Professional Documents
Culture Documents
ArcFlash PDF
ArcFlash PDF
5
Arc Flash
Arc Flash Calculations in Electrical Networks
Published by
Siemens AG
Smart Infrastructure
Digital Grid
Freyeslebenstraße 1
91058 Erlangen, Germany
SIEMENS PSS SINCAL Arc Flash Manual
Preface
Preface
The PSS SINCAL System Manual contains a general description for using the application.
The technical manuals for electrical networks contain detailed descriptions of the various
calculation methods for electrical networks - such as load flow, or short circuit calculations - and
their input data.
The technical manuals for pipe networks contain detailed descriptions of the various calculation
methods for pipe networks - water, gas and heating/cooling - and their input data.
The database description contains a complete description of the data models for electrical and
pipe networks.
Copyright
This manual and all the information and illustrations contained in it are copyrighted.
SIEMENS retains all rights, in particular the right to publish, translate, reprint, photocopy, make
microcopies or electronically store in a database.
Previously expressed written permission from SIEMENS is required for any reproduction or use
beyond the limits specified by copyright law.
Warranty
Even though our manuals are thoroughly checked for errors, no liability can be taken for errors
found or any resulting problems or difficulties. Modifications are frequently made to the text and the
software as a part of our routine updates.
2.1 Terminology 8
2.2 Network Modeling for Arc Flash Calculations according to IEEE 10
2.2.1 Determining Nodes for Arc Flash 10
2.2.2 Determining Adjacent Protection Devices 10
2.2.3 Determining Arc Current 10
2.2.4 Determining Incident Energy for Protection Device 12
2.2.5 Determining Incident Energy at Fault Node 17
2.2.6 Current Limit for Protection Devices 19
2.2.7 Direct Determination of Incident Energy for Fuses 20
2.2.8 Direct Determination of Incident Energy for Low-Voltage Circuit Breaker 20
2.2.9 Determination of Arc Flash Boundary 21
2.2.10 Direct Determination of Arc Flash Boundary 23
2.2.11 National Fire Protection Association (NFPA) Regulations 23
2.2.12 Coefficients According to the IEEE 1584 2018 Procedure 23
3.1 Terminology 29
3.2 Network Modeling for Arc Flash Calculations according to BGI/GUV-I 5188 30
3.2.1 Determining Nodes for Arc Flash according to BGI/GUV-I 5188 30
3.2.2 Determining Adjacent Protection Devices 30
3.2.3 Determining Arc Short Circuit Current 30
3.2.4 Determining the Arcing Power 31
3.2.5 Determination of the Arcing Energy in the Event of a Fault 31
3.2.6 Determination of the Equivalent Arcing Energy 31
3.2.7 Determining the Arc Flash Protection Class 32
April 2019
PSS SINCAL Arc Flash Manual SIEMENS
Table of Contents
April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Introduction to Arc Flash
PSS SINCAL Arc Flash is an effective tool for calculating incident energy for arcs in low- and
medium-voltage networks. The calculations are based on 3-phase short circuit calculations
according to:
● VDE or IEC
● ANSI or IEEE
● VDE or IEC taking into account pre-fault system loading
● Engineering Recommendation G74
PSS SINCAL uses empirical IEEE formulas to calculate the arc current from the 3-phase fault
current and then uses this to examine protection-device pickup in order to calculate the tripping
time (arcing time). With the help of time, current and the system configuration, PSS SINCAL
calculates the incident energy.
The required Personal Protective Equipment (PPE) is also determined according to National Fire
Protection Association (NFPA) 70 E 2015.
Only 3-phase fault currents are used, since 1- or 2-phase faults with arcs according to IEEE 1584
always become 3-phase.
The arc protection class for personal protective equipment against the thermal effects of an arc
flash (PPEgS) is also determined. This is then used to examine protection-device pickup in order to
calculate the tripping time (arcing time). With the help of time, current and the system configuration,
PSS SINCAL calculates the incident energy.
To perform arc flash calculations or enter special data for arc flash calculations, you first need to
switch ON the calculation methods for Arc Flash and Protection Device Coordination.
For the Arc Flash calculations, the following steps are necessary:
April 2019 7
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
The purpose of Arc Flash calculations according to IEEE is to determine the incident energy, the
arc flash hazard distance and required personal protective equipment.
Arc Flash calculations are based on 3-phase short circuit current calculations and a subsequent
examination of protection-device pickup to determine the arcing time.
No
Prepare results
2.1 Terminology
This chapter explains the most important terms for the arc flash according to IEEE.
8 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
A dangerous condition associated with the release of energy caused by an electrical arc.
Fault current flowing through electrical arc plasma, also called arc fault current and arc current.
Short circuit between two conductors where the impedance or resistance is basically zero.
Electrical Hazard
A dangerous condition in which inadvertent or unintentional contact or equipment failure can result
in shock, arc flash burn, thermal burn or blast.
Electrical Shock
Body parts that are either not insulated, or exposed that could inadvertently touch or come too
close to something at less than a safe distance.
A minimum distance that must be maintained from systems under live voltage to prevent second
degree burns in case of an arc.
Incident Energy
The effect of energy at a certain distance on a surface generated during an electrical arc event.
Incident energy is measured in joules per centimeter squared (J/cm 2).
Shock Hazard
A dangerous condition associated with the possible release of energy caused by contact or
approach to body parts.
Working Distance
The distance between a possible arc point and the head of the worker performing a task in a live
system.
Correction Factor CF
April 2019 9
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
VCB
VCBB
HCB
VOA
HOA
PSS SINCAL determines Arc Flash for all nodes and busbars that have Arc Flash configuration
data assigned to them and are attached in all three phases.
PSS SINCAL calculates the adjacent protection devices when it investigates the network starting
from the nodes under observation. The direction of the protection devices is considered in this type
of network analysis.
According to IEEE 1584, Arc Flash calculations assume that the protection is set correctly and that
these adjacent protection devices trip the faults.
First PSS SINCAL calculates the total 3-phase bolted fault current at the node depending on what
short circuit procedure was set.
10 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
Then PSS SINCAL calculates the arc current from the bolted short circuit current for the 3-phase
busbar according to the voltage as follows.
Voltage < 1 kV
Voltage ≥ 1 kV
lg … log 10
lg Iarc … Normalized arc current
Iarc … Arc current
Ibf … Bolted 3-phase short circuit
kt … Factor according to system configuration (open: -0.153, and closed: -0.097)
Vn … Rated voltage (phase-phase)
Then PSS SINCAL reduces all currents in the network by the factor for arc current to total bolted
fault current. This applies the arc effect to the protection device currents with a linear factor.
Depending on the voltage, the average values Iarc_Voc for 600 V, 2700 V and 14300 V are
determined as follows from the bolted 3-phase busbar short circuit current and the k factors from
the table of the Coefficients for determining the arc fault current.
Ibf … Bolted fault current for three-phase faults (symmetrical rms value) (kA)
Iarc_Voc … Average rms arcing current (kA)
G … Gap distance between electrodes (mm)
k1 to k10 … Coefficients for determining the arc fault current
lg … log 10
The average values are then used as follows to determine the interpolation values I arc_1, Iarc_2 and
Iarc_3.
𝐼𝑎𝑟𝑐_2700 − 𝐼𝑎𝑟𝑐_600
𝐼𝑎𝑟𝑐_1 = (𝑉𝑜𝑐 − 2.7) + 𝐼𝑎𝑟𝑐_2700
2.1
April 2019 11
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
𝐼𝑎𝑟𝑐_14300 − 𝐼𝑎𝑟𝑐_2700
𝐼𝑎𝑟𝑐_2 = (𝑉𝑜𝑐 − 14.3) + 𝐼𝑎𝑟𝑐_14300
11.6
Iarc_1 … First Iarc interpolation term between 600 V and 2700 V (kA)
Iarc_2 … Second Iarc interpolation term used when Voc is greater than 2700 V (kA)
Iarc_3 … Third Iarc interpolation term used when Voc is less than 2700 V (kA)
Voc … Open-circuit voltage (system voltage) (kV)
The interpolation values Iarc_1, Iarc_2, Iarc_3 and the rated voltage Voc make it possible to calculate the
final value for the arc current Iarc. The following two different models are used here:
If the voltage is in the range 600 V < Voc ≤ 2700 V, the following is used
𝐼𝑎𝑟𝑐 = 𝐼𝑎𝑟𝑐_3
𝐼𝑎𝑟𝑐 = 𝐼𝑎𝑟𝑐_2
The arc current Iarc is determined with the following equation for the 208 V ≤ Voc ≤ 600 V:
1
𝐼𝑎𝑟𝑐 =
0.6 2 1 0.62 − 𝑉𝑜𝑐 2
√[ ] × [ − ( )]
𝑉𝑜𝑐 𝐼𝑎𝑟𝑐_600 2 0.62 × 𝐼𝑏𝑓 2
How incident energy is calculated depends on the system configuration. This means that the
voltage, the expected currents and the system dimensions specify the procedure used to calculate
incident energy.
The formulas used for calculating the arc flash apply to tripping times up to 2 seconds.
The tripping time of the protection devices is determined using the arcing current and the reduced
arcing current (85 percent). The protection devices must be able to trip both currents.
This therefore provides two currents and two tripping times for determining the incident energy. The
higher incident energy must be used to determine the arc flash hazard.
12 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
The empirical model is valid for voltages from 208 V to 15 kV, currents from 700 A to 106 kA, and a
distance between conductors from 13 mm to 152 mm.
PSS SINCAL calculates normalized incident energy for a time of 0.2 seconds at a distance of
610 mm from the arc as follows:
lg … log 10
W N … Normalized incident energy
kt1 … Factor according to system configuration (open: -0.792, and closed: -0.555)
Factor according to network configuration (ungrounded: 0.0, and grounded:
kt2 …
-0.113)
G … Distance between conductors
Then PSS SINCAL determines the actual incident energy from the normalized incident energy, the
protection device’s tripping time and the actual distance between conductors.
𝑡 610𝑥
𝑊 = 4.184 × 𝐶𝑓 × 𝑊𝑁 × × 𝑥
0.2 𝑑
W … Incident energy
Cf … Calculation factor (1.5 at V ≤ 1.0 kV, or 1.0 at V > 1 kV)
W N … Normalized incident energy
t … Smallest tripping time
d … Distance to arc
x … Factor x according to the following table
The following table shows the distance factors for determining the incident energy.
Typical gap
System voltage (kV) Equipment type Distance factor x
between conductors (mm)
Open air 10 – 40 2.000
Switchgear 32 1.473
0.208 – 1
MCC and panels 25 1.641
Cable 13 2.000
Open air 102 2.000
>1–5 Switchgear 13 – 102 0.973
Cable 13 2.000
Open air 13 – 153 2.000
> 5 – 15 Switchgear 153 0.973
Cable 13 2.000
April 2019 13
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
If these requirements are not fulfilled, the incident energy must be calculated according to the Lee
method.
The equivalent width B1 and the equivalent height H1 are determined with the following equations:
𝑉𝑜𝑐 + 𝐴
𝐵1 = (660.4 + (𝐵 − 660.4) × ( )) × 25.4−1
𝐵
𝑉𝑜𝑐 + 𝐴
𝐻1 = (660.4 + (𝐻 − 660.4) × ( )) × 25.4−1
𝐵
The equivalent sizes B1 and H1 are used to determine the equivalent EES system size:
𝐻1 + 𝑊1
𝐸𝐸𝑆 =
2
14 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
● Typical system
● Shallow system
The system type is determined internally. The system is considered "shallow" if the following
conditions are fulfilled.
The correction factor CF is required for determining the incident energy W. The calculation
depends on the system type.
𝐶𝐹 = 𝑏1 × 𝐸𝐸𝑆 2 + 𝑏2 × 𝐸𝐸𝑆 + 𝑏3
1
𝐶𝐹 =
𝑏1 × 𝐸𝐸𝑆 2 + 𝑏2 × 𝐸𝐸𝑆 + 𝑏3
There is no correction for the arrangement of the conductors VOA and HOA. The following
therefore applies:
𝐶𝐹 = 1.0
The average values EVoc for 600 V, 2700 V and 14300 V are determined with the following
equations:
12.552
𝐸𝑉𝑜𝑐 = 𝑇 × 10𝑓𝐸𝑥𝑝
50
𝑘3𝐼𝑎𝑟𝑐_𝑉𝑜𝑐
𝑓𝐸𝑥𝑝 = 𝑘1 + 𝑘2𝑙𝑔𝐺 + 7 6 5 4 3 2
+ 𝑘11𝑙𝑔𝐼𝑏𝑓
𝑘4𝐼𝑏𝑓+ 𝑘5𝐼𝑏𝑓+ 𝑘6𝐼𝑏𝑓 + 𝑘7𝐼𝑏𝑓 + 𝑘8𝐼𝑏𝑓 + 𝑘9𝐼𝑏𝑓 + 𝑘10𝐼𝑏𝑓
1
+ 𝑘12𝑙𝑔𝐷 + 𝑘13𝑙𝑔𝐼𝑎𝑟𝑐_𝑥 + 𝑙𝑔
𝐶𝐹
April 2019 15
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
For ≤ 600 V:
𝐼𝑎𝑟𝑐_𝑥 = 𝐼𝑎𝑟𝑐_𝑚𝑖𝑛
𝐼𝑎𝑟𝑐_𝑥 = 𝐼𝑎𝑟𝑐_𝑉𝑜𝑐
The actual or final incident energy is calculated using the interpolation values E1, E2 and E3. The
interpolation values are calculated as follows:
𝐸2700 − 𝐸600
𝐸1 = (𝑉𝑜𝑐 − 2.7) + 𝐸2700
2.1
𝐸14300 − 𝐸2700
𝐸2 = (𝑉𝑜𝑐 − 14.3) + 𝐸14300
11.6
If the voltage is in the range 600 V < Voc ≤ 2700 V, the following is used:
𝐸 = 𝐸3
𝐸 = 𝐸2
𝐸 = 𝐸 ≤ 600
16 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
Lee Method
If the prerequisites for the empirical model are unattainable, PSS SINCAL calculates incident
energy with the Lee method.
𝑡
𝑊 = 2.142 × 106 × 𝑉𝑛 × 𝐼𝑏𝑓 ×
𝑑2
W … Incident energy
Un … Rated voltage
Ibf … Bolted 3-phase short circuit current
t … Smallest tripping time
d … Distance to arc
Unique Features
As the arc current cannot be defined exactly and these fluctuations have an effect on the tripping
time of the protection devices, the tripping times and incident energy are determined twice.
The arc currents are reduced to 85 % for the IEEE 1584 2002 procedure. For the IEEE 1584 2018
procedure they are defined as follows.
If there is more than one protection device at the same terminal, PSS SINCAL only includes the
one with the smallest tripping time in the calculations.
IEEE 1584 specifies that the incident energy must be defined from the total fault current and the
tripping characteristic curve of the protection device. For this incident energy needs to be
calculated twice. Once you use the total arc current and then you use the arc current reduced to
85 %. You do this because, under certain conditions, protection devices do not trip and longer fault
duration can result in greater incident energy. As the results, PSS SINCAL identifies the higher
incident energy.
If the fault is limited by more than one protection device, there is no clear directive for determining
the incident energy.
April 2019 17
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
The incident energy can be determined according to the settings of Protection Coordination –
Calculation Settings.
Fraction
The incident energy calculated at the node is the sum of the proportional incident energy. The
proportional incident energy is calculated here from the proportional arc current and the associated
tripping time.
This way of determining the total incident energy allows a simple way of integrating the current
limitation of protection devices. The proportional current is limited and the energy is determined
with the limited current.
Worst Case
With this examination, the arc current at the node is determined from the total bolted fault current at
the node. The tripping times of the protection devices are then calculated from the proportional arc
currents. The highest tripping time is used to calculate the incident energy.
The current limitation of protection devices has an effect on the proportional fault current. The total
fault current is therefore reduced by the current reduction provided by the limitation.
Best Case
With this examination, the arc current at the node is determined from the total bolted fault current at
the node. The tripping times of the protection devices are then calculated from the proportional arc
currents. The smallest tripping time is used to calculate the incident energy.
The current limitation of protection devices has an effect on the proportional fault current. The total
fault current is therefore reduced by the current reduction provided by the limitation.
18 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
Time Steps
With this approach, the arc current at the node is determined from the total bolted fault current at
the node. The tripping times of the protection devices are then calculated from the proportional arc
currents. The smallest tripping time is used to calculate the incident energy of the first time step. A
temporary switch is then opened at the tripping protection device in the network, and the total
bolted fault current at the node and the tripping time of the protection devices are then determined
again. The difference in time from the previous examination is used to determine the incident
energy of the current time step.
The current limitation of protection devices has an effect on the proportional fault current. The total
fault current is therefore reduced by the current reduction provided by the limitation.
Fuses interrupt high fault currents during the first half cycle and limit the fault current. Taking into
account the current limiting effect, the resulting short-circuit current is lower than the initial short-
circuit current derived by a standard short-circuit current calculation neglecting this effect.
Consequently, a reduced fault current can be considered of for the incident energy calculations.
The current limiting behavior can be defined for each OC protection device in the Additional Data
tab.
ic [kA peak]
10.0
icmax
1.0
icstart
ipstart ipmax
0.1
0.1 1.0 10.0 ip [kA eff]
April 2019 19
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
Currents less that ipstart do not limit the short circuit current.
Depending on the short circuit procedure, either the surge current ipeak (VDE or IEC) or imom peak
(ANSI or IEEE) is used to calculate the current limit.
𝑖𝑝𝑒𝑎𝑘
𝑖𝑝 =
√2
𝑖𝑚𝑜𝑚 𝑝𝑒𝑎𝑘
𝑖𝑝 =
√2
The characteristic curve can be interpolated to determine the amplitude of the limited current.
Then, of course, the effective value is also used to calculate incident energy. The tripping time is
determined for the current limit as follows:
1
𝑡=
2×𝑓
t … Tripping time
f … Frequency
For predefined classes of fuses, you can use empirical IEEE 1584 formulas to determine incident
energy directly.
PSS SINCAL contains fuse classes according to IEEE 1584 Section 5.6. These empirical formulas
are, however, only valid for a voltage of 600 V at a working distance of 455 mm.
For deviating configurations, fuse classes or rated current intensity, PSS SINCAL cannot determine
the incident energy directly.
For predefined types of switchgear, you can use empirical IEEE 1584 formulas to determine
incident energy directly.
PSS SINCAL contains the breaker types as per the following table in accordance with the IEEE
1584 2002 procedure.
20 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
These empirical formulas are, however, only valid for predefined voltage ranges, rated currents, or
a working distance of 460 mm and for currents from 700 A to 106 kA.
For deviating configurations, types of switchgear or rated currents, etc., PSS SINCAL cannot
determine the incident energy directly.
PSS SINCAL calculates the danger limit for an incident energy of W = 5.0 J/cm 2. The danger limit
is calculated in the same way as the incident energy.
The average values for 600 V, 2700 V and 14300 V are determined with the following equation.
𝐴𝐹𝐵𝑉𝑜𝑐 = 10𝑓𝐸𝑥𝑝
1 20
𝑘1 + 𝑘2𝑙𝑔𝐺 + 𝑘𝑝𝑎𝑟𝑡_𝑉𝑜𝑐 + 𝑘11𝑙𝑔𝐼𝑏𝑓 + 𝑘13𝑙𝑔𝐼𝑎𝑟𝑐_𝑉𝑜𝑐 + 𝑙𝑔 ( ) − 𝑙𝑔 ( )
𝑓𝐸𝑥𝑝 = 𝐶𝐹 𝑇
−𝑘12
𝑘3𝐼𝑎𝑟𝑐_𝑉𝑜𝑐
𝑘𝑝𝑎𝑟𝑡_𝑉𝑜𝑐 = 7 6 5 4 3 2
𝑘4𝐼𝑏𝑓 + 𝑘5𝐼𝑏𝑓 + 𝑘6𝐼𝑏𝑓 + 𝑘7𝐼𝑏𝑓 + 𝑘8𝐼𝑏𝑓 + 𝑘9𝐼𝑏𝑓 + 𝑘10𝐼𝑏𝑓
April 2019 21
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
The danger limit at a rated voltage ≤ 600 V is determined with the coefficients for 600 V and the arc
current Iarc ≤ 600 V, which is determined with the equation for specifying the arc current Iarc for
voltages in the range 208 V ≤ Voc ≤ 600 V.
1
𝐼𝑎𝑟𝑐 =
0.6 2 1 0.62 − 𝑉𝑜𝑐 2
√[ ] × [ 2 −( 2 )]
𝑉𝑜𝑐 𝐼𝑎𝑟𝑐_600 0.6 × 𝐼𝑏𝑓 2
Average values AFB600, AFB2700, AFB14300 enable the interpolation values AFB1, AFB2 and AFB3 to
be determined.
𝐴𝐹𝐵2700 − 𝐴𝐹𝐵600
𝐴𝐹𝐵1 = (𝑉𝑜𝑐 − 2.7) + 𝐴𝐹𝐵2700
2.1
𝐴𝐹𝐵14300 − 𝐴𝐹𝐵2700
𝐴𝐹𝐵2 = (𝑉𝑜𝑐 − 14.3) + 𝐴𝐹𝐵14300
11.6
AFB1 … First AFB interpolation term between 600 V and 2700 V (mm)
AFB2 … Second AFB interpolation term used when Voc is greater than 2700 V (mm)
AFB3 … Third AFB interpolation term used when Voc is less than 2700 V (mm)
If the open-circuit voltage Voc is within the range 600 V < Voc <= 2700 V:
𝐴𝐹𝐵 = 𝐴𝐹𝐵3
𝐴𝐹𝐵 = 𝐴𝐹𝐵2
If the open-circuit voltages Voc <= 600 V, it is not interpolated, so the final value is already the
average value.
Lee Model
𝑡
𝑑𝑏 = √2.142 × 106 × 𝑉𝑛 × 𝐼𝑏𝑓 × ( )
𝑊
22 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
For predefined types of switchgear, you can use empirical IEEE 1584 formulas to determine the
danger limit directly.
PSS SINCAL contains the breaker types as per the following table in accordance with the IEEE
1584 2002 procedure.
These empirical formulas are, however, only valid for predefined voltage ranges, rated currents, or
a working distance of 460 mm and for currents from 700 A to 106 kA.
For deviating configurations, types of switchgear or rated currents, etc., PSS SINCAL cannot
determine the danger limit directly.
The NFPA 70E 2015 defines approach boundaries and the protective clothing (Personal Protective
Equipment) necessary based on incident energy.
For incident energy greater than 40.0 cal/cm 2, there is no protective clothing. Working under
voltage is forbidden for these systems.
The coefficients according to the IEEE 1584 2018 procedure depend on the configuration (test
arrangement) of the electrodes or the dimensions of the limitation.
The following tables use the original terms from IEEE 1584 2018 for the configuration (test
arrangement) of the electrodes:
● VCB:
Vertical conductors/electrodes inside a metal box/enclosure.
● VCBB:
Vertical conductors/electrodes terminated in an insulating barrier inside a metal box/enclosure.
● HCB:
Horizontal conductors/electrodes inside a metal box/enclosure.
● VOA:
Vertical conductors/electrodes in open air.
● HOA:
Horizontal conductors/electrodes in open air.
April 2019 23
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
This section lists the coefficients for determining the arc current according to the arrangement of
the conductors.
24 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
HOA
k1 0.111147 0.000435 0.000904
k2 1.008 1.006 0.999
k3 -0.24 -0.038 -0.02
k4 0 0 0
k5 0 0 0
k6 -3.90E-09 7.86E-10 7.86E-10
k7 1.64E-06 -1.91E-07 -1.91E-07
k8 -0.000197 -9.13E-06 -9.13E-06
k9 0.002615 -0.0007 -0.0007
k10 1.1 0.9981 0.9981
This section lists the coefficients for determining the reduced current according to the arrangement
of the conductors.
This section lists the coefficients for determining the incident energy according to the arrangement
of the conductors.
April 2019 25
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to IEEE
26 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to IEEE
k11 0 0 -0.05
k12 -1.99 -1.639 -1.633
k13 1.04 1.078 1.151
This section lists the coefficients for determining the correction factor according to the arrangement
of the conductors.
There are no coefficients for the VOA and HOA configuration (test arrangement).
April 2019 27
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to BGI/GUV-I 5188
The aim of the arc flash calculation is to determine the arc flash energy, the equivalent arc flash
energy, and from this the necessary personal protective equipment expressed as the arc flash
protection class.
The arc flash calculation is based on two 3-phase short circuit current calculations.
● The prospective 3-phase short circuit current is used to determine the arcing power.
● The minimum 3-phase short circuit current is used to determine the tripping current with a
subsequent examination of the pickup of protection devices in order to determine the arcing
time.
28 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to BGI/GUV-I 5188
No
Prepare results
3.1 Terminology
This chapter explains the important terms for the arc flash according to BGI/GUV-I 5188.
Personal Protective Equipment against the Thermal Effects of an Arc Flash (PPEgS)
April 2019 29
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to BGI/GUV-I 5188
The maximum anticipated current that flows when the impedance at the fault location is negligible.
Transmission Factor
Factor that describes the spatial propagation of the thermal impact of the arc flash in the work
environment. It is determined by the geometric relationships of the equipment at the workplace.
Protection level of the PPEgS resulting from test level of the PPE at the specific working distance
and transmission factor.
Ratio between the actual arc flash short circuit current and the prospective short circuit current.
Ratio of the arcing power to the short circuit power of the electrical network at the fault location.
PSS SINCAL determines Arc Flash for all nodes and busbars that have Arc Flash configuration
data assigned to them and are attached in all three phases.
PSS SINCAL calculates the adjacent protection devices when it investigates the network starting
from the nodes under observation. The direction of the protection devices is considered in this type
of network analysis.
According to BGI/GUV-I 5188, Arc Flash calculations assume that the protection is set correctly
and that these adjacent protection devices trip the faults.
First PSS SINCAL calculates the total 3-phase bolted fault current at the node depending on what
short circuit procedure was set.
30 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Arc Flash Calculation Method according to BGI/GUV-I 5188
Then PSS SINCAL calculates the arc current from the bolted short circuit current for the 3-phase
busbar according to the voltage using the current limiting factor as follows.
𝐼𝑘𝑎𝑟𝑐 = 𝑘𝑏 × 𝐼𝑘"𝑚𝑖𝑛
For voltages > 1 kV the limiting property of the arc flash can be disregarded (k b = 1.0).
Then PSS SINCAL reduces all currents in the network by the current limiting factor. This applies
the arc effect to the protection device currents with a linear factor.
The arcing power Parc is determined from the reference arcing power k Parc and the maximum short
circuit power Sk"max.
For worst case examinations and plant configurations not in compliance with BGI/GUV-I the
following applies:
0.29
𝑘𝑃𝑎𝑟𝑐 =
𝑅 0.17
𝑋
The arcing energy in the event of a fault is determined from the arcing power PLB and the clearing
time t.
𝑊𝑎𝑟𝑐 = 𝑃𝑎𝑟𝑐 × 𝑡
The equivalent arcing energy is determined with the energies of the relevant test class
April 2019 31
PSS SINCAL Arc Flash Manual SIEMENS
Arc Flash Calculation Method according to BGI/GUV-I 5188
1 2
𝑊𝑎𝑟𝑐𝐸1 = 𝑊𝑎𝑟𝑐𝑃1 × ( ) × 𝑘𝑡
300.0
1 2
𝑊𝑎𝑟𝑐𝐸2 = 𝑊𝑎𝑟𝑐𝑃2 × ( ) × 𝑘𝑡
300.0
The arc flash protection class is determined by comparing the arcing energy in the event of a fault
with the equivalent arcing energies of the relevant test class.
32 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Example for Arc Flash
Below is a simple example of how Arc Flash works. The following descriptions show:
Basic Data
When you install PSS SINCAL, the program automatically provides a network ("Example OC"),
which can be used to check the simulation procedure.
To calculate Arc Flash, Arc Flash in the Calculate – Methods menu has to be activated (see
Presetting Calculation Methods in the chapter on User Interface in the User Manual).
The short circuit procedure calculates bolted short circuit currents. Preset the short circuit method
in the Short Circuit – Calculation Settings.
April 2019 33
PSS SINCAL Arc Flash Manual SIEMENS
Example for Arc Flash
Select Data – Protection Device Coordination – Arc Flash Configuration in the menu to open
the dialog box for creating and editing Arc Flash configurations.
This dialog box lists all Arc Flash configurations in the network. You can insert new Arc Flash
configurations as well as edit or delete existing ones. You can assign globally predefined Arc Flash
configurations to the nodes and busbars.
The Enclosure Height and Enclosure Width are required to determine the equivalent EES.
The Enclosure Depth is required to determine the type of system (typical or shallow).
The arc flash configuration is used to carry out calculations both in accordance with IEEE 1584 and
also DGUV.
The IEEE tab enables the system data to be defined according to IEEE 1584.
34 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Example for Arc Flash
The activation of the IEEE Configuration option causes the results for the arc flash calculation to
be provided according to IEEE.
The Type field determines the structure of the equipment according to IEEE 1584. PSS SINCAL
recognizes the following types of systems:
● Switchgear
● Cable
● Open air
● MCC and panels
The Arrangement of Conductors is used to define the alignment and arrangement of the
conductors.
● VCB:
Vertical conductors/electrodes inside a metal box/enclosure.
● VCBB:
Vertical conductors/electrodes terminated in an insulating barrier inside a metal box/enclosure.
● HCB:
Horizontal conductors/electrodes inside a metal box/enclosure.
● VOA:
Vertical conductors/electrodes in open air.
● HOA:
Horizontal conductors/electrodes in open air.
The Maximum Clearing Time makes it possible to calculate the arc flash results without protection
data. Without setting a clearing time, it is determined via the tripping of the protection devices in the
network.
The DGUV tab is used to define the system data according to DGUV.
The DGUV Configuration option is used to input the appropriate plant data. The activation of this
configuration causes the results for the arc flash calculation to be provided according to DGUV.
April 2019 35
PSS SINCAL Arc Flash Manual SIEMENS
Example for Arc Flash
The Type of Plant field is used to select the plant configuration. The following are available:
The Frequency Current field is used to define the frequency of the arc voltage in order to
determine the current limiting factor.
The Frequency Power field is used to define the frequency of the arc voltage in order to determine
the arcing power.
The Transmission Factor takes the geometry of the plant and the propagation of the arcing
energy into account.
Without a direct setting of the Maximum Clearing Time protection also has to be correct, since
PSS SINCAL can only calculate fault currents that actually exist.
For a detailed description on creating protection devices, see the section on Creating of Protection
Devices in the chapter on Protection Coordination, in the Input Data manual.
You can enter enhanced control settings for Arc Flash calculations at OC protection devices.
Basically, these define the Current Limit for the Protection Devices.
36 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Example for Arc Flash
For a precise description of input data for OC protection devices for the Arc Flash configuration,
see the section on Additional Data – Overcurrent Protection Settings in the chapter on Protection
Coordination in the Input Data manual.
You can assign an existing configuration in the Arc Flash Configuration list. If you select (none),
you can click the edit button to create and assign a new Arc Flash configuration.
April 2019 37
PSS SINCAL Arc Flash Manual SIEMENS
Example for Arc Flash
IEEE 1584 specifies that the incident energy must be defined from the total fault current and the
tripping characteristic curve of the protection device. If the fault is limited by more than one
protection device, there is no clear directive for determining the incident energy. The following
methods can be selected in the Determine Energy selection field.
● Fraction
● Worst Case
● Best Case
● Time Steps
The Energy Calculation IEEE and Energy Calculation DGUV selection fields enable the required
calculation procedure to be selected.
PSS SINCAL provides the results of the Arc Flash calculations at the nodes and busbars in the
network diagram. The most important parameters according to IEEE 1584 are available.
The pop-up menus for nodes and busbars open the data-output form. Depending on the input data
activated in the arc flash configuration, the results are provided according to IEEE and DGUV.
38 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Example for Arc Flash
Results IEEE
The IEEE Configuration field shows which calculation procedure (IEEE 1584 2002 or IEEE 1584
2018) was used. The appropriate fields are displayed according to the selected procedure.
The Type field specifies the structure of the plant according to IEEE 1584.
Risk due to NFPA 70E identifies the danger potential in two basic classes (warning or hazard).
PPE due to NFPA 70E contains the category of personal protection (PPE = Personal Protective
Equipment) you want to select.
● Incident Energy,
● Arc Flash Boundary,
● Working Distance,
● Limited Approach,
● Restricted Approach and
● Prohibited Approach
Bolted Fault Current identifies the current at the node used as a basis for determining the arc
current.
Total Arcing Current contains the arc current that calculates the incident energy.
The Maximum Clearing Time is the time in which the arc flash current is flowing.
April 2019 39
PSS SINCAL Arc Flash Manual SIEMENS
Example for Arc Flash
Calculation Method identifies which procedure determined the Arc Flash energy.
Reduced Arcing Current Used identifies whether the incident energy was for arc current that is
reduced to 85 %.
Results DGUV
The Protection Class specifies the personal protective equipment against the thermal effects of
the arc flash.
The Arcing Energy is the electrical energy fed to the arc flash.
The Arcing Power is the short circuit power based on the prospective short circuit current.
The Arcing Current is the r.m.s. value of the current flowing for the duration of the arc flash.
The Min. Fault Current is the minimum anticipated fault current. This current is the relevant
current for the tripping time of fuses.
The Ratio R/X is the ratio of the resistance to the inductive reactance based on the prospective
short circuit current of the plant.
The Short Circuit Power is the anticipated AC power at the moment the short circuit occurs.
The Clearing Time is the time in which the arc flash current is flowing.
40 April 2019
SIEMENS PSS SINCAL Arc Flash Manual
Example for Arc Flash
The Transmission Factor takes the geometry of the plant and the propagation of the arcing
energy into account.
The Factor Current Limiting is the ratio between the actual arc flash current and the prospective
short circuit current.
The Ref. Arcing Power is the ratio between the arcing power and the short circuit power of the
plant.
The Equivalent Arcing Energy of Class 1 and Class 2 is the energy based on the test level of the
respective class.
Arc Voltage Frequency for Determining specifies the frequencies used in the calculation for
determining the Arcing Current and Arcing Power.
In addition to conventional PSS SINCAL reports, there is a special report for creating labels for Arc
Flash danger in systems. Click View – Report View in the menu to open the report window. For a
detailed description of the report window, see the chapter on Reports in the System Manual.
Add the report for Arc Flash Labels to the active compilation. Then you can open the report in the
report window.
April 2019 41