Energy meter
Type EM2-DIN
• 6-dgt µP-based indicator
• Manual scrolling of partial and total energies:
kWh, kVArh.
• TRMS measurement of distorted waves (voltage/current)
• All configuration functions selectable by
built-in key-pad
• Password protection of programming parameters
• Front reset of partial energies
• Degree of protection (front): IP 40
• Optional serial RS 422/485 output (provided with
control relay)
• MODBUS, JBUS protocol.
Type Selection
Range code System Power supply Output
AV5: 250/433 VAC - 5 AAC 3: One phase, A: 24 VAC, -15% +10%, XX: No output (standard)
(max. 300 V (L-N)/ three-phase system, 50/60 Hz 1) XS: Serial output, RS 485
520 V (L-L) - 6 A) 3 or 4 wires, balan- B: 48 VAC, -15%+10%, multidrop bidirec-
ced load; 50/60 Hz 1) tional with control
three phase system, C: 115 VAC, -15% relay 1)
3 or 4 wires, unba- +10%, 50/60 Hz 1)
lanced load D: 230 VAC, -15%
+10%, 50/60 Hz
(standard)
1)
On request
Input Specifications
Accuracy (48 to 62 Hz) Temperature drift ±250 ppm/°C
(@ 25°C ±5°C, R.H. ≤ 60%) ±1% RDG (kWh) Display Backlighted LCD, h: 13mm,
±2% RDG (kvarh)
6-dgt
(hour time base) (PF≥0.7L/C,
0 to1.2In, 0.5 to 1.2Un) Decimal point position Automatic selection accord-
ing to the counted energy.
Additional errors
Max resolution: 1 Wh/1 VArh
Humidity <0.3% f.s., 60% to 90% R.H.
Min. resolution: 1 KWh/1 KVArh
Power supply ±0.5% RDG, -15 +10% p.s.
Magnetic field < 0.1% f.s. @ 400 A/m Max. and min. indication
Active energy Max. 999999 min. –199999
Rated input Reactive energy Max. 999999 min. 0
Current 2 inputs (one/three-phase Sampling rate 3 times / second
balanced load)
6 inputs (one/three-phase
unbalanced load)
Voltage 2 inputs (one/three-phase
balanced load)
4 inputs (one/three-phase
unbalanced load)
Insulation among the voltage and the
current inputs: 2000 Vrms;
among the current inputs:
2000 Vrms
Output Specifications
Relay output Data (bidirectional)
(only with RS485 output) Dynamic (reading only) System variables:
Type Driven only by the serial P, Q, cos ϕ, VL-L,
communication energies,
Contact Rating 1 x SPST (normally open) Single phase variables:
2 A, 250 VAC/DC, PL1, QL1, PFL1, VL1-N, AL1,
40 W/1200 VA 130.000 cycles PL2, QL2, PFL2, VL2-N, AL2,
Insulation By means of optocouplers, PL3, QL3, PFL3, VL3-N, AL3
4000 Vrms output to For the accuracy information
measuring input, refer to WM2-DIN
4000 Vrms output to Static (writing only) All programming data, reset
supply input. of energy:
Serial output (on request) - partial kWh
Type RS422/RS485; - partial kVArh
Multidrop bidirectional - total kWh
(static and dynamic - total kVArh
variables) Stored energy (EEPROM)
Connections 4 wires, max. distance ≤ 999999 kWh
1200 m, termination and/or ≤ 999999 kVArh
line bias by means of DIP- Data format 1-start bit, 8-data bit, no
switches directly on the parity/even parity, 1 stop bit
instrument Baud-rate 1200, 2400, 4800 and 9600
Addresses 255, selectable by key-pad selectable bauds
Protocol MODBUS/JBUS Insulation By means of optocouplers,
4000 Vrms output to
measuring inputs
4000 Vrms output to
supply input
Software Functions
Password Numeric code of max. 3 di- Programmable ratio 0.1 to 999.9
gits; 2 protection levels of Digital Filter
the programming data Filter operating range 0 to 100% of the
1st level Password “0”, no protection input electrical scale
2nd level Password from 1 to 255, all Filtering coefficient 1 to 64
data are protected Filter action Only on the variable being
Measurement scrolling total and partial active transmitted by the serial
energy (kWh), communication port
total and partial reactive
energy (kVArh)
Transformer ratio For CT up to 5000 A
Supply Specifications
AC voltage 230 VAC (standard), Power consumption ≤ 7 VA
-15%+10% 50/60 Hz
24 VAC, 48 VAC, 115 VAC
(on request),
-15%+10% 50/60 Hz
General Specifications
Operating temperature 0° to +50°C (32° to 122°F) Safety standards IEC 61010-1, EN 61010-1
(R.H. < 90% non-condensing) Connector Screw-type,
Storage temperature -10° to +60°C (14° to 140°F) max. 2.5 mm2 wires
(R.H. < 90% non-condensing) Housing
Insulation reference voltage 300 Vrms to ground Dimensions 6 DIN modules,
Insulation 4000 Vrms between all inputs/ 58.5 x 89 x 107 mm
outputs to ground Material ABS,
self-extinguishing: UL 94 V-0
Dielectric strength 4000 Vrms for 1 minute
Degree of protection Front: IP40
Noise rejection
CMRR 100 dB, 48 to 62 Hz Weight Approx. 500 g
(packing included)
EMC EN 50081-2, EN 50082-2
Approval CE
Mode of Operation
Waveform of the signals that can be measured
Wiring Diagrams
Single phase input connections
Fig. 1 Fig. 2
1 3 5 6 8 9 10 11 1 3 5 6 8 9 10 11
12 13 15 16 17 18 20 22 24 26 12 13 15 16 17 18 20 22 24 26
L L
Load N Source Load Source
N
Fig. 3 Fig. 4
1 3 5 6 8 9 10 11
1 3 5 6 8 9 10 11
12 13 15 16 17 18 20 22 24 26
12 13 15 16 17 18 20 22 24 26
L1 L1
L2 L2
Load L3 Source Load L3 Source
Fig. 5 Fig. 6
1 3 5 6 8 9 10 11
1 3 5 6 8 9 10 11
12 13 15 16 17 18 20 22 24 26
12 13 15 16 17 18 20 22 24 26
L1 L1
L2 L2
L3 L3
Load N Source Load N Source
Fig. 7 Fig. 8
1 3 5 6 8 9 10 11
1 3 5 6 8 9 10 11
12 13 15 16 17 18 20 22 24 26
12 13 15 16 17 18 20 22 24 26
L1 L1
L2 L2
Load L3 Source Load L3 Source
Fig. 9 Fig. 10
1 3 5 6 8 9 10 11
1 3 5 6 8 9 10 11
12 13 15 16 17 18 20 22 24 26
12 13 15 16 17 18 20 22 24 26
L1
L1
L2 L2
L3 L3
Load N Source Load N Source
KWh R
2. Display
2 L1 L2 L3 TOT KVArh
L
- 6-digit (maximum read-out 999999).
EM 2 -D IN EN ERGY M ETER
Alphanumeric indication by means of LCD display for:
- Displaying the configuration parameters
3 - All the measured variables.
” ” and ” ”
- To scroll all the basic measurements (system variables)
kWh kWh
L partial
total
kVARh L kVARh
total partial
Terminal boards
Dimensions
108 mm
89 mm
45 mm
90 mm
R
46
107 mm
49.5 mm
58.5 mm