Product PREMIERLINK™

Retrofit Rooftop
Specification Controller

33CSPREMLK

The PremierLink retrofit controllers


offer:
• continuous monitoring and
regulation of the rooftop unit
• compatibility with Carrier diagnostic
display tools
• other devices can read and write
data to the controller
• ability to connect unit to the Carrier
Comfort Network® (CCN) system

Features/Benefits
The PremierLink retrofit
rooftop controller is an
intelligent control that
continuously monitors and
regulates rooftop operation
with reliability and precision
that minimizes downtime to
ensure maximum occupant
comfort.
The PremierLink controller is compati-
ble with the Carrier Comfort
Network (CCN) system. Carrier’s diag-
nostic standard tier display tools such as
System Pilot™ or Touch Pilot™ device
can be used with the PremierLink con-
troller. User interfaces include the CCN
Service Tool, ComfortVIEW™ and
ComfortWORKS® software.
When the PremierLink controller is used
as part of the CCN system, other
devices such as the CCN data transfer,
3V™ linkage coordinator, or Comfort
a33-9147 Controller can read data from or write
data to the retrofit controller.

Copyright 2007 Carrier Corporation Form 33CS-33PS


Features/Benefits (cont)
Extensive control capabilities • compatibility with T58 communicat- The PremierLink controller offers venti-
The 33CSPREMLK retrofit controller ing sensor provides set point adjust- lation monitoring with an optional CO2
provides the following features and ment, timed override, force fan, and ventilation sensor. The CO2 ventilation
benefits: read equipment mode sensor measures the amount of ventilation
• compatibility with System Pilot as a needed by the space and a proportional
• provides software clock and local communicating sensor providing set integral derivative loop (PID) calculation
occupancy schedule for local occu- point adjustment, timed override, and makes adjustments to the economizer
pancy control (requires time broad- a user interface for programming, minimum position during occupied opera-
caster and hardware clock from configuration, and monitoring and tion. The indoor CO2 will be compared to
another device in the system) forcing points an outdoor CO2 reference before making
• uses remote timeclock input to pro- • support a local or global occupancy adjustments to the economizer minimum
vide occupancy control through exter- schedule or remote start input status position.
nal contacts or this input can be to determine occupancy
reconfigured for use with a door or Using a space sensor with set point
• individual fan start delay for each adjustment, timed override and service
window switch to disable heating and Premierlink™ board upon occupancy
cooling if a door or window is left port jack, the PremierLink controller will
change. provide intelligent compressor staging and
open
economizer operation.
• provides continous or intermittent fan Available for wide range of
operation in the occupied mode rooftop applications Modulating control of the economizer
• features supply air temperature limit- will assist mechanical cooling without
ing and integrated safeties for DX The PremierLink controller is available as adversely affecting compressor perfor-
(direct expansion), gas, electric and a field retrofit application and can control mance. Economizer assisted cooling is
heat pump units one or several rooftop units with (multiple determined from a comparison of space
• provides field tests that enables the controllers) from 3 to 25 tons. In addition, temperature, outside air temperature and
user to check output points and verify it has an integrated economizer controller an enthalpy switch input. The switch input
their functionality that eliminates the need for a separate cir- can also be used for differential enthalpy
• controls two stages of DX cooling to cuit board. input, meeting ASHRAE (American Soci-
maintain space temperature set point The PremierLink controller can be ety of Heating, Refrigeration, and Air
• ability to provide occupied and unoc- installed on the following Carrier rooftop Conditioning Engineers) Standard 90.1.
cupied dehumidification units: 48/50HE (2 to 5 tons), 50HEQ (2 The T58 Communicating Space tem-
• controls up to 3 stages of gas heat or to 5 tons), 48/50HJ (3 to 25 tons), perature sensor with service port jack pro-
combination of mechanical and elec- 50HJQ (3 to 15 tons), 48TF/50TFF (3 to vides set point adjustment, timed override,
tric heat to maintain space tempera- 121/2 tons), 50TFQ (3 to 10 tons), 48/ force fan and read equipment mode and
ture set point 50TJ (121/2 to 25 tons), and 48/50TM measures and maintains room tempera-
• ability to control exhaust fan based on (3 to 25 tons). Other Carrier equipment ture by communicating with the Premier-
economizer or occupancy on and non-Carrier equipment can also be Link controller.
2-stage heat units controlled by PremierLink controller. Con- Using an optional indoor humidity sensor,
• ability to control reversing valve on tact a Carrier Factory Sales representative the PremierLink control can provide
heat pump units for more information. dehumidification control on units that are
• provides temperature compensated equipped to provide dehumidification.
start of heating or cooling to achieve Flexibility for every application
set point by the start of the sched- The PremierLink controller is an ad- Simple mounting and ease of
uled occupied time vanced microprocessor-based control. installation
• provides alarms for analog tempera- PremierLink is precision controlled to
send heating and cooling only when The PremierLink controller has an inte-
ture input(s) out of range grated plastic cover with secured with two
• provides alarm for space tempera- needed, reducing energy use and operat-
ing costs. plastic tabs that can be removed for ease
ture deviation from desired set point of installation.
• adjustable filter maintenance timer
• allows manual and system overrides Carrier linkage compatibility For ease of installation, the PremierLink
of selected input/output channels When used as the air source for a 3V™ controller is provided with removable
• supports CCN remote timed override, zoning system, the PremierLink control- Molex connectors which include pigtails
set point adjustment and manual fan ler will use occupancy schedules, zone for easy installation to unit or sensors
control override temperature, and set points from the 3V using spade connectors or wire nuts. The
• provides Broadcast Acknowledger linkage coordinator. The PremierLink removable connectors are designed so
capability for CCN (configuration) controller provides the 3V linkage coordi- that they can be inserted one way so as to
• conforms to the general require- nator with the unit’s operating mode and prevent installation errors. The Premier-
ments for CCN devices supply-air temperature to provide coordi- Link controller also provides an RJ-11
• modulates control of economizer to nation of the individual member zone's modular phone jack for the Network Ser-
assist mechanical cooling without local mode with the system mode. vice Tool connection to the module via the
adversely affecting compressor Carrier Comfort Network® (CCN)
performance Additional control features communications.
• provides ventilation monitoring with The PremierLink controller provides addi-
optional CO2 ventilation sensor tional control features such as
• compatible with T55 space sensor Occupied/Unoccupied scheduling
and T56 space sensor with set point initialized via the network. The Premier-
adjustment, timed override and ser- Link controller offers override invoked
vice port jack from a wall sensor during unoccupied
hours from 1 to 4 hours in 1-hour
increments.

2
Specifications
User interface (4 to 32 C) for heating and 45 to 99 F (7 to 37 C) for
The PremierLink™ controller is designed to allow a service cooling.
person or building owner to configure and operate the unit Communications
through the CCN user interface. A user interface is not
required for day-to-day operation. All maintenance, config- The number of PremierLink controllers is limited only by
uration, setup, and diagnostic information is available the maximum number of controllers allowed on a CCN sys-
through the Level II communications port to allow data tem. Bus length may not exceed 4000 ft (1219 m), with no
access by an attached computer running Network Service more than 60 devices on any 1000 ft (305 m) section.
Tool, ComfortVIEW™, or ComfortWORKS® software. Optically isolated RS-485 repeaters are required every
Data access also can be obtained from System Pilot™ or 1000 ft (305 m). Status and control data is transmitted at a
Touch Pilot™ devices. baud rate of between 9600 and 38.4K.
Wiring connections Activity indicators
Field wiring is 18 to 22 AWG (American Wire Gage). The Two activity indicators present on the PremierLink control-
PremierLink controller is a NEC (National Electrical Code) ler indicate activity. A green LED will indicate activity on
Class 2 rated device. the communication port and a red LED will indicate status
of processor operation.
Inputs
• space temperature sensor
Dimensions
• set point adjustment Height: 53/4-in. (146 mm)
• outdoor air temperature sensor Width: 81/2-in. (216 mm)
• indoor air quality sensor Depth: 3-in. (76 mm)
• outdoor air quality sensor/indoor humidity sensor
• compressor lockout Minimum service dimensions
• fire shutdown Height: 7-in. (178 mm)
• supply fan status Width: 9-in. (229 mm)
• remote time clock/door switch Depth: 4-in. (102 mm)
• enthalpy status
Environmental ratings
Outputs Operating Temperature: –40 to 158 F (–40 to 70 C) at 10
• economizer to 95% RH (non-condensing)
• fan Storage Temperature: –40 to 185 F (–40 to 85 C) at 10 to
• cool stage 1 95% RH (non-condensing)
• cool stage 2
• heat stage 1 Vibration
• heat stage 2 Performance vibration: all planes/directions, 1.5G at 20
• heat stage 3/exhaust/reversing valve/dehumidify/ to 300 Hz
occupied
Shock
Power supply Operation: all planes/directions, 5G peak, 11 ms
2-wire, 24 VAC ± 15% at 40 va, 60 Hz Storage: all planes/directions, 100G peak, 11 ms
Power consumption Corrosion
Normal operating supply range is 18 to 32 VAC with mini- Office environment. Indoor use only.
mum consumption of 10 VA
Approvals
Hardware (memory)
Listed under UL 873, UL94-V0/5VB (plastic), and UL,
Internal flash memory of 64K Canada.
Specified sensing temperature range Standard compliance
The PremierLink controller space temperature range is CE Mark, ASHRAE 90 and ASHRAE 62-99 compliant.
–40 to 245 F (–40 to 118 C). The PremierLink controller
has an allowable control set point range from 40 to 90 F NOTE: Compliance standards subject to change without
notice.

Field-installed accessories
Supply air temperature sensor — The 33ZCSENSAT Space temperature sensor with override button —
supply air temperature sensor is required for all applica- The space temperature sensor monitors room temperature
tions to monitor the temperature of the air delivered. A which is used by the PremierLink controller to determine
second supply air temperature sensor set to thermostat the temperature of conditioned air that is allowed into the
mode (or a space temperature sensor) must be installed in space.
the return air for proper economizer and IAQ (indoor air
quality) control.

3
Field-installed accessories (cont)
The 33ZCT55SPT (T55) space temperature sensor The System Pilot device can be also be used to install,
with override button is required for all applications. The commission, and monitor a PremierLink controller, a
space temperature sensor monitors room temperature 3V™ zoning system, a universal controller, and all other
which is used by the PremierLink™ controller to deter- devices operating on the CCN system. The System Pilot
mine the temperature of conditioned air that is allowed device has a hardware clock and can be used as CCN
into the space. time broadcaster.
Space temperature sensor with override button Humidity sensor — The relative humidity sensor
and set point adjustment — The 33ZCT56SPT (33ZCSENSRH-01) is required for dehumidification
(T56) space temperature sensor with override button control. The rooftoop unit must be equiped with neces-
and set point adjustment can be used in place of the sary accesories to perfom dehumidification. The sensor
33ZCT55SPT (T55) space temperature sensor if local can also be used for monitoring only.
set point adjustment is required. The space temperature NOTE: The relative humidity sensor and outdoor CO2
sensor monitors room temperature which is used by the sensor cannot be installed on the same zone controller.
PremierLink controller to determine the temperature of CO2 sensor — Three different CO2 sensors are avail-
conditioned air that is allowed into the space. able for monitoring space indoor-air quality.
T58 communicating sensor with override button, The 33ZCSENCO2 sensor is an indoor, wall-mount-
set point adjustment, and manual fan control — ed sensor with an LED (light-emitting diode) display.
The 33ZCT58SPT (T58) communicating room sensor The sensor has an analog output (0 to 10 vdc or 4 to 20
with override button, set point adjustment, and manual mA) over a range of 0 to 2000 ppm. An SPDT contact
fan control can be used in place of the 33ZCT55SPT is provided to close at 1000 ppm with a hysteresis of
space temperature sensor. The T58 communicating 50 ppm.
room sensor measures and maintains room temperature
by communicating with the controller. The 33ZCT55CO2 sensor is an indoor, wall-mounted
sensor without display. The CO2 sensor also includes a
System Pilot™ (33PILOT-01) — The System Pilot space temperature sensor with override button.
device is a communicating room sensor with override
button and set point adjustment that can be used in The 33ZCT56CO2 sensor is an indoor, wall-mounted
place of the T56 space temperature sensor. The System sensor without display. The CO2 sensor also includes a
Pilot communicating room sensor measures and main- space temperature sensor with override button and tem-
tains room temperature by communicating with the perature offset.
controller.

Dimensions

a33-
9142

Carrier Corporation • Syracuse, New York 13221 6-07


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 New Book 1 Pg 4 Catalog No. 04-52330009-01 Printed in U.S.A. Form 33CS-33PS