Installation Sheet

Brass Immersion Well (4 Inch)


Order number: 4190-1104, WAC 4190-1104

The immersion well is made of a solid single piece of brass to ensure reliability and durability. It is 4¼ inches
long and extends approximately 2½ inches into the pipe. Sensors (4190-1102, 4190-1103, and 4190-1105) are
shipped with a ½ inch fitting that allows the sensors to screw directly into the well (see the illustration below).
Note: A small amount of thermal compound (4190-1114) is recommended to ensure optimal results.

Tee or elbow for mounting the well

Flo
w

Sensor mounting nut

Immersion sensor

Immersion well (solid brass) Well installation (angle facing into the flow)

Mounting the Immersion Well


To mount the well:
1. Install the well into the pipe using a ¾ inch FNPT saddle or Thredolet™ (supplied by other vendors)
Note: To ensure maximum strength, install the well at an angle facing the flow.
2. Fill the well with thermal compound (4190-1114) for optimum temperature sensing.
3. Screw the sensor into the well using the ½ inch MNPT fitting supplied with each sensor (4190-1102, 4190-1103, and
4190-1105).

May 2008 © 2008 Trane All rights reserved 3270 3281 G


Trane and the Trane logo are trademarks of Trane in the United States and other countries. All trademarks
referenced in this document are the trademarks of their respective owners.

Literature Order Number 3270 3281 G


Date May 2008
www.trane.com
Supersedes 3270 3281 F
For more information, contact your local Trane
office or e-mail us at comfort@trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice.

You might also like