Potter Panel Programming

Standard Stat-X Configuration


Panel #1, Support Rooms, and Gen Sets

1. Move programming switch to "Program".


2. Press the "Function" key (3) three times.
3. Press the "Set" key (3) three times.
4. Press the "Function" key (3) three times.
5. Display reads Program #0
6. Press the "Select" key until display reads #26.
a. If you pass #26, keep going until it comes around again.
7. Press the "Set" key.
8. Display reads "AL Pre-Discharge 60 seconds".
9. Press the "Select" key until 30 seconds is displayed.
10. Press the "Set" key.
11. Display reads "MD Pre-Discharge 30 seconds".
12. Press the "Set" key.
13. Display reads "Abort Type ULI".
14. Press the "Set" key.
15. Press the "Function" key until the Display reads "Push Programming Switch back up".
16. Move programming switch to "Run".
17. Move programming switch to "Program".
18. Press the "Function" key (3) three times.
19. Press the "Set" key (3) three times.
20. Press the "Function" key (3) three times.
21. Display reads Program #26
22. Press the "Select" key until display reads #0.
a. If you pass #26, keep going until it comes around again.
23. Press the "Set" key.
24. Display shows "Chemical Based".
25. Press the "Function" key until the Display reads "Output #1 Indicating".
26. Press the "Set" key until Display reads "Output #4 Aerosol"
27. Press the "Select" key until display reads "Output #4 Releasing"
28. Press "Set".
29. Move programming switch to "Run".
30. Test the System.
Potter Panel Programming
Custom Stat-X Configuration
Panels #2, #3, #4

1. Move programming switch to "Program".


2. Press the "Function" key (3) three times.
3. Press the "Set" key (3) three times.
4. Press the "Function" key (3) three times.
5. Display reads Program #0
6. Press the "Select" key until display reads #26.
a. If you pass #26, keep going until it comes around again.
7. Press the "Set" key.
8. Display reads "AL Pre-Discharge 60 seconds".
9. Press the "Select" key until 30 seconds is displayed.
10. Press the "Set" key.
11. Display reads "MD Pre-Discharge 30 seconds".
12. Press the "Set" key.
13. Display reads "Abort Type ULI".
14. Press the "Set" key.
15. Press the "Function" key until the Display reads "Push Programming Switch back up".
16. Move programming switch to "Run".
17. Move programming switch to "Program".
18. Press the "Function" key (3) three times.
19. Press the "Set" key (3) three times.
20. Press the "Function" key (3) three times.
21. Display reads Program #26
22. Press the "Select" key until display reads #0.
a. If you pass #26, keep going until it comes around again.
23. Press the "Set" key.
24. Display shows "Chemical Based".
25. Press the "Function" key until the Display reads "Output #1 Indicating".
26. Press the "Select" key until Display reads "Output #1 Aerosol"
27. Press the "Set" key until display reads "Output #2 Indicating".
28. Press the "Select" key until Display reads "Output #2 Aerosol"
29. Press "Set".
30. Move programming switch to "Run".
31. Test the System.