Professional Documents
Culture Documents
Changeover Guidelines
HCFC R-22 to HFC R-422A/D
for Medium and Low
Temperature Applications
Leading the Industry with Environmentally
Responsible Refrigerant Solutions
Emerson Climate Oil return is determined by a number of design
Technologies, Inc. and operating conditions. In some systems a small
does not advocate the amount, up to 5%, of POE may need to be added
wholesale changeover to assist in oil return.
of HCFCs to HFCs. If
a system is not leak- While 422A/D will operate properly with an oil charge
ing refrigerant to the of 100% POE, the POE can dislodge debris in older
atmosphere, and is systems requiring liquid line filter drier change outs
operating properly, there is no technical reason to replace to keep the system free of this debris.
the HCFC refrigerant. In fact, changing the refrigerant 3. The system capacity and efficiency will be some-
may void the U.L. listing of the system. However, once what different with R-422A/D than with HCFC R-22.
the decision has been made to make the change from In most multiple compressor racks, there should
HCFC R-22 to HFC R-422A/D, the following guidelines still be adequate capacity. However, it is strongly
are recommended. recommended that system capacity verification be
The following guidelines only apply to Copeland® done using the refrigerant manufacturer published
brand Discus™ compressors in existing refrigeration comparison factors.
medium and low temperature systems. Copeland The RLA values for R-422A/D are higher than those
Scroll® compressors are being evaluated for their for HCFC-22. The values are similar for those of
acceptance of these refrigerants in similar medium HFC-404A. The sizing of wires, contactors, and
and low temperature refrigeration systems. breakers should be checked to ensure that they
These refrigerants are not approved for use in any are adequate.
air conditioning systems using Copeland® brand 4. R-422A/D can be used in either low or medium
compressors. For any updates contact Emerson Cli- temperature systems. R-422A/D should not be
mate Technologies, Inc. mixed with any other refrigerant!
CONSIDERATIONS 5. When retrofitting from R-22 to R-422A the
1. Retrofitting systems that employ compressors expansion valves will need to be replaced with
manufactured prior to 1973 is not recommended. a valve suitable for R-404A. In some cases only
This is due to the different materials used in the power element of the expansion valve can be
motor insulation that have not been evaluated for changed, but where this is not possible the entire
compatibility with the new refrigerants and valve must be replaced with the equivalent capacity
lubricants. Failure to heed this advice will violate R-404A model.
the U.L. Standard For Field Conversion/Retrofit When retrofitting from R-22 to R-422D, the
Of Alternate Refrigerants In Refrigeration and Air expansion valve will likely not require replacement;
Conditioning Equipment (U.L.2170-2172). however, it is recommended that the valve loadings
2. HFC refrigerants have generally required the be evaluated to verify that they are adequate. Fol-
use of polyol ester (POE) lubricants in order to lowing the retrofit, superheat should be checked
ensure oil return. However, R-422A/D contains and adjusted if necessary.
a small percentage of isobutane that promotes 6. Filter-driers must be changed at the time of
adequate oil return in properly piped systems with conversion. This is proper air conditioning/
oil separators and no change out of the mineral refrigeration practice.
oil or alkylbenzene is required. Minor equipment
modifications such as replacement or adjustment a. Solid core driers such as Emerson Climate
of the expansion device may be required in some Technologies ADK are compatible with either
applications. HCFC R-22 or R-422A/D.
WARNING: Use only Emerson Climate Technologies Inc. approved refrigerants and lubricants in the manner
prescribed by Emerson Climate Technologies Inc. In some circumstances, other refrigerants and lubricants
may be dangerous and could cause fires, explosions or electrical shorting. Contact Emerson Climate Tech-
nologies Inc., Sidney, Ohio for more information.
b. Compacted bead type driers such as the 6. Thermocouple micron gauge
Emerson Climate Technologies EK series are
7. Leak detector
also compatible.
8. Refrigerant recovery unit including refrigerant
c. Loose fill type driers are not recommended and
cylinder
should be replaced with the types referenced
in a. and b. above. 9. Proper container for removed lubricant
7. Pressure regulators such as EPR valves may have 10. New liquid control device
to be reset. Contact the EPR manufacturer for the
correct settings. 11. Replacement liquid line filter-drier(s)
8. R-422A exhibit higher pressures than HCFC R- 12. New Mineral Oil lubricant
22 at normal condensing temperatures. This may 13. R-422A/D pressure temperature chart
require that the high pressure safety controls be
reset in order to operate as intended. 14. R-422A/D refrigerant
NOTE: R-422A/D is not compatible with the seal 4. Properly remove the HCFC R-22 from the compres-
material used in the HCFC R-22 Moduload Unload- sor. Measure and note the amount removed.
ing system of 3D compressors. If your system
5. Replace the liquid line filter-drier with one that is
has Moduload, the valve plate assembly MUST be
compatible with R-422A/D.
changed.
6. Replace the expansion valve or power element to
Consult your Emerson Climate Technologies wholesaler
a model approved for R-404A (only required when
for the proper part numbers.
retrofitting from R-22 to R-422A).
Many other system seals such as elastomeric seals,
7. Evacuate the system to 250 microns. A vacuum
gaskets, and valve packing may be affected by the
decay test is suggested to assure the system is
change over from HCFC R-22 to R-422A/D. The part
dry and leak free.
manufacturer should be contacted for their recommen-
dations as to whether the seals need to be changed or 8. Recharge the system with R-422A/D.
replaced.
9. Charge the system with R-422A/D. Charge to 90%
Before starting the changeover, it is suggested that at of the refrigerant removed in item 4. R-422A/D must
least the following items be readily available: leave the charging cylinder in the liquid phase. It
is suggested that a sight glass be connected be-
1. Safety glasses
tween the charging hose and compressor suction
2. Gloves service valve. This will permit adjustment of the
cylinder valve to assure the refrigerant enters the
3. Refrigerant service gauges compressor in the vapor state.
4. Electronic thermometer 10. Operate the system. Record the data and compare
5. Vacuum pump capable of pulling 250 microns to the data taken in item 2. Check and adjust theTEV
superheat setting if necessary. Make adjustments
to other controls as needed. Additional R-422A/D CAUTION: These guidelines are intended for
may have to be added to obtain optimum system use with R-422A/D only. Other refrigerants may
performance. not be compatible with the materials used in our
compressors or the lubricants recommended in
11. Properly label the components. Tag the compres-
this bulletin resulting in unacceptable reliability and
sor with the refrigerant used (R-422A/D) and the
durability of the compressor.
lubricant used. The proper color code for R-422A
is Yellow PMS (Paint Matching System) 128; for
R-422D, Green, PMS 375.
55 21 18 205 91 89
60 25 22 210 93 91
65 29 25 215 94 92
70 32 29 220 96 94
75 35 32 225 97 95
HFC R-422D Saturated Vapor/Liquid Pressure/Temperature Chart
Press. Vapor Liquid Press. Vapor Liquid Press. Vapor Liquid
PSIG Temp. °F Temp. °F PSIG Temp. °F Temp. °F PSIG Temp. °F Temp. °F
2.5” -40 -48
0 -36 -45
2 -32 -40 80 49 43 230 110 106
4 -27 -36 85 52 46 235 111 107
6 -23 -32 90 55 49 240 113 109
8 -20 -28 95 57 52 245 114 110
10 -16 -24 100 60 54 250 116 112
55 32 25 205 102 98
60 36 29 210 104 99
65 39 33 215 105 101
70 43 36 220 107 103
75 46 40 225 108 104
The information contained herein is based on technical data and tests which we believe to be reliable and is
intended for use by persons having technical skill, at their own discretion and risk. Since conditions of use are
beyond Emerson Climate Technologies, Inc. control, we can assume no liability for results obtained or damages
incurred through the application of the data presented.
1675 W. Campbell Road
Sidney, OH 45365-0669
(937) 498-3011
EmersonClimate.com
2007CC-13 R1 (6/07) Emerson and Copeland are the trademarks of Emerson Electric Co. or one of its affiliated
companies. ©2007 Emerson Climate Technologies, Inc. All rights reserved. Printed in the USA.