Features:
Accuracy class 1.0 as per IEC 62053-21(0.5S option).
Auto scrolling.
Advanced circuitry for accurate measurements, Parameter name & value displaying using 7 seg LEDs.
multiple communication option
6 digits display on each row for better readability.
Cost effective, user friendly load manager Automatic switching of display based on input source
- can be integrated with EMS. (EB/DG).
Load hours and ON hours for both sources.
Programmable to kWh or kVAh.
‘OLD' registers to store the previously cleared energy values.
Technical Specification: Additional Features:
LG+ 5220
Accuracy: Class 1 Default as per IEC 62053-21, Class 0.5 as per IEC 62053-22.
2 Row display with 6 digits each.
Sensing/Measurement:
True RMS, 1 Sec update time. 4 Quadrant Power & Energy. Simultaneous display of Energy for EB & DG in single page.
Input voltage: 4 Voltage inputs (VR, VY, VB, VN). Displays Basic : VLL, VLn, A (Avg. & PW), F.
Programmable 110 or 415V LL Nominal (Range 50 to 550V LL).
Primary Programmable up to 999 kV. Power : W, PF (Avg. & PW).
Burden: 0.2VA Max. per phase. Energy : Wh, LH, ON hrs, OLD Wh, OLD LH
Input current: (both for EB & DG)
Current inputs (AR, AY, AB) 500mA - 6A (Field configurable 1A or 5A).
Primary programmable up to 99 kA. Optional - Programmable relay output upto 2 relays.
Overload: 10A max continuous, 50A max for 3 Sec. Options : Under Voltage, Over Voltage, Under Amps, Over
Burden: 0.2VA Max. per phase. Amps, Under Frequency, Over Frequency, Under PF, Over
Input Frequency: 45Hz to 65Hz Watts, Over Wh, and Phase missing (both for EB & DG).
Aux-Supply (Control Power): 80 - 300V AC/DC Programmable tripping time upto 180 sec with hysteresis
(DC optional), 40-70Hz. of 1%.
Burden: 5VA Max LG+ 3220 (Two Row) / 3121 (Single Row)
Display Type:
10mm height bright red LED display. 2 Row display with 6 digits each.
and water
Panel 92 mm
Test of resistance to heat and fire IEC 60695-2
IEC 61010 – 1
92 mm
Safety standard
Note: Additional error of 0.1% of full scale, for meter input current below 500mA
Range of Products: Building Energy Management System (BEMS) | EMS | Demand Controller | Multifunction Meters | Electronic Energy Meters | Dual Energy Meter | Digital Panel Meters
| Automatic Changeover with Current Limiter (ACCL) |Power Factor Controller (PFC) | Earth Leakage Relay (ELR) | Earth Fault Relay (EFR) | Gateway | Branch Monitoring Unit | Smart Input
Output | Transducers | Converters