Professional Documents
Culture Documents
net/publication/310719997
CITATION READS
1 198
8 authors, including:
Martin Braun
Universität Kassel
214 PUBLICATIONS 1,982 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Gustav Lammert on 23 November 2016.
Abstract—In this paper an RMS simulation model of a low The goal of this paper is to develop a model of a PV
voltage photovoltaic system for dynamic studies in the range inverter suited for stability studies in a time range of several
of seconds up to minutes is developed. The model is based seconds up to minutes. The focus of this work lays not only
on a low voltage photovoltaic system model developed by the
Western Electricity Coordinating Council (WECC) Renewable on the modelling of the dynamic Q(V ) behavior, but also
Energy Modeling Task Force. The model is validated with an on the dynamic P (V ) behavior. The investigation is done by
experimental setup consisting of a photovoltaic emulator, an comparing a Matlab/Simulink model against an experimental
inverter, a cable and a grid emulator. The laboratory tests show setup with an off-the-shelf inverter. To show the possibilities
an unexpected dead time of the Q(V ) and P (V ) responses of the developed model, a dynamic study of a real German
which the authors could not find in published literature. The
novelty, compared to state-of-the-art models, is the introduction low voltage network with several PV systems is performed.
of a dead time in order to model the measured behavior The paper is structured as follows: The modelling is
correctly. The new model is capable of explaining the grid presented in Section II. In Section III the laboratory tests
coupled behavior of the investigated photovoltaic system in are presented. They contain a steady state and a dynamic
retrospective. Therefore, this work suggests more laboratory investigation. The test case is presented in Section IV and
investigations on the dynamic behavior of photovoltaic systems.
finally a conclusion and an outlook is given in Section V.
Index Terms—Photovoltaic generation, PV, distributed gen-
eration, dynamic modelling, simulation, power system stability, II. PV SYSTEM MODELLING
renewable energy.
A. Generic PV system model
This paper focuses on the dynamic modelling of grid con-
I. I NTRODUCTION
nected small-scale (residential, low voltage level connected)
In recent years the complexity of medium and low voltage PV systems. Various PV system models can be found in,
power grids increased significantly due to a rise of distributed e.g., [7], [8] and [9]. The simulation model developed in
generation such as wind and solar power [1]. PhotoVoltaic this paper is based on the generic model for distributed
(PV) systems have a large share of the total installed capac- and small PV systems provided by the Western Electricity
ity. The worldwide installed PV capacity has reached over Coordinating Council (WECC) Renewable Energy Modeling
180 GW in 2014. Small residential PV systems represent a Task Force [10]. The advantages of generic models are:
major portion of the total installed capacity in Europe [2]. They are independent of the manufacturer and the vendor,
For example, in Germany, about 65 % of the installed PV they are compatible with grid codes, their model structure
capacity is located in the low voltage grid [3]. The installed is open source and the model itself is simulation platform
PV capacity is expected to increase in the future due to PV independent [11]. Note that WECC has also developed a
cost reduction [2]. An investigation on the improved grid model that is suited for large-scale PV systems. This model
integration of PV systems in Germany can be found in [4]. is more detailed but due to the complex control not of interest
A techno-economic assessment of Q(V ) and P (V ) control in this paper. A DIgSILENT PowerFactory® implementation
can be found in [5]. An approach for the static simulation of a large-scale PV system model can be found in [12].
of PV systems can be found in [6]. The model for distributed and small PV systems [10] was
Because of the increasing presence of PV systems in the specifically developed to represent PV systems which are
low voltage level, it becomes important to study the dynamic connected to the distribution grid. Its main features that are
behaviour of PV systems at this voltage level. Dedicated of interest in this paper, are:
PV models are required for dynamic studies. Furthermore, 1) A time constant which specifies the rise time of the
aggregated models of large portions of low voltage grids for the output. This time constant is usually in the range
the use in stability studies of complex grids are required. of 20 ms for standard inverters.
The dynamic behavior of the voltage dependent reactive 2) Furthermore, the model contains a voltage dependent
power injection of PV inverters according to different Q(V ) reactive power characteristic for volt/var control. An
characteristics has been thoroughly investigated, e.g., in [7] example of such a Q(V ) characteristic is shown in
and [8]. Fig. 1. Typical parameters for Q(V ) characteristics in
Q(V )[pu] P (V )[pu]
Q3 P2
P1
Q2
1 V [pu]
V5 V6
1 V [pu]
V1 V2 V3 V4
Active
Q1 power
P
control
Fig. 6
Fig. 1. Reactive power to voltage characteristic Q(V )
V Measurement V’ P − jQ I PV
Fig. 4 I=
the high voltage level can be found in dedicated grid V 0∗
codes, e.g., in [13]. For the low voltage level no typical
parameters have been suggested in grid codes yet. Reactive
power Q
B. Modified generic PV system model control
Fig. 5
The small-scale PV model of WECC lacks some func-
tionalities that are of interest in this paper. Therefore, the
following capabilities have been added to the model: Fig. 3. Overview of the developed small-scale PV model for low voltage
grids.
1) A ramp rate limiter for the current output is added.
In state-of-the-art inverters these rate limiters can be
configured via a web interface of the real inverter. The block diagram of the measurement can be seen in
Therefore, it is important to include this feature in the Fig. 4. It consists of a measuring delay, which is basically a
model. dead time, and a first order time delay. The measuring delay
2) An active power to voltage characteristic, also called is due to the measurement equipment and signal processing
P (V ) characteristic, is added. In case of a high voltage and is approximated with Td,meas = 5 ms. The first order time
at the grid coupling point, a P (V ) characteristic allows delay emulates the calculation of the moving RMS value. In
to reduce the injected active power with regard to the recent PV inverters, five grid periods are used for calculation
terminal voltage. A typical P (V ) characteristic can be of the RMS value. As a 50 Hz system is considered, a value
seen in Fig. 2. The reduction in injected active power of Tmeas = 100 ms is chosen in this paper.
is realized in the inverter by leaving the Maximum The block diagram of the reactive power control can be
Power Point (MPP). seen in Fig. 5. It consists of a reactive power characteristic,
3) A representation of the voltage measurement is added. two first order time delays and a rate limiter. The reactive
The measurement takes place in the time range of up power characteristic Q(V ) is implemented according to Fig.
to 5 cycles. 1 and can be described by a discontinuous function
The resulting, refined PV model is based on the function-
alities of the WECC distributed PV system model. It has to
be noted that this model is only suited for small-scale PV
Q1 , V ≤ V1
Q2 −Q1 Q2 −Q1
systems. During the process of the model development, only V + Q − V , V1 < V < V2
V2 −V1
2 2 V2 −V1
the listed functionalities of the WECC model were imple- Q(V ) = Q2 , V2 ≤ V ≤ V3
mented and then combined with the missing functionalities
Q3 −Q2
V + Q − V Q3 −Q2
, V3 < V < V4
3 4 V4 −V3
V4 −V3
mentioned above.
Q ,
3 V4 ≤ V.
Fig. 3 shows an overview of the small-scale PV system
(1)
model. The model was implemented into Matlab/Simulink. It
consists of three main blocks: A representation of the voltage
measurement and models of the active as well as the reactive Measuring delay RMS calculation
power control. These three blocks will be described in detail
in the following. For this RMS-model, the active and reactive V0 V
powers are converted to RMS currents. This is represented 1
−Td,meas S
e 1 + Tmeas · s
by the block on the right in Fig. 3. Since only balanced
three-phase systems are considered, this approach is similar
to working with DQ0-components. Fig. 4. Block diagram of the measurement.
Characteristic P T1 Power electronics Rate limiter Characteristic P T1 Power electronics Rate limiter
V u(s) Q V u(s) P
1 1 1 1
Q(V ) 1 + TQ · s 1 + TQ,PE · s RQ (u(s)) P (V ) 1 + TP,PE · s RP (u(s))
1 + TP · s
Fig. 5. Block diagram of the reactive power control. Fig. 6. Block diagram of the active power control.
Voltage 1 (Slack) 2
The time constant TQ represents the set-up time of the Source
L R I
Q(V ) characteristics. This time is needed for the inverter
PV plant
to settle the output at the dedicated value. It can be con-
figured in the web interface of the inverter. This parameter
determines how fast the inverter changes its reactive power V slack V
injection after a change of the terminal voltage occurred. The
first order time delay constant TQ,PE emulates the physical Fig. 7. Laboratory setup for testing the small-scale PV system model.
behavior of the power electronics. As stated, e.g., in [14],
this time constant can be estimated to be below 20 ms.
In this paper a fast measurement equipment was assumed.
Therefore, the value TQ,PE = 10 ms was used. The rate
limiter RQ (u(s))) limits the positive and negative rate of
change of the injected reactive power. Here u(t) is the input
to the block. The rate limiter parameters can be adjusted in
the inverter’s web interface as well. (a) Photovoltaic emulator
The block diagram of the active power control can be seen
in Fig. 6. Its structure is identically to the block diagram of 400
Voltage [V]
constants, which are called TP and TP ,PE . TP represents the 0
set-up time of the injected active power and TP ,PE represents
the rise time of the power electronic current output. The −200
rate limiter RP (u(s))) limits the positive and negative rate
of change of the injected reactive power. −400
0 2 4 6 8
The time constants TP and TQ , that can be manually Time [s]
·10−2
configured and are typically set in the range of few seconds (b) AC source (c) AC source performing a voltage step
up to minutes. Therefore, the short time constants of the
power electronic (TP, PE and TQ, PE ) can be neglected for Fig. 8. Devices used for the laboratory setup.
studies in the range of several seconds to minutes. However,
the detailed eleboration is important to become aware of the
different effects that appear in the inverter.
Active [W] and reactive power [Var]
2000
III. L ABORATORY TESTS
A. System overview
The developed PV model was validated by laboratory
0
testing. Fig. 7 shows the general setup. It consists of a
programmable AC voltage source, a cable and an inverter Q(V )
connected to two emulators of solar strings. The PV emula- P (V )
tors and the programmable AC source are shown in Fig. 8(a) −2000
and 8(b). The AC voltage source is capable of performing I II III IV V VI VII VIII
voltage steps in the half cylce after the command is issued.
This can be seen in Fig. 8(c), where a voltage step from 0,95 1,00 1,05 1,10
V ≈ 247 V to V ≈ 262 V is performed at t = 0 s. The Voltage [V]
inverter has a nominal power of 5000 VA. It has a convenient
configurable web interface through which various parameters Fig. 9. Division of the Q(V ) and P (V ) characteristics into eight sections.
can be configured. The cable, that connects the inverter and
the grid emulator, has an inductance of L = 2.63 mH and
a resistance between R = 700 mΩ and R = 1200 mΩ and P (V ) characteristics of the inverter are investigated.
depending on its temperature. That corresponds to an R/X Therefore, the response of the inverter to voltage steps at the
ration of about 1.15. slack bus is investigated. The voltage steps are chosen such
First of all, a steady state validation of the model is that the operating point of the inverter shifts from one section
conducted. Thereafter, the dynamic behavior of the Q(V ) of the Q(V ) or P (V ) characteristic to another. To refer to the
different sections of the characteristics, they are divided into ·10−3
eight segments as seen in Fig. 9. During the tests, different Qmeas (V )
internal time constants of the inverter are varied. 2 Qconfig (V )
and P (V ) characteristic.
In the next step, the steady state operation points of the 1
inverter are compared with the simulation model after the
P (V ) and Q(V ) characteristics were adjusted according
to Table I. Fig. 11 shows a quasi-static time variation
of the slack bus voltage and the measured and simulated 0
terminal voltages of the inverter. It can be seen that both,
the Q(V ) and P (V ) characteristics are active. Furthermore,
the measured and simulated values coincide. The steady state 1,01 1,02 1,03 1,04 1,05
behavior was successfully validated at voltages above 1 pu. Voltage magnitude [pu]
C. Voltage dependent reactive power injection Q(V) (b) Comparison of the Q(V ) adjusted characteristic used in the simulation
and the measured characteristic in the laboratory.
The P (V ) and Q(V ) characteristics according to Table I
are configured in the inverter. Furthermore, a set-up time for Fig. 10. Steady state investigation of the inverter’s Q(V ) characteristic.
each characteristic is configured. For this experiment, set-up
times of 5 s and 20 s are chosen.
For validating the dynamic inverter behavior of the Q(V )
1,10
characteristic, a step of the slack bus voltage is applied. Its P (V )
magnitude is chosen such that the terminal voltage of the
Voltage magnitude [pu]
Parameters V1 [pu] V2 [pu] V3 [pu] V4 [pu] Q1 [kVar] Q2 [kVar] Q3 [kVar] V5 [pu] V6 [pu] P1 [kW] P2 [kW]
Configured in inverter 0.960 0.980 1.020 1.040 −2.500 0.000 2.500 1.080 1.100 2.800 0.800
Adjusted in simulation 0.964 0.985 1.024 1.045 −2.337 −0.050 2.210 1.085 1.103 2.800 0.800
Vslack Vslack
Vmeas Vmeas
1,06 1,06
Vsim Vsim
1,04 1,04
Voltage [pu]
Voltage [pu]
1,02 1,02
1 1
0,98 0,98
0 2 4 6 8 10 0 2 4 6 8 10
Time [s] Time [s]
3000 3000
1000 1000
500 500
0 0
0 2 4 6 8 10 0 2 4 6 8 10
Time [s] Time [s]
Fig. 12. Step response of the small-scale PV model for Q(V ) control after Fig. 13. Step response of the small-scale PV model for Q(V ) control
a step of the slack bus voltage. Top: Slack bus voltage V slack , measured after a step of the slack bus voltage. Top: Slack bus voltage V slack ,
and simulated voltages V meas and V sim at the inverter terminals. Bottom: measured and simulated voltages V meas and V sim at the inverter terminals.
Measured and simulated injected active powers Pmeas and Psim as well Bottom: Measured and simulated injected active powers Pmeas and Psim as
as measured and simulated injected reactive powers Qmeas and Qsim of well as measured and simulated injected reactive powers Qmeas and Qsim
the inverter. The configured set-up time for the Q(V ) characteristic is of the inverter. The configured set-up time for the Q(V ) characteristic
configured in the inverter’s web interface to 5 s. The adjusted time constants is configured in the inverter’s web interface to 20 s. The adjusted time
in the simulation are TP = 1.6 s and TD,P = 0.4 s. constants in the simulation are TP = 5.8 s and TD,P = 1.4 s.
Voltage [pu]
1,09 1,09
1,08 1,08
1,07 1,07
0 2 4 6 8 10 0 2 4 6 8 10
Time [s] Time [s]
Active [W] and reactive power [Var]
2400 2400
2200 2200
2000 2000
0 2 4 6 8 10 0 2 4 6 8 10
Time [s] Time [s]
Fig. 15. Step response of the small-scale PV model for P (V ) control after Fig. 16. Step response of the small-scale PV model for P (V ) control after
a step of the slack bus voltage. Top: Slack bus voltage V slack , measured a step of the slack bus voltage. Top: Slack bus voltage, measured voltage at
and simulated voltages V meas and V sim at the inverter terminals. Bottom: the inverter terminals. Bottom: Measured and simulated active and reactive
Measured and simulated injected active powers Pmeas and Psim as well power injection of the inverter. Configured inverter hardware setting for
as measured and simulated injected reactive powers Qmeas and Qsim of the P (V ) set-up time is 20 s. Adjusted parameters in the simulation are
the inverter. The configured set-up time for the P (V ) characteristic is TP = 10.6 s and TD,P = 2.2 s.
configured in the inverter’s web interface to 5 s. The adjusted time constants
in the simulation are TP = 2.5 s and TD,P = 0.5 s.
Characteristic Dead time P T1 Power electronics Rate limiter
V
is needed for the reduction of active power injection is less −TD,P S
1 1 P
P (V ) e RP (u(s))
then the setup time of 5 s configured in the inverter’s web 1 + TP s 1 + TP,PE s
interface. As done in Sec. III-C, the model of the active
power control is modified in order to simulate the physical Fig. 17. Block diagram of the active power control with dead time.
behavior correctly. Therefore a dead-time TD,P was included
after the P (V ) characteristics. The modified model of the
active power control can be seen in Fig. 17. In order to presented model can only be an approximation of the real
make the simulation results match the measurement results, inverter behavior.
the dead time TD,P and the time constant TP are adjusted
until sufficient overlapping is attained. IV. S IMULATION TEST CASE
To show a possible application of the investigated PV
E. Discussion of measurement results model, a larger test case was composed in Matlab/Simulink.
The three main observations from the measurements are: It consists of a real German 0.4 kV low voltage grid that
First, the P (V ) and Q(V ) characteristics configured in the is connected via a transformer to a 20 kV medium voltage
inverter have a slight offset, compared to the measurements. grid. The general setup can be seen in Fig. 18. The LV
The offset is smaller than 0.005 pu. Second, the time delay, grid consists of 234 nodes. Altogether 20 PV systems with
configured in the inverter, did not correspond to the time con- a total installed apparent power of 250 kVA were included
stant of the PT1 block, used in the simulation model. Third, in the system. The P (V ) and Q(V ) characteristics were
the measurements showed a dead time that was not expected. implemented for all PV systems. For the investigation, a low
This dead time is not known before the measurement is done load setup was selected, where the total injected PV power
and it varies with the set-up time that is configured in the is much higher than the total load consumption.
inverter’s web interface. To match the simulation and the The dynamic behavior of the low voltage grid was investi-
measurement results, the characteristics, the time constant gated for two configurations, as described in Table II. In the
and the dead time of the simulation model had to be adapted first configuration, the PV systems were placed as far away
manually. After adaptation of these parameters, a good match from the slack bus as possible, namely at the end of the
between measurements and simulations was obtained. P (V ) feeders. In the second configuration, the PV systems were
and Q(V ) controls are not yet part of low voltage grid codes. placed near the slack bus, namely at the beginning of the
Therefore the behavior of the inverter in the investigated feeders.
situations is not standardized yet. Also the internal control Fig. 19 shows the reverse power flow from the low voltage
loops of the inverter are not known in detail. Therefore, the grid into the medium voltage grid after a voltage step at
TABLE II
D ESCRIPTION OF THE TWO SIMULATED CONFIGURATIONS V. C ONCLUSION
Configuration Description
In this paper a small-scale RMS model for low voltage
1 PV systems are far from slack node
PV systems is developed, based on a distributed PV system
2 PV systems are close to slack node model proposed by WECC. The main focus of the work is
to emulate the dynamic behavior of the voltage dependent
active and reactive power injection via P (V ) and Q(V )
Slack bus characteristics. The developed simulation model is validated
I
against an experimental setup with an off-the-shelf inverter
LV grid in the power range of 5000 VA.
The new contribution of this paper is to show that there are
V slack
dead times in the measurement data that change significantly
with the set-up time configured in the inverter. However,
Fig. 18. Setup of the low voltage grid test case. no connection between these two variables can be found.
As far as the authors know, measurements of such dead
times have not been reported in literature yet. By including
1,1 Vslack these dead times into the PV model, the simulation and
Voltage V [pu]
2,0 Pcase2 As the cause of the dead time is not known by the authors,
1,8 it will be necessary to conduct future work on validating
PV system models. Also it will be beneficial to test more
1,6
scenarios in the laboratory.
0 5 10 15 20
Time [s] ACKNOWLEDGMENT
1,0
Reactive power [pu]
Fig. 19. Step response of the slack bus active and reactive power after a This work was supported by the German Federal Ministry
voltage step at the slack bus at t = 0 s. for Economic Affairs and Energy and the Projektträger Julich
GmbH (PTJ) within the framework of the project OpSim
(FKZ: 0325593B).
the medium voltage side. The voltage step at the slack bus R EFERENCES
occurs at t = 0 s. The voltage rise at the slack bus results in
[1] A. Monti and F. Ponci, “Power grids of the future: Why smart means
voltage rises at each bus in the system. The voltage rise at complex,” in Complexity in Engineering, 2010. COMPENG ’10., Feb
the terminals of the PV systems is such that their operating 2010, pp. 7–11.
points shift into sections where the active power injection is [2] F. T. Manoel Rekinger, “Global Market Outlook for Solar Power /
2015 - 2019,” SolarPower Europe, Technical Report, 2014.
reduced and where more reactive power is injected. Thus, [3] J. von Appen, M. Braun, T. Stetz, K. Diwold, and D. Geibel, “Time in
the operating point of some inverters shift into the sections the sun: The challenge of high pv penetration in the german electric
VII and VIII (see Fig. 9). Due to this, the injected active grid,” IEEE Power and Energy Magazine, vol. 11, no. 2, pp. 55–64,
March 2013.
power is reduced. In the investigated grid, the voltage at [4] T. Stetz, F. Marten, and M. Braun, “Improved low voltage grid-
each feeder is highest at its end points (for configurations of integration of photovoltaic systems in germany,” IEEE Transactions
high PV power and low load). Therefore, the active power on Sustainable Energy, vol. 4, no. 2, pp. 534–542, April 2013.
[5] T. Stetz, K. Diwold, M. Kraiczy, D. Geibel, S. Schmidt, and M. Braun,
injection in configuration 1 is generally lower than the one “Techno-economic assessment of voltage control strategies in low
in configuration 2. This can also be seen in Fig. 19. For voltage grids,” IEEE Transactions on Smart Grid, vol. 5, no. 4, pp.
the same reason, the injected reactive power is higher than 2125–2132, July 2014.
[6] D. Fetzer, G. Lammert, S. Gehler, J. Hegemann, and M. Braun,
in configuration 2. The high peak in active and reactive “A bisection newton power flow algorithm for local voltage control
power at t = 0 s is only due to the simulation method strategies,” Power Systems, IEEE Transactions on, submitted for
and can therefore be neglected. The dynamic behavior of publication.
[7] R. W. Marco Lindner, “A dynamic rms-model of the local voltage con-
the slack bus active and reactive powers is stable in both trol system q(v) applied in photovoltaic inverters,” 23rd International
configurations. Conference on Electricity Distribution, Lyon, 15-18 June 2015.
[8] F. Andren, B. Bletterie, S. Kadam, P. Kotsampopoulos, and C. Bucher,
“On the Stability of Local Voltage Control in Distribution Networks
With a High Penetration of Inverter-Based Generation,” IEEE Trans-
actions on Industrial Electronics, vol. 62, no. 4, pp. 2519–2529, Apr.
2015.
[9] M. Farivar, L. Chen, and S. Low, “Equilibrium and dynamics of
local voltage control in distribution systems,” in Decision and Control
(CDC), 2013 IEEE 52nd Annual Conference on, Dec 2013, pp. 4329–
4334.
[10] Western Electricity Coordinating Council (WECC) Renewable Energy
Modeling Task Force. (2014, April) WECC PV Power Plant Dynamic
Modeling Guide.
[11] North American Electric Reliability Corporation (NERC)
Special Report. (2010, May) Standard models for vari-
able generation. [Online]. Available: http://www.nerc.com/files/
StandardsModelsforVariableGeneration.pdf
[12] G. Lammert, L. D. Pabón Ospina, P. Pourbeik, D. Fetzer, and
M. Braun, “Implementation and Validation of WECC Generic Pho-
tovoltaic System Models in DIgSILENT PowerFactory,” IEEE PES
General Meeting 2016, Boston, USA, July 17-21, 2016.
[13] VDE Germany, Association for Electrical, Electronic & Information
Technologies, “Technical requirements for the connection and opera-
tion of customer installations to the high-voltage network (TCC High-
Voltage),” VDE application guide (VDE-AR-N 4120).
[14] R. I. Amirnaser Yazdani, Voltage-Sourced Converters in Power Sys-
tems : Modeling, Control, and Applications. WILEY, 2010.