B provided 3 m
Resultant from P-1 5.00 m
Suggested Length 12 m
Provided Length 13 m 90.69%
qu 129.04 KN/m2
Vu 106.46 KN
ØVc 232.35104 KN 45.82%
Mu 104.89 KN-m
No of Columns 6
Serial No. SER Load ULT Load DISTANCE Lever arm
P1 3918 5447 KN 6.075 m 0 m
P2 2722 3715 KN 2.775 m 6.075 m
P3 3455 4722 KN 6.075 m 8.85 m
P4 4482 6234 KN 0 m 14.925 m
P5 0 0 KN 0 m 14.925 m
P6 0 0 KN 14.925 m 14.925
Total Load 14577 20118 KN
Column Size 450 mm
Slab Thickness 450 mm
B.C. 1.0 TSF
Area Required 149.86 m2
Footing is Coincentric? No
B provided 9 m Distance of Cenroid of Footing From P1 7.4625
Resultant from P-1 7.82 m Distance of Edge of Footing form P1 1.55
Ultimate Presure Due to Ecentricity 15.358
Suggested Length 17 m
Provided Length 18 m 92.51%
qu 151.96 KN/m2
Vu 581.25 KN
ØVc 232.351041 KN 250.16%
Mu 1388.6 KN-m
No of Columns 6
Serial No. SER Load ULT Load DISTANCE Lever arm
P1 649 819 KN 4.626 m 0 m
P2 1370 1784 KN 7.81 m 4.626 m
P3 1632 2128 KN 7.81 m 12.436 m
P4 1757 2290 KN 8.43 m 20.246 m
P5 1058 1355 KN 6 m 28.676 m
P6 750 1200 KN 34.676 m 34.676
Total Load 7216 9576 KN
Column Size 450 mm Edge Distance from CL of Most Left Column= 0.5 m
Slab Thickness 400 mm Edge Distance from CL of Most Right Column= 0.45 m
Bearing Capacity 1.0 TSF Total Length of Footing= 35.626 m
Area Required 74.19 m2 Center Of Footing From Left Edge= 17.813 m
Resutant of Load From Left Edge= 16.93 m
B provided 2.6 m Ececntricity= 0.8841 m
Resultant from P-1 16.43 m UltimateSoil Pressure Due To Ecentricity= 22.27 KN/m2
Suggested Length 29 m
Provided Length 29.62 m 96.34%
qu 159.05 KN/m2
Vu 107.36 KN
ØVc 206.535 KN 51.98%
Mu 91.91 KN-m
Column Size 450 mm Edge Distance from CL of Most Left Column= 0.5 m
Slab Thickness 400 mm Edge Distance from CL of Most Right Column= 0.5 m
Bearing Capacity 1.0 TSF Total Length of Footing= 3 m
Area Required 4.12 m2 Center Of Footing From Left Edge= 1.5 m
Resutant of Load From Left Edge= #VALUE! m
B provided 2.5 m Ececntricity= #VALUE! m
Resultant from P-1 #VALUE! m UltimateSoil Pressure Due To Ecentricity= #VALUE! KN/m2
Suggested Length 2 m
Provided Length 6 m 27.47%
qu #VALUE! KN/m2
Vu #VALUE! KN
ØVc 206.535 KN #VALUE!
Mu #VALUE! KN-m
Column Size 600 mm Edge Distance from CL of Most Left Column= 0.6 m
Slab Thickness 900 mm Edge Distance from CL of Most Right Column= 2.35 m
Bearing Capacity 1.4 TSF Total Length of Footing= 10.375 m
Area Required 53.82 m2 Center Of Footing From Left Edge= 5.1875 m
Resutant of Load From Left Edge= 5.19 m
B provided 6 m Ececntricity= 0.001 m
Resultant from P-1 4.59 m UltimateSoil Pressure Due To Ecentricity= 0.1 KN/m2
Suggested Length 9 m
Provided Length 10.375 m 86.46%
qu 175.39 KN/m2
Vu 324.48 KN
ØVc 438.89 KN 73.93%
Mu 639.31 KN-m