Installation Proline Promag H 300 HART Orientation ‘The direction of the arrow on the sensor nameplate helps you to inst according to the flow direction (direction of medium flow through the pi rs a B | onzonval onentaton rename a oO = wi : dp c wsmitter at TP J 7 amare] ASI = ns with low process temperatures may decease the ambient temper this erent 2} Applications with high process temperatures may increase the ambient temperature. To manta 1 smanitnum ambien transmitter, this orientation i recommended 3} To prevent the electrons module ‘tom overheating inthe case of @ sharp nie Is temperature (eg. CIP or SIP processes, instal the iter component pointing downwards ‘With the empty pipe detection function switched on: empty pipe detecion only works if the transmitter housing is ponting upwards. natn the Horizontal «Ideally, the measuring electrode plane should be horizontal. This prevents brief insulation of the two measuring electrades by entrained air bubbles. ‘* Empty pipe detection only works if the transmitter housing is pointing upwards as otherwise there is no guarantee that the empty pipe detection function will actually respond to a partially filled or empty measuring tube. — GR 2 Sobel 1 EpD electrode forempty pipe detection (avaiable from, 2 Measuring electrodes for signal detection IN> 15 mm 5) EB Measuring devices with a nominal diameter < DN 15 mm (% in) do not have an EPD electrode. In this ease, empty pipe detection is performed via the measuring, electrodes. Inlet and outlet runs If possible, install the sensor upstream from itt ngs such as valves, T-pieces or elbows. Observe the following inlet and outlet runs to comply with accuracy specifications: