20 – 60 kW
ABB MicroGrid Inverter is an all-in-one solution that ABB MicroGrid Inverter incorporates safety features
maximizes use of solar PV power, in combination with for users and maintenance staff by mounting all the
energy storage, to supply reliable power for village electrical components behind enclosures inside one
electrification and small commercial/ industrial sites. cabinet.
The compact, factory tested, single cabinet design
minimizes installation and commissioning times. ABB Operating Modes
MicroGrid Inverter is a modular and scalable solution ABB MicroGrid Inverter ensures no load disruption by
capable of supporting increasing future load seamlessly transitioning between on-grid and off-grid
requirements. operation. Solar PV power is prioritized to supply the
load with a high efficiency. The connected batteries
Robust Converter Design are charged with the excess solar power, and from
ABB MicroGrid Inverter draws upon ABB’s extensive the grid when needed, to guarantee the continuous
UPS and solar inverter expertise. Particular attention supply of power after dusk. Any excess PV power can
has been paid to the physical robustness. ABB be returned to the grid to generate additional revenue
MicroGrid Inverter’s IP31-rated protection copes with when the batteries are fully charged.
dust, water condensation, excessive humidity (up to
95 percent), corrosive air contamination and rough Remote Monitoring
manhandling. To ensure reliable operation in harsh It is essential that operational staff can remotely
environments, Product-Name is designed to operate monitor the system performance and quickly react to
over a wide ambient temperature range from −5 to any status changes of the ABB MicroGrid Inverter. An
+50°C. Simple and fast serviceability is provided by Ethernet interface is provided as standard to enable
the swappable, modular converter architecture to customers to connect remotely. A local operator’s
ensure minimal downtime. touch panel is available optionally.
Technical specification
Type Code 20 kW 40 kW 60 kW
General Data
Nominal load power 20 kW 40 kW 60 kW
Max. PV input power 24 kW 32 kW 52.8 kW
Max. battery charging power 12 kW 24 kW 48 kW
PV Input
MPPT Operating range 440 – 800 V 500 – 800 V 480 – 800 V
Max. PV input DC Voltage 1000 V
No. of independent MPPT 2 2 1
No. of DC Input pairs/MPPT 1 1 2 / 12 (Optional)
AC Input
Nominal Input Voltage 3 × 380/220 V + N, 3 × 400/230 V + N, 3 × 415/240 V + N
Voltage tolerance –15 % / +15 %
Input Frequency 50 / 60 Hz (selectable)
Frequency Range (Normal Operation) -30% /+40 %
Frequency tolerance (Grid Export) 47...53 Hz / 57…63 Hz
Maximum Input current 36 A 71 A 108 A
Output
Nominal output voltage 3 × 380/220 V, 3 × 400/230 V, 3 × 415/240 V
Output rated current 29 A 58 A 87 A
Output Frequency 50 / 60 Hz
Battery
Nominal battery voltage 480 to 600 V
Battery type VRLA, (future Li-ion support)
Maximum charging current 24 A 48 A 96 A
Efficiency
Max. PV to load TBD TBD TBD
Max. AC to load TBD TBD TBD
Max. battery to load TBD TBD TBD
www.abb.com