YT OptiView w/ Standard Starter ELINK/MG YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Date YORK P N Checksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC (ASCII not available with E-LINK)
Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 1
1/16/2008
Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 2
1/16/2008
ENG ASCII YTM Warning Code ENG ASCII YTM Operational Code ENG ASCII YTM Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P57 P55 WARNING.FLT P58 P56 OPER.CODE P59 P57 SAFETY.FLT
0 0 No Abnormal Condition 0 0 Unit Stopped - Ready To Start 0 0 No Abnormal Condition
1 1 Real-Time Clock Failure 1 1 Unit Stopped - Local Shutdown 1 1 Evaporator - Low Pressure
2 2 Default Setpoints Loaded 2 2 Unit Stopped - Remote Shutdown 2 2 Evaporator - Transducer Or Leaving Liquid Probe
3 3 Evaporator Or Condenser Transducer Error 3 3 Unit Stopped - Warning Active 3 3 Evaporator - Temperature Transducer
4 4 Evaporator - Low Pressure Limit 4 4 Unit Stopped - Cycling Shutdown 4 4 Condenser - High Pressure Contacts Open
5 5 Condenser - High Pressure Limit 5 5 Unit Stopped - Safety Shutdown 5 5 Condenser - High Pressure
10 10 Purge - High Pressure 6 6 Unit Start Inhibit 6 6 Condenser - Pressure Transducer Out Of Range
11 11 Purge - Float Switch Error 7 7 Unit Starting 7 7 Auxiliary Safety - Contacts Closed
12 12 Purge - Excess Purge 8 8 Unit Running - No Abnormal Condition 8 8 Discharge - Low Temperature
14 14 Motor - High Current Limit 9 9 Unit Running - Warning Active 9 9 Discharge - High Temperature
15 15 Vanes Uncalibrated 10 10 Unit Running - Chiller Unload Before Shutdown 10 10 Oil - High Temperature
16 16 Vanes Uncalibrated - Fixed Speed Operation 11 11 Unit Coastdown 11 11 Oil - Low Differential Pressure
12 12 Oil - High Differential Pressure
21 21 Control Panel - Power Failure
23 23 Motor Or Starter - Current Imbalance
26 26 External I/O Board Serial Communications
49 49 Starter - Invalid Motor Selection
51 51 Evaporator - Low Pressure
52 52 Evaporator - Low Pressure - Smart Freeze
Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 3
1/16/2008
Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 4
1/16/2008
YT OptiView w/ SSS ELINK/MG YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Date YORK P N Checksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC (ASCII not available with E-LINK)
Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 5
1/16/2008
Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 6
1/16/2008
ENG ASCII YTM Warning Code ENG ASCII YTM Operational Code ENG ASCII YTM Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P57 P55 WARNING.FLT P58 P56 OPER.CODE P59 P57 SAFETY.FLT
0 0 No Abnormal Condition 0 0 Unit Stopped - Ready To Start 0 0 No Abnormal Condition
1 1 Real-Time Clock Failure 1 1 Unit Stopped - Local Shutdown 1 1 Evaporator - Low Pressure
2 2 Default Setpoints Loaded 2 2 Unit Stopped - Remote Shutdown 2 2 Evaporator - Transducer Or Leaving Liquid Probe
3 3 Evaporator Or Condenser Transducer Error 3 3 Unit Stopped - Warning Active 3 3 Evaporator - Temperature Transducer
4 4 Evaporator - Low Pressure Limit 4 4 Unit Stopped - Cycling Shutdown 4 4 Condenser - High Pressure Contacts Open
5 5 Condenser - High Pressure Limit 5 5 Unit Stopped - Safety Shutdown 5 5 Condenser - High Pressure
10 10 Purge - High Pressure 6 6 Unit Start Inhibit 6 6 Condenser - Pressure Transducer Out Of Range
11 11 Purge - Float Switch Error 7 7 Unit Starting 7 7 Auxiliary Safety - Contacts Closed
12 12 Purge - Excess Purge 8 8 Unit Running - No Abnormal Condition 8 8 Discharge - Low Temperature
14 14 Motor - High Current Limit 9 9 Unit Running - Warning Active 9 9 Discharge - High Temperature
15 15 Vanes Uncalibrated 10 10 Unit Running - Chiller Unload Before Shutdown 10 10 Oil - High Temperature
16 16 Vanes Uncalibrated - Fixed Speed Operation 11 11 Unit Coastdown 11 11 Oil - Low Differential Pressure
12 12 Oil - High Differential Pressure
21 21 Control Panel - Power Failure
23 23 Motor Or Starter - Current Imbalance
26 26 External I/O Board Serial Communications
Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 7
1/16/2008
Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 8
1/16/2008
YT OptiView w/ VSD ELINK/MG YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Date YORK P N Checksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC (ASCII not available with E-LINK)
Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 9
1/16/2008
Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 10
1/16/2008
ENG ASCII YTM Warning Code ENG ASCII YTM Operational Code ENG ASCII YTM Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P57 P55 WARNING.FLT P58 P56 OPER.CODE P59 P57 SAFETY.FLT
0 0 No Abnormal Condition 0 0 Unit Stopped - Ready To Start 0 0 No Abnormal Condition
1 1 Real-Time Clock Failure 1 1 Unit Stopped - Local Shutdown 1 1 Evaporator - Low Pressure
2 2 Default Setpoints Loaded 2 2 Unit Stopped - Remote Shutdown 2 2 Evaporator - Transducer Or Leaving Liquid Probe
3 3 Evaporator Or Condenser Transducer Error 3 3 Unit Stopped - Warning Active 3 3 Evaporator - Temperature Transducer
4 4 Evaporator - Low Pressure Limit 4 4 Unit Stopped - Cycling Shutdown 4 4 Condenser - High Pressure Contacts Open
5 5 Condenser - High Pressure Limit 5 5 Unit Stopped - Safety Shutdown 5 5 Condenser - High Pressure
10 10 Purge - High Pressure 6 6 Unit Start Inhibit 6 6 Condenser - Pressure Transducer Out Of Range
11 11 Purge - Float Switch Error 7 7 Unit Starting 7 7 Auxiliary Safety - Contacts Closed
12 12 Purge - Excess Purge 8 8 Unit Running - No Abnormal Condition 8 8 Discharge - Low Temperature
14 14 Motor - High Current Limit 9 9 Unit Running - Warning Active 9 9 Discharge - High Temperature
15 15 Vanes Uncalibrated 10 10 Unit Running - Chiller Unload Before Shutdown 10 10 Oil - High Temperature
16 16 Vanes Uncalibrated - Fixed Speed Operation 11 11 Unit Coastdown 11 11 Oil - Low Differential Pressure
17 17 Harmonic Filter - Operation Inhibited 12 12 Oil - High Differential Pressure
18 18 Harmonic Filter - Data Loss 21 21 Control Panel - Power Failure
19 19 Harmonic Filter - Input Frequency Out Of Range 23 23 Motor Or Starter - Current Imbalance
26 26 External I/O Board Serial Communications 29 29 VSD - High Heatsink Temperature
30 30 VSD - 105% Motor Current Overload
31 31 VSD - High Phase A Inverter Heatsink Temperature
32 32 VSD - High Phase B Inverter Heatsink Temperature
33 33 VSD - High Phase C Inverter Heatsink Temperature
34 34 VSD - High Converter Heatsink Temperature
35 35 VSD - Precharge Lockout
36 36 Harmonic Filter - High Heatsink Temperature
37 37 Harmonic Filter - High Total Demand Distortion
49 49 Starter - Invalid Motor Selection
51 51 Evaporator - Low Pressure
52 52 Evaporator - Low Pressure - Smart Freeze
Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 11
1/16/2008
ENG ASCII YTM Cycling Code ENG ASCII YTM Cycling Code
PAGE PAGE PAGE PAGE (continued)
P60 P58 CYCLING.CODE P60 P58 CYCLING.CODE
0 0 No Abnormal Condition 46 46 Harmonic Filter - High Phase C Instantaneous Current
1 1 Multi-Unit Cycling - Contacts Open 47 47 Harmonic Filter - Phase Locked Loop
2 2 System Cycling - Contacts Open 48 48 Harmonic Filter - Precharge - Low DC Bus Voltage
4 4 Oil - Low Temperature 49 49 Harmonic Filter - Low DC Bus Voltage
5 5 Control Panel - Power Failure 50 50 Harmonic Filter - DC Bus Voltage Imbalance
6 6 Leaving Chilled Liquid - Low Temperature 51 51 Harmonic Filter - 110% Input Current Overload
7 7 Leaving Chilled Liquid - Flow Switch Open 52 52 Harmonic Filter - Logic Board Power Supply
8 8 Condenser - Flow Switch Open 53 53 Harmonic Filter - Run Signal
9 9 Motor Controller - Contacts Open 54 54 Harmonic Filter - DC Current Transformer 1
10 10 Motor Controller - Loss Of Current 55 55 Harmonic Filter - DC Current Transformer 2
11 11 Power Fault
12 12 Control Panel - Schedule
13 13 Starter - Low Supply Line Voltage
14 14 Starter - High Supply Line Voltage
17 17 VSD Initialization Failure
18 18 VSD Shutdown - Requesting Fault Data
19 19 VSD - High Phase A Instantaneous Current
20 20 VSD - High Phase B Instantaneous Current
21 21 VSD - High Phase C Instantaneous Current
22 22 VSD - Phase A Gate Driver
23 23 VSD - Phase B Gate Driver
24 24 VSD - Phase C Gate Driver
25 25 VSD - Single Phase Input Power
26 26 VSD - High DC Bus Voltage
27 27 VSD - Logic Board Power Supply
28 28 VSD - Low DC Bus Voltage 73 73 VSD - Serial Communications
29 29 VSD - DC Bus Voltage Imbalance
30 30 VSD - High Internal Ambient Temperature
31 31 VSD - Invalid Current Scale Selection
32 32 VSD - Low Phase A Inverter Heatsink Temperature
33 33 VSD - Low Phase B Inverter Heatsink Temperature
34 34 VSD - Low Phase C Inverter Heatsink Temperature
35 35 VSD - Low Converter Heatsink Temperature
36 36 VSD - Precharge - DC Bus Voltage Imbalance
37 37 VSD - Precharge - Low DC Bus Voltage
38 38 VSD - Logic Board Processor
39 39 VSD - Run Signal
40 40 VSD - Serial Communications
41 41 VSD - Stop Contacts Open
42 42 Harmonic Filter - Logic Board Or Communications
43 43 Harmonic Filter - High DC Bus Voltage
44 44 Harmonic Filter - High Phase A Instantaneous Current
45 45 Harmonic Filter - High Phase B Instantaneous Current
Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 12