etc to the CMU; Interface I2 is between the SMU and CAG. models and methods to evaluate the condition of the high
The SMU send the monitoring data, analysis results, warning voltage equipment based on the online monitoring data or live
information etc to the provincial based CAG. The SMU can measuring data. The data or analysis results based on the CAG
also receive the analysis models, parameter configurations, platform can be published through web in the exclusive
data summon, time synchronization, device reset etc from the networks, and also it can offer the information to other system
CAG; as foundation data of the asset condition evaluation and
maintenance.
D. Substation System Structure
The substation online monitoring system is a distributed III. DESIGN OF CAC AND CMU
and hierarchy structure as Fig.4 shows, which is composed of
As the function models and interface models of the online
process level, unit/bay level, station level, remote monitoring
monitoring system have been built based on IEC61850
center.
standard, a typical system can be designed as the guidance for
The process level consists of all the monitoring devices or the implement of specific projects.
sensors of the transformers, reactors, circuit breakers, GISs Considering that most monitoring devices cannot support
(Gas Insulated Switchgear), MOAs (Metal Oxide Arrester), IEC61850 standard currently, the structure of the online
bushings etc. The monitoring devices including DGA monitoring system should be a structure with 3 levels, shown
(Dissolved Gas Analysis), PD (Partial Discharge), transformer in Fig.4, that is, CMU should be involved in the system. A
oil and winding temperature, transformer core ground current, typical structure of the online monitoring system based on
dielectric loss factor, temperature, moisture, pressure and IEC61850 standard should be like that shown in Fig.5.
density of the GIS cabinet etc. The intelligent electronic devices (short for IED) of the
The IEC61850 standard is the communication standard for online monitoring system are located in the station level and
the smart substation, which has been successfully used in the the process level respectively. Communication between the
substation automation system. At the pilot stage of the smart IEDs of the CAC and CMU are based on the IEC61850
substation project, not all of the online monitoring devices can standard; Communication between the CMUs and monitoring
comply with the IEC61850 standard, the CMU is adopted so devices in process level may apply MODBUS protocol based
that the online monitoring system can comply with the on industrial bus such as RS485 or other protocol and buses.
And in this structure the CAC and the CMU are new devices
IEC61850, as the development of new monitoring devices
involved to be compatible with the online monitoring system
which embedded with IEC61850 module, the CMU and
guides or standards of smart substation, therefore, functions of
unit/bay level can be omitted in future application.
these two devices should be discussed here.
The station level is the SMU, which controls the operation
of the whole online monitoring system, and also collect all the
monitoring results to analysis, diagnosis, warning, data display,
data storage and forward.
3
4
Fig.6 Software Modules of the CAC DEVICES IN THE ONLINE MONITORING SYSTEM
Monitoring type Monitoring parameters The number of
measuring points
The hardware of CAC can be an industrial computer or an DGA H2, CH4, C2H6, C2H4, 2
Embedded Computer. All the functions are executed by the C2H2, CO, CO2, H2O
software embedded in the CAC. Fig.6 shows the structure of PD Amplitude, count, phase 2
and type of partial
its software. discharge
B. THE DESIGN OF CMU Core Grounding Grounding current 2
CMU is a new type of device specifically designed to meet Current
the application requirement of the IEC61850 standard in smart Oil Temperature Temperature 4
Winding Temperature 4
substation. The major function of CUM is to covert non Temperature
IEC61850 models to the IEC61850 models and transfer the Moisture and Humidity, temperature, 224
data to CAC or to download commands from CAC to Density of SF6 pressure and density
monitoring devices through I0 interface. CMU is usually Insulation of Leakage current, resistive 63
MOA current, surge times
designed to communicate with all the monitoring devices in
one bay, such as transformer bay or feed line bay.
CMU is usually located in a control cabinet at the switch
yard, it should be able to withstand the tough environment and
strong electromagnetic condition in the substation. The
hardware must be designed to ensure long-term and stable
operation at the switch yard. And the software of CMU must
have a flexible architecture to meet the access of devices with
various types of communication protocols.Fig.7 shows the
software structure of the CMU.
4
5
REFERENCE
[1]Q/GDW Z410—2010 Technical Guide for Smart Electric Equipments
[2]Q / GDW 534 — 2010 Technical guide for on-line monitoring
Fig.11 Webpage of the Diagnosis Result system of transformation equipment
Fig.12-14 shows pictures of CAC, CMU and monitoring [3]Q / GDW 393 — 2009 Specifications of design for 110 ( 66 ) kV ~
220kV Smart Substation
devices installed in the substation. [4]Q / GDW 616 — 2011 Application specification for on-line Monitoring
device of transformation equipment based on DL/T 860
[5]DL/T 860—2006 Communication networks and systems in substations