Division 1, Groups A, B, C, D T5 Ex e CA Class I, Zone 1 CSA C22.2 No. 60079-7 EU classification per EN 60079-10-1
US classification per ANSI/NFPA 70 National Electrical Code® (NEC®) Article 500 or Article 505
Ex e (or Ex eb) EU Category 2G EN E60079-7 CA classification per CSAC22.1 Canadian Electrical Code (CEC) Section 18 or Annex J
Ex e (or Ex eb) IEC EPL Gb IEC E60079-7 No arcs,
Permitted Division Temperature Class Non-Incendive (NI) US Class I, Division 2 FM 3611 sparks or
Equipment Grouping
(optional except for Division 2) (T5 and T6 optional) (NI) CA Class I, Division 2 CSA C22.2 No. 213 hot surfaces
Permitted Group Non-Sparking AEx nA (or AEx nAc) US Class I, Zone 2 ISA 60079-15
Ex nA CA Class I, Zone 2 CSA C22.2 No. 60079-15 US (NEC® 505)
Ambient temperature ranges other than standard (-25°C ≤ Ta ≤ +40°C) must be marked.
Ex nA (or Ex nAc) EU Category 3G EN 60079-15 CA (CEC Section 18)
Ex nA (or Ex nAc) IEC EPL Gc IEC 60079-15 EU US (NEC® 500)
Explosionproof (XP) US Class I, Division 1 FM 3615 Typical gas IEC CA (CEC Annex J)
US (NEC® 505) (XP) CA Class I, Division 1 CSA C22.2 No. 30 Acetylene Group IIC Class I/Group A
American Flameproof Ex da (Expected 2013) EU Category 1G EN 60079-1 Hydrogen (Group IIB + H2) Class I/Group B
National Standard Ex da (Expected 2013) IEC EPL Ga IEC 60079-1
Type of Temperature Class Ethylene Group IIB Class I/Group C
Permitted Class Protection Group AEx d (or AEx db) US Class I Zone 1 ISA 60079-1
Propane Group IIA Class I/Group D
Ex d CA Class I, Zone 1 CSA C22.2 No. 60079-1
Methane Group I* Mining*
Class I, Zone 1, AEx d [ia] IIC T5 Ex d (or Ex db)
Ex d (or Ex db)
EN
IEC
Category 2G
EPL Gb
EN 60079-1
IEC 60079-1
Contain
the
*Not within scope of NEC®. Under jurisdiction of MSHA. Not within scope of CEC.
Limited Energy AEx nC (or AEx nCc) US Class I, Zone 2 ISA 60079-15
1725 II 2(1) G Ex nL CA Class I, Zone 2 CSA C22.2 No. 60079-15 First characteristic Numeral Second characteristic Numeral
Ex nL (or Ex nLc) EU Category 3G EN 60079-15
Ex nL (or Ex nLc) IEC EPL Gc IEC 60079-15 Protection against solid bodies Protection against liquid
Identification Number of Notified Body Category for I.S. Output
Pressurized Type X US Class I, Division 1 FM 3620 (NFPA 496) 0 No protection No protection
Involved in Production Control Stage Category Type X CA Class I, Division 1 NFPA 496
1 Objects greater than 50mm Vertical (90˚) dripping water
Equipment Group 1 (for Zone 0) Type Y US Class I, Division 1 FM 3620 (NFPA 496)
I (for mines) 2 (for Zone 1) Type Y CA Class I, Division 1 NFPA 496 2 Objects greater than 12mm 70˚ to 90˚ dripping water
II (for other than mines) 3 (for Zone 2) Objects greater than 2.5mm Sprayed water
Type Z US Class I, Division 2 FM 3620 (NFPA 496) 3
Type Z CA Class I, Division 2 NFPA 496 4 Objects greater than 1mm Splashed water
AEx px (or AEx pxb) US Class I, Zone 1 ISA 60079-2
5 Dust-protected Water jets
CA (CEC Section 18) Ex px CA Class I, Zone 1 CSA C22.2 No. 60079-2
Ex px (or Ex pxb) EU Category 2G EN 60079-2 6 Dust-tight Heavy seas
Explosion-Protected Equipment
I.S. Gas Protection Ex px (or Ex pxb) IEC EPL Gb IEC 60079-2 7 Effects of immersion
Output Group Level AEx py (or AEx pyb) US Class I, Zone 1 ISA 60079-2 8 Indefinite immersion
Ex py CA Class I, Zone 1 CSA C22.2 No. 60079-2
Ex d [ia] IIC T5 Gb Ex py (or Ex pyb) EU Category 2G EN 60079-2
Approximate U.S. enclosure type equivalent to IPXX
Ex py (or Ex pyb) IEC EPL Gb IEC 60079-2
Type of Protection AEx pz (or AEx pzc) US Class I, Zone 2 ISA 60079-2 Type IP Type IP Type IP
Group Ex pz CA Class I, Zone 2 CSA C22.2 No. 60079-2
Temperature Class Ex pz (or Ex pzc) EU Category 3G EN 60079-2 1 10 3S 54 6 and 6P 67
Ambient temperature ranges other than standard (-20°C < Ta < +40°C) must be marked. Ex pz (or Ex pzc) IEC EPL Gc IEC 60079-2 2 11 4 and 4X 55 12 and 12K 52
Restricted Breathing AEx nR (or AEx nRc) US Class I, Zone 2 ISA 60079-15 Keep
Ex nR CA Class I, Zone 2 CSA C22.2 No. 60079-15 flammable 3 54 5 52 13 54
Ex nR (or Ex nRc) EU Category 3G EN 60079-15 gas out 3R 14
Ex nR (or Ex nRc) IEC EPL Gc IEC 60079-15
EPL/Category Encapsulation AEx ma
Ex ma (also marked as Ex m)
US
CA
Class I, Zone 0
Class I, Zone 1
ISA 60079-18
CSA C22.2 No. 60079-18
IEC EU (ATEX) Typical Zone
Acronyms
Definition Ex ma EU Category 1G EN 60079-18
EPL Group Category Group of Application Ex ma IEC EPL Ga IEC 60079-18
Mines, “very high” AEx m US Class I, Zone 1 ISA 60079-18
level of protection Ma M1 AEx mb US Class I, Zone 1 ISA 60079-18
ATEX Atmosphère explosible
Ex mb (also marked as Ex m) CA Class I, Zone 1 CSA C22.2 No. 60079-18 CA Canada
I I N/A
Mines, “high” Ex mb IEC EPL Gb IEC 60079-18 CEC Canadian Electrical Code (CSA C22.1)
level of protection Mb M2
Ex mb EU Category 2G EN 60079-18 EPL Equipment Protection Level
Gas atmospheres,
AEx mc US Class I, Zone 2 ISA 60079-18 EU European Union
“very high” level Ga 1G 0 Ex mc (also marked Ex n) CA Class I, Zone 2 CSA C22.2 No. 60079-18 IEC International Electrotechnical Commission
of protection Ex mc EU Category 3G EN 60079-18
Ex mc IEC EPL Gc IEC 60079-18
I.S. Intrinsic Safety
Gas atmospheres,
“high” level of Gb II 2G II 1 Oil Immersion AEx o (or AEx ob) US Class I, Zone 1 ISA 60079-6 MSHA Mine Safety and Health Administration
protection Ex o CA Class I, Zone 1 CSA C22.2 No. 60079-6 NFPA National Fire Protection Association
Gas atmospheres, Ex o (or Ex ob) EU Category 2G EN 60079-6 NEC National Electrical Code (NFPA 70)
“enhanced” level Gc 3G 2
of protection Ex o (or Ex ob) IEC EPL Gb IEC 60079-6 US United States of America
Level of protection assigned to equipment based on its likelihood of becoming a source of ignition