You are on page 1of 21

9/27/2010

Abstract

• In Ontario, Canada, there have been ongoing restrictions in ability to transfer 
power from the Niagara Falls stations to load centers 100 km away. 
Case Study: 230‐kV Transmission  • Capacity of a five‐circuit 230‐kV transmission interface falls when wind speed 
across the conductors drops below 2 m/s. 
Corridor Rating using Mechanical  • Plans to supplement existing lines with two new circuits have been delayed. 
• In the meantime, Hydro One initiated advanced studies of overhead line 
g
Measurements to establish Long‐Axis  clearance using:
– Helicopters to perform laser surveys of the conductor position
Helicopters to perform laser surveys of the conductor position
Hot‐Wire Anemometer Wind Speed – Sonar to measure the conductor heights continuously
– New algorithms to invert a traditional overhead line rating calculation. 
• The process establishes spatially averaged wind speed along entire line sections, 
rather than relying on spot readings with differing exposures, measured at 
remote sites. 
William A. Chisholm • This presentation will describe the work with a focus on an intercomparison of 
methods to measure low wind speeds for line thermal rating.
W.A.Chisholm@ieee.org TERM OF ASSIGNMENT OF COPYRIGHT: The author assigns his copyright on the text "Case Study: 230‐kV 
Transmission Corridor Rating using Mechanical Measurements to establish Long‐Axis Hot‐Wire Anemometer Wind 
Speed ", for publication in the proceedings of the 1st National Seminar on Wind Engineering (SENEV 2010) .

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

CIGRE and IEEE References for
Organization of Seminar (1)
Thermal Rating of Lines

• CIGRE Committee B2 Tutorial, January 2009 • Heat Balance of Overhead Conductors
• CIGRE Technical Brochure 207 (Thermal behaviour  • Change of Tension, Sag and Clearance with 
of overhead conductors)  Conductor Temperature 
– In single span
• CIGRE Technical Brochure 299 (Guid for selection 
CIGRE Technical Brochure 299 (Guid for selection
– In multiple spans with freely swinging insulators
of weather parameters for bare overhead 
• Field Results
conductor ratings)
– Predictors of Clearance
• IEEE Standard 738 (Standard for calculating the  – Observations of Wind Speed, Direction and their 
current temperature of bare overhead  Standard Deviations
conductors)
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Organization of Seminar (2) Heat Balance for Outdoor Conductor

• Ampacity Inversion  • Heat Inputs
– Long‐Axis Hot‐Wire Method – PJ , Joule Heating, I2R where R is the ac resistance at 
– Inputs: Clearance, Line Current, Ambient Temperature,  the temperature of operation
Solar Radiation – PM 
M ,, Magnetic Heating from currents induced in the 
g g
– Outputs: Spatially Averaged Conductor Temperature  steel core from unbalanced stranding
and Wind Speed – PS , Solar Heating, up to 1000 W/m2 and affected by 
• Implementation by Utility and Results conductor absorptivity
– Pi , Corona Heating, usually can be ignored
• Conclusions and Discussion

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

1
9/27/2010

Heat Balance for Outdoor Conductor Heat Balance Model: Solar, Radiation

• Heat Outputs
– Pc , Convective cooling
• Wind speed v > 0.4 m/s, conductor diameter D =20 mm
Pr: Radiation Heat Loss
• Reynolds number Re =vD/ (f
f )about 1000 • Varies as (T
Varies as (Tc‐TTA ) 4 
A ) 
• Nusselt number Nu is a function of Re and wind angle PS: Solar Input  • Conductor Emissivity 

– Pr , Radiative cooling, varies as fourth power of  • Intensity 
• Azimuth
temperature rise above ambient • Elevation
– Pw, Evaporative cooling if the conductor is wet or  • Conductor 
Absorptivity
sublimation cooling if it is loaded with ice

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Heat Balance Model: Joule, Convection Overall Heat Balance

Radiation Heat Loss
(TC‐TA ) 4

PC : Convection Heat Loss Convection Heat Loss
(TC‐TTA  (Effective Wind Speed) 0.5
A ))∙ (Effective Wind Speed)  (TC‐TTA )x (Wind Speed) 0.5
A )x (Wind Speed) 
Line Current
Solar Input 
varies as I2R
• PJ
• PM varies nonlinearly
Line Current

Wind speed, angle to conductor Wind speed, angle to conductor
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Heat Balance for Outdoor Conductor Transient Thermal Response (IEEE 738‐2006)

• Steady State
PJ  PM  PS  Pi  Pc  Pr  Pw Step Change in Current

• Unsteady State
dT
mc av  Pj  PM  PS  Pc  Pr
dt Rise in Conductor Temperature
– m is mass per unit length of conductor to New Steady State
– c is the overall heat capacity of the steel/aluminum

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

2
9/27/2010

Effect of Wind Speed on 
Transient Thermal Response (IEEE 738‐2006)
Conductor Temperature (CIGRE B2 Tutorial)

Final Temperature

63.2% of Temperature Rise
In 20 minutes (time constant)

Initial Temperature
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Effect of Wind Speed on  Effect of Wind Angle on 
Conductor Temperature (CIGRE B2 Tutorial) Nusselt Number governing Heat Transfer

• CIGRE TB 207 Model for Wind at angle 

 0    24 : Nu90 0.42  0.68  sin( 1.08
Nu   


24    90 : Nu90 0.42  0.58  sin( 
 0.90

• Stranding, Catenary give minimum value of 0.42 
l f
Nu90 for axial flow along line (=0°).
• Older Model mixes forced, natural convection 
based on V.T. Morgan concept.
Critical Wind Speed Range:  0‐2 m/s (0‐7.2 km/h)
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Effect of Wind Angle on  Standard Deviation of Wind Direction 
Nusselt Number governing Heat Transfer also affects Nusselt Number


Nueff
Nu90

1
2  e
 2 2 2
0.05  0.95 sin  
2 0.25
d


W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

3
9/27/2010

Standard Deviation of Wind Direction  Standard Deviation of Wind Direction 
also affects Nusselt Number also affects Nusselt Number

Wind angle  Wind angle 
standard deviation standard deviation
 tends to   tends to 
increase as wind  increase as wind 
speed drops.
dd speed drops.
dd

At low wind speed, 
CIGRE TB207 
suggests yaw angle 
of 45°.

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Organization of Seminar (1) Changes in Sag of Single Span

• Heat Balance of Overhead Conductors
• Change of Tension, Sag and Clearance with 
Conductor Temperature 
– In single span
In single span
– In multiple spans with freely swinging insulators
• Calculation of distributed wind speed from 
measured clearance, ambient temperature and 
conductor current

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Conductor Elongation Factors Conductor Elongation Factors

Length As Manufactured Length As Manufactured

Increase in Length from Creep after 1 hour

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

4
9/27/2010

Changes in Sag of Single Span Conductor Elongation Factors

Length As Manufactured

Increase in Length from Creep after 1 hour
Increase in Length from Creep after
Increase in Length from Creep after ………  20 years
20 years

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Changes in Sag of Single Span Conductor Elongation Factors

Length As Manufactured

Increase in Length from Creep after 1 hour
Increase in Length from Creep after
Increase in Length from Creep after ………  20 years
20 years

Reversible Elastic Strain from change in Wind/Ice Loads

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Reversible Change: Elastic Strain Conductor Elongation Factors

Length As Manufactured

Increase in Length from Creep after 1 hour
Increase in Length from Creep after
Increase in Length from Creep after ………  20 years
20 years

Reversible Elastic Strain from change in Wind/Ice Loads

Reversible Thermal Strain from change in Temperature

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

5
9/27/2010

Reversible Change: Thermal Strain Effects of Heat

• Extreme electrical power system load now peaks 
in summer, thanks to air conditioning
• Temperature rise above ambient powered by 
square of current (I2R)
square of current (I
• Aluminum and steel expand when they get hot, 
reducing clearances.
• Excessive temperature rise anneals aluminum, 
damages splices

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Why the Hyperbolic Cosine Shape?
Organization of Seminar (1)

• Heat Balance of Overhead Conductors x

• Change of Tension, Sag and Clearance with 
Conductor Temperature 
– In single span
In single span z
dz
d
T
– In multiple spans with freely swinging insulators ds
dx d dx
• Calculation of distributed wind speed from  T
dx T  (T )s
ds ds ds
measured clearance, ambient temperature and  ds
conductor current mgs dz d dz
T  (T )s
ds ds ds
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Why the Hyperbolic Cosine Shape?
Multiple Spans – “Ruling Span” Theory

End
• Calculate behavior 
of “Ruling Span”
 (span) 3

RS  Start
End

 (span)
Start

• Transform result to  2
s  1 m other spans  SpanN 
Sag SpanN    Sag RS
 RS 

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

6
9/27/2010

Multiple Spans with Real Insulators Multiple Spans – Sag/Temperature Slope

• Winkleman AIEE 1959 / Chisholm and Barrett PWRD April 1989
• Perfect tension equalization (infinitely long 
insulator strings) is basis of ruling span theory.
• Horizontal component of tension up the 
p p
insulator string is small
but important: tensions
in adjacent spans are not
quite equal.

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Multiple Spans – Sag/Temperature Slope Multiple Spans – Sag/Temperature Slope

More Sag Change with Temperature  Less Sag Change with Temperature 
for Short Spans:  for Long Spans: 
15 mm/C° versus 11 mm/C° 42 mm/C° versus 47 mm/C°

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Multiple Spans – Sag/Temperature Slope Organization of Seminar (1)

Different Sag Changes with  • Heat Balance of Overhead Conductors
Temperature for Spans of 
• Change of Tension, Sag and Clearance with 
Same Length in Different Positions
Conductor Temperature 
– In single span
– In multiple spans with freely swinging insulators
• Field Results
– Predictors of Clearance
– Observations of Wind Speed, Direction and their 
Standard Deviations

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

7
9/27/2010

Typical Clearance Limits for Overhead Lines Automobile Dashboard Analogy

• Legal Vehicle Height 4.3 m.
• Added Electrical Buffer set to withstand Switching 
Surge Flashover Voltage.
• Examples of Total Clearance Requirement: 
Examples of Total Clearance Requirement:
– 5.5 m for 115 kV
– 6.1 m for 230 kV

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Ambient Adjusted Rating Analogy Weather‐Based Thermal Rating

• Measure Weather Parameters
• Measure Line Current
Estimate Speed Based on: • Perform Heat Balance Calculation
Temperature • Estimate the Conductor Temperature
Estimate the Conductor Temperature
Line Current (=Fuel Consumption)
• Calculate Thermal Expansion of Conductor
• Calculate the Tension Change from Known State 
(stringing, 30‐60 years ago)
• Calculate Catenary of “Ruling” Span
• Estimate Catenaries of Other Spans
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Tension Measurement Analogy Tension‐Based Thermal Observation

• Measure Weather Parameters
• Measure Line Current 
• Perform Heat Balance Calculation
• Estimate the Conductor Temperature
Estimate the Conductor Temperature
• Calculate Thermal Expansion of Conductor
• Measure the Tension Change from Known State 
(recent manual survey)
• Calculate Catenary of “Local Ruling” Span
• Estimate Catenaries of Other Spans
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

8
9/27/2010

Clearance Measurement Analogy Clearance‐Based Thermal Observations

• Measure Weather Parameters
• Measure Line Current 
• Perform Heat Balance Calculation
• Estimate the Conductor Temperature
Estimate the Conductor Temperature
• Calculate Thermal Expansion of Conductor
• Measure the Tension Change from Known State 
(recent manual survey)
• Measure Catenary of Reference Span
• Estimate Catenaries of Other Spans
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Sonar Equipment to measure Clearance is 
Clearance Monitoring with Sonar
Easily Calibrated from the Ground.
Echo Level (dB)

Distance (m)

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Raw Measurement Error < 6 cm
Overall Layout of Monitoring Program

2002 2003 2003/4 Permanent

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

9
9/27/2010

Temporary Measurement Sites for Clearance  Temporary Measurement Sites for Clearance 
and Weather and Weather

Looking East

Looking West

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Temporary Measurement Sites for Clearance  Permanent Installations to monitor 
and Weather Clearance and Weather

Weather Sensors: Sonic Anemometer,  Sonar Clearance Sensors on 
Temperature, RH 6x6” Wood Crossarms
Shaw Sensor (Conductor Replica) 

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Permanent Installations to monitor 
Typical Measured Clearance Data
Clearance and Weather

Standalone System on 4” ABS Pipes
with Solar Panels 
Sonar Clearance Sensors on 4” 
ABS Plastic Pipes and Line Power

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

10
9/27/2010

Typical Measured Clearance Data Typical Measured Weather Data

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Typical Measured Weather Data Regression Coefficient as “Grade”

• Ranked nine predictors:
– Other clearances in same section
– Tension
– Other clearances on adjacent line
– Other clearances on parallel line
Other clearances on parallel line
– Surface Temperature
– Clearance 20 miles away
– IEEE 738 (Ambient, Wind, Solar, Current)
– Ambient
– Line Current

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Clearances Along One Line: Good Predictor Far Away,  Excellent Correlation: 
Excellent Within Stringing Section Other Lines on Same Right‐of‐Way 

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

11
9/27/2010

Clearance in Parallel Line, 3‐15 km South:
Conductor Temperature: Good Predictor
Very Good Predictor

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

IEEE 738 Thermal Model: Good Square of Line Current: Mediocre Predictor
Ambient Temperature Alone: Mediocre

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Ranking Using Linear Regression Coefficient Organization of Seminar (1)

Predictor of Clearance Pearson r2


Square of Load Current 0.38-0.53 • Heat Balance of Overhead Conductors
Ambient Temperature 0.53-0.69 • Change of Tension, Sag and Clearance with 
IEEE 738 0.65-0.78
(Ambient, Load Current, Wind Speed, Solar)
Conductor Temperature 
Clearance in Another Stringing Section 0.69 – In single span
(98 spans away, different line direction)
Conductor Temperature 3 spans away 0.77 – In multiple spans with freely swinging insulators
Clearance in Parallel Right-of-Way, 2 km Away 0.85 • Field Results
Clearance in Adjacent Line on Same Right-of-Way 0.94 – Predictors of Clearance
Tension in Same Stringing Section 0.94 – Observations of Wind Speed, Direction and their 
Clearance in the Same Stringing Section >0.99 Standard Deviations

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

12
9/27/2010

Wind Parameters measured with  Wind Parameters measured with          
Sonic Anemometer Sonic Anemometer

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Standard Deviation of Wind Direction also  Wind Parameters measured with Aluminum 
affects Nusselt Number Conductor Replicas, Heated/Unheated

Wind angle 
standard deviation
 of 45° at 1 km/h 
suggests effective 
wind yaw angle of:
i d l f
48° for cross flow Sonic Anemometer 
(Nueff ‐13% ) (Vaisala)
30° for axial flow Heated and Unheated Portions
Located along Line Direction
(Nueff +55 %) (Shaw ThermalRate) 

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Comparison: Shaw Sensor Rating Estimate to  Comparison: Shaw Sensor Rating Estimate to 
Observed Ambient Temperature Observed Wind Speed (Ignoring Wind Angle)

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

13
9/27/2010

Comparison: Shaw Sensor Rating Estimate to  Comparison: Shaw Sensor Rating Estimate to 
Observed Wind Speed (Including Wind Angle) Observed Wind Speed (Including Wind Angle)

Remaining Scatter:
• High Ampacity when Wet
• Solar Input
• Wind Direction Standard Deviation

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Organization of Seminar (2) Clearance‐Based Thermal Rating

• Measure Clearance in Reference Span
• Ampacity Inversion  • Estimate Clearances of Other Spans
– Long‐Axis Hot‐Wire Method • Estimate Tension Change from Known State (recent 
– Inputs: Clearance, Line Current, Ambient  LIDAR survey of line at known temperature)
p ,
Temperature, Solar Radiation • Calculate Thermal Expansion of Conductor
– Outputs: Spatially Averaged Conductor Temperature  • Estimate Conductor Temperature
and Wind Speed • Measure Ambient Temperature and Current
• Implementation by Utility and Results • Perform Heat Balance Calculation
• Estimate Average Wind Speed
• Conclusions and Discussion • Calculate Limited‐Time Rating

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Conductor Temperature from Clearance Conductor Temperature from Clearance

Only a few points “above the line”, with clearances 
suggesting a temperature less than ambient.

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

14
9/27/2010

Four Conductor Temperature Estimates from  Standard Deviation of Four Temperatures 
Individual Clearance Readings (obtained from Clearances) versus Ambient

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Standard Deviation of Four Temperatures 
Organization of Seminar (2)
(obtained from Clearances) versus Currents

• Ampacity Inversion 
– Long‐Axis Hot‐Wire Method
– Inputs: Clearance, Line Current, Ambient Temperature, 
Solar Radiation
– Outputs: Spatially Averaged Conductor Temperature 
and Wind Speed
• Implementation by Utility and Results
• Conclusions and Discussion

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Running in Reverse, Item 3:
Wind Speed from Clearance Wind Speed from Clearance, 2002 Trial

• With known line currents and conductor 
temperatures estimated from clearances, iterate 
wind speed until heat balance converges.

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

15
9/27/2010

Wind Speed from Clearance, 2003 Trial Organization of Seminar (2)

• Ampacity Inversion 
– Long‐Axis Hot‐Wire Method
– Inputs: Clearance, Line Current, Ambient Temperature, 
Solar Radiation
– Outputs: Spatially Averaged Conductor Temperature 
and Wind Speed
• Implementation by Utility and Results
• Conclusions and Discussion

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Background: Power and Weather Background: Why Summer?

The black line shows the 
Addition to Base Load (MW), Ontario, 2005
Addition to Base Load (MW), Ontario 2004 expected effect when the 
weather is normal for that 
time of year. 

Blue lines indicate days when 
the weather effect was less 
than normal
than normal. 
• Warmer than normal days 
during the winter months
• Cooler than normal days 
during the summer

Red lines indicate days when 
the weather effect was greater 
The weather effect takes into account temperature, wind,  than normal. 
lighting, and humidity. The normal effect is determined by  • Below‐normal temperatures 
analyzing thirty years of records.  Source: IESO in winter
• Above‐normal temperatures 
in summer
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Background: Why Summer? Background : Why at Low Wind Speeds?

• Extreme loads in Ontario now peak in summer, 
thanks to air conditioning. (CIGRE Technical Brochure 207 Presentation)
Extra 150 MVA of Power Transfer at 2 m/s 
• Aluminum and steel expand when they get hot. (7.2 km/h) compared to 1 m/s (3.6 km/h)

• Temperature rise above ambient
Temperature rise above ambient powered by 
powered by
square of current (I2R).

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

16
9/27/2010

Power Transmission System in Ontario Power Transmission System in Ontario

Queenston (Sir Adam Beck) Generators
Queenston Flow West (QFW) Interface

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Background: Why Niagara? Organization of Seminar (2)

Two new 230‐kV circuits were constructed to 
supplement five existing parallel 230‐kV lines. • Ampacity Inversion 
These increase limits by 800 MW and enable Sir Adam  – Long‐Axis Hot‐Wire Method
Beck plants to deliver an additional 1.6 TWh/year.   – Inputs: Clearance, Line Current, Ambient Temperature, 
However, a land dispute delays the in‐service
However, a land dispute delays the in service date.
date. Solar Radiation
Hydro One has been able to operate around the  – Outputs: Spatially Averaged Conductor Temperature 
problem since 2004 by running its five existing 230‐kV  and Wind Speed
lines to their maximum thermal capability. • Implementation by Utility and Results
On some occasions, the 1800‐MW limit based on static  • Conclusions and Discussion
rating has been exceeded by 600 MW, preventing 
cuts to interruptible industrial loads.
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Conclusions:  Conclusions: Change of Tension, Sag and 
Heat Balance of Overhead Conductors Clearance with Conductor Temperature 

• Thermal Models (IEEE 738, CIGRE Brochure 207)  • A line between strain towers functions as a single 
balance I2R (Joule) heat input with losses from  unit, averaging the effects of wind, solar and 
convection, radiation, sunshine. temperature over distances of  5‐50 km.
• Convection depends on wind speed at 1
Convection depends on wind speed at 1‐2 2 m/s.
m/s • Calculating tension from clearance requires the 
Calculating tension from clearance requires the
• Convection depends on wind yaw angle to line. same care as calculating clearance from tension.
• Statistics of wind speed and direction are not well  – No ruling span approximation
incorporated in present models because raw data  – Effect of local spans more significant
are usually not available. • Calculating temperature from clearance usually 
has standard deviation less than 3Cº. 
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

17
9/27/2010

Conclusions:  Conclusions: 
Field Results, Predictors of Clearance Wind Speed Observations

• It is practical, inexpensive and reliable to measure  • Wind direction standard deviation increases 
clearance with ±6cm accuracy from ground level with  remarkably as wind speed decreases below 2 m/s.  
standard industrial sonar outdoors over a wide 
temperature and humidity range. This usually increases the convective cooling.
• It was better to:
It b tt t • Agreement between heated conductor heat 
Agreement between heated conductor heat
– predict clearance using another clearance measurement,  balance (Shaw Sensor) and effective wind speed 
taken 98 spans away on the same circuit, from nearby sonic anemometer is rather good.
• than to: • Neither measurement is a good predictor of line 
– use the IEEE Standard 738 thermal model with load 
current and weather data directly under the conductor. clearance with present methods.

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Conclusions: Reverse Rating Process to  Conclusions: Utility Implementation
obtain Distributed Wind Speed

• It is possible to invert the ampacity calculation  • Clearance‐based thermal rating offers strong 
process to establish the cross‐wind speed V90 advantages, especially when multiple lines 
averaged over an entire 5‐50 km stringing  present a combined limitation to power transfer.
section
section. – Inexpensive and autonomous installation
Inexpensive and autonomous installation
• The process gives noisy results that differ from  – Practical in‐service calibration
the measured wind speed under the line. – Multiple vendors, standard industrial technology
– Directly useful for estimating clearance of other spans
• Distributed wind speed provides a sound basis for 
thermal rating when line current exceeds 200 A.
W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Open Questions for Further Study Open Questions for Further Study

1. Measure component state (line, cable,  4. Rank of Other Predictors
transformer etc) in two ways. – Ultrasonic wind speed / direction
• They will disagree. – Shaw (Hot wire) sensor
2. What are measures of agreement?  – Sag at 100’ from insulator (Sagometer)
• Static case – X tracks Y with scatter 5. Rank of Same Predictors, Other Sites
• Dynamic case – X lags Y with delay – Limited comparisons with tension
3. We “understand” the static cases.  But what  – Limited comparisons on lines with poorly 
causes those delays? correlated load currents
– No comparisons in sheltered terrain

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

18
9/27/2010

About the Author
William A. (Bill) Chisholm, F (IEEE), Ph.D., P.Eng,  managed the 
Hydro‐One Niagara to Hamilton Real‐Time Thermal Rating 
project, starting in 2001 and ending in 2005 with 
commissioning of permanent clearance observation sites.  

• BASc in Engineering Science, University of Toronto, 1977 Appendix 1:
• M.Eng (part time), University of Toronto, 1979
• Ph.D. (part time) in Electrical Engineering, University of 
Waterloo 1983
Waterloo, 1983.  
Estimates of Initial Line Condition 
• 33 years of research background in power system lightning 
protection, icing and thermal rating (Sags, Tensions, Ground Proflie) 
• Retired as Principal Engineer at Kinectrics, 2007
• Professor, Université du Québec à Chicoutimi, 2007‐8
– Wrote book, Insulators for Icing and Polluted Environments
with Light Detection and Ranging

– Taught graduate course, Protection contre la foudre
Panelist, Conductors sessions at IEEE‐PES meetings (Lidar) 
• Member, joint IEEE/CIGRE Task Force B2.12, Weather 
Parameters for Bare Overhead Conductor Ratings
• Bronze medal, 200m fly, 2010 World Masters Championships

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

LIDAR  Conductor and Line Survey Using LIDAR

– Same principles as Radio Detection And Ranging 
(RADAR) or Sound Navigation and Ranging 
(SONAR)
– Source illuminates target with light. 
– Some of this light is reflected back to 
S f hi li h i fl db k
instrumentation where it is analysed. 
– Changes in reflected light allow some properties 
of the target to be classified. 
– The travel time of light out to the target and back 
determines the range.

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Raw Results of LIDAR Survey  Processed Results of LIDAR Survey

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

19
9/27/2010

Extracted Results from LIDAR Survey Input to SWING model for Coupled Spans 
from LIDAR survey:

• Heights of conductor attachments
• Span lengths
• Height, Horizontal distances to features
SWING models:
SWING models:
• Conductor physical parameters (stress‐strain 
description over temperature)
• Temperature at which insulators now hang 
vertical (< stringing temperature)
• Validated in 1999 IEEE WG comparison

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Conclusions

• It is practical to measure the conductor profile 
using LIDAR / Differential GPS quickly, at a 
constant temperature and state Appendix 2:
Predicting the Future Clearance of
Predicting the Future Clearance of 
• The large data set can be filtered to provide the  an Overhead Line based on 
simple input data needed for the SWING 
clearance model.
Available Real‐Time Data

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Adjacent Clearance: Good Predictor
Looking into the Near Future

• Need to be able to predict the clearance of an 
overhead line in ten to sixty minutes
• Evaluated three predictors:
– Clearance in Adjacent Circuit
Clearance in Adjacent Circuit
– Ambient Temperature
– Sonic wind speed
• Evaluated three time lags:
– 0, 10 minutes and 60 minutes

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

20
9/27/2010

How Quickly do Predictions Degrade? Ambient: Mediocre Predictor gets Worse

One Hour Ahead

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Sonic Wind Speed: Poor Predictor on its Own Could Tension Predict Clearance?

Tension (kg)

Clearance (m)
(Nascimento et al)

W.A.Chisholm@ieee.org W.A.Chisholm@ieee.org

Sources of Time Lag in Thermal Rating using 
Mechanical Measures (Clearance, Sag, Tension)

• Wave velocity 120‐140 m/s
• In 30‐km span, travel time is 250 s
• Minimum three oscillations before lumped weight 
settles to new position: 21 minutes
settles to new position: 21 minutes
• Mechanical time constant is different from 
conductor thermal time constant:
– Longer
– Poorly Damped

W.A.Chisholm@ieee.org

21

You might also like