You are on page 1of 15

TBB700 Series

BTL Certified BACnet® MS/TP Networked


Full Configurable PI Modulating
with On/Off Heating/ Cooling Control
DATA SHEET

FEATURES
․BTL certified BACnet MS/ TP, RS-485 open protocol
communication with complete baud rate selections
․Effective run time accumulation for system reading/
resetting
․The fan speed can be operated in the mode of auto
changeover or manual selected continuous mode.
․Room temperature or setpoint temperature
selectable for normal display
․Full configurable parameters such as switching
differential, cycle time, and etc.
․Proportional plus integral (PI) algorithm applied to
modulating control and/or floating control
․0(2) to 10 Vdc or 10 to 0(2) Vdc control signal output
selectable for direct / reverse acting output

․Optional multi-stage on/off control outputs


The TBB700 series are BACnet Master-Slave/
Token-Passing (MS/ TP), full configurable, open ․Minimum Cycle/ On/ Off time settable
protocol networked digital thermostats. They are
․Optional Remote sensor (RS) input interface for
suitable for 2-pipe or 4-pipe Fan-coil HVAC system of
connecting to remote temperature sensor
modulating and/or floating controls.
․Optional Energy Saving input (ESI) interface for
connecting to hotel card key , occupied/unoccupied
The thermostat measures temperature of a room or sensor or lighting interlock signal
distant space and then output 0(2)-10Vdc signal by ․Optional extra digital input for Window/ Door open
proportional-integral algorithm to control detection to save energy
cooling/heating devices and use relays to switch fan ․Adjustable unoccupied setpoints for heating and
speeds and extra on/off devices in the HVAC system cooling mode control
to maintain the room space near a desired
․Optional settable countdown Timer (0 to 24 hours)
temperature set point. The 1- or 3-fan speed can be
function to stop control output when time expires
operated in the mode of auto changeover or manual
selected continuous mode. ․Optional sleep mode function for raising 2℃
temperature setpoint in 2 hours
․Non-volatile memory (EEPROM) retains user settings
This series has a big LCD screen showing room during power loss
temperature or set point, and related status. And it
․User’s buttons and Energy Saving lockable
also has optional digital inputs for detection device
o o
such as room occupied/unoccupied detector to ․ C or F display, no fluctuation sensing algorithm
enhance energy savings. ․Control off output when system at “OFF” status
․Maximum and minimum set-point limits settable

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 1


SPECIFICATIONS

Supply Voltage:: :
Extra Digital Input ( DI ) Interface:
24Vac (+/-10%), 50/60 Hz For saving energy by stop cooling/heating and Fan
control outputs when DI is triggered by Normally open
BACnet Communication: : (N.O.) or normally close (N.C.) dry contact
BTL certified BACnet
Application Specific Controller(B-ASC) Control action for modulation outputs: :
Support B-ASC plus DS-RPM-B BIBBs Selectable direct or reverse control action of cooling and
RS485, 2/ 3 wires connection heating. Both are direct action by default.
BACnet MS/ TP open protocol, support 9.6/ 19.2/
38.4/ 57.6/ 76.8 kbps baud rate selections a. Cooling Control Action
N81 data format(BACnet Standard)
Control Action Output Signal
Display Range: : Direct 0(2) to 10 Vdc
o o
-30 to 120.0 C (-22.0 to 248.0 F) with suitable sensor Reverse 10 to 0(2) Vdc
Display Temperature Unit and Resolution:
o o b. Heating Control Action
0.1 C/ F
Control Action Output Signal
Indication Accuracy: :
o o o Direct 0(2) to 10 Vdc
+/-1.0 C (1.8 F) at 25 C and output off
Reverse 10 to 0(2) Vdc
Set-point Range:
o o o o
0~50 C / 32~122 F (default-10~30 C /50~86 F, Control Performance: :
o o
adjustable), 0.5 C/ F per setting step Proportional plus integral (PI) adaptive control


Set-point Adjust:
Countdown timer Function (optional):
By up and down arrows buttons or BACnet
communication 1~24 hours settable countdown timer to turn off control
outputs when enable
Analog Output Signal: :
0(2) to 10 Vdc or 10 to 0(2) Vdc
Maximum 3mA Sleep mode Function (optional):
For raising 2℃ temperature set-point in 2 hours when

Relay Output for On/ Off stage Control: enable
Up to 2 SPST or 1 SPDT + 1 SPST relays for on/off
devices control Operating Environment :
o
0 ~ 50 C, 5 ~ 95% RH (non-condensing)
Relay Output for Fan Control: :
Up to 3 SPST relays for 1- or 3-Fan speed control Wiring::
Up to 18 Screw-in terminals, each terminal capable of
2
Relay Output for Interlock Control:: accepting 14 to 22 AWG wires or 1.5 mm wires
1 SPST relay for Interlock control

Dimensions:

Electrical Rating: 94×118×34 mm (W × H × D)
SPDT relay -- 1.2A/ 250Vac, inductive load
SPST relay -- 2A/ 250Vac, inductive load Mounting: :
Mounts directly onto wall, panel, standard 65×65 mm
Remote Sensor ( RS ) Input Interface:: junction box (hole pitch 60 mm) or standard 2×4 inch
For connecting to external NTC Thermistor 3K ohm vertical junction box (hole pitch 83.5 mm)

Energy Savings Input ( ESI ) Interface: :


For saving energy by entering into unoccupied mode
when ESI is triggered by Normally open (N.O.) or
normally close (N.C.) dry contact

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 2


PRODUCT ORDERING INFORMATION

TBB7 □ □ □ - □ □ □ □ □ - □ □ □ □ □ - □

(1) (2) (3) - (4) (5) (6) (7) (8) - (9) (10)(11)(12) (13) - (14)

MODEL: TBB7
Item CODE Cooling Control Outputs*
0 None
1~6 No. of stages for On/Off digital output (DO)
(1) 7 1- floating output
8 1- 0(2) to 10 VDC Modulating output
9 1- 0(2) to 10 VDC Modulating with 1 extra On/Off digital output
A 1- 0(2) to 10 VDC Modulating with 2 extra On/Off digital output
B 1- 0(2) to 10 VDC Modulating with 3 extra On/Off digital output
X Specified

Item CODE Heating Control Outputs*


0 None
1~6 No. of stages for On/Off digital output (DO)
(2) 7 1- floating output
8 1- 0(2) to 10 VDC Modulating output
9 1- 0(2) to 10 VDC Modulating with 1 extra On/Off digital output
A 1- 0(2) to 10 VDC Modulating with 2 extra On/Off digital output
B 1- 0(2) to 10 VDC Modulating with 3 extra On/Off digital output
X Specified

Item CODE Application


A 2-Pipe Cooling only
B 4-Pipe Heating or Cooling (Manual Selectable)
(3) C 4-Pipe Heating and Cooling (Auto Changeover)
D 2-Pipe Heating only
E 2-Pipe Heating or Cooling (Manual Selectable)
X Specified

Item CODE FAN Control *


(4) 0 None
1~3 No. of speeds of FAN control

Item CODE Power of Thermostat, DO1, FAN – refer to wiring diagram for details
0 24Vac, 24Vac, None
(5) 24Vac, External power, External power
1
2 24Vac, 24Vac, External power
3 24Vac, 24Vac, 24Vac
4 Reserved
5 Reserved
6 Reserved
7 Reserved
8 Reserved
9 Reserved
A Reserved

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 3


B Reserved
C 24Vac, None, None
D 24Vac, External power, None
E 24Vac, None, External power
F 24Vac, None, 24Vac
X Specified

Item CODE Wiring for an On/Off Valve/actuator


(6) 0 None
2 2 Wires
3 3 Wires On/off (or 3-position floating valve/actuator)

Item CODE Color for Plastic Case


(7) 1 Pure White
2 Reserved

Item CODE Color of LCD Backlit


(8) 0 None
1 Reserved
2 White

Item CODE No. of input interfaces for Remote Temperature Sensor (RS) or/and
analog input (AI)
(9) 0 None
1 1 RS input
X Reserved

Item CODE No. of input interfaces for Energy Saving Input (ESI) or/and Digital
inputs (DI)
(10) 0 None
1 1 ESI input
2 1 ESI input and 1 extra Digital input

Item CODE Function of sleep mode


(11) 0 None
1 With Sleep mode function

Item CODE Function of Timer mode


(12) 0 None
1 With Timer mode function

Item CODE No. of Interlock Contact (ILC) signal outputs*


(13) 0 None
1 1 ILC

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 4


Item CODE BACnet Baud Rate(Kbps)
(14) 0 9.6
1 19.2
2 38.4
3 57.6
4 76.8
5 115.2

Example: TBB788C-3E010-11000-2 1 modulating cooling, 1 modulating heating, Cooling & Heating auto
changeover for 4-pipe control, 3-speed FAN control, 24Vac thermostat but external power (ex.230Vac) for Fan
speed control, no On/Off valve/actuator, Pure white color for case, no LCD backlit, 1 RS, 1 ESI, No sleep mode
function, No Timer function, No ILC, 38.4 Kbps.
* Note: Total number of cooling plus heating on/off stages and fan control and Interlock contact shall be within six.

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 5


WIRING EXAMPLES

Modulating with On/Off Device and FAN Control Type

Modulating with ILC and FAN Control Type

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 6


Modulating with On/Off Device, ILC, and FAN Control Type

Modulating with 4-pipe 2-wire On/Off Valves and FAN Control Type

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 7


Modulating with 3+2-wire On/Off Valves and FAN Control Type

Modulating with Multi-stage On/Off LOADs Control Type (int. power)

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 8


Modulating with Multi-stage On/Off LOADs Control Type (ext. power)

Modulating with 1 Floating Control Type

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 9


Modulating with 2 Floating Control Type

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 10


The modulating and on/off terminal assignment shall be referred to the following tables according to the number of modulating
and on/off of Cooling and Heating.

Models for Modulating with On-Off Device and 3-speed Fan Control Outputs
Analog Terminal Designation ON-OFF Terminal Designation

Model NO. AO 1 AO 2 Terminal 3 Terminal 6 Terminal 7 Terminal 8

TBB710A Cool 1 FAN Hi FAN Med FAN Low


(On/Off)

TBB701D Heat 1 FAN Hi FAN Med FAN Low


(On/Off)

TBB711E Cool 1/ Heat 1 FAN Hi FAN Med FAN Low


(On/Off)

TBB780A Cool 1 FAN Hi FAN Med FAN Low


(Modulating)

TBB788B Cool 1 Heat 1 FAN Hi FAN Med FAN Low


(Modulating) (Modulating)

TBB788C Cool 1 Heat 1 FAN Hi FAN Med FAN Low


(Modulating) (Modulating)

TBB708D Heat 1 FAN Hi FAN Med FAN Low


(Modulating)

TBB788E Cool 1/ Heat 1 FAN Hi FAN Med FAN Low


(Modulating)

TBB781B Cool 1 Heat 1 FAN Hi FAN Med FAN Low


(Modulating) (On/Off)

TBB781C Cool 1 Heat 1 FAN Hi FAN Med FAN Low


(Modulating) (On/Off)

TBB718B Heat 1 Cool 1 FAN Hi FAN Med FAN Low


(Modulating) (On/Off)

TBB718C Heat 1 Cool 1 FAN Hi FAN Med FAN Low


(Modulating) (On/Off)

TBB790A Cool 1 Cool 2 FAN Hi FAN Med FAN Low


(Modulating) (On/Off)

TBB709D Heat 1 Heat 2 FAN Hi FAN Med FAN Low


(Modulating) (On/Off)

To be continued …

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 11


Models for Modulating with Multi-stage On/Off Control Outputs
Analog Terminal Designation ON-OFF Terminal Designation

Model NO. Terminal Terminal Terminal Terminal Terminal


AO 1 AO 2
3 5 6 7 8

TBB780A Cool 1
(Modulating)

TBB788B Cool 1 Heat 1


(Modulating) (Modulating)

TBB788C Cool 1 Heat 1


(Modulating) (Modulating)

TBB708D Heat 1
(Modulating)

TBB788E Cool 1/ Heat 1


(Modulating)

TBB781B Cool 1 Heat 1


(Modulating) (On/Off)

TBB781C Cool 1 Heat 1


(Modulating) (On/Off)

TBB718B Heat 1 Cool 1


(Modulating) (On/Off)

TBB718C Heat 1 Cool 1


(Modulating) (On/Off)

TBB790A Cool 1 Cool 2


(Modulating) (On/Off)

TBB799B Cool 1 Heat 1 Cool 2 Heat 2


(Modulating) (Modulating) (On/Off) (On/Off)

TBB799C Cool 1 Heat 1 Cool 2 Heat 2


(Modulating) (Modulating) (On/Off) (On/Off)

TBB709D Heat 1 Heat 2


(Modulating) (On/Off)

TBB799E Cool 1/ Heat 1 Cool 2/


(Modulating) Heat 2
(On/Off)

TBB791B Cool 1 Cool 2 Heat 1


(Modulating) (On/Off) (On/Off)

TBB791C Cool 1 Cool 2 Heat 1


(Modulating) (On/Off) (On/Off)

TBB719B Heat 1 Cool 1 Heat 2


(Modulating) (On/Off) (On/Off)

TBB719C Heat 1 Cool 1 Heat 2


(Modulating) (On/Off) (On/Off)

To be continued …

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 12


TBB7A0A Cool 1 Cool 2 Cool 3
(Modulating) (On/Off) (On/Off)

TBB7AAB Cool 1 Heat 1 Cool 2 Cool 3 Heat 2 Heat 3


(Modulating) (Modulating) (On/Off) (On/Off) (On/Off) (On/Off)

TBB7AAC Cool 1 Heat 1 Cool 2 Cool 3 Heat 2 Heat 3


(Modulating) (Modulating) (On/Off) (On/Off) (On/Off) (On/Off)

TBB70AD Heat 1 Heat 2 Heat 3


(Modulating) (On/Off) (On/Off)

TBB7AAE Cool 1/ Heat 1 Cool 2/ Cool 3/


(Modulating) Heat 2 Heat 3
(On/Off) (On/Off)

TBB7A1B Cool 1 Cool 2 Cool 3 Heat 1


(Modulating) (On/Off) (On/Off) (On/Off)

TBB7A1C Cool 1 Cool 2 Cool 3 Heat 1


(Modulating) (On/Off) (On/Off) (On/Off)

TBB71AB Heat 1 Cool 1 Heat 2 Heat 3


(Modulating) (On/Off) (On/Off) (On/Off)

TBB71AC Heat 1 Cool 1 Heat 2 Heat 3


(Modulating) (On/Off) (On/Off) (On/Off)

TBB7B0A Cool 1 Cool 2 Cool 3 Cool 4


(Modulating) (On/Off) (On/Off) (On/Off)

TBB70BD Heat 1 Heat 2 Heat 3 Heat 4


(Modulating) (On/Off) (On/Off) (On/Off)

TBB7BBE Cool 1/ Heat 1 Cool 2/ Cool 3/ Cool 4/


(Modulating) Heat 2 Heat 3 Heat 4
(On/Off) (On/Off) (On/Off)

TBB7B1B Cool 1 Cool 2 Cool 3 Cool 4 Heat 1


(Modulating) (On/Off) (On/Off) (On/Off) (On/Off)

TBB7B1C Cool 1 Cool 2 Cool 3 Cool 4 Heat 1


(Modulating) (On/Off) (On/Off) (On/Off) (On/Off)

TBB71BB Heat 1 Cool 1 Heat 2 Heat 3 Heat 4


(Modulating) (On/Off) (On/Off) (On/Off) (On/Off)

TBB71BC Heat 1 Cool 1 Heat 2 Heat 3 Heat 4


(Modulating) (On/Off) (On/Off) (On/Off) (On/Off)

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 13


Models for Other Control Outputs
Analog Terminal Designation ON-OFF Terminal Designation

Model NO. AO 1 AO 2 Terminal 3/4 Terminal 6 Terminal 7 Terminal 8

TBB780A-3-ILC Cool 1 ILC (Interlock FAN Hi FAN Med FAN Low


(Modulating) Contact)

TBB788B-3-ILC Cool 1 Heat 1 ILC (Interlock FAN Hi FAN Med FAN Low
(Modulating) (Modulating) Contact)

TBB787C-3

Analog Terminal Designation ON-OFF Terminal Designation

Model NO. AO 1 AO 2 Terminal 3 Terminal 5 Terminal 6 Terminal 7 Terminal 8

TBB778C-3 Heat 1 Cool 1 Cool 1 FAN Hi FAN Med FAN Low


(Modulating)
CW CCW

(Floating) (Floating)

TBB787C-3 Cool 1 Heat 1 Heat 1 FAN Hi FAN Med FAN Low


(Modulating)
CW CCW

(Floating) (Floating)

TBB782C-0 Cool 1 Heat 1 Heat 1 Heat 2 Heat 2


(Modulating)
CW CCW CW CCW

(Floating) (Floating) (Floating) (Floating)

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 14


SYSTEM CONNECTION

Abies Technology, Inc. Tel:+886-2-89671237 FAX:+886-2-89671537 http://www.abiestech.com email:sales@abiestech.com 15

You might also like