The document contains comments on a fire protection system design. It notes that the location of the fire pump is not shown and that the pipe material does not comply with NFPA standards. It also requests clarification on the pipe size reference and states the pipe diameter should be 1-1/2 inches. Additional comments indicate the fire hose cabinets contain dry powder extinguishers so separate extinguishers are unnecessary and that foam or CO2 extinguishers do not need to be installed according to NFPA 13D standards.
The document contains comments on a fire protection system design. It notes that the location of the fire pump is not shown and that the pipe material does not comply with NFPA standards. It also requests clarification on the pipe size reference and states the pipe diameter should be 1-1/2 inches. Additional comments indicate the fire hose cabinets contain dry powder extinguishers so separate extinguishers are unnecessary and that foam or CO2 extinguishers do not need to be installed according to NFPA 13D standards.
The document contains comments on a fire protection system design. It notes that the location of the fire pump is not shown and that the pipe material does not comply with NFPA standards. It also requests clarification on the pipe size reference and states the pipe diameter should be 1-1/2 inches. Additional comments indicate the fire hose cabinets contain dry powder extinguishers so separate extinguishers are unnecessary and that foam or CO2 extinguishers do not need to be installed according to NFPA 13D standards.
ACCORDANCE WITH NFPA 13 (CHAPTER 6 & CHAPTER 10). 2) PROVIDE THE PIPE SIZE DERIVATION REFERENCE AS PER NFPA 13D & NFPA 14. IT SHOULD BE 1-1/2" IN DIAMETER.
1) THE FIRE HOSE CABINETS (FIRE HOSE
STATIONS) ARE EQUIPPED WITH A CLASS ABC 6KG DRY POWDER PORTABLE FIRE EXTINGUISHER. THERE IS NO NEED OF PROVIDING THEM SEPARATELY.
2) NFPA 13D DOES NOT MANDATE INSTALLATION
OF ANY FOAM TYPE OR CO2 PORTABLE FIRE EXTINGUISHERS. HAVE THEM REMOVED TOO.