COMMON COMMENT

1) CAN'T LOCATE WHERE THE FIRE


FIGHTING PUMP IS SHOWN.

1) PIPE MATERIAL IS NOT IN


ACCORDANCE WITH NFPA 13
(CHAPTER 6 & CHAPTER 10).
2) PROVIDE THE PIPE SIZE
DERIVATION REFERENCE AS PER
NFPA 13D & NFPA 14. IT SHOULD BE
1-1/2" IN DIAMETER.

1) THE FIRE HOSE CABINETS (FIRE HOSE


STATIONS) ARE EQUIPPED WITH A CLASS ABC
6KG DRY POWDER PORTABLE FIRE
EXTINGUISHER. THERE IS NO NEED OF
PROVIDING THEM SEPARATELY.

2) NFPA 13D DOES NOT MANDATE INSTALLATION


OF ANY FOAM TYPE OR CO2 PORTABLE FIRE
EXTINGUISHERS. HAVE THEM REMOVED TOO.