Oil Filled Cable & Accessories

Oil Filled Power Cable


P4
Supply Records of Oil Filled Power Cable P4

Characteristics P5

System Design P6

P9
Taihan s Oil Filled Power Cable

Manufacturing Facilities and Checkpoints of Quality Control

Tests P13

Construction P14

Accessories P18

Installation P22
TAIHAN ELECTRIC WIRE
P4 1978 Started Supply and Installation of 154kV OF Cable to
KEPCO, Korea.

1983 Contracted with TNB for Turnkey Project of 132kV OF


Cable Underground Network in Kuala Lumpur, Malaysia.

1985 Contracted with Dubai Electricity Company for Turnkey


Project of 132kV OF Cable Underground Network in
United Arab Emirates.

1986 Contracted with TNB for Turnkey Project of 132kV OF


Cable Underground Network in kuala Lumpur, Malaysia.

1988 Contracted with PLN for 150kV OF Cable Underground


Network Project in Surabaya, Indonesia.

1991 Contracted with Dubai Electricity Comapnay for Turnkey


Project of 132kV OF Cable Underground Network in
United Arab Emirates.
Taihan s Oil Filled Power Cable

1992 Started Supply and Installation of 345kV OF Cable to


KEPCO, Korea.
Supply Records of Oil Filled Power Cable
1994 Contracted with PLN for 150kV OF Cable Underground
Network Project in Semarang, Indonesia.

1995 Contracted with TNB for Turnkey Project of 132kV OF


Cable Underground Network in Malaysia.

Contracted with Meta-Epsi for Turnkey Project of 150kV


OF Cable Underground Network in Jakarta, Malaysia.

1996 Contracted with TNB for Turnkey Project of 132kV OF


Cable Underground Network in Kuala Lumpur City
Center, Malaysia.

1998 Contracted with SCECO-C for Turnkey Project of 132kV


OF Cable Underground Network in Riyadh, Saudi
Arabia.

1999 Contracted with TNB for Turnkey Project of 275kV OF


Cable Underground Network in Malaysia.

2000 Contracted with TPC for Turnkey Project of 161kV OF


Cable Underground Network in Taiwan.

2002 Contracted with TPC for Turnkey Project of 161kV OF


Cable Underground Network in Taiwan.
Characteristics
Through incessant research and development, the excellent functions of oil filled cable has been
improved since 1924.
Among the many excellent characteristics, some typical ones can be listed as follows.

There is absolutely no void within insulation


and is stable electrically.
The insulation oil, whose air bubbles and humidity are
sufficiently removed by performing degassing treatment, is
impregnated in insulating paper layer which is fully dried
under high vacuum beforehand and kept under high
degree of vacuum, and the cable is made accordingly.
Since a definite positive pressure is always kept inside of
the finished cable, there is absolutely no void in the cable

Taihan s Oil Filled Power Cable


insulation.

Operating potential gradient can be large.


Since no deterioration takes place in voids in the insulation
by ionizations as in the case with the solid-type cable, the
operating potential gradient can be large. Therefore, the
insulation thickness can be selected as thin.

Expansion and contraction of insulation oil


due to temperature change can be com-
pensated by the oil tanks.
Expansion and contraction of insulating oil, due to change
of load under use or due to change of the external
temperature, can be fully compensated by the oil tank
installed in a suitable position on the cable route.
Therefore, there can be no void in the insulation.

Possibility of cable self-monitoring


The inside of the cable is always kept at positive oil
pressure so that no humidity intrudes from the outside in
case damage occurs in the cable sheath, or in the joint
box. Further, in case the insulating oil leaks, the trouble is
detected earlier as the alarm device actuates and it is
possible to repair before occurrance of full-scale trouble in
the cable system.

P5
P6

System Design
OF cable system can be derived from economical decision and maker s engineering capability about
super high tension engineering. The reason is that many sites, around the world, have their own
characteristics, for instances, swamp or desert, field or mountain, and inland or seaside. So pracrical route
survey can only give precise answer just suitable to its own geographical characteristics.
We, Taihan based upon the accumulated technical know-how, have the capability to design any kind
of cable system requried and install at any site under any circumstances.
By the calculation through computer, cable and accessories can be fixed to make a turn-key system
for OF cable.

Cable Design
Taihan manufactures oil filled cables according to the following specification and accomplishes design and manufacture of
oil filled cables which are suitable for using conditions to meet the following requirements.
1) Standard specification 2) Cable design parameters
IEC : International Electrotechnical Commission a. Maximum Permissible Oil Pressure
b. Nominal Voltage and Conductor Sectional Area
Taihan s Oil Filled Power Cable

BS : British Standard(U.K)
AEIC : Association of Edition Illuminating c. Protective Cover
Company(U.S.A)
Taihan Standard : Taihan Electric Wire Co., Ltd.
Others

a. Maximum permissible Oil Pressure


Maximum Permissible Oil Pressure ( / )
Oil Pressure Type
Normal Operation Transient Operation
Low-Pressure 3 6
Medium-Pressure 6~8 11 ~ 14

b. Nominal Voltage and Conductor Sectional Area


Nominal Voltage Number of Conductor
(KV) Core Sectional Area ( ) Type
Upto 800 Hollow circular
Single
110 ~ 154 1,000 ~ 2,000 Segmental hollow
Three Upto 400 Compact round
Upto 800 Hollow circular
220 ~ 345 Single
1,000 ~ 2,000 Segmental hollow

c. Protective Cover
Metalic Sheath Reinforcement Armor Anti-corrosion Layer
Steel Tape Compound Jute
Lead Stainless Steel
- PVC or Polyethylene
Corrugated Aluminum - - PVC or Polyethylene
Note : Submarine cable is protected with steel tape and/or wire.
Oil Feeding System
Selection of proper oil feeding system is one of the most important factors in the system design. We, Taihan OF cable
engineers, will design any kind of feeding system to meet the requirement of our customer. We will install our OF cable
system at any site whether normal or difficult.
The general principle of oil feeding system can be explained hereunder.
1) The minimum oil pressure should be above 0.2 / at any time and any position.

2) The distance necessary to feed the oil and the place to fix the oil feeding tank must be investigated first, and then the
kind and volume of oil tank can be fixed.

Taihan s Oil Filled Power Cable

Single Core OF Cable


Outdoor Sealing End
Sealing End for SF6 Switchgear
Insulation Joint
Stop Insulation Joint
Straight Through Joint
Oil Pressure Tank
Gauge Panel
Link Box for Cross Bonding with Surge Diverter
Alarm Receiver
Oil Feeding Pipe
Control Cable

P7
P8

System Design Flow Chart

Selection of Cable Route


and Laying Method

Power Capacity
Determination

Route Survey

Selection of Optimum
Size of Conductor
Taihan s Oil Filled Power Cable

(Current Carrying Capacity)

Sheath Loss and Induced


Route Profile Off-set Calculation
Voltage Calculation

Selection of Stop Cable Manufacturing Consideration of the


Joint Position Condition Space for Future

Selection of Oil Feeding Consideration of


Transportation Condition
Tank Position Electromagnetic
Inducement

Determination of Oil Cable Pulling Tension


Feeding Method Calculation

Determination of Cable
Span

Fixing System Design


Manufacturing Facilities and
Checkpoints of Quality Control
The quality of a Taihan cable starts with select-ing and using only the best raw material. Be-fore
Taihan cables are manufactured the cop-per, aluminum, lead and lead alloy, paper, oil and
plastic etc. are all tested in raw mate-rial form. A fully equip-ped laboratory carries out
numerous tests, physical, analytical, chemical, electrical and mechanical. And throughout the
manu-facturing stages, further tests ensure that pro-duct quality is main-tained.

Taihan s Oil Filled Power Cable


Paper Lapping Machine
With full automatic tension control apparatus, our paper lapping machine, made by Pirelli in Italy, can manufacture OF
cable up to 345kV by a single passage

Paper lapping tension Bending test immediately after paper lapping


The lapping tension of paper is calculated by a When the leading end has passed the hauling ma-
computer which considers the type of paper, the width chine, a sample in the length of several meters is
of paper, and the diameter on which the paper is subjected to a bending test in order to ascertain that the
lapped. condition of paper lapping is suitable to working
standard.
Humidity control
Paper lapping machines are installed in an special
control room in order to keep the humidity in the room.
The room is kept at slightly higher than atmospheric
pressure so that the entry of dust, litter and fine
particles of metal which are detrimental to the insulation
of cable can be prevented.

P9
P10

Cabler
Besides singe core, all kind of cables should be passed this machine for cabling. Smooth and clean pass lines for paper
core are essential to manufacture high quality cable.

Drying Tank
Dielectric power loss, one of the important characteristics of OF cable can be achieved by complete drying method.

Temperature control of drying tanks Vacuum degree

The temperature of drying tank is measured at several The vacuum degree of a drying tank is measured at two
points, recorded continuously, and checked to make sure points, recorded continuously, and checked. Vacuum
that the temperature is held within the control limit. pumps are in automatic operation and when something
goes wrong, they activate and alarm on the central
Temperature control of conductor during heating control panel.

During the initial hours of drying, the cable is heated by Control of drying period
an electric current flowing directly through its conductor,
which is called the electric current drying method. In this The manufacturing standard specifies the period of
period, a program controller developed by our company drying according to the type of cable to avoid insufficient
controls the speed of temperature rise automatically and or excessive drying. ln addition to that, the drop test and
records the temperature. leak test of drying tank utilizing the relationship between
Taihan s Oil Filled Power Cable

the residual moisture content in paper and its equilibrium


vapor pressure tell us whether or not the operation is
within the contrl limit.
Insulating Oil Degasifier and Impregnating Panel
This equipments can degas and refine the insulating oil, alkylbenzene type synthetic oil,
to give and excellent insulating stability for cable.
Affer vacuum sheath process, degassed and refined oil can be put into cable.

Degasifying Inspection of oil before


oil-impregnation
Before degasifying, the oil is stored in a
low vacuum tank, the vacuum degree The state of oil entering into a vacuum
being monitored, as the pretreatment. bottle is oberved to ascertain if the oil
During degasification, the vacuum contains bubbles or foreign matter. A
degree is continuously recorded, and sampling test for resistivity, power
the rate of oil flow is automatically factor, and water content is also carried
controlled to the vacuum degree so as out.
to obtain a uniform degasification
degree. Vacuum degree control during
After degasifying, the resistivity,
power factor, water content for all oil are
oil- impregnation
measured. In order to reduce moisture
infiltration, the oil is held under the The vacuum degree of the cable during
pressure of nitrogen during storage. oil-impregnation is measured and
recorded by a worker every two hours.

Taihan s Oil Filled Power Cable


Electromagnetic valves mounted on an
Control of vacuum degree of oil-impregnating panel automatically
cable before oil-impregnation close in case of failure of power supply
or abnormally low vacuum degree, thus
Usually, after the aluminum sheath protecting the cable from the entrance
covering, vacuum degree of cables has of air.
to be checked before being impreg-
nated with oil. This period is utilized to Completion of oil-impregnation
measure the vacuum degree of the
cable just before oil-impregnation in The judgement that oil-impregnation is
order to make sure the aluminum completed is made when the oil
sheath is no pinhole. pressure ceases to drop.

P11
P12

Vacuum Sheathing Equipment


To withstand inner oil pressure and prevent outer mechanical shock, OF cable should be made with metallic layer. To
maintain the low moisture contents of dried insulation paper while sheathing metal layer, OF cable should be made under
the vacuum continuously.
The manufacturing condition for Aluminum Press and Lead Extruder is almost same. For instance, working condition of
aluminum press is as follows.

Vacuum sheathing Temperature control

After the completion of drying, the cable is covered with The temperatures of the die-block, the ingot heating
an aluminum sheath while still being held in high vacuum furnace, and ingots are continuously recorded for
degree. Throughout this process, the vacuum degree in consistent operation.
the cable is monitored and recorded continuously, and
any abnormality in vacuum degree triggers and alarm. Surface inspection

Automatic operation As the metallic sheath is one of the vital parts of oil filled
cables, its surface is inspected continuously in order to
The aluminum press has fully automatic operation to confirm that surface damage, pinhole, and other defects
avoid human error and to obtain stablized quality. do not exist.
Taihan s Oil Filled Power Cable

Machine for Reinforced Tapes


After lead sheathing, non-magnetic tapes for example stainless tape, will be wrapped on the lead sheath to reinforce the
creep characteristics.

PE/PVC Extruder
As an anti-corrosion protection, in many cases underground cable is used with plastic outer sheathes.
Tests
Before the cables leave factory for their destinations all over the world, a thorough program of
extensive testing is carried out.

Routine Test
The tests are carried out on all supplied lengths and the
results are recorded. The scope of the test is mainly
based on IEC 141-1.

Type Tests
Each new type of cable is submitted to a type approval
test that is executed in our high voltage research
laboratory. A type tests on short cable lenghs may be
agreed. If proof is provided that type tests have

Taihan s Oil Filled Power Cable


previously been carried out on cables of similar
construction, no further test needs to be carried out.
The scope of the test is mainly based on IEC 141-1.

Site Tests
The scope of the tests after installation is mainly based
on IEC 141-1.

P13
P14
Construction
Single Core
Conductor Insulation Aluminum Sheath
Rated Oil Passage Thickness Thickness Approx.
Nominal Approx. Overall
Voltage Thickness Material Thickness of of
Area I.D of O.D Dia.
Steel Sprial Sheath Jacket of Cable
kV mm2 mm mm mm mm mm mm mm

600 18.0 0.8 37.9 23.4 2.3 6.0 118


800 18.0 0.8 42.0 23.4 2.4 6.0 122
1200 18.0 0.8 47.2 23.4 2.5 6.0 129
Kraft
1400 18.0 0.8 50.3 23.4 2.6 6.0 133
Paper
1600 18.0 0.8 53.3 23.4 2.6 6.0 136
1800 18.0 0.8 56.1 23.4 2.7 6.0 140
345
Taihan s Oil Filled Power Cable

2000 18.0 0.8 58.8 23.4 2.8 6.0 143


BIL =
600 18.0 0.8 37.9 19.5 2.2 6.0 107
1,300kV
800 18.0 0.8 42.0 19.5 2.3 6.0 114
1200 18.0 0.8 47.2 19.5 2.4 6.0 120
1400 18.0 0.8 50.3 PPLP 19.5 2.4 6.0 124
1600 18.0 0.8 53.3 19.5 2.5 6.0 127
1800 18.0 0.8 56.1 19.5 2.5 6.0 130
2000 18.0 0.8 58.8 19.5 2.6 6.0 134
600 14.0 0.8 35.6 19.5 2.1 6.0 106
800 14.0 0.8 40.6 19.5 2.2 6.0 112
1200 14.0 0.8 45.7 19.5 2.4 6.0 118
Kraft
1400 14.0 0.8 48.9 19.5 2.4 6.0 122
Paper
1600 14.0 0.8 51.9 19.5 2.5 6.0 126
1800 14.0 0.8 54.8 19.5 2.5 6.0 129
275
2000 14.0 0.8 57.5 19.5 2.6 6.0 132
BIL =
600 14.0 0.8 35.6 17.5 2.0 6.0 99
1,050kV
800 14.0 0.8 40.6 17.5 2.1 6.0 105
1200 14.0 0.8 45.7 17.5 2.3 6.0 114
1400 14.0 0.8 48.9 PPLP 17.5 2.3 6.0 117
1600 14.0 0.8 51.9 17.5 2.4 6.0 121
1800 14.0 0.8 54.8 17.5 2.4 6.0 124
2000 14.0 0.8 57.5 17.5 2.5 6.0 128
Lead Sheath
Maximum Maximum
Approx. Approx. Thickness Thickness Approx. Approx. Approx.
Volume Overall Volume Conductor Electrostatic
Cable of of Cable
of Cable Dia. of Cable Resistance Capacity
Weight Oil Sheath Jacket of Cable Weight Oil
kg/km Ir/km mm mm mm kg/km Ir/km /km, 20 /km, 20

19,500 3,900 3.7 6.0 111 29,500 3,100 0.0299 0.27


22,000 4,250 3.8 6.0 115 32,900 3,360 0.0227 0.29
26,900 4,640 3.9 6.0 121 38,600 3,660 0.0151 0.31
29,500 4,920 4.0 6.0 125 41,800 3,870 0.0131 0.33
31,900 5,160 4.1 6.0 128 45,100 4,080 0.0114 0.34
34,500 5,420 4.1 6.0 131 47,900 4,280 0.0102 0.36

Taihan s Oil Filled Power Cable


37,200 5,680 4.2 6.0 134 51,100 4,470 0.00915 0.37
17,200 2,580 3.5 6.0 103 26,100 1,750 0.0299 0.25
20,000 2,990 3.6 6.0 107 29,300 2,210 0.0277 0.27
24,600 3,270 3.7 6.0 113 34,800 2,400 0.0151 0.30
27,000 3,450 3.8 6.0 116 38,000 2,560 0.0131 0.31
29,600 3,070 3.9 6.0 119 41,000 2,720 0.0114 0.33
32,000 3,850 3.9 6.0 123 43,800 2,870 0.0102 0.34
34,500 4,070 4.0 6.0 125 47,000 3,020 0.00915 0.35
16,700 2,940 3.4 6.0 100 24,800 2,290 0.0299 0.28
19,800 3,320 3.5 6.0 105 28,700 2,600 0.0227 0.31
24,200 3,630 3.7 6.0 111 34,400 2,830 0.0151 0.35
26,800 3,880 3.8 6.0 115 37,500 3,020 0.0131 0.37
29,300 4,110 3.8 6.0 118 40,300 3,190 0.0122 0.39
31,700 4,320 3.9 6.0 121 43,300 3,370 0.0102 0.40
34,300 4,560 4.0 6.0 124 46,600 3,550 0.00915 0.42
15,400 2,070 3.3 6.0 96 23,100 1,600 0.0299 0.26
18,400 2,500 3.4 6.0 101 26,900 1,840 0.0277 0.29
23,100 2,770 3.6 6.0 107 32,500 2,000 0.0151 0.32
25,600 2,940 3.7 6.0 110 35,600 2,150 0.0131 0.33
28,100 3,140 3.7 6.0 114 38,400 2,290 0.0122 0.35
30,400 3,310 3.8 6.0 117 41,400 2,440 0.0102 0.36
32,900 3,500 3.9 6.0 120 44,500 2,570 0.00915 0.38

P15
P16

Construction
Conductor Insulation Aluminum Sheath
Rated Oil Passage Thickness Thickness Approx.
Nominal Approx. Overall
Voltage Thickness Material Thickness of of
Area I.D of O.D Dia.
Steel Sprial Sheath Jacket of Cable
kV mm2 mm mm mm mm mm mm mm

200 14.0 0.8 24.4 18.0 1.9 6.0 97


400 14.0 0.8 30.6 18.0 2.0 6.0 104
600 14.0 0.8 35.6 18.0 2.1 6.0 110
220 800 14.0 0.8 40.6 18.0 2.2 6.0 115
Kraft
BIL = 1000 14.0 0.8 42.2 18.0 2.2 6.0 119
Paper
900kV 1200 14.0 0.8 45.7 18.0 2.3 6.0 123
1400 14.0 0.8 48.9 18.0 2.4 6.0 126
Taihan s Oil Filled Power Cable

1500 14.0 0.8 50.4 18.0 2.4 6.0 127


2000 14.0 0.8 57.5 18.0 2.5 6.0 136
200 14.0 0.8 24.4 14.0 1.7 4.5 83
400 14.0 0.8 30.6 13.0 1.8 4.5 87
600 14.0 0.8 35.6 12.5 1.8 4.5 93
154
800 14.0 0.8 40.6 Kraft 12.5 2.0 4.5 96
BIL =
1000 14.0 0.8 42.2 Paper 13.5 2.1 4.5 102
750kV
1200 14.0 0.8 45.7 13.5 2.2 4.5 106
1500 14.0 0.8 50.4 13.5 2.2 4.5 111
2000 14.0 0.8 57.5 13.5 2.4 4.5 119

Three Core
Conductor Insulation Aluminum Sheath
Rated Thickness Thickness Approx. Approx.
Nominal Approx. Overall
Voltage Material Thickness of of Cable
Area O.D Dia.
Sheath Jacket of Cable Weight

kV mm2 mm mm mm mm mm kg/km

150 14.7 14.0 2.5 4.5 126 18,300


200 17.0 Kraft 13.0 2.5 4.5 129 19,200
154
250 19.0 Paper 12.5 2.6 4.5 131 21,000
325 21.7 12.5 2.7 4.5 134 24,100
Lead Sheath
Maximum Maximum
Approx. Approx. Thickness Thickness Approx. Approx. Approx.
Volume Overall Volume Conductor Electrostatic
Cable of of Cable
of Cable Dia. of Cable Resistance Capacity
Weight Oil Sheath Jacket of Cable Weight Oil
kg/km Ir/km mm mm mm kg/km Ir/km /km, 20 /km, 20

10,400 2,230 3.0 6.0 79 15,000 1,440 0.0889 0.23


13,400 2,610 3.2 6.0 87 19,200 1,680 0.0441 0.26
16,100 2,890 3.3 6.0 92 22,200 1,890 0.0299 0.29
19,000 3,250 3.4 6.0 97 26,100 2,120 0.0227 0.32
19,400 3,310 3.5 6.0 100 27,900 2,200 0.0181 0.34
23,400 3,470 3.6 6.0 103 30,800 2,310 0.0151 0.36
26,200 3,680 3.7 6.0 106 33,700 2,410 0.0131 0.38

Taihan s Oil Filled Power Cable


27,900 3,800 3.7 6.0 108 37,100 2,490 0.0122 0.39
34,100 4,270 3.9 6.0 113 43,200 2,750 0.00915 0.43
7,600 1,480 2.8 4.5 73 12,700 1,150 0.0131 0.27
9,900 1,640 2.9 4.5 78 15,800 1,270 0.0122 0.34
12,100 1,820 3.0 4.5 83 18,900 1,390 0.0102 0.39
14,800 2,050 3.1 4.5 88 22,300 1,600 0.00915 0.43
17,300 2,220 3.3 4.5 94 26,100 1,720 0.0181 0.43
19,800 2,380 3.3 4.5 97 28,900 1,850 0.0151 0.45
23,000 2,630 3.5 4.5 102 33,700 1,980 0.0122 0.51
29,100 3,140 3.6 4.5 110 40,700 2,240 0.00915 0.57

Lead Sheath
Maximum Maximum
Approx. Thickness Thickness Approx. Approx. Approx.
Volume Overall Volume Conductor Electrostatic
of of Cable
of Cable Dia. of Cable Resistance Capacity
Oil Sheath Jacket of Cable Weight Oil
Ir/km mm mm mm kg/km Ir/km /km, 20 /km, 20

6,000 3.9 4.5 123 32,400 4,480 0.1210 0.19


5,530 3.9 4.5 124 33,700 4,120 0.0906 0.23
5,740 3.9 4.5 125 35,500 4,290 0.0732 0.25
5,920 4.0 4.5 128 38,300 4,650 0.0563 0.28

P17
P18
Accessories
As oil filled cable accessories, there are sealing ends(EB-A, EB-G, EB-O), joint boxes(IJ, NJ, SJ,
SIJ), oil feeding and alarm equipments.

Sealing Ends
Indoor and outdoor sealing end (EB-A) SF6 gas immersed sealing end (EB-G)
Sealing end is sends and takes electric power into and Sealing end is used for terminating the cable for the
out of cable. Porcelain bushings are needed to be SF6 gas switch gear. Epoxy bushings are needed to
insulated between the earth potential parts and the high be insulated between the earth potential parts and the
voltage parts, and this sealing end has stress relief cone high voltage parts. The inner construction of this
formed of wide paper or a condenser cone formed of sealing end is similar to that of an indoor and outdoor
insulating paper layers and metal foil for inside sealing end except that the sealing end is completely
reinforcement according to the voltage uesd. Connector enclosed and immersed in gas to the higher
is fastened to the cable conductor by compression insulation strength and to prevent dust from
method and a flexible terminal lug is placed between the collecting, etc.
conductor and the lead wire to avoid applying
unnecessary external force against the sealing end.
Taihan s Oil Filled Power Cable

Nominal Dimension(mm) Nominal Dimension(mm)


Voltage Voltage
(kV) A B C D E (kV) A B C D E F
110 1,480 1,725 435 360 315 110~161 80 112 220 298 320 757
154 1,830 2,075 435 360 315 220~300 110 202 480 559 582 960
220 2,940 3,290 500 480 470 330~420 110 252 540 617 640 1,400
275 3,350 3,700 500 480 470
345 3,975 4,250 600 550 510
Oil immersed type sealing end (EB-O)
This construction of this sealing end is similar to the of an
indoor and outdoor sealing end except that the sealing
end is completely enclosed and immersed in oil to prevent
dust from collecting, and the size of EB-O is much smaller
than the one of EB-A, this type of sealing end is for
connecting cable with transformer

Rated Dimension(mm)
Voltage
(kV) A B C D E F G H I
110 ~ 161 990 1,170 1,260 585 450 375 340 320 380
220 ~ 345 1,350 1,550 1,700 900 640 420 390 420 550

Taihan s Oil Filled Power Cable


Joint Box
Straight through joint (NJ) Rated Nominal Area Dimension(mm)
This joint is used for jointing cables, and electrical jointing Voltage of Conductor
and oil passage are part of its function or structure. And (kV) (mm2) L D
this joint has same quality as, or better than cable itself, less than 1,000 1,300 130
110 ~ 161
and is free from any electrical and mechanical defects due 1,200 ~ 2,000 1,530 180
to the trouble developed by the power transmission 220 ~ 300 less than 2,000 2,000 200
system. 330 ~ 420 less than 2,000 2,400 240

P19
P20

Insulation joint (IJ)


The structure of this joint is almost same as straight
Rated Nominal Area Dimension(mm)
through joint box, and the difference between them is to Voltage of Conductor
put an insulator flange at the center of copper casing. (kV) (mm2) L D
This box is used for jointing cables and at the same less than 1,000 1,300 130
time for insulating on metal sheath from the other metal 110 ~ 161
1,200 ~ 2,000 1,530 180
sheath to get a sheath voltage reducing under safety
220 ~ 300 less than 2,000 2,000 200
level.
330 ~ 420 less than 2,000 2,400 240
Taihan s Oil Filled Power Cable

Oil stop joint (SJ)


This joint is used for dividing the oil feeding section in
case that route length is too long or oil pressure change Rated Nominal Area Dimension(mm)
is too excessive at static or transient operation. Also Voltage of Conductor
(kV) (mm2) L D
this joint is used for connecting the cables electrically,
110 ~ 161 less than 2,000 2,900 250
and at any time for stopping the oil passage to separate
the oil feeding section of both cables. 220 ~ 300 less than 2,000 3,400 350
330 ~ 420 less than 2,000 4,100 350
Oil feeding tank
The inner oil of oil filled cables expands or shrinks automatically, and enough oil has to be kept in the oil feeding tank to
supply oil to the cables for a significant length of time even if the oil should be out. There are many kinds of oil feeding
tanks, for example, pressure tank(inner and outer gas type) and special oil feeding tank, etc.

PT BPT

Taihan s Oil Filled Power Cable


Valve panel
The valve panel(guage panel) shall be installed at the intermediate of
pressure tank and sealing end or oil stop joint and have such a function
as to sense and indicate the oil pressure. If necessary, the pressure
guage shall be provided with the electrical contacts which shall make the
electric cirucit for the oil pressure alarm.

Other Accessories
Cross bond link box
The cross bonding link box shall be used for connecting the bonding
wire properly and be provided with surge diverters to discharge at the
suitable for installation in joint handholes and manholes and be fully
watertight.

Alarm device Piping Indication Panel


It is advisable to have an alarm device to notify the guard when the
cables are out of order or damaged.
Usually a transmitter is located at the oil tank and a receiver is placed in the control room. We manufacture three
kinds of alarm devices; one alarm device operates when the minimum pressure or volume is reached. Another
continuously indicates the pressure or volume, and the third has an indicator and a recorder. The proper one should be
chosen after duly considering the functional importance of the cable and the maintenance system adopted for the line.

Oil feeding pipe


The oil feeding pipes used for connecting the cables to the oil tank lead are made of armored lead, copper and etc. We
will choose the most suitable one for your particular system.

Terminal box for control cable


The alarm transmitter and receiver are connected with control cables. Since many alarm transmitters are generally
used, this terminal box is placed near the transmitters to allow the circuits to be opened or checked.

P21
P22

Installation

Taihan has many achievements and excellent techniques, relative to cable installation work and
is making performance doubly sure in regard to safety of operations, besides vigorously
promoting development, rationalization and speedy installation. And also Taihan is performing its
work consistently, from planning to testing after installation, including laying of oil filled cables,
sealing ends assembly, construction of joints, and oil feeding equipment. There are the following
methods in laying of oil filled cables and special features are as follows.

Direct Burial
Where the road is narrow, the construction of conduit
under the road is usually not permitted.
Where the number of cables is few and no future
increase is expected.
Where the road digging is easy.
Taihan s Oil Filled Power Cable

Underground Duct
In case of a main underground transmission line where
the number of cables are many or expected to be
increased in near future.
In case of hard pavement or where hard pavement will
be constructed in future.
Where digging is difficult due to heavy traffic.

Special Laying
In case cables are installed in special places where there
are bridges or railways, special laying methods are
employed as follows ;

When a cable crosses a river or canal, cables are


attached to the bridge. If there is no suitable bridge in the
neighborhood, an exclusive bridge should be buit or a
method of submarine laying should be adopted.
As long as the strengh and space of the bridge
permits, it is best to attach the cables to the bridge.
Whether it is better to build an exclusive bridge or to lay
submarine cable depends on the cost and difficulty of
construction.
In case of crossing a railway, there are two methods; one
is digging through the railway bed, and the other is
piercing from the side of the railway by using an
excavator. When the cable crosses many tracks like a
surface from railroad or suburban railway, digging the
railway bed is usually adopted. Except for the above
case, piercing by using an excavator is adopted.
Looking to the Future

In order to provide all the requirement of a world market that asks for ever higher voltages, Taihan
hace a dedicated policy of high investment into research.
It’s this policy which keeps Taihan at the front of thier field-innovating, testing new tecniques and
incorporating the latest technological advancements.

Taihan s Oil Filled Power Cable


Large conductor size

P23
ELECTRIC WIRE CO., LTD.
www.taihan.com

Head Office R & D Center Anyang Plant Siheung Plant Ansan Plant
Insong Building, 194-15, 996, Siheung-dong, 785, Gwanyang-dong, 113-119, Siheung-dong, 603, Seonggok-dong,
1-ga, Hoehyeon-dong, Geumcheon-gu, Dongan-gu, Anyang, Geumcheon-gu, Ansan, Gyeonggi-do,
Jung-gu, Seoul, Korea Seoul, Korea Gyeonggi-do, Korea Seoul, Korea Korea
Tel. 82-2-316-9114 Tel. 82-2-890-9504 Tel. 82-31-420-9114 Tel. 82-2-890-9114 Tel. 82-31-490-5114
Fax. 82-2-757-2942 Fax. 82-2-806-0186 Fax. 82-31-423-2685 Fax. 82-2-808-6320 Fax. 82-31-491-3721

Kuala Lumpur Singapore Office Riyadh Office Skytel Co., Ltd. Malesela Taihan Telecom & Energy
Office Electric Cable (Pty) Ltd. Cables Corp.
15th Floor, Kenanga 629 Aljunied Road Al Akariyah Shopping 4th Floor of the Montel Vereeniging 1930, 85, Denton Avenue,
International, JL. Sultan #05-19, Cititech Center 2, Room No. Building, Chingeltel Steel Road, Peacehaven New Hyde Park,
lsmail, 50250 Kuala Industrial Building, 726, Olaya Road, District 1st. Horoo, Vereeniging 1939, NY 11040, U.S.A
Lumpur, Malaysia Singapore 389838, P.O.Box 201, Riyadh, Ulaanbaatar-13, Gauteng, South Africa
Singapore Saudi Arabia Mongolia
Tel. 60-3-2161-8017 Tel. 65-842-5069 Tel. 966-1-419-0227 Tel. 976-1-318488 Tel. 27-16-450-8333 Tel. 1-718-347-6030
Fax. 60-3-2161-3628 Fax. 65-842-5076 Fax. 966-1-419-0262 Fax. 976-1-318487 Fax. 27-16-450-8266 Fax. 1-718-347-6045