and Maintenance
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
Scientific research has shown that certain man-made • Before installing/servicing this unit,
chemicals can affect the earth’s naturally occurring technicians MUST put on all PPE required for
stratospheric ozone layer when released to the the work being undertaken (Examples; cut
atmosphere. In particular, several of the identified resistant gloves/sleeves, butyl gloves, safety
chemicals that may affect the ozone layer are glasses, hard hat/bump cap, fall protection,
refrigerants that contain Chlorine, Fluorine and Carbon electrical PPE and arc flash clothing).
(CFCs) and those containing Hydrogen, Chlorine, ALWAYS refer to appropriate Material Safety
Fluorine and Carbon (HCFCs). Not all refrigerants Data Sheets (MSDS)/Safety Data Sheets
containing these compounds have the same potential (SDS) and OSHA guidelines for proper PPE.
impact to the environment. Trane advocates the
responsible handling of all refrigerants-including • Wh en working wit h or ar oun d hazard ous
industry replacements for CFCs and HCFCs such as chemicals, ALWAYS refer to the appropriate
saturated or unsaturated HFCs and HCFCs. MSDS/SDS and OSHA/GHS (Global
Harmonized System of Classification and
Important Responsible Refrigerant Labelling of Chemicals) guidelines for
information on allowable personal exposure
Practices levels, proper respiratory protection and
Trane believes that responsible refrigerant practices handling instructions.
are important to the environment, our customers, and • If t here is a risk o f en erg ized electrical
the air conditioning industry. All technicians who contact, arc, or flash, technicians MUST put
handle refrigerants must be certified according to local on all PPE in accordance with OSHA, NFPA
rules. For the USA, the Federal Clean Air Act (Section 70E, or other country-specific requirements
608) sets forth the requirements for handling, for arc flash protection, PRIOR to servicing
reclaiming, recovering and recycling of certain the unit. NEVER PERFORM ANY SWITCHING,
refrigerants and the equipment that is used in these DISCONNECTING, OR VOLTAGE TESTING
service procedures. In addition, some states or WIT HOUT PROP ER ELECT RIC AL PPE AND
municipalities may have additional requirements that ARC FLASH CLOTHING. ENSURE
must also be adhered to for responsible management ELECTRICAL METERS AND EQUIPMENT ARE
of refrigerants. Know the applicable laws and follow PROPERLY RATED FOR INTENDED
them. VOLTAGE.
WARNING WARNING
Follow EHS Policies! Explosion Hazard!
Failure to follow instructions below could result in Failure to follow instructions below could result in
death or serious injury. an explosion which could result in death or
serious injury, and equipment damage.
• All Ingersoll Rand personnel must follow NEVER bypass system safeties in order to pump
Ing erso ll R an d Environ men tal, Healt h an d down the unit component's refrigerant into the
Safety (EHS) policies when performing work microchannel heat exchanger (MCHE) coil. Do
such as hot work, electrical, fall protection, NOT depress the compressor contactor since it
lockout/tagout, refrigerant handling, etc. All effectively bypasses the high-pressure control.
policies can be found on the BOS site. Where
local regulations are more stringent than
these policies, those regulations supersede Copyright
these policies.
This document and the information in it are the
• Non-Ingersoll Rand personnel should always property of Trane, and may not be used or reproduced
follow local regulations. in whole or in part without written permission. Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
WARNING to notify any person of such revision or change.
Refrigerant under High Pressure!
Failure to follow instructions below could result in Trademarks
an explosion which could result in death or
All trademarks referenced in this document are the
serious injury or equipment damage.
trademarks of their respective owners.
System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure
before opening the system. See unit nameplate for Revision History
refrigerant type. Do not use non-approved • Configure to Order model number structure has
refrigerants, refrigerant substitutes, or refrigerant been released and is now reflected in the model
additives. structure. All referenced model numbers have been
updated to reflect this.
• Wiring matrix has been updated.
• Please note the Installation checklist has been
moved to the Pre-Installation section.
• Minor running edits included.
SS-SVX10L-EN 3
Table of Contents
Model Number Description . . . . . . . . . . . . . . . . . 6 Low Outdoor Ambient Cooling . . . . . . . . 33
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . . 6 Evaporator Defrost Control
(EDC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
General Information . . . . . . . . . . . . . . . . . . . . . . . . 7 Low Pressure Cut-Out (LPCO) . . . . . . . . . 33
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . 7 High Pressure Cut-Out (HPCO) . . . . . . . . 33
Internal Overload Protector
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 (IOL) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Inspection Checklist . . . . . . . . . . . . . . . . . . . 8
Electromechanical Controls . . . . . . . . . . . . . . 34
Testing for Leaks . . . . . . . . . . . . . . . . . . . . . . . . . 8 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Lifting Recommendations . . . . . . . . . . . . . . . . . 8 Evaporator Fan (Indoor Supply
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Air) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . 34
Unit Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Structural Preparation . . . . . . . . . . . . . . . . . 9 Service Test Modes for ReliaTel™
Rooftop Mounting . . . . . . . . . . . . . . . . . . . . 9 Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Ground Level Mounting . . . . . . . . . . . . . . . 9 Test Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Installation Checklist . . . . . . . . . . . . . . . . . . . . . . 9 Step Test Mode . . . . . . . . . . . . . . . . . . . . . . 35
Refrigerant Piping. . . . . . . . . . . . . . . . . . . . . 9 Resistance Test Mode . . . . . . . . . . . . . . . . 35
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . 10 Auto Test Mode . . . . . . . . . . . . . . . . . . . . . . 35
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . 11 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Troubleshooting ReliaTel™
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Cooling Condenser . . . . . . . . . . . . . . . . . . . . . . 20
System Status Checkout Procedure . . . . . . . 36
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Method 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Refrigerant Piping Guidelines. . . . . . . . . . . . . 22 Method 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Refrigerant Piping Procedures (Outdoor Temperature Tests. . . . . . . . . . . . . . . . . . . . . . . 37
Units). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 Test 1 - Zone Temperature
Thermistor (ZTEMP). . . . . . . . . . . . . . . . . . 37
Refrigerant Piping Procedures (Indoor
Test 2 - Cooling Set Point (CSP) and
Unit). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Heating Set Point (HSP). . . . . . . . . . . . . . . 37
Leak Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Test 3 - System Mode and Fan
System Evacuation. . . . . . . . . . . . . . . . . . . 24 Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Insulating and Isolating Refrigerant Test 4 - LED Indicator Test (SYS ON,
Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 HEAT, & COOL) . . . . . . . . . . . . . . . . . . . . . . 38
Refrigerant Charging Procedure . . . . . . . . . . 25 Programmable & Digital Zone Sensor
Charging Levels. . . . . . . . . . . . . . . . . . . . . . 26 Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Testing Serial Communication
Liquid Charging . . . . . . . . . . . . . . . . . . . . . . . . . 27 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 28 RLCI Loss of Communications. . . . . . . . . 39
Unit Power Supply . . . . . . . . . . . . . . . . . . . 28 Resetting Cooling and Heating
Low Voltage Wiring . . . . . . . . . . . . . . . . . . 28
Lockouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Electromechanical Controls . . . . . . . . . . . 28
Method 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
ReliaTel Controls. . . . . . . . . . . . . . . . . . . . . 29
Method 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . 30
Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . 32 Zone Temperature Sensor (ZTS) Service
Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Pre-Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Control Circuit Features . . . . . . . . . . . . . . . . . . 33
Discharge Temperature Limit Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
(DTL). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Annually (Cooling Season) . . . . . . . . . . . . . . . 40
4 SS-SVX10L-EN
Table of Contents
SS-SVX10L-EN 5
Model Number Description
Cooling Condenser
Digit 1–3 — Unit Function Digit 8 — Voltage Digit 15 — Controls
A = Generation A 0 = None
6 SS-SVX10L-EN
General Information
This manual describes proper installation, operation, manual should remain weather-protected with the unit
and maintenance procedures for air-cooled systems. until all installation procedures are complete.
By carefully reviewing the information within this N o t e : It is not the intention of this manual to cover all
manual and following the instructions, the risk of possible variations in systems that may occur or
improper operation and/or component damage will be to provide comprehensive information
minimized. It is important that periodic maintenance be concerning every possible contingency that may
performed to help assure trouble free operation. be encountered during an installation. If
Should equipment failure occur, contact a qualified additional information is required or if specific
service organization with qualified, experienced HVAC problems arise that are not fully discussed in this
technicians to properly diagnose and repair this manual, contact your local sales office.
equipment.
Use the “Installation Checklist,” p. 9 provided In this
I m p o r t a n t : All phases of this installation must comply manual to verify that all necessary installation
with the NATIONAL, STATE & LOCAL procedures have been completed. Do not use the
CODES. In addition to local codes, the checklist as a substitute for reading the information
installation must conform with National contained in the manual. Read the entire manual
Electric Code -ANSI/NFPA NO. 70 LATEST before beginning installation procedures.
REVISION.
Any individual installing, maintaining, or servicing this
equipment must be properly trained, licensed and
Unit Description
qualified. These condensers come with single, dual and
I m p o r t a n t : Do not remove the VFD without first manifolded compressor options. Single compressor
contacting technical support! For outdoor units feature a single refrigeration circuitry,
performance-related questions and requiring only one set of refrigerant lines. Dual
diagnostic support in North America call 1- compressor/dual circuit models give true stand-by
877-872-6363. Any return requires a claim protection; if one compressor fails, the second will
number FIRST. Removal of the VFD prior to automatically start-up. During light load conditions,
this step will void the unit’s warranties. only one compressor will operate to save energy.The
dual manifolded scroll compressors come with two
Installation procedures should be performed in the stages of capacity modulation and a single
sequence that they appear in this manual. Do not refrigeration circuit.
destroy or remove the manual from the unit. The
SS-SVX10L-EN 7
Pre-Installation
Unit Inspection Lifting Recommendations
Inspect material carefully for any shipping damage. If
damaged, it must be reported to, and claims made
WARNING
against the transportation company. Compare the Improper Unit Lift!
information that appears on the unit nameplate with Failure to properly lift unit could result in unit
ordering and submittal data to ensure the proper unit dropping and possibly crushing operator/
was shipped. Available power supply must be technician which could result in death or serious
compatible with electrical characteristics specified on injury, and equipment or property-only damage.
component nameplates. Replace damaged parts with Test lift unit approximately 24 inches (61 cm) to
authorized parts only. verify proper center of gravity lift point. To avoid
dropping of unit, reposition lifting point if unit is
Inspection Checklist not level.
To protect against loss due to damage incurred in
transit, complete the following checklist upon receipt of NOTICE
the unit.
Equipment Damage!
Inspect individual pieces of the shipment before
Use spreader bars to prevent straps from
accepting the unit. Check for obvious damage to the
damaging the unit. Install the bars between lifting
unit or packing material.
straps, both underneath the unit and above the
Inspect the unit for concealed damage before it is unit to prevent the straps from crushing the unit
stored and as soon as possible after delivery. cabinet or damaging the finish.
Concealed damage must be reported within 15
days. If concealed damage is discovered, stop Before preparing the unit for lifting, estimate the
unpacking the shipment. Do not remove damaged approximate center of gravity for lifting safety. Because
material from the receiving location. Take photos of of placement of internal components, the unit weight
the damage if possible. The owner must provide may be unevenly distributed. See “Weights,” p. 20 for
reasonable evidence that the damage did not occur approximate unit weights.
after delivery. The crated unit can be moved using a forklift of suitable
Notify the carrier’s terminal of damage immediately capacity. For lifting the unit, attach lifting straps or
by phone and by mail. Request an immediate joint slings securely to the lifting holes at each corner (see
inspection of the damage by the carrier and the unit drawings in “Weights,” p. 20). Use spreader bars
consignee. to protect the unit casing from damage. Test lift the
unit to determine proper balance and stability.
Notify the sales representative and arrange for
repair. Do not repair the unit until the damage is
inspected by the carrier’s representative. Clearances
Provide enough space around the unit to allow
Testing for Leaks unrestricted access to all service points. Refer to the
“Dimensional Data,” p. 11 for unit dimensions and
All units are shipped with a holding charge of nitrogen
minimum required service and free air clearances.
in each circuit and should be leak tested before
Observe the following points to ensure proper unit
installation.
operation.
1. Remove the access panel.
1. Do not install the unit under a low overhang.
2. Locate the liquid line or suction line access valve for Condenser discharge must not be restricted—refer
each circuit. to notes in “Dimensional Data drawings,” p. 11.
3. Install gauges to determine if the circuits are still I m p o r t a n t : Do not obstruct condenser discharge
pressurized. If not, the charge has escaped and air. This can result in warm air
should be repaired as required to obtain a leak-free recirculation through the coil.
circuit.
2. Do not locate the unit in a position where runoff
water can fall into the fan discharge openings.
3. Condenser intake air is supplied from three or four
sides of the unit. Adhere to the minimum required
clearances given in unit dimensional drawings (see
“Dimensional Data,” p. 11).
8 SS-SVX10L-EN
Pre-Installation
Structural Preparation
Roof
NOTICE Construction
Roof Damage! Roof Trussing
System contains oil and refrigerant under high
pressure. Roofs should be protected from
exposure to oils and refrigerant in the system. If Ceiling
rooftop is not protected, damage to the roof may
occur.
Ground Level Mounting
I m p o r t a n t : Refer to local building codes for proper For ground level installation, the unit base should be
installation. All installation must comply adequately supported and hold the unit near level. The
with local building codes. installation must meet the guidelines set forth in local
codes. The support should extend two inches beyond
Rooftop Mounting the unit base channels at all points. The unit and
If the unit will be roof mounted, determine for certain support must be isolated from any adjacent structure
that the structure is strong enough to support the unit to prevent possible noise or vibration problems. Any
and any required accessories, see “Weights,” p. 20. ground level location must comply with required
The unit should be elevated on a level, field fabricated clearances given in the unit dimensional drawings (see
four-inch steel or wood 4" x 4" mounting frame. “Dimensional Data,” p. 11).
Complete the frame and secure it into position before
lifting the unit to the roof. The mounting frame must
support a minimum of three of the unit’s four sides and
Installation Checklist
should span roof supports to distribute the load on the Complete this checklist once the unit is installed to
roof. verify that all recommended procedures have been
accomplished before starting the system. Do not
operate the system until all items covered by this
checklist are complete.
Inspect unit location for proper required service
clearances.
Inspect unit location for proper free air clearances.
Inspect unit location for secure, level mounting
position.
Remove coil protection boards on microchannel
units.
Refrigerant Piping
Properly sized/constructed liquid and suction lines
connected to stubs at both the indoor and outdoor
units?
Insulated the entire suction line?
Insulated portions of liquid line exposed to
extremes in temperature?
SS-SVX10L-EN 9
Pre-Installation
Performed initial leak test? proper terminals in the unit control section?
Evacuated each refrigerant circuit to 500 microns? Installed system indoor thermostat?
Charged each circuit with proper amount of R- Installed system low voltage interconnecting wiring
410A? to proper terminals of outdoor unit, indoor unit and
system thermostat?
Electrical Wiring
Provided unit power wiring (with disconnect) to
10 SS-SVX10L-EN
Dimensional Data
Figure 2. Height, width and depth measurements
H
W
D
D W
SS-SVX10L-EN 11
Dimensional Data
Figure 3. 5, 6, 6.25 and 7.5 ton condensing unit, single compressor, microchannel
SEE NOTE 3
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
SERVICE PANEL 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
SEE NOTE 4
HAIL GUARD
(OPTIONAL)
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE) SEE NOTE 1
35 15/16"
(912.8) REFRIGERANT ACCESS
WITH HAIL GUARD
33 7/8"
(860.4)
1/16"
(1.59) 6" (152.4) 2 7/8"
6" (152.4) (73)
21 11/16" 1 7/8"
(550.9) (47.6) 40 15/16"
(1039.8)
33 13/16" 41 15/16"
(858.8) (1065.2)
WITH HAIL GUARD
SERVICE PANEL SIDE
40 3/4" BOTTOM
(1035) 34 3/4"
(882.6) OF UNIT
4 3/16"
(106.36)
1 13/16" 27 11/16" 2 5/16"
(46) (703.3) (58.7)
12 SS-SVX10L-EN
Dimensional Data
Figure 4. 5, 6, 6.25 and 7.5 ton condensing unit, dual compressor, microchannel
SEE NOTE 3
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
SERVICE PANEL 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
SEE NOTE 4
HAIL GUARD
(OPTIONAL)
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE) SEE NOTE 1
35 15/16"
(912.8) REFRIGERANT ACCESS
WITH HAIL GUARD
33 7/8"
(860.4)
1/16"
(1.59) 6" (152.4) 2 7/8"
6" (152.4) (73)
21 11/16" 1 7/8"
(550.9) (47.6) 40 15/16"
(1039.8)
33 13/16" 41 15/16"
(858.8) (1065.2)
WITH HAIL GUARD
SERVICE PANEL SIDE
40 3/4" BOTTOM
(1035) 34 3/4"
(882.6) OF UNIT
4 3/16"
(106.36)
1 13/16" 27 11/16" 2 5/16"
(46) (703.3) (58.7)
SS-SVX10L-EN 13
Dimensional Data
Figure 5. 8.33 and 10 ton condensing unit, single and manifolded compressor. microchannel
SEE NOTE 3
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
SERVICE PANEL WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING)
HAIL GUARD
SEE NOTE 4 (OPTIONAL)
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE
SEE NOTE 1
39 15/16"
(1014.4) REFRIGERANT ACCESS
HAIL GUARD 4 1/4" WITH HAIL GUARD
(OPTIONAL) (108)
1 1/4" 37 15/16"
(31.7) LINE VOLTAGE
(963.6)
CONTROL WIRING
39 1/8"
SERVICE PANEL (993.8)
34 1/16" (865.2)
26 7/8"
(682.6)
14 5/16"
(363.5)
1/16"
(1.6) 1 7/8"
6" 25 11/16" 6" (47.6)
(152.4) (652.5) (152.4) 2 7/8" (73)
50 15/16"
37 11/16" (1294)
(957.3)
51 15/16"
(1319.2)
WITH HAIL GUARD
50 3/4"
(1289) BOTTOM
44 3/4" OF UNIT
(1136.6)
3 13/16"
(96.8)
14 SS-SVX10L-EN
Dimensional Data
NOTES:
1. ACCESS OPENING IS FOR FIELD INSTALLED BAYLOAM ACCESSORY.
2. MINIMUM CLEARANCE FOR PROPER OPERATION IS 36" (914.4) FROM
WALLS, SHRUBBERY, PRIVACY FENCES ETC. MINIMUM CLEARANCE
BETWEEN ADJACENT UNITS IS 72" (1828.8). RECOMMENDED SERVICE
CLEARANCE 48" (1219.2)
SERVICE PANEL 3. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR 100" (2540)
MINIMUM. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES
NOT POUR DIRECTLY ON UNIT
4. OUTDOOR AIR TEMPERATURE SENSOR OPENING (DO NOT BLOCK OPENING).
HAIL GUARD
SEE NOTE 4
(OPTIONAL)
SERVICE CLEARANCE
48" (1219.2) (SEE NOTE 2
FOR CLEARANCE)
SEE NOTE 1
39 15/16"
(1014.4) REFRIGERANT ACCESS
WITH HAIL GUARD
37 15/16"
(963.6)
39 1/8"
SERVICE PANEL (993.8)
26 7/8"
(682.6)
14 5/16"
(363.5)
1/16"
(1.6) 1 7/8"
6" 25 11/16" 6" (47.6)
(152.4) (652.5) (152.4) 2 7/8" (73)
50 15/16"
37 11/16" (1294)
(957.3)
51 15/16"
(1319.2)
WITH HAIL GUARD
SERVICE PANEL SIDE
50 3/4"
(1289) BOTTOM
44 3/4" OF UNIT
(1136.6)
3 13/16"
(96.8)
SS-SVX10L-EN 15
Dimensional Data
Figure 7. 10.4 and 12.5 ton condensing unit, dual compressor, microchannel
SEE NOTE 2
SEE NOTE 3
16 SS-SVX10L-EN
Dimensional Data
Figure 8. 13, 15, 16.7 and 20 ton condensing unit, dual compressor, microchannel
SS-SVX10L-EN 17
Dimensional Data
Figure 9. 13, 15, 16.7 and 20 condensing unit, manifolded compressor, microchannel
18 SS-SVX10L-EN
Dimensional Data
Figure 10. 20.9 and 25 ton condensing unit, manifolded compressor, microchannel
SS-SVX10L-EN 19
Weights
Cooling Condenser
Table 1. TTA unit and corner weights — lbs (60 Hz)
20 SS-SVX10L-EN
Weights
Figure 11. TTA072, 090, 120, 150, TTA060, 076, 101 Figure 12. TTA180, 240, 300, TTA156, 201, 251
#3 #4
#4 #1
#1
#3
#2
SER
ACC VICE
ESS #2
SER
SER ACC VICE
ACC VICE ESS
ESS
LIFTING HOLES
LIFTING HOLES (BOTH SIDES)
(BOTH SIDES)
SS-SVX10L-EN 21
Installation
Refrigerant Piping Guidelines
Figure 13. Allowable elevation difference: TTA above indoor unit
Figure 14. Allowable elevation difference: TTA or TWA below indoor unit
N o t e : Route refrigerant piping for minimum linear length, minimum number of bends and fittings.
22 SS-SVX10L-EN
Installation
Refrigerant Piping Procedures Figure 15. Outdoor units - refrigerant piping (with dry
nitrogen)
(Outdoor Units)
WARNING
R-410A Refrigerant under Higher
Pressure than R-22!
Failure to use proper equipment or components as
described below, could result in equipment failing
and possibly exploding, which could result in
death, serious injury, or equipment damage.
The units described in this manual use R-410A
refrigerant which operates at higher pressures
than R-22. Use ONLY R-410A rated service
equipment or components with these units. For
sp ecific h an dlin g co ncerns with R- 410A, please
contact your local Trane representative.
WARNING
Explosion Hazard!
Failure to follow instructions below could result in 3. Remove the refrigerant connection seal caps and
an explosion which could result in death or open the service valve slowly to release the
serious injury, and equipment damage. nitrogen from the unit.
NEVER bypass system safeties in order to pump
down the unit component's refrigerant into the NOTICE
micro channel heat exchang er (MC HE) coil. Do System Component Damage!
NOT depress the compressor contactor since it Do not remove the seal caps from refrigerant
effectively bypasses the high-pressure control. connections, or open the service valves until
prepared to braze refrigerant lines to the
Each unit ships with a holding charge of dry nitrogen. connections. Excessive exposure to atmosphere (>
The nitrogen should be removed and the entire system 5 min.) may allow moisture or dirt to contaminate
evacuated (at the proper time) to avoid possible the system, damaging valve seals and causing ice
contamination. formation in system components.
1. Remove the compressor service access panel.
2. Locate the liquid and suction line service valves. WARNING
Check that the piping connection stubs on the Explosion Hazard and Deadly Gases!
valves (Figure 15, p. 23) line up properly with the
holes in the unit cabinet. Failure to follow all proper safe refrigerant
handling practices could result in death or serious
injury.
Never solder, braze or weld on refrigerant lines or
any unit components that are above atmospheric
pressure or where refrigerant may be present.
Always remove refrigerant by following the
guidelines established by the EPA Federal Clean
Air Act o r o ther state o r local cod es as ap pro priat e.
After refrigerant removal, use dry nitrogen to
bring system back to atmospheric pressure before
opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from
soldering, brazing or welding with refrigerant
vapors present can form highly toxic gases and
extremely corrosive acids.
SS-SVX10L-EN 23
Installation
TEST xref (using insertion from resource mgr): 5. Shut off nitrogen supply.
24 SS-SVX10L-EN
Installation
NOTICE NOTICE
Operating Under Vacuum! Equipment Damage!
Failure to follow these instructions will result in This is POE oil, which readily absorbs moisture.
compressor failure. Always use new oil and never leave containers
Do not operate or apply power to the compressor open to atmosphere while not in use.
while under a vacuum.
Table 3. TTA approved oils
4. Evacuate the system to hold a 500 micron vacuum.
Unit Model Number Approved Oils
5. Close off valve to vacuum pump and observe the
micron gauge. If gauge pressure rises above 500 TTA0604DA, TTA0604DD,
microns in one minute, then evacuation is TTA0724*A, TTA0724*D,
TTA0764DD, TTA0904*D,
incomplete or the system has a leak. TTA0764DA, TTA0904*A,
TTA1014DC, TTA1014DD, Trane Oil Part Number
6. If vacuum gauge does not rise above 500 microns in
TTA1204*C, TTA1204*D, OIL00094 (1 quart container)
10 minutes, the evacuation should be complete. TTA1264DD, TTA1504*D,
TTA1564DD, TTA1804*D,
NOTICE TTA1564DC, TTA1804*C,
TTA2404*D
Equipment Damage! Trane Oil Part Number
TTA1014DA, TTA1204*A,
Charge with access port on the liquid line service TTA2014DC, TTA2014DD, OIL00079 (1 quart container)
valve only. TTA2404*C, TTA2514DC, or OIL00080 (1 gallon
TTA3004*C container)
7. With vacuum pump and micron gauge blanked off,
open valve on R-410A cylinder and allow refrigerant For units equipped with compressors containing site
pressure to build up to about 80 psig. glasses, the oil level must be visible through the sight
8. Close valve on the R-410A supply cylinder. Close glass when the compressor is running under stabilized
valves on manifold gauge set and remove conditions and a few minutes after the compressor has
refrigerant charging hoses from liquid and gas stopped.
gauge ports.
9. Leak test the entire system. Using proper Refrigerant Charging Procedure
procedures and caution, as described in the
previous section, repair any leaks found and repeat If charging by weight, refer to for starting change. If
the leak test. refrigerant adjustments are needed because of length
of line, refer to the Charging Charts and Superheat
values in the unit’s Service Facts.
Insulating and Isolating Charge by weight through the gauge port on the liquid
Refrigerant Lines line. Once the charge enters the system, backseat
(open) the liquid line service valve and disconnect the
Insulate the entire suction line with refrigerant piping
charging line and replace the cap on the gauge port.
insulation. Also insulate any portion of the liquid line
exposed to temperature extremes. Insulate and isolate Notes:
liquid and suction lines from each other. Isolate • R-410A should only be charged in the liquid
refrigerant lines from the structure and any duct work. state.
Important: • When possible, always charge the
1. To prevent possible noise or vibration refrigerant into the liquid line of the unit.
problems, be certain to isolate • If the entire charge can’t be charged into the
refrigerant lines from the building. liquid line, the balance of the unit charge
2. All suction and hot gas bypass piping (if can be metered through a charging
installed) should be insulated from the manifold set as liquid — preferably through
termination in the air handler to the a schrader valve into the suction line to the
condensing unit cabinet entry. Failure compressor — only while the compressor is
to do so can cause condensate drip off running.
and performance degradation. • Check and adjust superheat using the
3. Prior to starting a unit, it is advisable to superheat table in the unit’s Service Facts,
have the approved oils available in the then re-check charging charts to determine
event oil needs to be added to the if charge corrections are necessary.
system.
SS-SVX10L-EN 25
Installation
NOTICE
Equipment Damage!
Never charge liquid refrigerant into the suction
line of the unit with the compressor off.
Charging Levels
Table 4. Estimated charge levels at AHRI rated line lengths (25 feet) - 50 & 60 Hz
Matched Set Circuit 1 Circuit 2 Liquid Line Diameter Vapor Line Diameter
26 SS-SVX10L-EN
Installation
Table 4. Estimated charge levels at AHRI rated line lengths (25 feet) - 50 & 60 Hz (continued)
Matched Set Circuit 1 Circuit 2 Liquid Line Diameter Vapor Line Diameter
Notes:
1. For line lengths other than 25', please refer to the Application Guide (SS-APG008*-EN) for charge levels, oil addition and line sizes.
2. TTA0604DA and TTA0724*A need a reducer for vapor line. (1.375 to 1.125 inch) (1 3/8” to 1 1/8”).
3. TTA2514DC and TTA3004*C are provided with a transition tube to be installed outside of the unit for front or rear access, (1.625 to
2.125 inch) (1 5/8" to 2 1/8"). See Refrigerant Charging Procedure for transition tube location and electrical connections.
SS-SVX10L-EN 27
Installation
28 SS-SVX10L-EN
Installation
Figure 17. Electromechanical jobsite connections I m p o r t a n t : For the EDC switch to be functional and
Disconnect Switch
thereby facilitate reliable unit operation,
(By Others) make the EDC connections from the indoor
to the outdoor control boxes.
B Air Handler
Figure 18. ReliaTel jobsite connections
Disconnect Switch
Electric (By Others)
T’stat Note 2
Heat Accessory
C
B
B
Air Handler
A Disconnect Switch
(By Others)
B
A. 3 power wires, line voltage for 3 phase, (2 power wires for D Disconnect Switch
single phase) (By Others) Note 2
B. 3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
C. Cooling only thermostat: 3 to 7 wires depending on stages of A Disconnect Switch
(By Others)
D.
electric heat
3 to 7 wires depending on type of outdoor unit(s)
C E F
SS-SVX10L-EN 29
Installation
Field Wiring
Figure 19. Night setback panel field wiring
30 SS-SVX10L-EN
Installation
SS-SVX10L-EN 31
Installation
Refrigerant Circuit
Figure 23. Typical split system cooling refrigerant circuit — microchannel
COOLING ONLY CIRCUIT DIAGRAM
DISCHARGE
TEMPERATURE
LIMIT (DTL)
GAUGE HIGH PRESSURE
CONNECTION SWITCH (HPCO)
D
NOTE A
FIELD SUPPLIED
S INTER-CONNECTING
TUBING
COMPRESSOR
EQUALIZER
EXPANSION TUBE
VALVE BULB
OUTDOOR COIL
AIR
GAUGE
CONNECTION SERVICE
VALVE
AIR
V
TXV
LOW PRESSURE
INDOOR COIL
SWITCH (LPCO)
SERVICE
VALVE
32 SS-SVX10L-EN
Pre-Start
Control Circuit Features compressor and the outdoor fans if suction pressure
drops below the Low Pressure Cut-Out setting. Once
N o t e : Not all of these features may be required for your the suction pressure has returned to normal, the
unit, check electrical schematic. compressor and outdoor fans will cycle back on.
Discharge Temperature Limit (DTL) High Pressure Cut-Out (HPCO)
The control’s sensor is located on the discharge line. This control’s sensor is located in the discharge line.
This device will shut off the compressor and the This device will shut off the compressor and the
outdoor fan(s) if the discharge temperature exceeds the outdoor fan(s) if the discharge pressure exceeds the
DTL setting. Once the discharge temperature has High Pressure Cut-Out’s setting. Once the discharge
returned to normal, the compressor will cycle back on. pressure has returned to normal, the compressor will
cycle back on.
Low Outdoor Ambient Cooling
The Evaporator Defrost Control is standard equipment WARNING
on Air Handlers and will permit low ambient cooling
Prevent Injury!
down to 50°F. For cooling operation down to 0°F, use
an Accessory Head Pressure Control on the outdoor Due to agency safety requirements, no schrader
unit. core is to be installed beneath the HPCO. Removal
of the HPCO without evacuating the system charge
Evaporator Defrost Control (EDC) could cause injury and release of refrigerant.
SS-SVX10L-EN 33
Startup
Electromechanical Controls cooling mode, fan operation coincides with the cooling
run cycles. If the system is equipped with heat and is
The 24–volt, electromechanical controls feature a operating in the heating mode while the fan switch is at
control transformer and contactor pressure lugs for A U T O , fan operation coincides with the heating run
power wiring. Once the unit is properly installed and cycles. When the fan switch is positioned at O N , fan
pre-start procedures are complete, start the unit by operation is continuous.
turning the System Switch on the indoor thermostat to
either H E A T , C O O L or A U T O . The system should Cooling Mode
operate normally.
With the disconnect switch in the O N position, current
NOTICE is supplied to the compressor sump heater(s), phase
monitor and control transformer. The sump heater(s)
Equipment Damage! supplies heat to the compressor(s) during the “ O f f ”
Ensure the disconnect for the indoor air handler is cycle. The phase monitor looks at the incoming power
closed before operating the system. Operating the to verify that there is no reversed phase, no phase
outdoor unit without the indoor fan energized can imbalance, and no loss of phase. If the phase monitor
cause unit trip-out on high pressure control and/or detects any of these three conditions, it will shut off
liquid flood back to the compressor. control voltage. The transformer steps down the line
voltage to 24V for the low voltage control circuit. When
General the room thermostat system switch is positioned at
C O O L and the fan switch is at A U T O , the compressor
Operation of the system cooling (and optional heating) contactor energizes on a call for cooling. When the
cycles is controlled by the position of the system switch contacts of the compressor contactor close, operation
on the room thermostat. Once the system switch is of the compressor and condenser fan begins. The
placed in either the H E A T or C O O L position, unit evaporator fan contactor also energizes on a call for
operation is automatic. The optional automatic cooling and initiates evaporator fan operation.
changeover thermostat, when in the A U T O position,
On units with dual circuits, except the 10 and 20 ton,
automatically changes to heat or cool with sufficient
the second stage of cooling is initiated as a result of the
room temperature change.
2-stage thermostat calling for additional cooling. For
Evaporator Fan (Indoor Supply Air) the 10 and 20 ton dual circuit units, both compressors
operate in an unloaded condition in the first stage of
The evaporator fan is controlled by an O N / A U T O cooling and fully loaded in the second stage.
switch on the room thermostat. With the switch
positioned at A U T O and the system operating in the
34 SS-SVX10L-EN
™ Controls
Service Test Modes for ReliaTel™
Test Modes There are three methods in which the “ S e r v i c e T e s t ”
can be cycled at LTB-Test 1(T1) and LTB-Test 2 (T2).
Upon power initialization, the RTRM performs self-
diagnostic checks to ensure that all internal controls Step Test Mode
are functional. It also checks the configuration
parameters against the components connected to the This method initiates the different components of the
system. The system LED located on the RTRM module unit, one at a time, by temporarily shorting across the
is turned “ O n ” within one second of power-up if two test terminals for 2 to 3 seconds.
internal operation is okay. For the initial start-up of the unit, this method allows
Use one of the following “ T e s t ” procedures to bypass the technician to cycle a component “ O n ” and have up
some time delays and to start the unit at the control to one hour to complete the check. Service Test Mode
panel. Each step of unit operation can be activated will be ignored if a short is present across Test 1 and
individually by temporarily shorting across the “ T e s t ” Test 2 at start-up.
terminals for 2 to 3 seconds. The system LED located
on the RTRM module will blink when the test mode has Resistance Test Mode
been initiated. The unit can be left in any “ T e s t ” step This method can be used for start-up when a decade
for up to one hour before it will automatically box for variable resistance outputs is available. This
terminate, or it can be terminated by opening the main method initiates the different components of the unit,
power disconnect switch. Once the test mode has been one at a time, when a specific resistance value is placed
terminated, the system LED will glow continuously and across the two test terminals. The unit will remain in
the unit will revert to the “ S y s t e m ” control. the specific test mode for approximately one hour even
though the resistance is left on the test terminals.
Auto Test Mode The unit will start the first test step and change to the
next step every 30 seconds. At the end of the test
This method is not recommended for start-up due to
mode, control of the unit will automatically revert to
the short timing between individual component steps.
the applied “ S y s t e m ” control method. For unit test
This method initiates the different components of the
steps, test modes, and step resistance values to cycle
unit, one at a time, when a fixed jumper is installed
the various components, refer to Table 5, p. 35.
across the test terminals.
SS-SVX10L-EN 35
Troubleshooting
Troubleshooting ReliaTel™ outputs, and all of the external controls (relays,
contactors, etc.) that the RTRM outputs energize, for
Controls each respective mode. Proceed to Step 6.
WARNING 6. Step the system through all of the available modes,
and verify operation of all outputs, controls, and
Live Electrical Components! modes. If a problem in operation is noted in any
Failure to follow all electrical safety precautions mode, you may leave the system in that mode for
when exposed to live electrical components could up to one hour while troubleshooting. Refer to the
result in death or serious injury. sequence of operations for each mode, to assist in
When it is necessary to work with live electrical verifying proper operation. Make the necessary
components, have a qualified licensed electrician repairs and proceed to Step 7 and Step 8.
or other individual who has been properly trained
7. If no abnormal operating conditions appear in the
in handling live electrical components perform
test mode, exit the test mode by turning the power
these tasks.
“ O f f ” at the main power disconnect switch.
The RTRM has the ability to provide the service 8. Refer to the individual component test procedures if
personnel with some unit diagnostics and system other microelectronic components are suspect.
status information.
Before turning the main power disconnect switch System Status Checkout
“ O f f , ” follow the steps below to check the ReliaTel™
Refrigeration Module (RTRM). All diagnostics & system Procedure
status information stored in the RTRM will be lost when “ S y s t e m S t a t u s ” is checked by using one of the
the main power is turned “ O f f ” . following two methods:
To prevent injury or death from electrocution, it is the
responsibility of the technician to recognize this hazard Method 1
and use extreme care when performing service
If the Zone Sensor Module (ZSM) is equipped with a
procedures with the electrical power energized.
remote panel with LED status indication, you can check
N o t e : The J6 & J7 screw terminals must be tightened the unit within the space. If the ZSM does not have
in order to accurately measure voltage in the LED’s, use “Method 2,” p. 37. BAYSENS010B,
required steps. BAYSENS011B, BAYSENS119A, BAYSENS020A,
1. Verify that the system LED on the RTRM is burning BAYSENS021A, BAYSENS023A, BAYSENS109 and
continuously. If the LED is lit, go to Step 3. BAYSENS110 all have the remote panel indication
feature. The LED descriptions are listed below.
2. If the LED is not lit, verify that 24 VAC is present
between J1-1 and J1-2. If 24 VAC is present, • LED 1 (System)
proceed to Step 3. If 24 VAC is not present, check – “ O n ” during normal operation.
the unit main power supply, check transformer
– “ O f f ” if a system failure occurs or the LED fails.
(TNS1). Proceed to Step 3 if necessary.
– “ F l a s h i n g ” indicates test mode
3. Utilizing “Method 1,” p. 36 or “Method 2,” p. 37 in
the System Status Checkout Procedure section, • LED 2 (Heat)
check the following: – “ O n ” when the heat cycle is operating.
• System status – “ O f f ” when the heat cycle terminates or the
• Heating status LED fails.
• Cooling status – “ F l a s h i n g ” indicates a heating failure.
N o t e : If a System failure is indicated, proceed to • LED 3 (Cool)
Step 4. If no failures are indicated, proceed to
Step 5. – “ O n ” when the cooling cycle is operating.
4. If a System failure is indicated, recheck Step 1 and – “ O f f ” when the cooling cycle terminates or the
Step 2. If the LED is not lit in Step 1, and 24 VAC is LED fails.
present in Step 2, then the RTRM has failed. – “ F l a s h i n g ” indicates a cooling failure.
Replace the RTRM.
The following information describes the complete
5. If no failures are indicated, use one of the TEST listing of failure indication causes.
mode procedures described in the “Service Test
Modes chapter,” p. 35 to start the unit. This
procedure will allow you to check all of the RTRM
36 SS-SVX10L-EN
Troubleshooting
SS-SVX10L-EN 37
Troubleshooting
Range = 100 to 900 Ohms approximate Test 3 - System Mode and Fan Selection
H e a t S P = Terminals 2 and 5 The combined resistance of the M O D E selection switch
Range = 100 to 900 Ohms approximate and the F A N selection switch can be measured
between terminals 2 and 4 on the Zone Sensor. The
possible switch combinations are listed in Table 7, p.
38 with their corresponding resistance values.
Test 4 - LED Indicator Test (SYS ON, high resistance in both directions, LED is open. If low in
HEAT, & COOL) both directions, LED is shorted.
WARNING Method 3
To test LED’s with ZSM connected to unit, test voltages
Live Electrical Components! at LED terminals on ZSM. A measurement of 32 VDC,
Failure to follow all electrical safety precautions across an unlit LED, means the LED has failed.
when exposed to live electrical components could
result in death or serious injury. I m p o r t a n t : Measurements should be made from LED
common (ZSM terminal 6 to respective LED
When it is necessary to work with live electrical
terminal).
components, have a qualified licensed electrician
or other individual who has been properly trained
in handling live electrical components perform Programmable & Digital Zone
these tasks.
Sensor Test
Method 1 Testing Serial Communication Voltage
Testing the LED using a meter with diode test function.
1. Verify 24 VAC is present between terminals J6-14 &
Test both forward and reverse bias. Forward bias
J6-11.
should measure a voltage drop of 1.5 to 2.5 volts,
depending on your meter. Reverse bias will show an
Over Load, or open circuit indication if LED is
functional.
Method 2
Testing the LED with an analog Ohmmeter. Connect
Ohmmeter across LED in one direction, then reverse
the leads for the opposite direction. The LED should
have at least 100 times more resistance in reverse
direction, as compared with the forward direction. If
38 SS-SVX10L-EN
Troubleshooting
SS-SVX10L-EN 39
Maintenance
WARNING record the reading in the “Maintenance Log,” p. 42.
Hazardous Voltage w/Capacitors! Remove any accumulation of dust and/or dirt from
the unit casing.
Failure to disconnect power and discharge
capacitors before servicing could result in death or Remove corrosion from any surface and repaint.
serious injury. Check the gasket around the control panel door to
Disconnect all electric power, including remote ensure it fits correctly and is in good condition to
disconnects and discharge all motor start/run prevent water leakage.
capacitors before servicing. Follow proper Inspect the control panel wiring to ensure that all
lockout/tagout procedures to ensure the power connections are tight and that the insulation is
cannot be inadvertently energized. For variable intact.
frequency drives or other energy storing
N o t e : Condenser fan motors are permanently
components provided by Trane or others, refer to
lubricated.
the appropriate manufacturer’s literature for
allowable waiting periods for discharge of Check refrigerant piping and fittings for leaks
capacitors. Verify with a CAT III or IV voltmeter Inspect the condenser coils for dirt and debris. If the
rated per NFPA 70E that all capacitors have coils appear dirty, clean them.
discharged.
For additional information regarding the safe
discharge of capacitors, see PROD-SVB06*-EN.
Coil Cleaning
Regular coil maintenance, including annual cleaning-
enhances the unit's operating efficiency by minimizing:
NOTICE
• compressor head pressure and amperage draw
Operating Under Vacuum! • water carryover
Failure to follow these instructions will result in • fan brake horsepower
compressor failure. • static pressure losses
Do not operate or apply power to the compressor
while under a vacuum. At least once each year — or more often if the unit is
located in a “dirty” environment — clean the coil using
Perform all of the indicated maintenance procedures at the instructions outlined below. Be sure to follow these
the intervals scheduled. This will prolong the life of the instructions as closely as possible to avoid damaging
unit and reduce the possibility of costly equipment the coils.
failure.
Microchannel (MCHE) Coils
Monthly NOTICE
Conduct the following maintenance inspections once Coil Damage!
per month.
Failure to follow instructions below could result in
Check unit wiring to ensure all connections are tight coil damage.
and that the wiring insulation is intact. DO NOT use any detergents with microchannel
Inspect the condenser coils for dirt and debris. If the condenser coils.
coils appear dirty, clean them. Use pressurized water or air ONLY, with pressure
no greater than 600psi.
With the unit operating in the cooling mode, check
the suction and discharge pressures and compare For additional information regarding the proper
them with Pressure Curve values in unit Service microchannel coil cleaning procedure, refer to RT-
Facts. Record these readings on the “Maintenance SVB83*-EN
Log,” p. 42. Due to the soft material and thin walls of the MCHE
coils, the traditional field maintenance method
Annually (Cooling Season) recommended for Round Tube Plate Fin (RTPF) coils
does not apply to microchannel coils. Moreover,
The following maintenance procedures must be chemical cleaners are a risk factor to MCHE due to the
performed at the beginning of each cooling season to material of the coil. The manufacturer does not
ensure efficient unit operation. recommend the use of chemical cleaners to clean
Perform all of the monthly maintenance microchannel coils. Using chemical cleaners could lead
inspections. to warranty claims being further evaluated for validity
and failure analysis.
With the unit operating, check unit superheat and
40 SS-SVX10L-EN
Maintenance
The recommended cleaning method for microchannel the pressure washer aimed perpendicular to the face of
condenser coils is pressurized water or air with a non- the coil during cleaning. Optimum clearance between
pinpoint nozzle and an ECU of at least 180 with the sprayer nozzle and the microchannel coil is 1”–3”.
pressure no greater than 600 psi. To minimize the risk
of coil damage, approach the cleaning of the coil with
SS-SVX10L-EN 41
42
Superheat (°F) Subcooling (°F)
Evaporator Entering Air Compressor (at compressor) (at service valve)
Maintenance Log
Note: Perform each inspection once per month (during cooling season) while unit is operating
SS-SVX10L-EN
Wiring Diagram Matrix
Table 8. Wiring schematics R-410A cooling
Model Refrigerant Schematics Device Location Diagrams
Ton Voltage Hz Ph
Number Circuit ReliaTel Electromechanical ReliaTel Electromechanical
TTA0604DA 5 380-415 50 3 Single 12132171 12132168 12132182 12132181
TTA0604DD 5 380-415 50 3 Dual 12132172 12132169 12132182 12132181
TTA07243A 6 208-230 60 3 Single 12132171 12132168 12132182 12132181
TTA07244A 6 460 60 3 Single 12132171 12132168 12132182 12132181
TTA0724WA 6 575 60 3 Single 12132171 12132168 12132182 12132181
TTA0724KA 6 380 60 3 Single 12132171 12132168 12132182 12132181
TTA07243D 6 208-230 60 3 Dual 12132172 12132169 12132182 12132181
TTA07244D 6 460 60 3 Dual 12132172 12132169 12132182 12132181
TTA0724WD 6 575 60 3 Dual 12132172 12132169 12132182 12132181
TTA0724KD 6 380 60 3 Dual 12132172 12132169 12132182 12132181
TTA0764DA 6.25 380-415 50 3 Single 12132171 12132168 12132182 12132181
TTA0764DD 6.25 380-415 50 3 Dual 12132172 12132169 12132182 12132181
TTA09043A 7.5 208-230 60 3 Single 12132171 12132168 12132182 12132181
TTA09044A 7.5 460 60 3 Single 12132171 12132168 12132182 12132181
TTA0904WA 7.5 575 60 3 Single 12132171 12132168 12132182 12132181
TTA0904KA 7.5 380 60 3 Single 12132171 12132168 12132182 12132181
TTA09043D 7.5 208-230 60 3 Dual 12132172 12132169 12132182 12132181
TTA09044D 7.5 460 60 3 Dual 12132172 12132169 12132182 12132181
TTA0904WD 7.5 575 60 3 Dual 12132172 12132169 12132182 12132181
TTA0904KD 7.5 380 60 3 Dual 12132172 12132169 12132182 12132181
TTA1014DA 8.33 380-415 50 3 Single 12132171 12132168 12132182 12132181
TTA1014DD 8.33 380-415 50 3 Dual 12132172 12132169 12132182 12132181
TTA1014DC 8.33 380-415 50 3 Manifold 12132172 12132169 12132182 12132181
TTA12043A 10 208-230 60 3 Single 12132171 12132168 12132182 12132181
TTA12044A 10 460 60 3 Single 12132171 12132168 12132182 12132181
TTA1204WA 10 575 60 3 Single 12132171 12132168 12132182 12132181
TTA1204KA 10 380 60 3 Single 12132171 12132168 12132182 12132181
TTA12043D 10 208-230 60 3 Dual 12132172 12132169 12132182 12132181
TTA12044D 10 460 60 3 Dual 12132172 12132169 12132182 12132181
TTA1204WD 10 575 60 3 Dual 12132172 12132169 12132182 12132181
TTA1204KD 10 380 60 3 Dual 12132172 12132169 12132182 12132181
TTA12043C 10 208-230 60 3 Manifold 12132172 12132169 12132182 12132181
TTA12044C 10 460 60 3 Manifold 12132172 12132169 12132182 12132181
TTA1204WC 10 575 60 3 Manifold 12132172 12132169 12132182 12132181
TTA1264DD 10 380-415 50 3 Dual 12132172 12132169 12132182 12132181
TTA15043D 12.5 208-230 60 3 Dual 12132172 12132169 12132182 12132181
TTA15044D 12.5 460 60 3 Dual 12132172 12132169 12132182 12132181
TTA1504WD 12.5 575 60 3 Dual 12132172 12132169 12132182 12132181
TTA1504KD 12.5 380 60 3 Dual 12132172 12132169 12132182 12132181
TTA1564DD 13.0 380-415 50 3 Dual 12132171 12132168 12132185 12132184
TTA1564DC 13 380-415 50 3 Manifold 12132172 12132169 12132185 12132184
TTA18043D 15 208-230 60 3 Dual 12132171 12132168 12132185 12132184
TTA18044D 15 460 60 3 Dual 12132171 12132168 12132185 12132184
TTA1804WD 15 575 60 3 Dual 12132171 12132168 12132185 12132184
TTA1804KD 15 380 60 3 Dual 12132171 12132168 12132185 12132184
TTA18043C 15 208-230 60 3 Manifold 12132172 12132169 12132185 12132184
TTA18044C 15 460 60 3 Manifold 12132172 12132169 12132185 12132184
TTA1804WC 15 575 60 3 Manifold 12132172 12132169 12132185 12132184
SS-SVX10L-EN 43
Wiring Diagram Matrix
44 SS-SVX10L-EN
Warranty
For Commercial Unitary freight allowed to Buyer’s city (or port of export for
shipments outside the conterminous United States) a
Equipment Rated Under 20 Tons replacement product or, at the option of the warrantor,
and Related Accessories parts for the repair of the product not conforming to
this warranty and which have been returned to the
P r o d u c t s C o v e r e d — This warranty is extended by warrantor.
Trane, and applies to the following products:
The warrantor’s warranty is conditional on the
• All packaged and split system air conditioners and Customer providing written notice to the warrantor
heat pumps have a rated capacity of less than 20 within thirty (30) days of the discovery of the defect. No
tons. product shall be returned to the warrantor without the
• All packaged combinations gas/electric air warrantor’s written permission. No liability whatever
conditioners having a rated capacity of less than 20 shall attach to warrantor until said products have been
tons. fully paid for and then said liability shall be limited to
the purchase price of the equipment shown to be
• All packaged combination gas/electric air
defective.
conditioners having a rated capacity of 1.5 through
5 tons single phase electric power and used for The warranty does not apply to any compressor or gas-
commercial applications. (As used in this warranty, fired heat exchanger which has been repaired or
a commercial application is any application where altered in such manner as, in the judgement of the
the end purchaser uses the product for other than warrantor, affects its stability or reliability. This
personal, family or household purposes.) warranty does not cover (1) any heat exchanger which
has been fired with an improper type of fuel (2) a heat
• All accessories for the above products which are
exchanger which is installed in a beauty parlor, dry
sold by Trane and applied in accordance with Trane
cleaning establishment, de-greasing plant or in any
specifications.
corrosive atmosphere; or (3) any heat exchanger which
is not shown to be defective by the warrantor’s
Basic Warranty inspection.
The warrantor warrants for a period of twelve (12) This warranty does not cover damage due to accident,
months from the initial start-up or eighteen (18) abuse, improper use, external causes, freezing,
months from date of shipment, whichever is sooner, corrosion, erosion or deterioration. Local
that the products covered by this warranty (1) are free transportation, related service labor, air filters,
from defects in material and manufacture, and (2) have diagnosis calls, refrigerant and related items are not
the capacities and ratings set forth in the warrantor’s covered.
catalogs and bulletins. If any part of your air
conditioner fails because of a manufacturing defect, THE WARRANTY AND LIABILITY SET FORTH HEREIN
Warrantor will furnish without charge the required ARE IN LIEU OF ALL OTHER WARRANTIES AND
replacement part. LIABILITIES, WHETHER IN CONTRACT OR IN
NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW OR IN
If the heat exchanger fails because of a manufacturing FACT, INCLUDING IMPLIED WARRANTIES OR
defect within five years from the date of start-up, MERCHANTABILITY AND FITNESS FOR A
Warrantor will furnish without charge a replacement PARTICULAR PURPOSE AND ANY IMPLIED
heat exchanger. In addition, if the optional, factory WARRANTIES OTHERWISE ARISING FROM THE
installed, stainless steel heat exchanger fails because COURSE OF DEALING OR TRADE. IN NO EVENT
of a manufacturing defect within ten years from the SHALL THE WARRANTOR BE LIABLE FOR ANY
date of start-up, Warrantor will furnish without charge INCIDENTAL OR CONSEQUENTIAL DAMAGES.
a replacement heat exchanger.
The warrantor makes certain further warranty
Any local transportation, related service labor and protection available on an optional, extra-cost basis.
diagnosis calls are not included. In addition, if the Any further warranty must be in writing. If you wish
sealed motor-compressor fails because of a further help or information concerning this warranty,
manufacturing defect within the second through fifth contact: Trane — Warrantor, 2701 Wilma Rudolph
year from the date of original purchase, Warrantor will Blvd., Clarksville, TN 37040
furnish without charge the required replacement
compressor.
SS-SVX10L-EN 45
Warranty
46 SS-SVX10L-EN
Notes
SS-SVX10L-EN 47
Ingersoll Rand (NYSE: IR) advances the quality of life by creating comfortable, sustainable and efficient
environments. Our people and our family of brands — including Club Car®, Ingersoll Rand®, Thermo King® and
Trane® — work together to enhance the quality and comfort of air in homes and buildings; transport and protect
food and perishables; and increase industrial productivity and efficiency. We are a global business committed to a
world of sustainable progress and enduring results.
ingersollrand.com
Ingersoll Rand has a policy of continuous product and product data improvements and reserves the right to change design and specifications
without notice.
We are committed to using environmentally conscious print practices.