You are on page 1of 24

Ducted(Central) Split

Air Conditioner
SERVICE MANUAL
MODELS: LN-0320CC/AC(F)
LN-0420CC/AC(F)
LN-0520CC/AC(F)
LN-0321CC/AC(F)
LN-0421CC/AC(F)
LN-0521CC/AC(F)
Contents
Model Number Nomenclature.............................................................................................. 3

General Data ......................................................................................................................... 4

Dimensions ........................................................................................................................... 5

Wiring Diagram ..................................................................................................................... 6

Troubleshooting Guide ........................................................................................................ 8

Features of Controller ........................................................................................................ 14

Exploded View and Replacement Parts List .................................................................... 15

Specification of Components............................................................................................ 21

—2—
Model Number Nomenclature

L N - 0 5 2 0 C C (F)
F: Electronic thermostat + wirless remote control

C: Convertible
H: Horizontal Flow
D: Down Flow

A: GOLD FIN + Cooling Only


C: Cooling Only
H: Heat Pump

Development Sequence

1 : 115/60/1 2 : 220/60/1 3 : 208-230/60/1


5 : 200-220/50/1 6 : 220-240/50/1 7 : 100/50(60)/1
8 : 380-415/50/3 9 : 380-415/60/3 A : 220/50/3
B : 220/60/3 C : 440-460/50/3 D : 440-460/60/3

Nominal cooling capacity


03 : 3 ton 08 : 7.5 ton 15 : 15 ton
04 : 4 ton 09 : 8.5 ton 18 : 17.5 ton
05 : 5 ton 10 : 10 ton 20 : 20 ton
06 : 6.25 ton 13 : 12.5 ton 25 : 25 ton

LG
Ducted Split Air Conditioner

—3—
General Data
Table-1
Nominal ton (Ton) 3 4 5
Models LN-0320CC/AC(F) LN-0420CC/AC(F) LN-0520CC/AC(F)
Capacity ARI Net Cooling Capacity (BTU/hr) 35,000 48,000 58,000
(Kcal/h) 8,820 12,096 14,616
Electrical Data Voltage (V,PH) 220V,1PH 220V,1PH 220V,1PH
M.C.A(with standard motor) Cooling (Amps) 20.2 23 30
Power Input Cooling (Watt) 4,000 5,000 6,700
Performance Air Circulation Nominal CFM CFM 1,300 1,695 1,900
EER Cooling (BTU/hr.W) 7.89 9.6 8.5
Sound Rating Cooling dB(A) 8 8 8
Features Filter type Washable & antifungus Washable & antifungus Washable & antifungus
Compressor Type Reciprocating Reciprocating Reciprocating
Quantity 1 1 1
Outdoor Coil Type High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.276 0.276 0.276
(mm) 7 7 7
Row/FPI 2R/18FPI 2R/18FPI 2R/18FPI
Lengh (inch) 32.2 48.8 53.4
(mm) 818.6 1240.4 1357.4
Face area (sq.ft) 6.67 11.22 12.27
(m2) 0.62 1.04 1.14
Indoor Coil Type High efficiency High efficiency High efficiency
Tube size(O.D) (inch) 0.375 0.375 0.375
(mm) 9.52 9.52 9.52
Row/FPI 2R/18FPI 2R/18FPI 3R/16FPI
Lengh (inch) 15.16 15.75 15.75
(mm) 385 400 400
Face area (sq.ft) 3.55 4.63 4.63
(m2) 0.33 0.43 0.43
Outdoor Fan Type Propeller Propeller Propeller
No. Used/Diameter(in.) 1EA/18.1" 1EA/22.7" 1EA/22.7"
Drive Type Direct Direct Direct
CFM 2048 3743 3743
No. Motor/Motor output(Hp) 1/0.12 1/0.3 1/0.3
Motor RPM 930 970 970
Indoor Fan Type Centrifugal Blower Fan
No. Used 1EA 1EA 1EA
Diameter/Width(in.) 7.9"/7.2" 7.9"/11" 7.9"/11"
Drive Type/Motor Step Direct/3 Direct/3 Direct/3
No.motors 1EA 1EA 1EA
Motor output(standard/oversized) 0.47hp/N.A 0.47hp/N.A 0.73hp/N.A
Motor rpm(Standard/oversized) 1,192/N.A 1,192/N.A 1,195/N.A
Drain Connection Size(in.) 3/4" 3/4" 3/4"
Refrigerant Refrigerant Charge (Lbs) 3.7 6.8 8.3
Dimensions Indoor unit (WxHxD) (inch) 18.5*18.9*39.9 23.6*19.7*44.7 23.6*19.7*44.7
(mm) 470*480*1014 600*500*1135 600*500*1135
Outdoor unit (WxHxD) (inch) 34.3*31.5*12.6 28.4*33.7*27.2 28.4*33.7*27.2
(mm) 870*800*320 722*855*691 722*855*691
Weight Indoor unit (kg) 53 59 63
(lbs) 117 130 139
Outdoor unit (kg) 65 105 110
(lbs) 143 214 243
1) Test Condition of ARI Rated Cooling Capacity :
Ambient:95°F , Air entering temprature : 80°F DB and 67°F WB
2) ARI standard
210/240 or 360 for EER
270 for Sound
3) Filters are standard supply.
—4—
General Data
Table-2
Nominal ton (Ton) 3
Models LN-0321CC/AC(F)
Capacity ARI Net Cooling Capacity (BTU/hr) 35,000
(Kcal/h) 8,820
Electrical Data Voltage (V,PH) 220V,1PH
M.C.A(with standard motor) Cooling (Amps) 20.2
Power Input Cooling (Watt) 3,750
Performance Air Circulation Nominal CFM CFM 1,200
EER Cooling (BTU/hr.W) 9.3
Sound Rating Cooling dB(A) 8
Features Filter type Washable & antifungus
Compressor Type Scoll
Quantity 1
Outdoor Coil Type High efficiency
Tube size(O.D) (inch) 0.276
(mm) 7
Row/FPI 2R/17FPI
Lengh (inch) 32.2
(mm) 756
Face area (sq.ft) 6.67
(m2) 0.62
Indoor Coil Type High efficiency
Tube size(O.D) (inch) 0.375
(mm) 9.52
Row/FPI 2R/18FPI
Lengh (inch) 15.16
(mm) 360
Face area (sq.ft) 3.55
(m2) 0.33
Outdoor Fan Type Propeller
No. Used/Diameter(in.) 1EA/18.1"
Drive Type Direct
CFM 2048
No. Motor/Motor output(Hp) 1/0.12
Motor RPM 930
Indoor Fan Type
No. Used 1EA
Diameter/Width(in.) 7.9"/7.2"
Drive Type/Motor Step Direct/3
No.motors 1EA
Motor output(standard/oversized) 0.47hp/N.A
Motor rpm(Standard/oversized) 1,192/N.A
Drain Connection Size(in.) 3/4"
Refrigerant Refrigerant Charge (Lbs) 3.7
Dimensions Indoor unit (WxHxD) (inch) 18.5*18.9*39.9
(mm) 470*480*1014
Outdoor unit (WxHxD) (inch) 34.3*31.5*12.6
(mm) 870*800*320
Weight Indoor unit (kg) 53
(lbs) 117
Outdoor unit (kg) 65
(lbs) 143

—5—
Dimensions
LN-0320CC/AC(F), LN-0420CC/AC(F), LN-0520CC/AC(F)

D
1. Indoor unit
E G
Unit Dimensions Unit: inch(mm) H
F
MODEL LN-0320CC/AC(F), LN-0321CC/AC(F) LN-0420CC(F), LN-0520CC/AC(F)
A 18.5 (470) 23.6 (600)
B 18.9 (480) 19.7 (500)
C 39.9 (1014) 44.7 (1135)
D 3.3 (84) 5.4 (136)
Condensate
E 11.9 (303) 13.0 (329) Drain-Horizontal
F 5.6 (142) 7.1 (181) 3/4" NPT-Female
G 12.0 (304) 12.6 (319)
H 0.6 (15) 0.6 (15) C Suction line
I 4.3 (110) 6.7 (170) P
J 6.3 (160) 9.4 (240)
K 1.7 (43) 2.5 (64) Q
L 2.0 (50) 2.8 (71) L
M 2.0 (52) 2.3 (58)
R
N 1.8 (45) 2.1 (54)
Liquid
Liqid line
P 1.3 (32) 1.5 (38)
Q 8.7 (221) 11.2 (285) B N
K Filter Provision
R 19.1 (485) 23.0 (584) I
A
J M
Condensate
Drain-Upflow
3/4" NPT-Female

2. Outdoor unit Unit: inch(mm)


LN-0320CC/AC(F) LN-0420CC/AC(F)
LN-0321CC/AC(F) LN-0520CC/AC(F)

31.5"(800)
33.7"(855)

21.5"(546)
12.6"(320)
34.3"(870)
28.4"(722) 27.2"(691)

—6—
Wiring Diagram
LN-0520CC/AC(F), LN-0420CC/AC(F)

FACTORY WIRING BK: BLACK OR: ORANGE YL:YELLOW


DIAGRAM WIRING
OPTIONAL WIRING BR: BROWN RD: RED WH: WHITE
FIELD WIRING BL: BLUE GN/YL: GREEN/YELLOW NOTES (with LG's THERMOSTAT) L
AC 24V
N
Fan
OUTDOOR UNIT INDOOR UNIT 1
1Ø 220V,60Hz Comp
POWER SUPPLY TRANS 2
GN/YL BK RD
GN/YL Heater
WH
3
WH
ELECTRO-MECHANICAL
BK RD
PILLAR THERMOSTAT
BK
TERMINAL OR TERMINAL
BLOCK
OR 1 AC 24V
R
(N) (L) BL
WH BK BL 2 Fan
G
PILLAR PILLAR
TERMINAL TERMINAL 3 Comp
Y
4 Heater
W
FUSE
(250V,10A) 5
MECHANICAL
BL BK THERMOSTAT
COMP
S R
C 1 2 TERMINAL
BLOCK
MAGNETIC CONTACT

RD BK
POWER RELAY
(For I/MOTOR)
WH WH L1 L2
A A
(For COMP)

1Ø 220V,60Hz
*P.T.C

4
BK 6 POWER SUPPLY
B B
CAPACITOR

WH
T1 T2 THERMOSTAT USING
RD FOR EVA ELECTRIC
WH OR BL HEATER
BK TERMINAL
OR BLOCK
CAPACITOR RD
TERMINAL

MAGNETIC CONTACT
BLOCK
OR T1 T2

(F or E/Heater)
YL A
OR b 3 4 TERMINAL
BLOCK
OUTDOOR UNIT

INDOOR UNIT

c B
L1 L1

MOTOR a
OR BK (IN)
MODEL a b c
LN _ 04**** BK(SUPER_HI) BL(HI) RD(LOW)
CAPACITOR
MOTOR YL LN _ 05**** BL(HI) BK(SUPER_HI) RD(LOW) EH ELECTRIC
(OUT) BR HEATER
* : P.T.C IS AN OPTIONAL PART,
IT IS DEPENDED ON THE TYPE
AND GRADE OF COMPRESSOR.
REFER TO THE TECHNICAL GUIDE BOOK OR
SERVICE MANUAL FOR DETAIL INFORMATION. P/NO : 3854A20068D

FACTORY WIRING BK: BLACK OR: ORANGE YL:YELLOW


OPTIONAL WIRING BR: BROWN RD: RED WH: WHITE
DIAGRAM WIRING
L
FIELD WIRING BL: BLUE GN/YL: GREEN/YELLOW NOTES (with locally purchased THERMOSTAT) AC 24V
N
Fan
OUTDOOR UNIT INDOOR UNIT 1
1Ø 220V,60Hz Comp
POWER SUPPLY TRANS 2
GN/YL BK BL TIME DELAY P.C.B
GN/YL Heater
WH
3
BL
WH RD ELECTRO-MECHANICAL
BK
PILLAR THERMOSTAT
BK RD
TERMINAL OR RD YL BK TERMINAL
BLOCK
OR 1 AC 24V
R
(N) (L) BL
WH BK BL 2 Fan
G
PILLAR PILLAR
TERMINAL TERMINAL 3 Comp
Y
4 Heater
W
FUSE
(250V,10A) 5
MECHANICAL
BL BK THERMOSTAT
COMP
S R
C 1 2 TERMINAL
BLOCK
MAGNETIC CONTACT

RD BK
POWER RELAY
(For I/MOTOR)

WH WH L1 L2
A A
(For COMP)
*P.T.C

4
BK 6 1Ø 220V,60Hz
B B
CAPACITOR

WH
POWER SUPPLY
T1 T2 THERMOSTAT
RD FOR EVA USING
WH OR BL
ELECTRIC
BK HEATER
OR
TERMINAL
CAPACITOR RD BLOCK
TERMINAL
BLOCK
MAGNETIC CONTACT

YL OR
T1 T2
3 4
(F or E/Heater)

TERMINAL A
OR b BLOCK
OUTDOOR UNIT

INDOOR UNIT

c
B
L1 L1
MOTOR a MODEL a b c
OR BK (IN)
LN _ 04**** BK(SUPER_HI) BL(HI) RD(LOW)
CAPACITOR
YL LN _ 05**** BL(HI) BK(SUPER_HI) RD(LOW)
MOTOR
(OUT) BR ELECTRIC
* : P.T.C IS AN OPTIONAL PART, EH HEATER
IT IS DEPENDED ON THE TYPE
AND GRADE OF COMPRESSOR.
REFER TO THE TECHNICAL GUIDE BOOK OR
SERVICE MANUAL FOR DETAIL INFORMATION.
P/NO : 3854A20068D

—7—
Wiring Diagram
LN-0320CC/AC(F), LN-0321CC/AC(F)

FACTORY WIRING BK: BLACK OR: ORANGE YL:YELLOW


OPTIONAL WIRING BR: BROWN RD: RED WH: WHITE
DIAGRAM WIRING
FIELD WIRING BL: BLUE GN/YL: GREEN/YELLOW NOTES (with LG's THERMOSTAT) L
AC 24V
N
Fan
OUTDOOR UNIT INDOOR UNIT 1
1Ø 220V,60Hz Comp
POWER SUPPLY TRANS 2
GN/YL BK RD
GN/YL Heater
WH
3
WH
ELECTRO-MECHANICAL
BK RD
PILLAR THERMOSTAT
BK
TERMINAL OR TERMINAL
BLOCK
OR 1 AC 24V
R
(N) (L) BL
WH BK BL 2 Fan
G
TERMINAL PILLAR
BLOCK TERMINAL 3 Comp
Y
4 Heater
W
FUSE
(250V,10A) 5
MECHANICAL
BL BK BK THERMOSTAT
COMP
S R
C 1 2 TERMINAL
BLOCK
MAGNETIC CONTACT

RD BK
POWER RELAY

WH L1 L2
A
1Ø 220V,60Hz
A
(For I/Motor)
(For Comp)

4 POWER SUPPLY
BK 6
B B USING
CAPACITOR

T1 T2 ELECTRIC
THERMOSTAT HEATER
RD FOR EVA
WH TERMINAL
OR BL BLOCK
BK
OR

MAGNETIC CONTACT
RD
TERMINAL
T1 T2
BLOCK A

(For E/Heater)
CAPACITOR

OR b 3 4 TERMINAL
BLOCK
B
OUTDOOR UNIT

OR YL L1 L2
INDOOR UNIT

c
MOTOR a a b c
OR BK (IN)
BK(SUPER_HI) ELECTRIC
BL(HI) RD(LOW) EH HEATER
CAPACITOR
MOTOR YL
(OUT) BR

P/NO : 3854A20091C

FACTORY WIRING BK: BLACK OR: ORANGE YL:YELLOW


OPTIONAL WIRING BR: BROWN RD: RED WH: WHITE
DIAGRAM WIRING
FIELD WIRING BL: BLUE GN/YL: GREEN/YELLOW NOTES (with locally purchased THERMOSTAT) L
AC 24V
N
Fan
OUTDOOR UNIT INDOOR UNIT 1
1Ø 220V,60Hz Comp
POWER SUPPLY TRANS 2
GN/YL BK BL TIME DELAY P.C.B
GN/YL Heater
WH
3
BL
WH RD ELECTRO-MECHANICAL
BK
PILLAR THERMOSTAT
BK RD
TERMINAL OR RD YL BK TERMINAL
BLOCK
OR 1 AC 24V
R
(N) (L) BL
WH BK BL 2 Fan
G
TERMINAL PILLAR
BLOCK TERMINAL 3 Comp
Y
4 Heater
W
FUSE
(250V,10A) 5
MECHANICAL
BL BK BK THERMOSTAT
COMP
S R
C 1 2 TERMINAL
BLOCK
MAGNETIC CONTACT

RD BK
POWER RELAY

WH L1 L2
A
1Ø 220V,60Hz
A
(For I/Motor)
(For Comp)

4 POWER SUPPLY
BK 6
B B USING
CAPACITOR

T1 T2 ELECTRIC
THERMOSTAT HEATER
RD FOR EVA
WH TERMINAL
OR BL BLOCK
BK
OR
MAGNETIC CONTACT

RD
TERMINAL
T1 T2
BLOCK A
(For E/Heater)

CAPACITOR

OR b 3 4 TERMINAL
BLOCK
B
OUTDOOR UNIT

OR YL L1 L2
INDOOR UNIT

c
MOTOR a a b c
OR BK (IN)
BK(SUPER_HI) ELECTRIC
BL(HI) RD(LOW) EH HEATER
CAPACITOR
MOTOR YL
(OUT) BR

P/NO : 3854A20091C

—8—
Troubleshooting Guide
In general, possible trouble is classified in two causes.
The one is called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air
Conditioning caused by a defect in the refrigeration circuit and improper application.
Unit runs but ineffective cooling

Ineffective Cooling or Heating

Check of cold (warm) air cir- Check of outdoor coil Check heat load increase in
culation for smooth flow. (heat exchanger) & the fan cooling operation.
operation.

Unexpected residue
Dirty indoor coil Check gas leakage.
(heat exchanger.)

Added electrical utencil


Malfunction of fan. Repair gas leak.

Check of inside gas


Clogging of air filter. Replacement of unit if the pressure.
unit is beyond repair.

Obstruction at air outlet.


Adjust refrigerant
charge.

Countermeasure against
above trouble.

Malfunction of compressor.

Check clogging in refrigera-


tion circuit.
Satisfactory operation with
Replacement of
temperature difference of
compressor
inlet & outlet air ;
Repair clogging in refrigera- COOLING : 7~10°C
tion circuit. HEATING : 15~17°C

—9—
Troubleshooting Guide

Fails to Start

Check power source. Check of circuit breaker


and fuse.

Check control switch


setting. Check control switch.

Compressor only fails to Fan only fails to start.


start.
Electric heater is not energized

Improper wiring.
Drop of power voltage. Loose terminal connection.

Defect of fan motor


Improper wiring
Defect of compressor capacitor.
capacitor.

Irregular motor resistance


(Ω)
Capacitor check.
Irregular motor insulation
(Ω)

Replacement of capacitor.
Replacement of fan motor.

Improper electric heater


Irregular motor resistance ( Ω ) Regular but fails to start.

Replacement of electric
Irregular motor insulation ( Ω ) heater.
Replacement of compressor.

Replacement of compressor

— 10 —
Troubleshooting Guide

PACKAGE AIR CONDITIONER VOLTAGE LIMITS

NAME PLATE RATING MINIMUM MAXIMUM


220 V 187 V 253 V

1. No cooling and heating operation performed


1) Both the blower and the compressor do not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Other parts except the • Electric supply interrupted Measure power sypply
unit • Defective power wiring with a tester in case that • Repair a switch box and
• Cut off power fuse the same power source is relative instrument.
supplied to other equip- • Replacement of fuse
ment except the unit, • Request a power
what and where troubled supplier to repair.
can be discovered by
checking the operation of
other equipment.

Too low voltage Measure it with a tester. Check the power source.
Use a thick cable if nec-
essary.
Magnetic switch for com- Control point is on condi- Make short-circuit, then Replace it if necessary.
pressor & fan motor tion of "OFF" due to trou- measure it with tester.
ble.

Operating switch Troubled or defective Check it with the eyes or Repair or replace it.
contactor tester.

2) Only Indoor blowers do not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Motor • Over heated Check it with tester Repair or replace it.


• Wiring short

Capacitor Defected Check it with a tester. Replace it.

• Cut- OFF of wiring


Electric wiring • Short circuited on Rewiring or Repair.
Check it with a tester.
operation

— 11 —
Troubleshooting Guide

3) Only outdoor fan does not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Motor • Over-heated Check how it is insulated. Repair or replace it.


• Wire short

Electric Wiring Cut off of wiring Check it with a tester. Rewiring or repair.
Short circuited on
operation

4) Only compressor does not work

WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Magnetic switch for Defective contact, Check it with the eyes on Repair or replace it.
compressor motor magnetic coil troubled. with a tester.

Compressor motor Troubled over-heated Check how it is insulated. Replace or repair the
(layer short) compressor.

High pressure switch Troubled or defective Check it with a tester. Replace it if neces-
(Option part) contact or operating sary.

Electric circuit Defective connection or Check it with a tester. Rewiring or push reset
disconnection of the circuit button.
for compressor.

— 12 —
Troubleshooting Guide

2. The Units discontinue after the operation started


WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Outdoor coil Coil is dirty *1 Checking Wash it by means of


something like chemical
washing.

In-condensable gas Air intruded into the In the event that Extract air by vacuum
blended. refrigerant pipe line *1 difference between the pump, then replenish
saturating temperature (charge) the refrigerant.
corresponding to high
pressure and the
temperature of air
discharged from the
outdoor coil is more than
15°C, incondensable gas
may be blended.

High pressure switch Improper adjustment Check it with a pressure Read just it to normal
(Option part) gauge. operating pressure.
(Note)
Don't alternate the
specified adjusting
pressure. If the adjusted
pressure exceed the
specified range, it will
cause a great accident.

Refrigerant A shortage of refrigerant Check pressure Replenish the


amount. * 2 refrigerant. Repair the
spot where it is leaked.

Outdoor Fan Reverse rotation of fan Confirm the wind blowing If reversed, connect
Obstacle out upward. interchanged wires to
Air short circuit *1 each terminal.
Check it with eyes.
Power wirings.

Note: Use an appropriate measuring instrument for readjustment.


*1: High-pressure switch moves.
*2: Low- pressure switch moves.

— 13 —
Troubleshooting Guide
3. The unit is working, but not cooling and heating sufficiently
(Both blower and compressor are working)
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Load Much Cooling or Heating Heat load increased. Do necessary disposal


load Window or door has many respectively.
cracks or gaps.

Air flow Obstacle disturbs Intake Checking Correct it.


of uniform airflow.

Short air volume Reverse rotation of Checking Correct it.


blower.

Refrigerant Shortage in the charged Coil inlet pipe is frosted Recharge it.
refrigerant. (Repair the leakage spot).

Air passage Improper or foreign bodies Checking Correct or clear the


foreign bodies.

Air filter Clogged with dust Checking Cleaning

4. All the functions are performed as specified, but very noisy and vibrant
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY

Compressor Liquid refrigerant flooding • Check for refrigerant over-charge.


back from the evaporator. • Check to see if the intake air temperature is
extremely cold.
• Check for insufficient air flow quantity.

Faulty Discharge valve • Checking • Replace the


and suction valve. compressor

Blower Fan broken. Checking Repair or replace it.


Clear the foreign bodies.
Foreign matters intruded.

Screws Looseness or fail-off of Checking Correct


screws

Electric troubles Defective contact. Checking Repair and clean or


(Magnetic contactor) Defective contact point. replace it.
Rusting and foreign mat-
ters in the iron core con-
tact face. Defective con-
tact of the
operating switch.

Others Improper installation Checking Correct it.

— 14 —
Features of Controller
1. Timer PCB Circuit Diagram

12V

8 R06M DO1M
R03M R01M 12V
1K Q01M 1N4148 AC220V
220K 47K KRC107K 60Hz
3 + 1
2 - RY01M
JQ1a-12V

C01M
+
R02M
3.3uF 47K IC01M
4 KA393
L1
D02D~D05D ZNR
12V 1SR139-600 INR14D471
IC01D D04D D02D L2
Magnetic
0 1 Relay
7812
+ D05D
D03D
C04D C01D
104 470uF L3
C02D
25V 104 RY01M
TRANS JQ1a-12V

2. Timer PCB ASSY

D1 CN4 CN1
C3 IC1 C1 D2
D7 C2

D3 CN2
R7

R3
R2
R4

D4
C5
D5
R1
Q1

IC2
C4
C7
IC3

R9

CN3
R10
R5

R8

D6
Q2
R6

RY1
C8
C6

PCB: 2Q01062A

— 15 —
Exploded View and Replacement Parts List
1. Indoor Unit
• Exploded View[LN-0520CC/AC(F), LN-0420CC/AC(F), LN-0320CC/AC(F)
LN-0521CC/AC(F), LN-0421CC/AC(F), LN-0321CC/AC(F)]

268716
249951

669200

261704

W0CZZ

266140 354212-2
552101 354212-1

330860-1 330860-2

359011

346810

267110
152302

— 16 —
Exploded View and Replacement Parts List
• Replacement Parts List
LN-0520CC/AC(F)
LOCATION No. DESCRIPTION LN-0520CC LN-0520AC(F) QUANTITY
249951 CONTROL BOX ASSY, INDOOR 4995A200135A 1
261704 TRANSFORMER, POWER 6170A10001G 1
266140 CONTROL, DEFROST 6614A30001J 1
330860-1 DRAIN PAN 3086A10006A 1
330860-2 DRAIN PAN 3086A10007A 1
346810 MOTOR ASSY, INDOOR 4681A20022G 1
354212-1 EVAPORATOR ASSY, FIRST 5421A10002J 1
354212-2 EVAPORATOR ASSY, FIRST 5421A10002K 1
359011 FAN ASSY, BLOWER 2A00578M 1
552101 TUBE, CAPILLARY 3E92334N 6
669200 RELAY 6920AP3194B 1
W0CZZ CAPACITOR, DRAWING 0CZZA20001B 1
268716 TIMER 3Q01017C 1
267110 REMOCON - 6711A20041R 1
152302 FILTER - 5230A20003J 1

LN-0420CC/AC(F)
LOCATION No. DESCRIPTION LN-0420CC LN-0420AC(F) QUANTITY
249951 CONTROL BOX ASSY, INDOOR 4995A200136A 1
261704 TRANSFORMER, POWER 6170A10001G 1
266140 CONTROL, DEFROST 6614A30002J 1
330860-1 DRAIN PAN 3086A10007A 1
330860-2 DRAIN PAN 3086A10008A 1
346810 MOTOR ASSY, INDOOR 4681A20022H 1
354212-1 EVAPORATOR ASSY, FIRST 5421A10002M 1
354212-2 EVAPORATOR ASSY, FIRST 5421A10002N 1
359011 FAN ASSY, BLOWER 2A00578M 1
552101 TUBE, CAPILLARY 5425AR3147P 4
669200 RELAY 6920AP3194B 1
W0CZZ CAPACITOR, DRAWING 0CZZA20001B 1
268716 TIMER 3Q01017C 1
267110 REMOCON - 6711A20041R 1
152302 FILTER - 5230A20003J 1

LN-0320CC/AC(F)
LOCATION No. DESCRIPTION LN-0320CC LN-0320AC(F) QUANTITY
249951 CONTROL BOX ASSY, INDOOR 4995AP2136V 1
261704 TRANSFORMER, POWER 6170A10001G 1
266140 CONTROL, DEFROST 6614A30002J 1
330860-1 DRAIN PAN 3086A10011A 1
330860-2 DRAIN PAN 3086A10012A 1
346810 MOTOR ASSY, INDOOR 4681A20022H 1
354212-1 EVAPORATOR ASSY, FIRST 5421A20070A 1
354212-2 EVAPORATOR ASSY, FIRST 5421A20070B 1
359011 FAN ASSY, BLOWER 2A00578U 1
552101 TUBE, CAPILLARY 3H01535E 4
669200 RELAY 6920AP3194B 1
W0CZZ CAPACITOR, DRAWING 2A00986D 1
268716 TIMER 3Q01017C 1
267110 REMOCON - 6711A20041R 1
152302 FILTER - 5230A20003J 1

— 17 —
Exploded View and Replacement Parts List
LN-0321CC/AC(F)
LOCATION No. DESCRIPTION LN-0321CC LN-0321AC(F) QUANTITY
249951 CONTROL BOX ASSY, INDOOR 4995A20146C 1
261704 TRANSFORMER, POWER 6170A10001G 1
266140 CONTROL, DEFROST 6614A30002J 1
330860-1 DRAIN PAN 3086A10011A 1
330860-2 DRAIN PAN 3086A10012A 1
346810 MOTOR ASSY, INDOOR 4681A20022H 1
354212-1 EVAPORATOR ASSY, FIRST 5421A20070A 1
354212-2 EVAPORATOR ASSY, FIRST 5421A20070B 1
359011 FAN ASSY, BLOWER 2A00578U 1
552101 TUBE, CAPILLARY 3H01535E 4
669200 RELAY 6920AP3194B 1
W0CZZ CAPACITOR, DRAWING 2A00986D 1
268716 TIMER 3Q01017C 1
267110 REMOCON - 6711A20041R 1
152302 FILTER - 5230A20003J 1

— 18 —
Exploded View and Replacement Parts List
2. Outdoor Unit
• Exploded View [LN-0520CC/AC(F), LN-0420CC/AC(F)]

554031-2

249951
667482
W0CZZ-2

666000
554160

552203-2
W0CZZ-1
554031-1

552203-1
546810

559010

— 19 —
Exploded View and Replacement Parts List
• Exploded View [LN-0320CC/AC(F), LN-0321CC/AC(F)]

249951

552203-1

552203-2
W0CZZ-1
666000
554031

W0CZZ-2

554160
546810

559010

— 20 —
Exploded View and Replacement Parts List
• Replacement Parts List
LN-0520CC/AC(F)
LOCATION No. DESCRIPTION LN-0520CC LN-0520AC(F) QUANTITY
546810 MOTOR ASSY, OUTDOOR 4681A20039A 1
552203-1 VALVE, SERVICE 2A00499E 1
552203-2 VALVE, SERVICE 2H01890A 1
554031-1 CONDENSER ASSY, BENT 5403A10001B 5403A20057F 2
554031-2 CONDENSER ASSY, BENT 5403A10001D 5403A20057H 2
554160 COMPRESSOR ASSY, FINAL 2A01094E 1
559010 FAN ASSY, PROPELLER 5901A10010A 1
666000 SWITCH, MAGNET 2A00771F 1
W0CZZ-1 CAPACITOR, DRAWING 2A00986D 1
W0CZZ-2 CAPACITOR, DRAWING 6120AR2194T 1
667482 P.T.C ASSY 3A01911B 1
249951 CONTROL BOX ASSY, OUTDOOR 4995A20135A 1

LN-0420CC/AC(F)
LOCATION No. DESCRIPTION LN-0420CC LN-0420AC(F) QUANTITY
546810 MOTOR ASSY, OUTDOOR 4681A20039A 1
552203-1 VALVE, SERVICE 2A00499E 1
552203-2 VALVE, SERVICE 2A00393A 1
554031-1 CONDENSER ASSY, BENT 5403A10001F 2
554031-2 CONDENSER ASSY, BENT 5403A10001H 2
554160 COMPRESSOR ASSY, FINAL 5417A20009A 1
559010 FAN ASSY, PROPELLER 5901A10010A 1
666000 SWITCH, MAGNET 2A00771F 1
W0CZZ-1 CAPACITOR, DRAWING 2A00986D 1
W0CZZ-2 CAPACITOR, DRAWING 2A00986A 1
667482 P.T.C ASSY 3A01911B 1
249951 CONTROL BOX ASSY, OUTDOOR 4995A20135A 1

LN-0320CC/AC(F)

LOCATION No. DESCRIPTION LN-0320CC LN-0320AC(F) QUANTITY


546810 MOTOR ASSY, OUTDOOR 4681A20008M 1
552203-1 VALVE, SERVICE 2A00392F 1
552203-2 VALVE, SERVICE 2A00393A 1
554031 CONDENSER ASSY, BENT 5403A20066V 5403A20066D 1
554160 COMPRESSOR ASSY, FINAL 2A01196A 1
559010 FAN ASSY, PROPELLER 1A00195B 1
666000 SWITCH, MAGNET 2A00771F 1
W0CZZ-1 CAPACITOR, DRAWING 2A00986D 1
W0CZZ-2 CAPACITOR, DRAWING 2A00986B 1
667482 P.T.C ASSY 3A01911B 1
649950 CONTROL BOX ASSY, OUTDOOR 4995AP2136V 1

— 21 —
Exploded View and Replacement Parts List
LN-0321CC/AC(F)
LOCATION No. DESCRIPTION LN-0321CC LN-0321AC(F) QUANTITY
546810 MOTOR ASSY, OUTDOOR 4681A20008M 1
552203-1 VALVE, SERVICE 2A00392F 1
552203-2 VALVE, SERVICE 2A00393A 1
554031 CONDENSER ASSY, BENT 5403A20066D 5403A20066D 1
554160 COMPRESSOR ASSY, FINAL 2A01196A 1
559010 FAN ASSY, PROPELLER 1A00195B 1
666000 SWITCH, MAGNET 2A00771F 1
W0CZZ-1 CAPACITOR, DRAWING 2A00986D 1
W0CZZ-2 CAPACITOR, DRAWING 2A00986A 1
667482 P.T.C ASSY - 1
649950 CONTROL BOX ASSY, OUTDOOR 4995AP2136S 1

— 22 —
Specification of components
LN-0320CC/AC(F) LN-0321CC/AC(F) LN-0420CC/AC(F) LN-0520CC/AC(F)
Comp P/No. 2A01169A 2A01169A 5417A20009A 2A01094E
MODEL NAME SQ036KAA SQ036KAA AVD5548EXN CRN5-0500-PFV
RLA 19 16 19.2 34.3
LRA 105 81 110 142
QUANTITY 1 1 1 1
INDOOR MOTOR P/No. 4681A20022H 4681A20022H 4681A20022H 4681A20022G
OUTPUT 347 W 347 W 347 W 345 W
SHAFT DIA 15mm 15mm 15mm 15mm
RPM 1,192 (Hi) 1,192 (Hi) 1,192 (Hi) 1,195 (Hi)
OUTDOOR MOTOR P/No. 4681A20008M 4681A20008M 4681A20039A 4681A20039A
OUTPUT 90 W 90 W 207 W 207 W
SHAFT DIA 12mm 12mm 15mm 15mm
RPM 930 930 970 970
QUANTITY 1 1 1 1
OUTDOOR FAN P/No. 2A00986B 1A00195B 5901A10010A 5901A10010A
Diameter 460 mm 460 mm 556 mm 556 mm
INDOOR BLOWER P/No. 2A00278U 2A00278U 2A00278M 2A00278M
Diameter*Width 190mm * 182mm 190mm * 182mm 190mm * 270mm 190mm * 270mm
CAPACITOR for COMP P/No. 2A00986A 2A00986A 2A00986A 6120AR2194T
SPEC 40µF, 370/400V, 50/60Hz 45µF, 370/400V, 50/60Hz 45µF, 370/400V, 50/60Hz 55µF, 370/400V, 50/60Hz
CAPACITOR for IDM P/No. 2A00986D 2A00986D 0CZZA20001B 0CZZA20001B
SPEC 6µF, 370/400V, 50/60Hz 6µF, 370/400V, 50/60Hz 15µF, 450V, 50Hz, 50MM 15µF, 450V, 50Hz, 50MM
CAPACITOR for ODM P/No. 2A00986D 2A00986D 2A00986D 2A00986D
SPEC 6µF, 370/400V, 50/60Hz 6µF, 370/400V, 50/60Hz 6µF, 370V/400, 50/60Hz 6µF, 370V/400, 50/60Hz
FILTER P/No. 5230A20003K 5230A20003K 5230A20003J 5230A20003J
SIZE 460mm * 460mm 460mm * 460mm 582mm * 484mm 582mm * 484mm
QUANTITY 1 1 1 1
CAPILLARY TUBE P/No. 3H01535E 3H01535E 5426AR3147P 3E92334N
SPEC ID1.6 * 900mm ID1.6 * 900mm ID1.6 * 900mm ID1.4 * 760mm
QUANTITY 4 4 4 6
TRANSFORMER P/No. 6171AQ2138G 6170A10001G 6171AQ2138G 6171AQ2138G
SPEC AC 250V/2A AC 250V/2A AC 250V/2A AC 250V/2A
QUANTITY 1 1 1 1
CONTACTOR for COMP P/No. 2A00771F 2A00771F 2A00771F 2A00771F
SPEC 40A, 24V CONTROL 40A, 24V CONTROL 40A, 24V CONTROL 40A, 24V CONTROL
RELAY for IDM P/No. 6920AP3194B 6920AP3194B 6920AP3194B 6920AP3194B
SPEC AC 24V, 20A AC 24V, 20A AC 24V, 20A AC 24V, 20A

— 23 —
April, 2002
P/No.: 3828A20220D Printed in Korea