Professional Documents
Culture Documents
1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4. Dimensional diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5. Circuit diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5.1 "COSIMAT N" and "QPF" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
7. Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.1 Regulating the mains coupling point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7.2 Reactive-current or cos phi balancing of AVK alternators operating in parallel with the mains . . . . . . 12
7.3 Reactive-current balancing of AVK alternators in isolated parallel operation . . . . . . . . . . . . . 13
7.4 Reactive-current balancing with an other-make alternator in isolated parallel operation . . . . . . . . 14
7.4.1 Measurement at other-make alternator . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
7.4.2 Measurement at the load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8. Starting up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
8.1 Flow chart for checking the "QPF" . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
9. Important notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1. General The main features of the "QPF" regulator are:
The main tasks of a regulating device for a synchronous ● Regulating facility for cos phi or reactive power.
threephase AC generator (alternator) are as follows:
● Wide adjusting range of PI regulating parameters (by
● Regulating the alternator voltage in isolated opera-tion potentiometer).
When the alternator is operating in parallel, at differing loads ● Standardised 4 ... 20 mA output (X-GND) for actual value
and when the mains voltage changes, it is necessary to adjust or manipulated variable.
the level of excitation constantly in order to obtain a stable
cos phi or a stable reactive-power supply from the alternator. ● Standardised 0 ... 20 mA or 4 ... 20 mA (with line rupture
identification) setpoint input.
Together with the "COSIMAT N", the "QPF" regulator allows
the cos phi value or reactive current to be regulated automat- ● Balancing and mains-coupling regulation possible by
ically. means of interconnection of several "QPF" regulators.
The "QPF" regulator is connected to the "COSIMAT N" by ● Fully sealed, for resistance to vibrations and environmen-
way of the N-M/m control leads. tal influences.
1
2. Functional description of "QPF" If the effective power falls, cos phi regulation cuts in again.
The "QPF" regulator measures the alternator voltage (U-W) The "QPF" allows various set value sources and ranges to be
and alternator current in phase (V). selected.
For measuring the current, a current transformer with internal The following set value sources can be selected:
burden (e.g. 7Ω / 10W for a ../1A transformer, 10VA) is
needed. ● External set value potentiometer.
The rated voltage and rated current are calibrated on the ● Internal set value potentiometer.
"QPF".
● External 0.20 mA or 4 ... 20 mA setpoint source.
These quantities, along with set, limit and adjusting values, are
processed by a microcontroller. The set value range "only excited" or "over- and under-excited"
can be adjusted.
All complex quantities (angle phi and reactive power) are
constantly recalculated and can be supplied to the stan- The adjusting signal of the PI regulator reaches the "COSIMAT N"
dardised output X-GND (4 ... 20 mA). by way of the control connections N-M/m and can also be
supplied at the X-GND output instead of the measuring
Cos phi or reactive power are regulated by a PI regulator. quantities.
The regulating parameters can be altered by potentiometers.
If several "QPF" regulators are arranged in an appropriate
During cos phi regulation, the limit zones circuit, mains coupling and balancing regulation of cos phi
or reactive power is also possible (see "Applications").
"minimum effective power"
The regulating function or the issuing of the actuating signal
and only takes place once the "QPF" regulator has been released
by a potential-free, normally-open contact (13-14).
"maximum reactive power"
The "QPF" functions are selected with an 8-pin encoding
are constantly monitored. switch (SEL1).
If the limit values are overstepped, reactive-power regulation Three LEDs indicate all relevant operating statuses.
automatically cuts in.
2
3. Technical data
3
4. Dimensions diagram
5. Circuit diagram
5.1 "COSIMAT N" and "QPF"
4
6. Connections, adjusting elements and The set value potentiometer is not needed.
displays Input resistance (S-A) with the power input is 100 Ω.
"only excited"
»13« - »14«
or
The "QPF" is released at these connections by a potenti-
al-free normally-open contact. It is released by closing the
"over- and under-excited"
contact.
can be adjusted (see "Adjusting elements" - SEL1).
»UH1/0« - »UH2/80 VAC« - »220 VAC«
The connecting lead should always be screened when
installed, with the screen installed at one end at connecti- Supply voltage
on »A«.
The reliable tolerance in supply voltage is +10 / -20%.
Set value potentiometers
The supply can be drawn from auxiliary windings or
Set value potentiometers should be connected up in such exciter machines, or if appropriate directly from the
a way that minimum alternator excitation is achieved at alternator or system voltage by way of matching transfor-
the left-hand limit (A = start, S = slipring are connected) mers.
and maximum excitation at the right-hand limit (E = end
and S are connected). Matching transformers should have an installed output of
at least 15 VA.
"Only over-excited"
The cos phi 1 or reactive power 0 is at the left-hand limit
of the set value potentiometer (A and S connected). »N« - »M/m«
The right-hand stop corresponds to the maximum over- "COSIMAT N" control lead
excited (inductive) value.
The control lead to the "COSIMAT N" should always be
"Over-excited/under-excited" screened when installed, with the screen installed at one
The centre position of the external potentiometer (approx. end at connection »GND« (at the "QPF").
2.5kΩ) corresponds to cos phi 1 or reactive power 0.
When turned to the right, the alternator moves into the
over-excited (inductive) range and when turned to the left »k« - »l«
it moves into the under-excited (capacitive) range.
Measuring the alternator current in phase V of the alter-
Set value power source nator.
The set value input can also be supplied from a 0 ... 20 Input k-l is not a power input !
mA or 4 ... 20mA power source if appropriately enco-
ded (SEL1.8). The appropriate current transformer (can be supplied)
must be in circuit with a load resistor.
The power-source positive terminal should be connected
to »S« and the negative terminal to »A«. At the rated alternator current, a voltage of 3 to 7 VAC
is required.
5
»X« - »GND« »UN CAL«
Actuating signal or actual value issued as 4 ... 20 mADC Calibration of the alternator rated voltage.
current.
A constant-voltage measuring device (digital multimeter)
The connecting lead should always be screened when should be connected to measuring points UN CAL (posi-
installed, with the screen installed at one end at connecti- tive at upper and negative at lower measuring point).
on »GND« (at the "QPF").
At the alternator rated voltage, set potentiometer UN CAL
The maximum load for the power source is 500Ω. to +4 VDC.
Actual-value output
6.2 Adjusting elements
"Only over-excited"
Cos phi 1 or reactive power 0 corresponds to 4 mA. The »P«
maximum over-excited value corresponds to 20 mA.
P parameter change of PI regulator.
"Over-excited/under-excited"
Cos phi 1 or reactive power 0 corresponds to 12 mA. Left-hand limit corresponds to:
The maximum over-excited value (cos phi 0) corresponds Minimum amplification of regulator difference.
to 20 mA. The maximum under-excited value (cos phi 0)
corresponds to 4 mA. Right-hand limit corresponds to:
Maximum amplification of regulator difference.
Actuating signal output
»Qmax«
»IN CAL«
Reactive power monitoring and limiting in cos phi regu-
Calibration of the alternator rated current. lating operation.
A constant-voltage measuring device (digital multimeter) Left-hand limit corresponds to: Minimum permitted reacti-
should be connected to measuring points IN CAL (positive ve power, corresponds to approx. 0.15xSN.
at upper and negative at lower measuring point).
Right-hand limit corresponds to: maximum permitted re-
At the alternator rated current, set potentiometer IN CAL active power, corresponds to approx. 0.75xSN.
to +4 VDC.
»IN CAL« and »UN CAL«: see 6.1 Connections.
At part load, the calibration value can be selected
proportionally (e.g. 0.5x IN = +2 VDC).
6
6.2.1 SEL1 encoding switch If the set value line is ruptured within the 4 ... 20 mA range,
no release for regulating is obtained. The fault is indicated by
The functions of the "QPF" regulator are selected with the 8-pin LED "A" flashing.
encoding switch SEL1 (see FIG. 3).
SEL1.3
NOTE
ON = set value over- and under-excited
Only adjust when de-energised (with the al-
ternator at a standstill). 3 = set value over-excited
5 = OFF
SEL1.2
In the "adjusting regulation" position, it is possible to balance
ON = set value 4... 20 mA the reactive power of AVK alternators in isolated/parallel
operation (see "Applications").
2 = OFF
All "QPF" regulators must be connected by the "C-GND"
SEL1.2 must be used in conjunction with SEL1.8 ! summation line.
7
When selecting balancing regulation, 6.2.1.1 Encoding
SEL1.8
8
6.2.1.2 Encoding examples
Example 1 Example 3
The "QPF" regulator is to be used as a cos phi regulator. It When AVK synchronous alternators are in isolated/parallel
should only be possible to select over-excited set values with operation, the reactive power is to be balanced automatically
an external potentiometer. by the "QPF" regulator.
Example 2 Example 4
The alternator’s reactive power is to be regulated. A 4 ... 20 mA The "QPF" regulator is intended to regulate the cos phi of the
set value is specified by an SPC. The set value may only be mains coupling point. The set value is selected at an external
modified within the over-excited range. potentiometer in the over-excited range. The manipulated
variable is issued at X-GND.
9
6.3 Displays
»Q«
»Phi«
»A«
The »A« LED comes on once the "QPF" regulator has been
released.
The »A« LED flashes if the set value line is interrupted in set
value format 4 ... 20 mA (= power input).
10
7. Applications
In addition to the individual application of the "QPF", there are various operating modes for cos phi or reactive-power
regulation/balancing.
Five operating modes which can be achieved by connecting up individual "QPF" units appropriately are presented below.
According to VDEW, a consumer’s installation must be operated at cos phi 0.9 to 1 (inductive) in order to avoid additional
costs for reactive energy (view from EVU into consumer’s installation).
The excitation of a synchronous alternator can be specifically adjusted when operating in parallel to the mains as a means of
reactive-power compensation.
For this purpose, a special version of the "QPF-" unit, the "QPF-NK" is used at the mains coupling point.
11
7.2 Reactive-current or cos phi balancing of AVK alternators operating in parallel with the mains
If several alternators are in operation in parallel to the mains, the cos phi of the individual alternators will normally be regulated.
"QPF" regulators permit set values to be specified from a central point (SPC).
The individual "QPF" regulators are released by actuating the appropriate alternator switch.
FIG. 9 Reactive-current or cos phi balancing of AVK alternators in operation in parallel with the mains
12
7.3 Reactive-current balancing of AVK alternators in isolated parallel operation
For isolated parallel operation of AVK synchronous alternators, regulated reactive-power balancing can be carried out by using
"QPF" regulators.
The "QPF" regulators may only be released if at least two alternators are being operated in parallel.
13
7.4 Reactive-current balancing with an other-make alternator in isolated parallel operation
The measurement at the other-make alternator is fed into the "QPF" regulator of the AVK alternator as a set value.
The "QPF" regulator on the other-make alternator need not be released separately as a measuring unit.
The "QPF" regulator on the AVK alternator may only be released once both alternators are in operation and delivering power.
FIG. 11 Reactive-current balancing with an other-make alternator by measuring at the other-make alternator
14
7.4.2 Measurement at the load
If a load coupling point is available, it is possible to take measurements here instead of at the other-make alternator. As a
measuring unit, the "QPF" unit at the load coupling point does not need to be released.
The "QPF" regulator on the AVK alternator may only be released once both alternators are in operation and delivering power.
15
8. Starting up ● Release "QPF".
The procedure for starting up described here refers to the isolated ● Since the basic setting at the "QPF" set value potentiometer
use of the "QPF" regulator, as described in FIG. 2. corresponds to cos phi 1 or reactive current 0, cos phi 1
is restored.
The flow diagram in FIG. 13 is a universally useful aid for
starting up. ● Remove release from "QPF".
Basic setting ● Set cos phi 1 at the set value potentiometer of the
"COSIMAT N".
»P« Centre position
»I« Centre position ● From this basic position, the "QPF" can now be released
»Qmax« Right-hand limit position in parallel operation.
»W« Centre position or left-hand limit
position, depending on encoding ● A tendency to oscillate can be damped by increasing the
I component and, if appropriate, reducing the P compo-
nent of the "QPF" parameter.
SEL1
The codes must be selected before starting up the unit. Qmax setting
Only adjust when de-energised (with the al- 0.6 (in kVar) of the apparent rated power, as "induc-tive/over-
ternator at a standstill). excited" reactive power, would therefore be permissible from
the point of view of the alternator. However, reactive power
Setpoint potentiometer must not normally be fed into the EVU network.
Set the setpoint potentiometer to starting position cos phi 1 or The Qmax basic setting (right-hand limit position) permits a
reactive current 0. maximum reactive power in cos phi operation that corre-
sponds to approx. 0.75 (in kVar) of the apparent rated power
Regulator release (if correctly calibrated).
Disconnect the release. The Qmax facility is effective for capacitive and inductive
reactive power.
Starting up
With Qmax limiting, however, the Qmax value is defined as
● Run alternator with "COSIMAT N" in parallel. an over-excited, i.e. inductive, set value.
● Switch DMM measuring unit to mADC and connect ● Slowly turn the Qmax from the right-hand limit position
positive to X and negative to GND. (the Qmax function acts after a delay of 4..5 seconds) to
● the left, until the LED "Q" flashes.
Select actual-value output at SEL 1.4.
● Reduce the effective power (the cos phi changes towards
● If "over-excitation only" has been selected at SEL1, the inductive "0") until LED "Q" goes out.
measuring unit now shows approx. 4 mADC.
If "over-excitation/under-excitation" has been selected, the ● Move Qmax slightly to the right.
measuring unit now shows approx. 12 mADC.
● Run the alternator again at rated effective output.
● If the alternator is now run further into the range of
over-excitation (e.g. cos phi 0.8 ind.), the measured ● Qmax must not respond. By turning Qmax slightly to the
value increases. right, the permissible reactive power for operating purpo-
ses is prevented from becoming the same as the Q max
● Continue to run the alternator at ind. cos phi 0.8. value.
16
8.1 Flow chart for checking the "QPF"
FIG. 13 shows a universal flow chart for checking the "QPF" settings and connections.
To prevent faults when starting up, this flow diagram must always be observed as it indicates all options of the "QPF" regulator
in summarized form.
17
9. Important notes
● The functions of the "QPF" are selected by the 8-pin SEL1
encoding switch.
18
AvK Deutschland GmbH & Co. KG
Bunsenstraße 17
85053 Ingolstadt, Germany
Phone: +49(0)841-792-0
Fax: +49(0)841-792-250
e-mail: infoavkin@newage-avkseg.com
www.newage-avkseg.com