEC 61850 Certificate Level A1 for REF615. Certificate number: 30710144-Consulting 08-0115
32. References
The download area on the right hand side of the web page contains the latest product documentation, such as technical reference manual,
installation manual, operators manual,etc. The selection tool on the web page helps you find the documents by the document category and
language.
The Features and Application tabs contain product related information in a compact format.
The www.abb.com/substationautomation portal offers you information about the distribution automation product and service range.
You will find the latest relevant information on the REF615 protection relay on the product page.
64 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 65
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
66 ABB
Feeder Protection 1MAC105361-PG Rev. E
REF615 ANSI
Issued: 04.15.2011
Product Version 4.0
ABB 67