You are on page 1of 7

IEEE Transactions on Power Delivery, Vol. 4, No.

1, January 1989 30 1

APPLYING METAL-OXIDE SURGE ARRESTERS ON DISTRIBUTIONSYSTEMS


S S Kershaw, Sr Member G L Gaibrois, Sr Member K B Stump, Sr Member
McGraw-EdisonPower Systems - -
Detroit Edison ComDany __ and Automation, Inc
Siemens Energy
Cooper Industries, Inc Detroit, MI Roswell, GA
Olean, NY

ABSTRACT METAL-OXIDE SURGE ARRESTER CHARACTERISTICS


Metal-oxide surge arresters are rapidly replacing silicon-carbide Most metal-oxide surge arresters are constructed without series
arresters for protecting electric power system equipment insula- gaps; they rely, instead, on their valve elements to withstand the
tion from overvoltages. Selecting the proper metal-oxide surge line voltage during normal system operation. The valve elements go
arrester voltage rating, however, is based on different principles of into conduction sharply a t a precise voltage level and cease to con-
arrester response to power-frequency voltages than those used for duct when the voltage drops below this level. A series gap is not usu-
selecting silicon-carbide arresters.This paper discuses the primary ally required to insulate a metal-oxide arrester from ground be-
parameters for selecting metal-oxide surge arresters. cause the arrestervalve elements permit only low leakage currents
at operating voltages-nor is a series gap needed to interrupt
power-follow current that does not exist as long as bhe applied volt-
INTRODUCTION age is below the conduction voltage.
A metal-oxide surge arrester will operate successfully and main-
The selection of metal-oxide surge arrestersrequires a reevalua- tain its protective characteristics provided it is not required to dissi-
tion of arrester application concepts. Different criteria than those pate more energy than it can tolerate. Hence, a metal-oxide arrester
used for selecting silicon-carbide arrestersmust be employed even can operate at voltages above its conduction level for times dictated
though the basic functions of a surge arrester remain unchanged. by the energy it must dissipate. When the overvoltage applied to a
All surge arresters must metal-oxide surge arrester is reduced to the arrester's maximum
continuous operating voltage (MCOV)rating before its energy dissi-
1.Withstand continuously the power-frequency voltage at which it pation capability is reached, the metal-&de arrester will maintain
is intended to operate. its protective characteristics and will not fail.
2. Limit overvoltages on electric power systems by discharging The range of voltages at which a metal-mide arrester will operate
transient energy in the form of current. successfully includes all voltages up to the 'conduction (turn-on)
voltage. Conduction voltage depends on temperature, decreasing as
3.0perate in the same environment as the protected equipment. the temperature increases. Since valve-element temperature is de-
termined by the ambient environment and energy input-includ-
ing power-frequency voltage-the voltage level at which metal-
SILICON-CARBIDE ARRESTER CHARACTERISTICS oxide arrester will operate properly becomes a time-and-energy
criterion. The voltage at which it can satisfactorily perform on
Silicon-carbide arresters contain series gaps that protect the operating-duty-cycle tests is only a point in time (20 or 24 minutes)
valve elements from continuous power-frequencyvoltage and long- with a known energy input (20 or 24 discharges of 5- or 10-kAsurge
time overvoltage excursions such as those caused by ferroresonant current impulses with an 8/20 waveshape).
conditions. The series gap in a silicon-carbide arrester is the in-
sulating means during normal voltage conditions. Besides keeping
voltage across the valve elements below gap sparkover values, the Thermal Considerations
gap performs the very necessary secondary function of interrupting
the power-frequency current that follows the transient current dis- The primary consideration in applying metal-&de arresters is
charged by the arrester. It does this by not restriking on subsequent the thermal environment. As shown in Figure 1, the V-I curve for a
half-cycles of power-frequency voltage aRer the first follow-current metal-oxide arrester changes with temperature at the low end of
zero has occurred. the current range. As the ambient temperature of the environment
Silicon-carbide arrester voltage rating is established by a n increases or the energy input to the metal-oxide arrester increases,
operating duty cycle (ODC)test that consists of discharging a surge the temperature of the metal-cnride surge arrester valve element in-
current through the arrester while the arrester is energized at creases. This increases the magnitude of the current drawn which,
power-frequency voltage. Operations are repeated a t 1-minute in- in turn, causes additional heating. If the temperature exceeds the
tervals either 20 [521 or 24 [31 times at prescribed angles on the thermal capability of the metal-oxide valve element, thermal runa-
power-frequency voltage wave. The test voltage a t which the arres- way occurs and the arrester goes into a failure mode.
ter passes the duty cycle without significant damage is the rated
voltage. Selecting a silicon-carbide distribution arrester has tradi- DISCHARGE VOLTAGE
tionally been based on voltage rating; that is, the maximum voltage / .........
..-...... ... ................................................ /
that can occur on unfaulted phases during single line-to-ground
faults must not exceed the arrester's voltage rating.

LEAKAGECURRENT
aa WM 032-5 A paper recommended and approved
~

by the IEEE Surge Protective Devices Committee of < 0.01 amp 100-500 amps 1-100 kA
Power Engineering Society for presentation at the
IEEEIPES 1988 Winter Meeting, New York, New York, CURRENT
January 31 -
February 5, 1988. Manuscricpt
Fig. 1.Comparison of the non-linear characteristics of metal-oxide
submitted September 1, 1987; made available for
printing November 13, 1987.
surge arrester and silicon-carbide surge arrester valve
elements.

0885-8977/89/0100-0301$01.00O1989 IEEE
302
Failure Mechanism Potential Metal-Oxide Arrester Application Problems
Figure 2 shows the voltage-current relationship of a 27-kVmetal- A Detroit Edison Company study (Appendix A) shows that pu
oxide distribution-class surge arrester at three voltage levels: nor- voltages as high as 168can occur on unfaulted phases ifthe neutral
mal operating voltage, duty-cycle-rated voltage, and a voltage conductor is inadequately grounded throughout the distribution
above rated voltage. Note that Current I, is out of phase with Volt- system and the wire size is too small. Although this would be un-
age El (operating voltage). At Voltage E,, the metal-oxide arrester usual, it can occur when converting an older ungrounded system
valve element is primarily capacitive and the watts loss-or power and emphasizes the importance of good grounding practices during
dissipation- is negligible.At Arrester Rated Voltage, E2,the resis- construction and maintenance.
tive component of corresponding Current I2 is apparent and the When earth resistivity or system conversion results in ineffec-
metal-oxide arrester valve element will heat as a result of the power tively grounded systems, special attention must be given to the
being generated. If the metal-oxide arrester operates for a long time TOV capability of a metal-oxide surge arrester. A higher duty-cycle
at Duty-Cycle-RatedVoltageE, or if the temperature rise is acceler- rating and MCOV may be required or, better yet, part of the system
ated by a n increase in environmental temperature or a discharge of may need to be rebuilt to bring it up to today's technology. If the
transient energy, I2 will increase toward I,, starting the runaway arrester duty-cycle rating and MCOV are i ncreased, the insulation
condition. Under ambient conditions, Current I, occurs when the coordination of the system must be rechecked to assure that the
arresterrated voltage is exceeded. At ElevatedVoltage E,, the resis- required protective margins are still met.
tive component of current is dominant and the watts loss is signifi-
cant. Applying a Metal-Oxide Arrester on a n Ungrounded System
The method used to apply a metal-oxide surge arrester on a n un-
grounded system is different from the method used to apply a sili-
con-carbide arrester on a n ungrounded system, particularly when
accidental grounds can exist for long periods of time. In these cases,
the metal-oxide arrester MCOVrating must be equal to-or greater
than-the maximum system phase-to-phase voltage. However if
fault-detection relaying is such that fault duration is precisely
limited a n MCOV rating approaching maximum line-to-ground
voltage may be used. This would result in a duty-cycle rating lower
than that recommended for a silicon-carbide arrester, but close
attention must be given to the metal-oxide arrester's TOV capabil-
ity so that it is not exceeded during fault conditions.

Ferroresonant Overvoltages

Ferroresonance may not persist when a metal-oxide arrester


operates; however, it should be considered.Ferroresonant overvolt-
ages that can develop during single-phase switching or fuse blow-
0 2 4 6 8 1 0 1 2 1 4 1 6 1 8 ing can, under some conditions, be more damaging to a metal-oxide
TIME (milliseconds) arrester. For instance, a 2.5-pu overvoltage on a 13.2-kV system
Fig. 2.Voltage-currentrelationshipsof a 27-kvmetal-oxide surgearrester. would not cause most 10-kV-ratedsilicon-carbide arresters (normal
application) to spark over, but would cause a metal-oxide surge
Maximum Continuous Operating Voltage (MCOV) arrester to go into thermal runaway.
Because of the thermal considerations cited, a metal-oxide surge Ungrounded Wye-Delta Systems
arrester must be selected based on a maximum voltage that it can
withstand continuously rather than a duty-cycle voltage rating. Ungrounded wye-delta systems are particularly susceptible to
ANSYlEEE Standard C62.11-1987 defines this maximum continu ferroresonant overvoltages. On the other hand, ungrounded wye-
ous operating voltage as "the maximum designated rms value of delta systems have the advantage that, when both single- and
power-frequencyvoltage that may be applied continuously between three-phase loads need tb be serviced, different-impedance trans-
the terminals of the arrester." [21 The standard implies that this formers can be used in the three-phase bank and zero-sequence
MCOVcan exist in a continuous ambient temperature not to exceed currents are eliminated in the primary, particularly during fault
40°C with temporary ambient temperature excursions not to conditions.
exceed 60°C. Ungrounded wye-delta systems present an unusual condition for
metal-oxide surge arresters on the open phase of the wye with a n
Rmporary Overvoltage (TOW unbalanced load on the delta secondary as well as during faults. As
shown in Appendix B, voltages of 2.7 pu-high enough to force the
When applying a metal-oxide surge arrester,temporary overvolt- normally applied arrester rating into thermal runaway-can exist
ages that can occur on electric power systems and the duration on the open primary. This condition can occur if a three-phase secon-
that these overvoltages can exist must also be taken into consider- dary load is removed during work on the system, leaving a single-
ation. Metal-oxide surge arresters have a voltage-time characteris- phase load connected for lighting, refrigeration, etc. Rather than in-
tic that is easily represented on a linear-voltage log-time plot. These stalling higher-rated metal-oxide arresters on these wye-delta sys-
curves are available from metal-oxide surge arrester tems and thereby jeopardizing equipment protection, the following
manufacturers. practices are recommended:
APPLYINGA METAL-OXIDE ARRESTER 1.Balance the load so that the load on one phase of the delta is no
ON A DISTFUBUTION SYSTEM more than four times that on each of the other two phases. If
nearly balanced three-phase loads are served from a transformer,
'Ib properly apply a metal-oxide surge arrester on a distribution it is not subject to this overvoltage.
system, the arrester's MCOVmust be equal to-or greater than-
the maximum normal operating voltage of the power system and 2. Ground the wye. This would eliminate the problem, but may raise
the arrester's TOV capability must not be exceeded during abnor- concerns for serving unbalanced three-phase loads and single-
mal conditions such as faults or open circuits involving less than phase loads. It also provides a path for zero-sequence currents
three phases. For four-wire, solidly grounded distribution systems, that may be a problem.
the duty-cycle voltage rating for both a silicon-carbide arresterand 3.Close the disconnect on the phase that has the large single-phase
a metal-oxide arrester is usually the same. However, this implies load last.
that neutral wires are adequately bonded to grounds and are sized
to handle zero-sequence currents during faults to prevent excessive
voltages on unfaulted phases.
303
4.Apply a grounding resistor or reactor in the neutral of the un- BIOGRAPHIES
grounded-wye windings.
5.Close a neutral grounding switch during the energization of the Stanley S Kershaw, Jr (SM '67) was
phases and open it after all three phases have been closed. The born in Mt Vernon, New York, on
neutral switch must be able to clear the unbalanced load current April 11,1930,and received his BSEE
that may be flowing. degree from Purdue University in
1953. Upon graduation from Purdue,
6.Place arresters on the source side of circuit interrupters to pre-
he joined the Line Materials Com-
vent arrester damage due to over-voltages. This may, however, pany, now McGraw-Edison Power
reduce the overvoltage protection level because of longer lead
lengths. Systems, a subsidiary of Cooper
Industries, Inc. Throughout his
McGraw-Edison career, he has been
Effect of Actual Regulated Voltage on Metal-Oxide Arrester responsible for the design, develop-
Maximum Continuous ODeratinp Vol-e (MCOV) ment, and application of surge arres-
ter products. He has been awarded
Special attention must be given to the actual regulated voltage on eight surge arrester design patents.
distribution systems. Standards on voltage apply only to the cus- An active member of the 1[EEE Surge Protective Devices (SPD)
tomer's meter. Out on the feeder, much larger swings are permitted Committee since 1962, Mr K e r s h a i i s past chairman of that
as long as the voltage at the customer's meter is within standard. committee and is now chairman of the SPD Working Group on
An Electric Power Research Institute (EPRI) study found, on a ran-
dom sample, voltages 17 percent above nominal. [4] Arrester MCOV Surge Arrester Application Guide. He is also a member of ANSI
Committee C62 and is chairman of the C62 Working Group on
and actual maximum phase-to-ground voltage must be taken into
Continuous Revision of Surge Arrester Standards and Guides. In
account when selecting metal-oxide surge arresters for a specific addition, he is chairman of the IEEE Power Engineering Society
application.
Awards Committee and is the chief US. delegate to IEC Technical
When regulators are used to control system voltage, special care Committee No. 37 on Surge Arresters. He is a registered pro-
is required to make sure the MCOV rating of metal-oxide surge fessional engineer in the state of Wisconsin.
arresters is not exceeded. For instance, unstable voltage swings
may result when threesingle-phase voltage regulathrs are installed
on a n unstable neutral point. When three single-phase regulators Gilbert L Gaibrois (A'54, M '60, SM
are connected wye, the controls measure the line-to-neutral voltage '79) was born in Nice, France, on
so that, if the neutral is permitted to float, there is no stable refer- February 28, 1929, and received his
ence point from which to excite the regulator controls. Each reg- BSEE degree in Geneva, Switzer-
ulator control will measure this shift and try to correct it. The oper- land, in 1949. From 1949 to 1951, Mr
ation of the regulator bank under these conditions will be erratic. Gaibrois worked with the Societe
Anonyme des Ateliers de Secheron in
Geneva as a test engineer.
CONCLUSIONS He joined The Detroit Edison Com-
pany in Detroit, Michigan, in 1952 as
The primary advantages of a metal-oxide surge arrester over a a test and field engineer and, in 1957,
silicon-carbide surge arrester are the extreme nonlinearity (flat- assumed the responsibility of ther-
ness) of the metal-oxide voltage versus current characteristic and mal loading all apparatus equipment
the elimination of the requirement for a series gap and its and 'line conductors. He became prin-
associated gap sparkover voltage. Without a gap,the metal-oxide cipal engineer at Detroit Edison in 1963 and, at present, is insula-
valve element must support system voltage continuously, neces- tion coordination and grounding engineer.
sitating the consideration of thermal stability. Maximum con- Mr Gaibrois is a member and past chairman of the IEEE Surge
tinuous operating voltage (MCOV) and temporary overvoltage Protective Devices (SPD) Committee and past secretary of the
(TOV) capabilities are the important parameters for selecting a IEEE Power Engineering Society Technical Council. He is a regis-
metal-oxide surge arrester for a particular application. For exam- tered professional engineer in the state of Michigan.
ple, in special situations in which temporary overvoltages due to
ferroresonance can occur, the total arrester energy dissipation
per event may be a consideration. Keith B Stump was born in
Richmond, Indiana, on February 12,
REFERENCES 1941, and received his BSEE degree
from Ohio University in 1963 and his
1.Standard 99-1-1970. Lightning Arresters. Part 1: Nonlinear
0 0 -
MSEE degree from Purdue Univer-
Resistor-Qpe Arresters for Alternating-Current Systems, sity in 1965. He was employed by
International Electrotechnical Committee, NY,NY,1970. Allis-Chalmers Corporation i n
Milwaukee, Wisconsin, from 1965
2.ANSI Standard C62.ll-1987, Metal-Oxide Surge Arresters for through 1977.
Alternating-Current Power Circuits, American National Stan- Mr Stump joined Siemens-Allis,
dards Institute, NY,Nk: 1987. Inc., in January 1978 during the for-
3.ANSI Standard C62.1-1984, Surge Arresters for Alternating- mation of the jointly owned electrical
Current Power Circuits, American National Standards Institute, equipment company. In 1986, the
comnanv was Durchased bv Siemens
NY,NY,1984. AG and became Siemens Energy & AGtomaGon,Inc. At present, Mr
4.Distribution Fault-Current Analysis, El 3085, Project 1209-1, Stump is in the Power Systems Technology Department. His ac-
Electric Power Research Institute, Palo Alto, CA, May 1983. tivities have primarily been in the area of system simulation and
analysis. He is involved in simulation analysis of utility power sys-
ACKNOWLEDGMENTS tems including switching surges, subsynchronous, resonance,
surge arrester modeling and application, and various power system
The authors wish to thank the following gentlemen for their con- transient phenomena.
tributions to this paper: A member of Eta Kappa Nu and %U Beta Pi, Mr Stump is also a
member of the IEEE Power Apparatus and Systems Society.He is a
George D Allen, American Electric Power Company; member of the IEEE Surge Protective Devices (SPD) Committee
James J Burke, Power Technologies, Inc; and is chairman of Subcommittee 3.4, Application of Surge Protec-
Michael V Lat, Ontario Hydro; tive Devices. A member of the Overvoltage Protective Devices Sub-
W Edward Reid, McGraw-EdisonPower Systems; committee's Working Group 3.3.11, Metal-Oxide Surge Arresters, he
Thomas J Fbzek, Detroit Edison Company. also serves on all application working groups.
304
APPENDM A

DETERMINATION OF MAXIMUM OVERVOLTAGES POSSIBLE


ON UNFAULTED PHASES OF MULTIGROUNDED NEUTRAL
DISTRIBUTION SYSTEMS DURING SINGLE PHASE-TO-GROUNDFAULTS

Detroit Edison Company developed a computer program for cal- For most four-wire multigrounded distribution systems, the wer-
culating the maximum expected overvoltages on the unfaulted voltage factor is 1.2pu or less and the voltage on the arrester during
phases of multigrounded neutral distribution systems during a single line-to-ground fault does not exceed 1.14pu above MCOV
sipgle phase-&ground faults. The program was based on a 1972
report on voltage ratings for the application of lightning arresters 13.2/.\/3x 105 x 1 2 = 1.14 pu above MCOV. (2)
on distribution systems published by the IEEE Working Group on 8.4
Surge protective Devices Committee.* The program output lists
the maximum overvoltages expected at various nodes along a distri- This 1.14 pu above MCOV can be sustained by all manufacturers’
bution circuit for earth return, neutral return, and multigrounded metal-oxide surge arresters for minutes, giving the circuit ample
neutral return. These calculations take into account the system time to open.
impedance, ground-fault resistance, and the earth resistivity. The Studies were also performed on lines consisting entirely of 636-
assumed earth resistivity was 100 ohm-meters. kcmil bare aluminum phase conductors. In each study, a different
Studies were performed using no. 6 copper, no. 2 copper and 110 type of neutral conductor inadequately grounded throughout the
ACSR neutral conductors. The overvoltages for neutral return and circuit was modeled. When a no. 6 copper ground wire was modeled,
multigrounded neutral return were highest for the no. 6 copper con- the maximum expected overvoltage was 1.68pu for a single-phase
ductor and lowest for the no. 2 copper Conductor. Because ofhigher fault occurring 10 circuit miles from the substation. This corre-
conductor impedance, the calculated overvoltages with a WO ACSR sponds to a L6 pu voltage above MCOV of the arrester in the exam-
neuty 7 conductor were higher than those with a no. 2 copper neu- ple above. If the system neutral was adequately grounded, the sys-
tral :a. ,refor neutral return and multigrounded neutral return by tem overvoltage would be lowered to 1.33pu.
apprc mately 2 percent and 1 percent, respectively. Because the In computing the maximum expected overvoltages for l/O-ACSR
overvdage calculations for earth return are independent of the neutral conductor, the overvoltage factor was 1.55 pu for fault 10
neutral wire, the maximum overvoltages were the same for allthree miles from the substation with insufficient grounding. If the sys-
wire sizes. tem neutral was adequately grounded, the system overvoltage was
Assuming a faillt approximately 1.5 miles from the substation, lowered to 1.29 pu. The overvoltage factor is reduced slightly more
the maximum calculated system overvoltage varied from 1.12pu for with a no. 2 copper neutral conductor than it is with a l/O-ACSR
multigrounded neutral return with a no. 2 copper neutral conduc- neutral condudor.
tor to 147 pu for neutral return with a no. 6 copper neutral
conductor.
If, for example, a 10-kV-operating-duty-cycle-rated metal-oxide
arrester with a n MCOV of 8.4 kV is installed on a 13.2-kVdistribu-
tion circuit regulating at 5 percent above normal, a 1.47pu overvol-
tage would stress the arrester at 140 pu above MCOV
13.2/.\/3 x 105 x 1.47 = 1.40 pu above MCOV. (1)
8.4

A 1.40-pu voltage (11.76-kV)on a 10-kV arrester would cause ther-


mal runaway in a relatively short time.

*“voltage Rating Investigation for Application of Lightning


Arresters on Distribution Systems,” IEEE ?Ikansactions o n Powei
Apparatus Systems, PAS-91: pp 1067-1074,1972.
305

APPENDIXB
WYE-DELTA BANK

NOTE:Use 1:l ratio for calculations.


-A
I

VA = VAN
NORMAL Y-A v~ = k'm PHASE B OPEN;

+
B UNBALANCED LOAD Vc = VCN NO LOAD
EFFECTIVE IB vA
v, 2 = v, ,v, = 0 = v,

PRESTER
vm, = VAp-VA
=7 . 2 m- F m
= +
7.2 (0.5 j0.866) - 6.235 (0 +jl)
= +
3.6 i6.235 - i6.235
\ I

Or
= 3.6O.l- t', 1 .,

VARR = vCN + vC U
= 7.2M&+ vE!
!l
= -
7.2 (0.5 j0.866) + 6.235 (0 + j l )
= 3.6 - j6.235 + j6.235
= 3.6U

NOTE: UNBALANCED LOAD ACROSS PHASE B ONLY


v,, =vm-v,-v, WOULD NOT ALTER THE ABOVE RESULTS.
= 7.2 U?&-12.47 a- 12.47 L9.Q
= +
7.2 (0.5 j0.866) - 2 (12.47) (0 + j1.0)
= 3.6 + j6.235 - j24.94
= 3.6 - j18.705 = 19.05-
Or
v, = v,, -v,
= 7.!&&- 12.47m
-
= 7.2 (0.5 - i0.866) 12.47 (0 + 11.0)
= 3.6 - j6.235 -j12.47
= 3.6 - j18.705 = 19.05 U 9 . l \'
306

Discussion surge arresters in distribution systems. This discussion is intended to


supplement and comment on some of the application areas presented in the
R. M.Simpson (Carolina Power and Light, Raleigh, NC): The authors are paper.
to be applauded for their efforts to provide information to users on the In a 4-wire multi-grounded neutral (MGN) overhead system, the surge
proper application of gapless metal oxide surge arresters. The paper does a arrester is connected between the phase conductor and neutral conductor.
commendable job of identifying the major causes of temporary overvoltage The n o d practice when calculating the zero-sequence impedance of the
conditions and providing application guidelines which allow the user to take MGN line and the unfaulted phase-to-neutralvoltage durhg ground faults is
these conditions into account. In the case of an ungrounded wye-delta to assume that there are zero-impedance connections between the neutral
system, the reader should note that the recommended practices are not conductor and ground. Under these conditions, the phase-to-neutral and
always practical or even applicable if single-phase switching or fuse phase-to-ground voltages at any point along the line are equal and easily
blowing occurs at a location remote from the transformer bank (and calculated. But when there is a finite impedance between the neutral
therefore the arresters). For example, operations personnel may not be conductor and ground at each pole ground location, calculation of the
aware of the existence of an ungrounded wye-delta bank beyond the switch/ unfaulted phase-to-neutral voltage is quite complex, except when the
fuse point in order to follow recommended practices 3 and 5. Also, placing impedancebetween the neutral conductor and ground at each pole ground is
arresters on the source side of circuit interrupters at the transformer bank infinite. As intuitively expected, the unfaulted phase-to-neutral voltages are
(No. 6) still leaves them on the load side of a remote single-phase switch/ higher with infinite pole ground impedances.
fuse point. When the grounding impedances are infinite, the unfaulted phase-to-
Manuscript received January 4, 1988. neutral voltages are easily found for a phase-to-neutral fault, as all current
returns in the neutral conductor. We have made many calculations for this
condition, considering different conductor sizes and using only the
John G. Dalton (Duke Power Company, Charlotte, NC): The authors are impedances of the overhead l i e , with results similar to those in Appendix
to be commended on a worthy paper that stresses some very significant A. For example, with a 636 kcmil ACSR phase conductor and a 210 ACSR
differences between metal-oxide and silicon-carbide surge arresters. Unlike neutral, the unfaulted phase-to-neutral voltage is 1.53 pu will all return in
silicon-carbide arresters, metal-oxide disks (or valve blocks) are continu- the neutral conductor, and 1.30 pu with zero impedance connections
ously exposed to system voltage. Consequently, users should be knowl- between the neutral conductor and earth. These are essentially the same
edgeable of the muximum power-frequency voltage that may be applied to values calculated by the contributor from Detroit Edison. The largest value
the arrester during normal and abnormal operating conditions. Problems which we have calculated is 1.54 pu for a 795 kcmil ACSR phase conductor
may occur if Distribution Engineers are not aware of the actual voltage and a 210 ACSR neutral.
regulation on their feeders. High phase-to-neutral voltages can also occur during ground faults with
Hopefully Appendix A will caution users that if grounding is inadequate spacer cable construction for the primary circuits, with the unfaulted phase-
on a four-wire multigrounded system then the TOV during a ground fault to-neutral voltages in the vicinity of 1.5 pu, even when the connections
can be considerably higher than the commonly used value of 1.20 pu. between the neutral conductor and ground have zero impedance. Thus, the
Concerning Appendix B, I would like to make several comments about impact of lines with spacer cable should be recognized in metal oxide
this unusual situation that are worth mentioning: arrester applications.
In the section dealing with ungrounded systems, it is suggested that if the
1) Any size single-phase load connected across winding B only will metal oxide arrester MCOV rating equals system maximum phase-to-phase
NOT cause an overvoltage problem. voltage, the application is acceptable when permanent ground faults are
2) Any size single-phase load across phase A onb (or phase C) WILL allowed to persist. The maximum voltage-to-ground on the unfaulted phases
result in a high overvoltage across the arrester on phase B. in an ungrounded system can exceed the system maximum phase-to-phase
3) With unbalanced load on all three phases, no overvoltage problem operating voltage, due to the system and equipment phase-to-ground
occurs as long as the amount of load on phase B is at least 40%of the capacitances. The exact value depends upon the system parameters, but
largest loads on phases A and C. For example, if windings A and C some references suggest that if the ratio of Xco to XI is less than -40, the
were loaded at 1% and 25 % of rating respectively, then winding B unfaulted phase-to-ground voltages could be as high as 1.1 times the system
would need to be loaded to at least 10% (0.4 x 25%) of rating. maximum phase-to-phase voltage. If the Goto XIratio is greater than -
40, but less than zero, then the unfaulted phase-to-ground voltages can be
Manuscript received January 22, 1988.
much higher than 1.1 times system maximum phase-to-phase voltage,
depending upon the exact ratio. This should be recognized in applying metal
oxide arresters in ungrounded systems.
J. L. Koepfinger (Duquesne Light, Pittsburgh, PA): This paper provides The header for the section dealing with the voltage during single-pole
an update on the application of metal oxide arresters (MOA) to distribution switching of the ungrounded wye-delta transformer bank is somewhat
circuits. It is unfortunate that it raises more questions than it answers. For misleading. This transformer bank connection can be applied in any type of
example, it is indicated that several situations can occur which will cause primary system, whether it is a multi-grounded neutral primary system, a
temporary overvoltage that can cause failure of the MOA. There is no uni-grounded 3-wire primary system, or an ungrounded primary system.
indication as to the relative probability of these conditions existing. Most The header should indicate that it is the response of the ungrounded wye-
arrester application is based upon probability, thus it must be considered in delta transformer bank which is being discussed. Furthermore, it should be
applying MOA’s. emphasizedthat the 2.7 pu over voltage with one primary phase open occurs
In discussing TOV that occur on multi-ground distribution circuits in under worst case loading conditions, but with the secondary load reasonably
appendix A one of the calculations made reference to an inadequate balanced, the voltage will not exceed 1.Oper unit. Our calculations support
grounded neutral. Does inadequate mean that the neutral was not grounded. the four times unbalance load factor given in recommendation 1. Inciden-
If so, this would cause other operating problems in addition to failure of tally, this phenomenon can also occur with the T-T connected pole top
arresters. transformer supplying 4-wire delta service.
What is the effect of load and transformer saturation on the reduction of To prevent the overvoltages during single-pole switching of the un-
the TOV’s during phase to ground faults on a multi grounded common grounded wye-delta bank, recommendation 2 suggests connecting the
neutral system? This should reduce the TOV. neutral point of the wye-connected primary windings to the multi-grounded
There is need for a guide to assist the utility application engineer in neutral conductor of the primary system. Although this will prevent the
applying the right MOA. One part of the guide should provide a table or overvoltagesduring single-pole switching, both with and without secondary
easy calculationto determine the proper multi ground neutral wire size to be load, most practitioners would recommend against permanent grounding. If
used with phase conductors so damaging TOV’s will not result. an open phase occurs in the primary feeder on the source side of the
More field data and studies are needed to provide information on the transformer bank, the bank will try to supply the load on the open phase.
adequacy of using MOA’s in place of Silicon Carbide arresters on Under these conditions, the loading on the transformers is determined by
distribution circuits. the load on the open primary phase and the connected secondary load, and
Manuscript received January 27, 1988. not just by the load connected to the secondary for which the bank was
sized. The loading may then be in the range where the transformer fuses do
not provide overload protection, and transformer thermal failure results.
In the section titled, “Potential Metal-Oxide Arrester Application
D. R. Smith (Westinghouse Electric Corporation, Pittsburgh, PA): The Problems,” it is stated that if the duty-cyle rating and MCOV rating are
paper identifies important areas to be considered when applying metal oxide decreased, the insulation coordination of the system must be rechecked to
307

assure that required protective margins are met. Did the.authors mean to say effective? Which is the disconnect with the largest single phase load that
that if the duty cycle rating and MCOV rating are increased, then the should be closed last? On the user side, the delta side, the single phase load
coordination should be rechecked? is between two phases. Do the authors mean to close the primary
Manuscript received February 12, 1988. disconnect last which has a line current substantially in phase with the single
phase load?
JOHN E. HARDER, Westinghouse E l e c t r i c Corporation, Manuscript received February 26, 1988.
Bloomington, Indiana: The authors have presented a
very u s e f u l paper describing several p o t e n t i a l S. S. Kershaw, G . L. Gaibrois, and K. B. Stump thank all of the
problem areas i n the application o f metal oxide discussers for their comments. Their contributions will make this paper a
arresters t o d i s t r i b u t i o n systems. This discussion much more useful tutorial on the application of metal-oxide surge arresters
focuses on one o f those concerns: the selection o f (MOSAs) on distribution systems.
the appropriate r a t i n g o f metal oxide arrester for It is appropriate to address Mr. Koepfinger’s discussion first. The IEEE
applications where the l i n e t o ground voltage on the Surge Protective Devices Committee (SPDC) was concemed that many
unfaulted phases may be higher than expected during a distribution system engineers think that metal-oxide surge arresters can
single l i n e t o ground f a u l t on the system. always be substituted for silicon-carbide (Sic) arresters based solely on
duty-cycle rating. SPDC members believe that it is important to call
As ably pointed out by the authors, the l i n e t o attention to conditions in which arrester application is independent of duty-
ground voltage i s affected by f a c t o r s such as l i n e cycle rating (e.g., conditions affecting the thermal stability of MOSAs). In
construction, wire size, effectiveness o f driven most cases, it is high-impedance, grounded distribution systems for which
grounds, etc. Consider a remote area where the selection criteria may be different. These conditions were addressed in
unbalances i n phase loading may r e s u l t i n a small the paper. For low-impedance (four-wire, multigrounded) systems, the
amount o f current through the driven grounds, application of MOSA’s and Sic arresters is usually the same. Fast
d e t e r i o r a t i n g t h e i r effectiveness. Many arresters i n interruption of faults and suppression of temporary overvoltages (TOVs)
that v i c i n i t y may be subjected t o excessive due to the saturation characteristics of the connected load are contributing
overvoltages during s i n g l e l i n e t o ground faults. In factors. As indicated in Appendix A of the paper, an exception can occur
addition, the t o t a l c l e a r i n g time f o r f a u l t s i n these when grounding is ineffective. The questions raised in the paper are
remote areas (with allowance f o r f a i l u r e o f the intended to help distribution system engineers to recognize potential
recloser closest t o the f a u l t t o operate properly?), problems, and, therefore, to be better able to make the proper decisions
may be r e l a t i v e l y long. One o f the problems, i t about MOSA applications.
seems, i s t h a t the industry has very l i t t l e Mr. Smith’s comments about the use of MOSAs on spacer-cable circuits
assessment concerning the numbers o f i n s t a l l a t i o n s are noteworthy. A study conducted by an SPDC working group in 1972
l i k e t h i s which may f o r whatever reason be concluded that higher arrester voltage ratings are required on spacer-cable
vulnerable, and the magnitude o f overvoltages and systems than normally used on open-wire circuits. (1) Although the working
times involved. group recommendations have, for the most part, been ignored, the authors
recommend that they be reviewed for MOSA applications.
Once the magnitude o f the overvoltage and i t s We agree with Mr. Smith’s comments regarding phase-to-ground
duration are established, there remains the question voltages exceeding phase-to-phase voltages on unfaulted phases during line-
o f selection o f the most appropriate arrester to-ground faults. The possibility that these higher voltages may exist must
rating. The time a t overvoltage c a p a b i l i t y o f metal be recognized before sound applicationschoices can be made; however, due
oxide arresters varies among the manufacturers. to their short duration, they should not exceed the thermal capability of the
Thus, f o r a given time a t overvoltage requirement a arresters.
10 kV arrester or manufacturer A may be satisfactory, Ungrounded wye-delta systems should, indeed, be ungrounded wye-delta
while a 12 kV a r r e s t e r o f manufacturer B may be banks. The 2.7-pu overvoltage cited is the worst case that could occur
required. I t seems cumbersome f o r users t o have t o during a phase-to-phase fault on the secondary with one primary open. We
specify one a r r e s t e r r a t i n g f o r most o f the agree that a permanent ground on the primary wye neutral is not a
d i s t r i b u t i o n system, and another r a t i n g f o r c e r t a i n recommended practice for the reasons given; this leads to the corrective
remote areas ... and the r a t i n g depending upon the
manufacturer o f the arrester. Users, i t seems, need
measures recommended in Items 4 and 5 (temporary grounding or
impedance grounding).
t o be able t o specify an a r r e s t e r r a t i n g which can be Regarding the last paragraph of Mr. Smith’s discussion, the correction
used system wide. has been made; decreased has been changed to increased.
Mr. Jackson’s discussion also pertains to the section on ungrounded wye-
I t would seem h e l p f u l t o have the industry delta banks. The basis for the load unbalance ratio of four times is a
standardizing bodies develop application guidelines calculated number that assumes the primary phase-to-ground voltage is
for arresters nn d i s t r i b u t i o n systems which would limited to 1 pu with one primary phase open. The four-times-unbalanced-
e s s e n t i a l l y eliminate the f a i l u r e o f arresters on load factor was supported specifically by Mr. Smith and, in general, by Mr.
unfaulted phases due t o excessive voltages, from Dalton in their discussions. The primary phase feeding the largest
which more sophisticated users could take exception secondary load-connected across the transformer winding associated with
i f they preferred a lower rated arrester. the feeding primary winding-should be closed last.
All of the discussions reemphasize the concerns about applying arresters
I t seems t o t h i s discusser t h a t the industry needs t o on all types of overhead and underground distribution systems. The authors
(1) quantify the extent o f the problem and (2) agree with Mr. Harder that the extent of the problem in these areas is
e s t a b l i s h application guidelines which accommodate unknown, but system conditions that could cause arrester failure must be
the expected overvoltages. What i s the author’s addressed. A metal-oxide surge arrester application guide, now being
opinion concerning how t o best deal with t h i s facet developed by the IEEE Surge Protective Devices Committee, will discuss
o f the problem? some of the distribution system conditions that may jeopardize arrester
operation. However, because potential problem conditions are functions of
Manuscript received February 17, 1988. specific configurations and parameters, it may be impossible to establish
guidelines that will cover all conditions.
David W.Jackson (R. W. Beck and Associates, Waltham, MA): In their The authors appreciate the supporting comments from Messrs. Dalton
recommendations for dealing with possibly destructive overvoltages which and Simpson as well as those from the other discussers.
might occur on ungrounded wye-delta systems with unbalanced loads the
authors have suggested limiting any unbalanced load on one phase to no Reference
more than four times the load on either of the other phases. They have also 1. Working Group of the IEEE Surge Protective Devices Committee,
suggested closing the disconnect on the large single phase load last. Several “Voltage Rating Investigation for the Application of Lightning
questions arise. Arresters on Distribution Systems,” IEEE Transactions on Power
What is the basis for the load unbalance ratio of four times? Has this Apparatus and Systems, Vol. PAS-91, pp. 1067-1074, 1972.
limitation been explored analytically or experimentally to prove that it is Manuscript received April 13, 1988.

You might also like