Type Selection
Range code Measurement Power supply 1st output
AV5: 250/433 VAC - 5 AAC 3: One phase, three-phase A: 24 VAC, -15% +10%, XX: No output (standard)
(max. 300 V (L-N)/ system, 3 or 4 wires, 50/60 Hz 1) 2) O1: Single open collector
520 V (L-L) - 6 A) balanced load; B: 48 VAC, -15%+10%, output (30 V/100 mADC)1)
AV7: 400/690 VAC - 5 AAC three phase system, 50/60 Hz 1) 2) O2: Dual open collector
(max. 480 V (L-N)/ 3 or 4 wires, C: 115 VAC, -15%+10%, output (30 V/100 mADC)1)
830 V (L-L) - 6 A) 1) unbalanced load 50/60 Hz 1) 2) R1: Single relay output
D: 230 VAC, -15%+10%, (AC1-8 AAC, 250 VAC)1)
50/60 Hz (standard) 2) R2: Dual relay output
L: 18 to 60 VDC/AC 3) (AC1-8 AAC, 250 VAC)1)
H: 90 to 260 VDC/AC 3)
1)
2nd output
On request
2)
This power supply cannot be used if the RS485 module is needed X: No output (standard)
3)
Compatibel with any kind of output
S: Serial output, RS 485
multidrop bidirec-
tional 1)
Input Specifications
Accuracy (48 to 62 Hz) Un: 250 V (AV5), 400 V (AV7) Rated input
In: 5A Current 2 inputs (one/three-phase
Voltage/current balanced load)
(@ 25°C ± 5°C, R.H. ≤ 60%) ±0.5% f.s. (0 to 1.2 In, 6 inputs (one/three-phase
0.5 to 1.2 Un) unbalanced load)
Voltage 2 inputs (one/three-phase
Active power/energy balanced load)
(@ 25°C ± 5°C, R.H. ≤ 60%) ±1% f.s. (PF ≥ 0.7 L/C, 4 inputs (one/three-phase
0 to 1.2 In, 0.5 to 1.2 Un) unbalanced load)
Reactive power/energy Insulation among the voltage and the
(@ 25°C ± 5°C, R.H. ≤ 60%) ±1% f.s. (PF ≥ 0.7 L/C, current inputs: 2000Vrms;
0 to 1 In, 0 to 1 Un) among the current inputs:
Power factor (PF) 2000 Vrms
(@ 25°C ± 5°C, R.H. ≤ 60%) ±1% f.s., (PF ≥ 0.7 L/C, Temperature drift ±250 ppm/°C
0.6 to 1.2 In, 1 to 1.2 Un)
Display Backlighted LCD, h 13mm,
Additional errors 3-dgt (instantaneous meas.)
Humidity < 0.3% f.s., 60% to 90% R.H. 6-dgt (energies)
Power supply ±0.5% rdg, -15 +10% p.s.
Magnetic field < 0.1% f.s. @ 400 A/m
Output Specifications
Pulse output (on request) Data (bidirectional)
Static type From 0.1 to 999.9 pro- Dynamic (reading only) System variables:
(according to DIN 43864) grammable pulses for kWh, P, Q, PF, VL-L,
KVArh, open collector (NPN energies,
transistor) Single phase variables:
VON 1.2 VDC/ max. 100 mA PL1, QL1, PFL1, VL1-N, AL1,
VOFF 30 VDC max. PL2, QL2, PFL2, VL2-N, AL2,
Relay type 1 x SPDT PL3, QL3, PFL3, VL3-N, AL3
AC 1 - 8 A, 250 VAC Static (writing only) All programming data, reset
DC 12 - 5 A, 24 VDC of energy:
AC 15 - 2.5 A, 250 VAC - partial kWh
DC 13 - 2.5 A, 24 VDC - partial kVArh
Pulse duration 200 ms (ON), ≥ 200 ms (OFF) - total kWh
Insulation By means of optocouplers, - total kVArh
4000 Vrms output to Stored energy (EEPROM)
measuring input, ≤ 999999 kWh
4000 Vrms output to ≤ 999999 kVArh
supply input. Data format 1-start bit, 8-data bit, no
Serial output (on request) parity/even parity, 1 stop bit
Type RS422/RS485; Baud-rate 1200, 2400, 4800 and 9600
Multidrop bidirectional (static selectable bauds
and dynamic variables) Insulation By means of optocouplers,
Connections 2 or 4 wires, max. distance 4000 Vrms output to
1200 m, termination directly measuring inputs
on the module 4000 Vrms output to
Adresses 1 to 255, selectable supply input
by key-pad
Protocol MODBUS/JBUS
Software Functions
Password Numeric code of max. 3 di- Example: the CT is a
gits; 2 protection levels of 100A/5A so the ratio is 20,
the programming data consequently the maximum
1st level Password “0”, no protection counted energy is 299980
2nd level Password from 1 to 255, all kWh or kVArh.
data are protected Single phase: Active power (kW),
Measurement scrolling reactive power (kVAr),
System: Active power (kW), power factor (cos ϕ),
reactive power (kVAr), current (A),
power factor (cos ϕ), phase-neutral voltage (V)
current (A), Transformer ratio For CT up to 5000 A
average phase-phase volt- Programmable ratio 0.1 to 999.9
age (V)
total and partial active ener- Digital Filter
gy (kWh), Filter operating range 0 to 100% of the
total and partial reactive input electrical scale
energy (kVArh) Filtering coefficient 1 to 64
Partial energy meters: Filter action On the display and on the
the counters of kWh and variable being transmitted
kVArh are automatically by the serial communication
reset when the energy port.
reaches the value
(14999*CT).
Supply Specifications
AC voltage 230 VAC (standard), Power consumption ≤ 30 VA/12 W (90 to 260 V)
-15%+10% 50/60 Hz ≤ 20 VA/12 W (18 to 60 V)
24 VAC, 48 VAC, 115 VAC
(on request),
-15% +10% 50/60 Hz
18 to 60 VDC/AC
90 to 260 VDC/AC
General Specifications
Operating temperature 0° to +50°C (32° to 122°F) Degree of protection Front: IP65
(R.H. < 90% non-condensing) Weight Approx. 500 g
Storage temperature -10° to +60°C (14° to 140°F) (packing included)
(R.H. < 90% non-condensing)
Insulation reference voltage 300 Vrms to ground
Insulation 4000 Vrms between all inputs/
outputs to ground
Dielectric strength 4000 Vrms for 1 minute
Noise rejection
CMRR 100 dB, 48 to 62 Hz
EMC EN 50 081-2, EN 50 082-2
Safety standards IEC 61010-1, EN 61010-1
Other standards Pulse output: DIN43864
Connector Screw-type,
max. 2.5 mm2 wires x 2
Housing
Dimensions 96 x 96 x 140 mm
Material ABS,
self-extinguishing: UL 94 V-0
Mode of Operation
Accuracy class of the instrument as a relation of PI/Pn and cos ϕ (power factor)
2%
2%
1%
1%
5%
AV5 Un: 250 V Un: 430 V In: 5 A UI = 400 V (delta voltage) UI = 230 V
II = 265 A (single phase cur- II = 110 A (CT=300A)
rent)
Cos ϕ = 0.85 (system power Cos ϕ = 0.85 (sin ϕ = 0.52)
factor) (CT=300A) Un = 250 V
Un = 430 V In = 5 A
PI/QI (installation power) Pn /Qn (rated power of the In = 5 A
CT (ratio) = 300
One phase system: instrument): A
5 A = 60
PI = UI · II · cos ϕ One phase system: CT (ratio) = 300
5 = 60
QI = UI · II · sin ϕ Pn = Qn = Un · In · CT(ratio)
QI = 3 · UI · II · sin ϕ
Three phase, 3-wire system: Three phase, 3-wire system: PI = √3 · UI · II · cos ϕ = 3 · 230 · 110 · 0.52
= √3 · 400 · 265 · 0.85 = 39.46 kVAr
PI = √3 · UI · II · cos ϕ
Pn = Qn = √3 · Un · In · CT(ratio) = 155.87 kW
QI = √3 · UI · II · sin ϕ QI = 3 · Un · In · CT (ratio)
Three phase, 4-wire system: Pn = √3 · Un · In · CT (ratio) = 3 · 250 · 5 · 60
Three phase, 4-wire system:
Pn = Qn = 3 · Un · In · CT(ratio) = √3 · 430 · 5 · 60 = 225 kVAr
PI = 3 · UI · II · cos ϕ = 233.17 kW
QI = 3 · UI · II · sin ϕ where: PI 155.87 PI 39.46
Un = the rated input voltage = = 0.698 = = 0.175
where: Pn 223.17 Pn 225
of WM2-96.
UI = the real star voltage of
In = the rated input current of
the electrical system being WM2-96. In both examples the accura-
measured. CT (ratio) = the value of the
cy of the measurement is
I = the maximum phase cur- 1% f.s. when considering the
current transformer ratio.
rent of the electrical system changing of the measured
being measured. voltage from 0.9Un to 1Un
Cos ϕ = the average cos ϕ of and the measured current
the electrical system being from 0.1In to 0.9In with a
measured. cos ϕ of 0.85 (sin ϕ 0.52).
Wiring Diagrams
Single phase input connections
Fig. 1 Fig. 2
2. Display
Instantaneous measurements:
1 - 3-digit (maximum read-out 999)
Energies:
- 6-digit (maximum read-out 999999).
” ” and ” ”
- To scroll all the basic measurements (system variables)
- To increase or decrease programming values
V L1 - L2 - L3 V L1 V L2 V L3
(average)
L (V L1-N ) L (V L2-N ) L (V L3-N )
I L1 L2 L3 L I L1 L I L2 L I L3
kW L kW L kW L2 L kW L3
L1
L1 L2 L3
kWh kWh
total
L partial
kVARh L kVARh
total partial
Available Modules
Dimensions
Terminal Boards
AR1034
RS485 output