PANDEMIC READY PATIENT ROOMS

Easily Change Between Normal Operation and Isolation Room Mode


During a pandemic there is a sudden increase in demand for airborne infectious isolation rooms (AIIR). Traditionally hospitals are built with very few AIIR as these spaces are seldom used and are
more expensive to build and operate than standard patient rooms. The pandemic ready patient room solution from Price and Antec Controls allows the hospital to build one room that can be used
for either standard patient care or an AIIR, and can change between operational modes at the touch of a button.
ROOM REQUIREMENTS
ASHRAE Standard 170-2017 Ventilation of Health Care Facilities dictates the following requirements
for standard patient rooms and airborne infectious isolation rooms.

Standard Patient Room Airborne Infectious Isolation Room


NORMAL OPERATION ISOLATION MODE

Airflow – Fresh 2 ACH Airflow – Fresh 2 ACH

Airflow – Total 4 ACH Airflow – Total 12 ACH

Pressure Differential No requirement Pressure Differential Negative 0.01 in. w.g. pressure monitor required

Washroom Exhaust. Room exhaust located


Exhaust Washroom exhaust Exhaust
near patient head and directed ducted outdoors.

Return Room return grille located near door Return Return not allowed

Only allowed if room air is recirculated


Recirculation Allowed Recirculation
locally through a HEPA filter.

Supply Diffuser Not specified Supply Diffuser Located near entry door. Air moves from clean to less-clean.
LAYOUT A
CO2/Humidity LCD
Thermostat (TSTAT)
Exhaust Grille (735H) · Normal Operation: Controls
room temperature setpoint.
· Normal Operation:
Exhausts air out of washroom.
· Isolation Mode: Controls room
· Isolation Mode: Exhausts air temperature setpoint.
Exhaust Damper/Actuator out of washroom.
· Normal Operation: Damper
closed.

· Isolation Mode: Damper


Room Pressure Monitor (PMT)
modulates to control exhaust · Normal Operation: No room
airflow and maintain negative pressure requirement.
room pressure based on PMT
control signal. · Isolation Mode: Measures and
displays room pressure. Activates
FFU, closes return damper, and
modulates exhaust damper to
maintain negative room pressure.

Return Damper/Actuator
· Normal Operation: Damper
open to allow return airflow to the
air handler.
Single Duct Terminal Unit
· Isolation Mode: Damper closed with Reheat (SDV)
to prevent return airflow to the air
· Normal Operation: Modulates
handler.
supply airflow to the room.

· Isolation Mode: Modulates


supply airflow to the room.

Return Grille (80SR) Combination Exhaust and


· Normal Operation: Room air is Recirculating Fan Filter Unit (FFU)
returned to the air handler. · Normal Operation: FFU not in
use.
· Isolation Mode: Not in use. Recirculation Diffuser (SMD) Supply Diffuser (SMD)
· Isolation Mode: FFU turns on · Normal Operation: Not in use. · Normal Operation: Fresh air
based on PMT control signal. Air supplied to the room.
is drawn out of the room through · Isolation Mode: Recirculated,
a HEPA filter, exhausting a portion HEPA filtered air from FFU · Isolation Mode: Fresh air supplied
and recirculating the remainder. supplied to the room. to the room.
LAYOUT B
Exhaust Grille (735H) CO2/Humidity LCD
· Normal Operation: Thermostat (TSTAT)
Exhausts air out of washroom. · Normal Operation: Controls room
temperature setpoint.
· Isolation Mode: Exhausts air
out of washroom. · Isolation Mode: Controls room
temperature setpoint.
Room Pressure Monitor (PMT)
· Normal Operation: No room
pressure requirement.

Exhaust Damper/Actuator · Isolation Mode: Measures and


· Normal Operation: Damper displays room pressure. Activates
closed. FFU, closes return damper, and
modulates exhaust damper to
· Isolation Mode: Damper maintain negative room pressure.
modulates to control exhaust
airflow and maintain negative
room pressure based on PMT
control signal.

Return Damper/Actuator
· Normal Operation: Damper Single Duct Terminal Unit
open to allow return airflow to with Reheat (SDV)
the air handler. · Normal Operation: Modulates
supply airflow to the room.
· Isolation Mode: Damper closed
to prevent return airflow to the air · Isolation Mode: Modulates
handler. supply airflow to the room.

Return Grille (80SR)


· Normal Operation: Room air is Combination Exhaust and
returned to the air handler. Recirculating Fan Filter Unit (FFU)
· Normal Operation: Not in use. Supply Diffuser (SMD)
· Isolation Mode: Not in use. · Normal Operation: Fresh air
· Isolation Mode: FFU turns on supplied to the room.
based on PMT control signal. Air
is drawn out of the room through · Isolation Mode: Fresh and
a HEPA filter, exhausting a portion recirculated, HEPA filtered air from
and recirculating the remainder. FFU supplied to the room.
LAYOUT C
Exhaust Grille (735H)
· Normal Operation:
CO2/Humidity LCD
Exhausts air out of washroom. Thermostat (TSTAT)
· Normal Operation: Controls room
· Isolation Mode: Exhausts air temperature setpoint.
out of washroom.
· Isolation Mode: Controls room Room Pressure Monitor (PMT)
temperature setpoint. · Normal Operation: No room
pressure requirement.
Return Damper/Actuator · Isolation Mode: Measures and
· Normal Operation: Damper displays room pressure. Activates
open to allow return airflow to FFU, closes return damper, and
the air handler. modulates exhaust damper to
maintain negative room pressure.
· Isolation Mode: Damper closed
to prevent return airflow to the air
handler.

Exhaust Damper/Actuator
· Normal Operation: Damper
closed.

· Isolation Mode: Damper


modulates to control exhaust
airflow and maintain negative
room pressure based on PMT
control signal.

Single Duct Terminal Unit


with Reheat (SDV)
Combination Exhaust and · Normal Operation: Modulates
Recirculating Fan Filter Unit (FFU) supply airflow to the room.
· Normal Operation: Air is drawn · Isolation Mode: Modulates
out of the room through a HEPA supply airflow to the room.
filter, and returned to the air
handler or recirculated to the
room. Supply Diffuser (SMD)
· Normal Operation: Fresh and
· Isolation Mode: Airflow through recirculated, HEPA filtered air from
FFU is increased in response to FFU supplied to the room.
PMT control signal. Air is drawn
out of the room through a HEPA · Isolation Mode: Fresh and
filter, exhausting a portion and recirculated, HEPA filtered air from
recirculating the remainder. FFU supplied to the room.
EQUIPMENT FOR LAYOUT A EQUIPMENT FOR LAYOUT B EQUIPMENT FOR LAYOUT C
Combination Exhaust Combination Exhaust Combination Exhaust
and Recirculating Fan Filter Unit and Recirculating Fan Filter Unit and Recirculating Fan Filter Unit
FFU-1-3/S/I/EXHAUST/24/48/EX-RC/RSR/HEPA/ FFU-1-3/S/I/EXHAUST/24/48/EX-RC/RSR/HEPA/ FFU-1-3/S/I/EXHAUST/24/48/EX-RC/RSR/HEPA/
FC/ECM/115/CF/RMB/BACnet/BFC/DSW-115// FC/ECM/115/CF/RMB/BACnet/BFC/DSW-115// FC/ECM/115/CF/RMB/BACnet/BFC/DSW-115//
ASSP////PL-AL/F-AL/PL-B12/F-B12 ASSP////PL-AL/F-AL/PL-B12/F-B12 ASSP////PL-AL/F-AL/PL-B12/F-B12

Room Pressure Monitor Room Pressure Monitor Room Pressure Monitor


PMT-1-4//I/I//SRPS1/BAC/ PMT-1-4//I/I//SRPS1/BAC/ PMT-1-4//I/I//SRPS1/BAC/

Return Damper/Actuator Return Damper/Actuator Return Damper/Actuator


MISCF-GRD-CE/S/I/RET/12/24V MISCF-GRD-CE/S/I/RET/12/24V MISCF-GRD-CE/S/I/RET/12/24V

Exhaust Damper/Actuator Exhaust Damper/Actuator Exhaust Damper/Actuator


MISCF-GRD-CE/S/I/EX/12/24V MISCF-GRD-CE/S/I/EX/12/24V MISCF-GRD-CE/S/I/EX/12/24V

Single Duct Terminal Unit Single Duct Terminal Unit Single Duct Terminal Unit
with Reheat & LCD Thermostat with Reheat & LCD Thermostat with Reheat & LCD Thermostat
SDV8//I/2801/6/EHP/CFM//EC/2.0/277-1/2/IDSW/ SDV8//I/2801/6/EHP/CFM//EC/2.0/277-1/2/IDSW/ SDV8//I/2801/6/EHP/CFM//EC/2.0/277-1/2/IDSW/
FUS///200/400/0/200/200/FF///////PS//CO2H-F/ FUS///200/400/0/200/200/FF///////PS//CO2H-F/ FUS///200/400/0/200/200/FF///////PS//CO2H-F/
VAV-LF/PIC/PRB/BAC/65/550/140///////// VAV-LF/PIC/PRB/BAC/65/550/140///////// VAV-LF/PIC/PRB/BAC/65/550/140/////////

Supply Diffuser Supply Diffuser Supply Diffuser


SMD//I/18/18/36/4A/24/24/SR/12//B12 SMD//I/18/18/36/4A/24/24/SR/12//B12 SMD//I/18/18/36/4A/24/24/SR/12//B12

Exhaust Grille Exhaust Grille Exhaust Grille


735H//I/24.000/16.000/F/S//////#4 735H//I/24.000/16.000/F/S//////#4 735H//I/24.000/16.000/F/S//////#4

Return Grille Return Grille


80SR//I/24/24///2///TOP/12/BN////B12 80SR//I/24/24///2///TOP/12/BN////B12
RETURN GRILLE NOT REQUIRED

Recirculating Diffuser
SMD//I/18/18/36/3A/24/24/SR/12//B12 RECIRCULATING DIFFUSER NOT REQUIRED RECIRCULATING DIFFUSER NOT REQUIRED
priceindustries.com

UNITED STATES CANADA Product Improvement is a continuing endeavour at Price. Therefore, specifications are subject to change without notice.
Consult your Price Sales Representative for current specifications or more detailed information. Not all products may be
2975 Shawnee Ridge Court NW 638 Raleigh Street
available in all geographic areas. All goods described in this brochure are warranted as described in the Limited Warranty
Suwanee, Georgia USA 30024 Winnipeg, Manitoba Canada R2K 3Z9 shown at priceindustries.com. The complete Price product catalog can be viewed online at priceindustries.com.
PH: 770.623.8050 FAX: 770.623.6404 PH: 204.669.4220 FAX: 204.663.2715 ® Price is a registered trademark of Price Industries Limited. © 2020. Printed in Canada. | v100