July - September 2003

Issued by : EBG - Electrical Systems & Equipment, LARSEN & TOUBRO LIMITED, Powai Works, Mumbai 400 072

Siesmic Testing L&T switchboard


Natural calamities like earth- In order to face such eventualities, with
quakes can have disasterous it is essential to assess the Seismic Qualification
effect on the surroundings and siesmic requirement at the
L&T's switchboard has
living beings. This is more so for location of the plant and define the
same when specifications are been Seismically qualified.
the area in and around power
plants, specially based on Nuclear drafted for associated equipment.
It can also help the respective The testing was carried out
Power and Hydro Electric Power.
equipment manufacturer to at Earthquake Engineering &
understand the siesmic Vibration Research Centre
In case of a Nuclear Power Plant,
failure to arrest radioactive requirements and offer the right (EVRC) - Central Power
equipment. Reasearch Institute (CPRI),
process and shut down the
reactor in the event of an Bangalore.
This also increases the
earthquake can cause large scale
responsibility of the equipment After the test, operation of
destruction.
manufacturers, who, in turn, have all the equipment, including
to translate these requirements in
Similarly, in case of a Hydro the circuit breaker, was
the design of the equipment so
Electric Plant, severity of tremours checked and found to be
as to make it suitable to withstand
is aggrevated due to higher water and perform in the eventuality of satisfactory. The structural
levels in reservoirs. It can cause an earthquake. integrity was also checked
major failure of power supply and was found to be OK. All
system. Hence, it becomes Siesmic Qualification of the the connections and circuit
essential for all the emergency equipment is the only way to components remained
equipment to function properly so ensure that it will function properly healthy. The structure and
that effective control can be in the event of an earthquake, thus the equipment mounting
exercised and the situation can be improving the overall safety of the were in good condition.
brought under control. plant.

Visit us at www.LNTEBG.com
FEATURE

Siesmic Qualification of Electrical Equipment


- Mr. C.S. Kore
Switchgear Design & Product Development

Power Plants consist of various Surface waves generally have the measured by the modified Mercalli
structures, systems and strongest vibrations, causing most scale ranging in values from I (“not
equipment. The catastrophic of the damage. Body waves felt except by very few, favorably
consequences of natural consist of compressional and situated”) to XII (“damage total,
calamities like earthquakes, shear waves, which travel through lines of sight disturbed, objects
cyclones and floods need to be the earth’s interior starting from the thrown into air”).
considered while designing the focus. The arrival time of
equipment for assuring safety of compressional and shear waves Earthquakes experienced by
the plant. Amongst these, at selected seismograph stations
‘Earthquakes’, due to their high equipment : To design an
throughout the world can indicate
levels of risk, pose the greatest equipment suitable for Seismic
the location and time of an
challenge to the engineers. zone, the equipment designer
earthquake and often its focal
must know the maximum
depth. Richter scale and modified
Earthquakes : An earthquake may Mercalli scale are the two common earthquake intensity that the
be described as the vibratory and measurements to express the equipment will experience in the
often violent movement of earth’s severity of an earthquake. location of its final operation. In
surface, which is preceded by a general, seismic waves in
release of energy from the earth’s Richter scale indicates the equipment housed in a building are
crust. The alternating ground different from those experienced
magnitude of an earthquake,
motion, caused by the Earthquake by the ground or the foundation.
which is measured by the
is harmful because of the
amplitude of the seismic waves
acceleration and thereby, the
and is related to the amount of Each medium (e.g. different layers
inertial forces it induces in the
energy released. The modified of earth’s crust, foundation of
system components.
Mercalli scale, expressing the building), because of its stiffness,
intensity of an earthquake, is a mass and damping
Earthquakes produce two general
subjective means to describe characteristics, responds
types of vibrations :
severity of shock felt at a location. differently to the seismic waves.
L First is known as surface
The Richter scale is logarithmic Therefore, the characteristics of
waves, which travel along the
earth’s surface i.e. an excitation with ground waves alter as they pass through
L Second is called body waves,
motion for an earthquake
each medium. Thus, the intensity
measuring 6 on Richter scale will
which travel through the earth. and frequency experienced by the
be ten times
equipment can be quite different
more than an
from what is experienced by the
Equipment earthquake
measuring 5 on building foundation.
Building
Richter scale
(or about thirty Hence, electrical equipment and
Building foundation times the structure, failure of which during
energy). The earthquake can be disasterous,
Layers of the e a r t h q u a k e need to be capable of withstanding
earth’s crust
intensity at a ‘Earthquake forces’. These
particular components need to be
Focus of earthquake location is Seismically qualified.
The test procedure followed for material to the environment.’) e.g. L predict the equipment
Seismic Qualification is prepared 220V DC power supply from performance by analysis
based on IEEE 344-1987 batteries is the most reliable L test the equipment under
‘Recommended Practice for system and is used for the supply simulated seismic conditions
Seismic Qualification of Class-1E of the control circuit of circuit L qualify the equipment by a
equipment for Nuclear Power breakers and other controls such combination of test and
Generating Stations’. as diesel engine schematics. analysis
L qualify the equipment through
Seismic qualification : A brief Class II – Those structures and the use of experience data
overview : The present Seismic components which are important
withstand criteria of electrical to reactor operation, but not Choice of a method is based on
equipment for Nuclear power essential for safe shutdown and the practicality of the method for
plants have evolved through the isolation of the reactor, and whose the type, size, shape and
development and growth of failure could not result in the complexity of the equipment
nuclear power generating stations release of a substantial amount of configuration. Equipment being
for almost five decades. The radioactivity. e.g. 415V AC 3 phase qualified must demonstrate that it
human loss and extensive property system, derived from can perform its safety function
damage caused by the 1964 uninterruptible power supply during and after an earthquake.
Alaska earthquake aroused system comprising rectifier,
widespread attention to proper inverter and a dedicated battery A few definitions
Seismic design of buildings and bank. Operating Basis Earthquake
structures. Seismic design and (OBE) – An earthquake that could
qualification of PCCs and MCCs Class III / IV - Those structures reasonably be expected to occur
is often a difficult and time not directly related to reactor at the plant site during the
consuming process because of operation or safety in the event of operating life of the plant
the very complex nature of both a design-basis accident and considering the regional and local
the earthquake and the electrical whose failure would not result in geology and seismology and
equipment. the release of a significant amount specific characteristics of local
of radioactivity. subsurface material. (For a given
Seismic qualification is necessary site, OBE is expressed in terms
for those equipment and e.g. The 6.6 kV and 415V 3 phase of magnitude of worst earthquake
structures, which are designed to system, connected to emergency occurred in the 300 km radius
remain functional during/after the diesel generator to provide power from the plant. OBE level of
occurrence of an earthquake. supply in the event of failure of earthquake is expected to occur
Class IV power supply. Class IV at the site once in 100 years.)
Equipment classification in a power supply is derived from
Nuclear Power Plant : 220kV grid through start-up Safe Shutdown Earthquake
Class I – Those structures and transformer and from the turbo- (SSE) – An earthquake that is
components, including generator through unit transformer. based upon an evaluation of
instruments and controls, failure The loads connected to Class III maximum earthquake potential
of which might cause or increase and Class IV systems can tolerate considering the regional and local
the severity of a design basis short and prolonged power supply geology and seismology and
accident or result in uncontrolled interruptions respectively. specific characteristics of local
release of a substantial amount of subsurface material. (For a given
radioactivity. (Class 1E as defined As can be seen, the performance site, SSE is expressed in terms
in the IEEE Std C37.100-1992. of Class I equipment is most of magnitude of worst earthquake
‘The safety classification of the critical for safety against radiation occurred in the 300 km radius
electric equipment and systems hazard in the event of any failure. from the plant increased in
that are essential to reactor Hence, these equipment need to intensity. SSE level of earthquake
emergency shutdown, be seismically qualified. is expected to occur at the site
containment isolation, reactor core once in 10000 years.)
cooling, and containment and Seismic qualification : The
reactor heat removal, or otherwise Required Response Spectrum
seismic qualification methods are
are essential in preventing (RRS) – The response spectrum
grouped into four general
significant release of radioactive issued by the user as a part of his
categories that :
specifications for qualification or suitable locations to determine not exhibit resonance in the lower
artificially created to cover future response of equipment along all frequency range.
applications. The RRS constitutes three axes at those points in the
a requirement to be met. structure that reflect the Vibrational aging : Seismic
equipment response associated qualification tests on the
Test Response Spectrum (TRS) with structural integrity. equipment must include OBE
– The response spectrum that is tests. SSE tests are preceded by
developed from the actual time Refurbishment : It is classified OBE tests that produce the
history of the motion of the shake into maintenance and repairs. equivalent fatigue effect. The
table. Maintenance e.g. calibration of number of OBE shall be justified
relays etc. may be performed and for each site or shall produce the
Equipment are required to be testing continued. When equivalent effect of 5 OBE.
tested for following tests: maintenance is performed during Following the aging using 5 OBE,
L Resonance Search Test OBE testing, it becomes part of the equipment is subjected to SSE
L Operating Basis Earthquake the post earthquake field to verify functionality of the
(OBE) Test maintenance checks and equipment.
L Safe Shutdown Earthquake procedures for the equipment.
(SSE) Test Repairs e.g. rewelding of portions For both the OBE and SSE, Test
of the equipment, replacing Response Spectra (TRS) is
Testing : The test method is damaged components, such as derived based on Required
decided based on factors like sheared bolts, if necessary during Response Spectra (RRS)
location of the equipment, nature the OBE test or SSE test, retest supplied by the customer. TRS for
of the expected earthquake. is required unless justified the test should envelop the RRS.
otherwise.
Mounting : The equipment is During the above OBE & SSE
mounted on the shake table in a Exploratory test i.e. resonance tests (duration for the each OBE
manner that simulates the search test, are generally not a
& SSE test is 20 to 30 sec.-that is
intended service mounting part of the seismic qualification
typical duration of an earthquake),
(recommended bolt size, type, requirements. These are run on
the equipment is monitored for
torque, configuration and weld the equipment to determine the
operability. After the tests, the
pattern). The orientation of the best test method for qualification
equipment is checked for
equipment during the test is or to determine the dynamic
operability and structural integrity.
documented and is the only one characteristics of the equipment.
This is to ensure highest reliability
for which the equipment is These tests are carried out at input
and continuous performance after
qualified. The interposing structure levels well below the required
seismic qualification vibration level. such field conditions.
if any used during the tests shall
be such that their use will not filter The input levels of 0.2g are used.
The resonance search is carried Conclusion :
out or change any frequencies
out upto 50Hz. (Sweep rate : 1 Whenever any equipment,
from the input motion.
octave per min.) especially the one involved in
Monitoring : Functional electrical power distribution, is
monitoring equipment is used to The earthquake is relatively rich in required to be siesmically stable,
evaluate the functionality of the energy content in the frequency it is very important to incorporate
equipment before, during and after range of 1 to 15Hz. The energy the necessary precautions in the
vibration test exposure. The content above the frequency of basic design itself. This is
monitoring will vary depending on 15Hz reduces considerably and is extremely important to ensure
the specific equipment. Vibration very less beyond 33Hz. Hence, as complete reliability of the
sensors are to be located at a basic rule, the structure should equipment.

For further details on this subject, please contact:


EBG - Electrical Systems & Equipment, Larsen & Toubro Limited, Saki-Vihar Road, P.O. Box 8901, Powai, Mumbai 400 072
Fax: 022-2858 1024 * E-mail: kotnisnd@Intebg.com

Printed by Printania Offset Pvt. Ltd.,D 20/21, Shalimar Industrial Estate, Matunga (East), Mumbai 400 019. Tel.: 2407 7996/