YT OptiView w/ Standard Starter ELINK/MG YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Date YORK P N Checksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC (ASCII not available with E-LINK)

ENG ASCII GPIC York Talk LON LON N2 ENG


PAGE PAGE Object Point Profile  SNVT Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Name  Type POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 AV.1 A. Control nviCoolSetPt SNVT_temp_p ADF 1 Leaving Chilled Liquid Setpoint - Selected S P03
P04 P02 AV.2 A. Control nivCapacityLimit SNVT_temp_p ADF 2 Motor Current Limit Setpoint - Selected S P04
P05 P03 A A. Control ADF 3 P05
P06 P04 A A. Control ADF 4 S P06
P07 P05 BV.1 D. Control nviChillerEnable SNVT_switch BD 1 Remote Start/Stop [Stop / Start] P07
P08 P06 D. Control BD 2 P08
P09 P07 D. Control BD 3 P09
P10 P08 B D. Control BD 4 P10
P11 P09 AI.1 A. Monitor nvoLvgCHWTemp SNVT_temp_p ADF 5 Leaving Chilled Liquid Temperature S P11
P12 P10 AI.2 A. Monitor nvoEntCHWTemp SNVT_temp_p ADF 6 Return Chilled Liquid Temperature S P12
P13 P11 AI.5 A. Monitor nvoEvapPress SNVT_press_p ADF 7 Evaporator Pressure S P13
P14 P12 AI.6 A. Monitor nvoCondPress SNVT_press_p ADF 8 Condenser Pressure S P14
P15 P13 AV.14 A. Monitor nvoOilDiffPress SNVT_press_p ADF 9 Oil Pressure Differential S P15
P16 P14 AI.4 A. Monitor nvoEntCNDTemp SNVT_temp_p ADF 10 Return Condenser Liquid Temperature S P16
P17 P15 AI.3 A. Monitor nvoLvgCNDTemp SNVT_temp_p ADF 11 Leaving Condenser Liquid Temperature S P17
P18 P16 AI.11 A. Monitor nvoActualCapacity SNVT_lev_percent ADF 12 Motor Current Percent FLA P18
P19 P17 A. Monitor ADF 13 P19
P20 P18 A. Monitor ADF 14 P20
P21 P19 A. Monitor ADF 15 P21
P22 P20 A. Monitor ADF 16 P22
P23 P21 A. Monitor ADF 17 P23
P24 P22 A. Monitor ADF 18 P24
P25 P23 AV.1 A. Monitor nvoActiveSetpt SNVT_temp_p ADF 19 Leaving Chilled Liquid Setpoint - Selected S P25
P26 P24 AV.20 A. Monitor nvoCapacityLimit SNVT_temp_p ADF 20 Motor Current Limit Setpoint - Selected S P26
P27 P25 AV.6 A. Monitor nvoEvapSatTemp SNVT_temp_p ADF 21 Evaporator Saturation Temp S P27
P28 P26 AV.7 A. Monitor nvoCondSatTemp SNVT_temp_p ADF 22 Condenser Saturation Temp S P28
P29 P27 AI.7 A. Monitor nvoDischTemp SNVT_temp_p ADF 23 Discharge Temperature S P29
P30 P28 AI.32 A. Monitor nvoOilTemp SNVT_temp_p ADF 24 Oil Sump Temperature S P30
P31 P29 AI.36 A. Monitor n/a n/a ADF 25 Purge Pressure S P31
P32 P30 AV.15 A. Monitor nvoRunHours SNVT_time_hours ADF 26 Unit Operating Hours S P32
P33 P31 AV.16 A. Monitor nvoSystemStarts SNVT_count ADF 27 Unit System Starts S P33
P34 P32 A A. Monitor ADF 28 P34
P35 P33 A A. Monitor ADF 29 P35
P36 P34 BO.1 D. Monitor nvoOnOff SNVT_switch BD 5 Motor Run Contacts S P36
P37 P35 BO.15 D. Monitor n/a n/a BD 6 Vent Line Solenoid S P37
P38 P36 BO.2 D. Monitor nvoCHPump SNVT_switch BD 7 Chilled Liquid Pump S P38
P39 P37 BI.4 D. Monitor nvoPanelSwitch SNVT_switch BD 8 Panel Stop Switch [Start enabled / Stop] S P39
P40 P38 BI.1 D. Monitor nvoCHFlowSwitch SNVT_switch BD 9 Chilled Liquid Flow Switch S P40
P41 P39 B D. Monitor BD 10 P41
P42 P40 B D. Monitor BD 11 P42

Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 1
1/16/2008

ENG ASCII GPIC York Talk LON LON N2 ENG


PAGE PAGE Object Point Profile  SNVT Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Name  Type POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 B D. Monitor BD 12 P43
P44 P42 B D. Monitor BD 13 P44
P45 P43 B D. Monitor BD 14 P45
P46 P44 B D. Monitor BD 15 P46
P47 P45 B D. Monitor BD 16 P47
P48 P46 B D. Monitor BD 17 P48
P49 P47 B D. Monitor BD 18 P49
P50 P48 B D. Monitor BD 19 P50
P51 P49 B D. Monitor BD 20 P51
P52 P50 B D. Monitor BD 21 P52
P53 P51 B D. Monitor BD 22 P53
P54 P52 B D. Monitor BD 23 P54
P55 P53 B D. Monitor BD 24 P55
P56 P54 AV.19 Code Monitor nvoAntiRecycle SNVT_time_minute ADI 1 Anti-Recycle Time Remaining S P56
P57 P55 SC.4 Code Monitor nvoWarningCode SNVT_str_asc ADI 2 Unit Warning Fault Code S P57
P58 P56 SC.1 Code Monitor nvoOperationCode SNVT_str_asc ADI 3 Operation Code S P58
P59 P57 SC.2 Code Monitor nvoSafetyCode SNVT_str_asc ADI 4 Safety Fault Code S P59
P60 P58 SC.3 Code Monitor nvoCyclingCode SNVT_str_asc ADI 5 Cycling Fault Code S P60
P61 P59 C Code Monitor ADI 6 P61
P62 P60 C Code Monitor ADI 7 P62
P63 P61 AI.50 Code Monitor n/a n/a ADI 8 Pre Rotation Vanes Position S P63
P64 P62 C Code Monitor ADI 9 P64
P65 P63 C Code Monitor ADI 10 P65
P66 P64 A A. Monitor ADF 30 P66
P67 P65 A A. Monitor ADF 31 P67
P68 P66 A A. Monitor ADF 32 P68
P69 P67 A A. Monitor ADF 33 P69
P70 P68 A A. Monitor ADF 34 P70
P71 P69 A A. Monitor ADF 35 P71
P72 P70 A A. Monitor ADF 36 P72
P73 P71 A A. Monitor ADF 37 P73
P74 P72 A A. Monitor ADF 38 P74
P75 P73 A A. Monitor ADF 39 P75
P76 P74 A A. Monitor ADF 40 P76
P77 P75 A A. Monitor ADF 41 P77
P78 P76 A A. Monitor ADF 42 P78
P79 P77 A A. Monitor ADF 43 P79
P80 P78 B D. Monitor BD 25 P80
P81 P79 B D. Monitor BD 26 P81
P82 P80 B D. Monitor BD 27 P82
P83 P81 B D. Monitor BD 28 P83
P84 P82 B D. Monitor BD 29 P84

Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 2
1/16/2008

ENG ASCII YTM Warning Code ENG ASCII YTM Operational Code ENG ASCII YTM Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P57 P55 WARNING.FLT P58 P56 OPER.CODE P59 P57 SAFETY.FLT
0 0 No Abnormal Condition 0 0 Unit Stopped - Ready To Start 0 0 No Abnormal Condition
1 1 Real-Time Clock Failure 1 1 Unit Stopped - Local Shutdown 1 1 Evaporator - Low Pressure
2 2 Default Setpoints Loaded 2 2 Unit Stopped - Remote Shutdown 2 2 Evaporator - Transducer Or Leaving Liquid Probe
3 3 Evaporator Or Condenser Transducer Error 3 3 Unit Stopped - Warning Active 3 3 Evaporator - Temperature Transducer
4 4 Evaporator - Low Pressure Limit 4 4 Unit Stopped - Cycling Shutdown 4 4 Condenser - High Pressure Contacts Open
5 5 Condenser - High Pressure Limit 5 5 Unit Stopped - Safety Shutdown 5 5 Condenser - High Pressure
10 10 Purge - High Pressure 6 6 Unit Start Inhibit 6 6 Condenser - Pressure Transducer Out Of Range
11 11 Purge - Float Switch Error 7 7 Unit Starting 7 7 Auxiliary Safety - Contacts Closed
12 12 Purge - Excess Purge 8 8 Unit Running - No Abnormal Condition 8 8 Discharge - Low Temperature
14 14 Motor - High Current Limit 9 9 Unit Running - Warning Active 9 9 Discharge - High Temperature
15 15 Vanes Uncalibrated 10 10 Unit Running - Chiller Unload Before Shutdown 10 10 Oil - High Temperature
16 16 Vanes Uncalibrated - Fixed Speed Operation 11 11 Unit Coastdown 11 11 Oil - Low Differential Pressure
12 12 Oil - High Differential Pressure
21 21 Control Panel - Power Failure
23 23 Motor Or Starter - Current Imbalance
26 26 External I/O Board Serial Communications
49 49 Starter - Invalid Motor Selection
51 51 Evaporator - Low Pressure
52 52 Evaporator - Low Pressure - Smart Freeze

Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 3
1/16/2008

ENG ASCII YTM Cycling Code


PAGE PAGE
P60 P58 CYCLING.CODE
0 0 No Abnormal Condition
1 1 Multi-Unit Cycling - Contacts Open
2 2 System Cycling - Contacts Open
4 4 Oil - Low Temperature
5 5 Control Panel - Power Failure
6 6 Leaving Chilled Liquid - Low Temperature
7 7 Leaving Chilled Liquid - Flow Switch Open
8 8 Condenser - Flow Switch Open
9 9 Motor Controller - Contacts Open
10 10 Motor Controller - Loss Of Current
11 11 Power Fault
12 12 Control Panel - Schedule
13 13 Starter - Low Supply Line Voltage
14 14 Starter - High Supply Line Voltage

Revision: YT OptiView (Rev J_02).xls Tab: Standard Property of York International York, PA Page: 4
1/16/2008

YT OptiView w/ SSS ELINK/MG YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Date YORK P N Checksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC (ASCII not available with E-LINK)

ENG ASCII GPIC York Talk LON LON N2 ENG


PAGE PAGE Object Point Profile  SNVT Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Name  Type POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 AV.1 A. Control nviCoolSetPt SNVT_temp_p ADF 1 Leaving Chilled Liquid Setpoint - Selected S P03
P04 P02 AV.2 A. Control nivCapacityLimit SNVT_temp_p ADF 2 Motor Current Limit Setpoint - Selected S P04
P05 P03 A A. Control ADF 3 P05
P06 P04 A A. Control ADF 4 P06
P07 P05 BV.1 D. Control nviChillerEnable SNVT_switch BD 1 Remote Start/Stop [Stop / Start] S P07
P08 P06 D. Control BD 2 P08
P09 P07 D. Control BD 3 P09
P10 P08 B D. Control BD 4 P10
P11 P09 AI.1 A. Monitor nvoLvgCHWTemp SNVT_temp_p ADF 5 Leaving Chilled Liquid Temperature S P11
P12 P10 AI.2 A. Monitor nvoEntCHWTemp SNVT_temp_p ADF 6 Return Chilled Liquid Temperature S P12
P13 P11 AI.5 A. Monitor nvoEvapPress SNVT_press_p ADF 7 Evaporator Pressure S P13
P14 P12 AI.6 A. Monitor nvoCondPress SNVT_press_p ADF 8 Condenser Pressure S P14
P15 P13 AV.14 A. Monitor nvoOilDiffPress SNVT_press_p ADF 9 Oil Pressure Differential S P15
P16 P14 AI.4 A. Monitor nvoEntCNDTemp SNVT_temp_p ADF 10 Return Condenser Liquid Temperature S P16
P17 P15 AI.3 A. Monitor nvoLvgCNDTemp SNVT_temp_p ADF 11 Leaving Condenser Liquid Temperature S P17
P18 P16 AI.11 A. Monitor nvoActualCapacity SNVT_lev_percent ADF 12 Motor Current Percent FLA S P18
P19 P17 AI.16 A. Monitor nvoCurrent_A SNVT_amp ADF 13 Solid State Starter Phase A Current S P19
P20 P18 AI.17 A. Monitor nvoCurrent_B SNVT_amp ADF 14 Solid State Starter Phase B Current S P20
P21 P19 AI.18 A. Monitor nvoCurrent_C SNVT_amp ADF 15 Solid State Starter Phase C Current S P21
P22 P20 AI.13 A. Monitor nvoVoltage_A SNVT_volt ADF 16 Solid State Starter Phase A Voltage S P22
P23 P21 AI.14 A. Monitor nvoVoltage_B SNVT_volt ADF 17 Solid State Starter Phase B Voltage S P23
P24 P22 AI.15 A. Monitor nvoVoltage_C SNVT_volt ADF 18 Solid State Starter Phase C Voltage S P24
P25 P23 AV.1 A. Monitor nvoActiveSetpt SNVT_temp_p ADF 19 Leaving Chilled Liquid Setpoint - Selected S P25
P26 P24 AV.20 A. Monitor nvoCapacityLimit SNVT_temp_p ADF 20 Motor Current Limit Setpoint - Selected S P26
P27 P25 AV.6 A. Monitor nvoEvapSatTemp SNVT_temp_p ADF 21 Evaporator Saturation Temp S P27
P28 P26 AV.7 A. Monitor nvoCondSatTemp SNVT_temp_p ADF 22 Condenser Saturation Temp S P28
P29 P27 AI.7 A. Monitor nvoDischTemp SNVT_temp_p ADF 23 Discharge Temperature S P29
P30 P28 AI.32 A. Monitor nvoOilTemp SNVT_temp_p ADF 24 Oil Sump Temperature S P30
P31 P29 AI.36 A. Monitor n/a n/a ADF 25 Purge Pressure S P31
P32 P30 AV.15 A. Monitor nvoRunHours SNVT_time_hours ADF 26 Unit Operating Hours S P32
P33 P31 AV.16 A. Monitor nvoSystemStarts SNVT_count ADF 27 Unit System Starts S P33
P34 P32 A A. Monitor ADF 28 P34
P35 P33 A A. Monitor ADF 29 P35
P36 P34 BO.1 D. Monitor nvoOnOff SNVT_switch BD 5 Motor Run Contacts S P36
P37 P35 BO.15 D. Monitor n/a n/a BD 6 Vent Line Solenoid S P37
P38 P36 BO.2 D. Monitor nvoCHPump SNVT_switch BD 7 Chilled Liquid Pump S P38
P39 P37 BI.4 D. Monitor nvoPanelSwitch SNVT_switch BD 8 Panel Stop Switch [Start enabled/Stop] S P39
P40 P38 BI.1 D. Monitor nvoCHFlowSwitch SNVT_switch BD 9 Chilled Liquid Flow Switch S P40
P41 P39 B D. Monitor BD 10 P41
P42 P40 B D. Monitor BD 11 P42

Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 5
1/16/2008

ENG ASCII GPIC York Talk LON LON N2 ENG


PAGE PAGE Object Point Profile  SNVT Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Name  Type POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 B D. Monitor BD 12 P43
P44 P42 B D. Monitor BD 13 P44
P45 P43 B D. Monitor BD 14 P45
P46 P44 B D. Monitor BD 15 P46
P47 P45 B D. Monitor BD 16 P47
P48 P46 B D. Monitor BD 17 P48
P49 P47 B D. Monitor BD 18 P49
P50 P48 B D. Monitor BD 19 P50
P51 P49 B D. Monitor BD 20 P51
P52 P50 B D. Monitor BD 21 P52
P53 P51 B D. Monitor BD 22 P53
P54 P52 B D. Monitor BD 23 P54
P55 P53 B D. Monitor BD 24 P55
P56 P54 AV.19 Code Monitor nvoAntiRecycle SNVT_time_minute ADI 1 Anti-Recycle Time Remaining S P56
P57 P55 SC.4 Code Monitor nvoWarningCode SNVT_str_asc ADI 2 Unit Warning Fault Code S P57
P58 P56 SC.1 Code Monitor nvoOperationCode SNVT_str_asc ADI 3 Operation Code S P58
P59 P57 SC.2 Code Monitor nvoSafetyCode SNVT_str_asc ADI 4 Safety Fault Code S P59
P60 P58 SC.3 Code Monitor nvoCyclingCode SNVT_str_asc ADI 5 Cycling Fault Code S P60
P61 P59 C Code Monitor ADI 6 P61
P62 P60 C Code Monitor ADI 7 P62
P63 P61 AI.50 Code Monitor n/a n/a ADI 8 Pre Rotation Vanes Position S P63
P64 P62 C Code Monitor ADI 9 P64
P65 P63 C Code Monitor ADI 10 P65
P66 P64 A A. Monitor ADF 30 P66
P67 P65 A A. Monitor ADF 31 P67
P68 P66 A A. Monitor ADF 32 P68
P69 P67 A A. Monitor ADF 33 P69
P70 P68 A A. Monitor ADF 34 P70
P71 P69 A A. Monitor ADF 35 P71
P72 P70 A A. Monitor ADF 36 P72
P73 P71 A A. Monitor ADF 37 P73
P74 P72 A A. Monitor ADF 38 P74
P75 P73 A A. Monitor ADF 39 P75
P76 P74 A A. Monitor ADF 40 P76
P77 P75 A A. Monitor ADF 41 P77
P78 P76 A A. Monitor ADF 42 P78
P79 P77 A A. Monitor ADF 43 P79
P80 P78 B D. Monitor BD 25 P80
P81 P79 B D. Monitor BD 26 P81
P82 P80 B D. Monitor BD 27 P82
P83 P81 B D. Monitor BD 28 P83
P84 P82 B D. Monitor BD 29 P84

Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 6
1/16/2008

ENG ASCII YTM Warning Code ENG ASCII YTM Operational Code ENG ASCII YTM Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P57 P55 WARNING.FLT P58 P56 OPER.CODE P59 P57 SAFETY.FLT
0 0 No Abnormal Condition 0 0 Unit Stopped - Ready To Start 0 0 No Abnormal Condition
1 1 Real-Time Clock Failure 1 1 Unit Stopped - Local Shutdown 1 1 Evaporator - Low Pressure
2 2 Default Setpoints Loaded 2 2 Unit Stopped - Remote Shutdown 2 2 Evaporator - Transducer Or Leaving Liquid Probe
3 3 Evaporator Or Condenser Transducer Error 3 3 Unit Stopped - Warning Active 3 3 Evaporator - Temperature Transducer
4 4 Evaporator - Low Pressure Limit 4 4 Unit Stopped - Cycling Shutdown 4 4 Condenser - High Pressure Contacts Open
5 5 Condenser - High Pressure Limit 5 5 Unit Stopped - Safety Shutdown 5 5 Condenser - High Pressure
10 10 Purge - High Pressure 6 6 Unit Start Inhibit 6 6 Condenser - Pressure Transducer Out Of Range
11 11 Purge - Float Switch Error 7 7 Unit Starting 7 7 Auxiliary Safety - Contacts Closed
12 12 Purge - Excess Purge 8 8 Unit Running - No Abnormal Condition 8 8 Discharge - Low Temperature
14 14 Motor - High Current Limit 9 9 Unit Running - Warning Active 9 9 Discharge - High Temperature
15 15 Vanes Uncalibrated 10 10 Unit Running - Chiller Unload Before Shutdown 10 10 Oil - High Temperature
16 16 Vanes Uncalibrated - Fixed Speed Operation 11 11 Unit Coastdown 11 11 Oil - Low Differential Pressure
12 12 Oil - High Differential Pressure
21 21 Control Panel - Power Failure
23 23 Motor Or Starter - Current Imbalance
26 26 External I/O Board Serial Communications

38 38 LCSSS - Phase Loss


39 39 LCSSS - Current Imbalance
40 40 LCSSS - 105% Motor Current Overload
41 41 LCSSS - High Current
42 42 LCSSS - Open SCR
43 43 LCSSS - Shorted Phase A SCR
44 44 LCSSS - Shorted Phase B SCR
45 45 LCSSS - Shorted Phase C SCR
46 46 LCSSS - High Phase A Temperature - Running
47 47 LCSSS - High Phase B Temperature - Running
48 48 LCSSS - High Phase C temperature - Running
49 49 Starter - Invalid Motor Selection
51 51 Evaporator - Low Pressure
52 52 Evaporator - Low Pressure - Smart Freeze

Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 7
1/16/2008

ENG ASCII YTM Cycling Code


PAGE PAGE
P60 P58 CYCLING.CODE
0 0 No Abnormal Condition
1 1 Multi-Unit Cycling - Contacts Open
2 2 System Cycling - Contacts Open
4 4 Oil - Low Temperature
5 5 Control Panel - Power Failure
6 6 Leaving Chilled Liquid - Low Temperature
7 7 Leaving Chilled Liquid - Flow Switch Open
8 8 Condenser - Flow Switch Open
9 9 Motor Controller - Contacts Open
10 10 Motor Controller - Loss Of Current
11 11 Power Fault
12 12 Control Panel - Schedule
13 13 Starter - Low Supply Line Voltage
14 14 Starter - High Supply Line Voltage

56 56 LCSSS Initialization Failure


57 57 LCSSS Shutdown - Requesting Fault Data
58 58 LCSSS - Low Phase A Heatsink Temperature
59 59 LCSSS - Low Phase B Heatsink Temperature
60 60 LCSSS - Low Phase C Heatsink Temperature
61 61 LCSSS - Phase Locked Loop
62 62 LCSSS - Power Fault
63 63 LCSSS - High Supply Line Voltage
64 64 LCSSS - Low Supply Line Voltage
65 65 LCSSS - Invalid Model Selection
66 66 LCSSS - Run Signal
67 67 LCSSS - Serial Communications
68 68 LCSSS - Stop Contacts Open

70 70 LCSSS - Logic Board Processor


72 72 LCSSS - Power Fail

74 74 LCSSS - Serial Communications


75 75 LCSSS - Phase Loss

Revision: YT OptiView (Rev J_02).xls Tab: with SSS Property of York International York, PA Page: 8
1/16/2008

YT OptiView w/ VSD ELINK/MG YORK TALK 3 Micro Board: 031-01730 / 02430 -xxx
Item Version Date YORK P N Checksum Baud COMMENTS
1 C.OPT.02.09.008 19.2K
2
3
4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC (ASCII not available with E-LINK)

ENG ASCII GPIC York Talk LON LON N2 ENG


PAGE PAGE Object Point Profile  SNVT Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Name  Type POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 AV.1 A. Control nviCoolSetPt SNVT_temp_p ADF 1 Leaving Chilled Liquid Setpoint - Selected S P03
P04 P02 AV.2 A. Control nivCapacityLimit SNVT_temp_p ADF 2 Motor Current Limit Setpoint - Selected S P04
P05 P03 A A. Control ADF 3 P05
P06 P04 A A. Control ADF 4 P06
P07 P05 BV.1 D. Control nviChillerEnable SNVT_switch BD 1 Remote Start/Stop [Stop / Start] S P07
P08 P06 D. Control BD 2 P08
P09 P07 BV.10 D. Control nviVSDFixedSpd SNVT_switch BD 3 Variable Speed Drive Fixed Speed [Auto/Fixed] S P09
P10 P08 B D. Control BD 4 P10
P11 P09 AI.1 A. Monitor nvoLvgCHWTemp SNVT_temp_p ADF 5 Leaving Chilled Liquid Temperature S P11
P12 P10 AI.2 A. Monitor nvoEntCHWTemp SNVT_temp_p ADF 6 Return Chilled Liquid Temperature S P12
P13 P11 AI.5 A. Monitor nvoEvapPress SNVT_press_p ADF 7 Evaporator Pressure S P13
P14 P12 AI.6 A. Monitor nvoCondPress SNVT_press_p ADF 8 Condenser Pressure S P14
P15 P13 AV.14 A. Monitor nvoOilDiffPress SNVT_press_p ADF 9 Oil Pressure Differential S P15
P16 P14 AI.4 A. Monitor nvoEntCNDTemp SNVT_temp_p ADF 10 Return Condenser Liquid Temperature S P16
P17 P15 AI.3 A. Monitor nvoLvgCNDTemp SNVT_temp_p ADF 11 Leaving Condenser Liquid Temperature S P17
P18 P16 AI.11 A. Monitor nvoActualCapacity SNVT_lev_percent ADF 12 Motor Current Percent FLA S P18
P19 P17 AI.53 A. Monitor nvoCurrent_A SNVT_amp ADF 13 Variable Speed Drive Phase A Current S P19
P20 P18 AI.54 A. Monitor nvoCurrent_B SNVT_amp ADF 14 Variable Speed Drive Phase B Current S P20
P21 P19 AI.55 A. Monitor nvoCurrent_C SNVT_amp ADF 15 Variable Speed Drive Phase C Current S P21
P22 P20 A. Monitor ADF 16 P22
P23 P21 A. Monitor ADF 17 P23
P24 P22 A. Monitor ADF 18 P24
P25 P23 AV.1 A. Monitor nvoActiveSetpt SNVT_temp_p ADF 19 Leaving Chilled Liquid Setpoint - Selected S P25
P26 P24 AV.20 A. Monitor nvoCapacityLimit SNVT_temp_p ADF 20 Motor Current Limit Setpoint - Selected S P26
P27 P25 AV.6 A. Monitor nvoEvapSatTemp SNVT_temp_p ADF 21 Evaporator Saturation Temp S P27
P28 P26 AV.7 A. Monitor nvoCondSatTemp SNVT_temp_p ADF 22 Condenser Saturation Temp S P28
P29 P27 AI.7 A. Monitor nvoDischTemp SNVT_temp_p ADF 23 Discharge Temperature S P29
P30 P28 AI.32 A. Monitor nvoOilTemp SNVT_temp_p ADF 24 Oil Sump Temperature S P30
P31 P29 AI.36 A. Monitor n/a n/a ADF 25 Purge Pressure S P31
P32 P30 AV.15 A. Monitor nvoRunHours SNVT_time_hours ADF 26 Unit Operating Hours S P32
P33 P31 AV.16 A. Monitor nvoSystemStarts SNVT_count ADF 27 Unit System Starts S P33
P34 P32 A A. Monitor ADF 28 P34
P35 P33 A A. Monitor ADF 29 P35
P36 P34 BO.1 D. Monitor nvoOnOff SNVT_switch BD 5 Motor Run Contacts S P36
P37 P35 BO.15 D. Monitor n/a n/a BD 6 Vent Line Solenoid S P37
P38 P36 BO.2 D. Monitor nvoCHPump SNVT_switch BD 7 Chilled Liquid Pump S P38
P39 P37 BI.4 D. Monitor nvoPanelSwitch SNVT_switch BD 8 Panel Stop Switch [Start enabled / Stop] S P39
P40 P38 BI.1 D. Monitor nvoCHFlowSwitch SNVT_switch BD 9 Chilled Liquid Flow Switch S P40
P41 P39 B D. Monitor BD 10 P41
P42 P40 B D. Monitor BD 11 P42

Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 9
1/16/2008

ENG ASCII GPIC York Talk LON LON N2 ENG


PAGE PAGE Object Point Profile  SNVT Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Name  Type POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 B D. Monitor BD 12 P43
P44 P42 B D. Monitor BD 13 P44
P45 P43 B D. Monitor BD 14 P45
P46 P44 B D. Monitor BD 15 P46
P47 P45 B D. Monitor BD 16 P47
P48 P46 BV.42 D. Monitor n/a n/a BD 17 Adaptive Capacity Control Valid Surge Map (False =0, T rue =1) S P48
P49 P47 BV.43 D. Monitor n/a n/a BD 18 Adaptive Capacity Control New Surge Point (False =0, T rue =1) S P49
P50 P48 BO.30 D. Monitor n/a n/a BD 19 Variable Speed Drive Water Pump Relay S P50
P51 P49 BV.46 D. Monitor n/a n/a BD 20 Harmonic Filter Installed (False =0, True =1) S P51
P52 P50 BV.44 D. Monitor n/a n/a BD 21 Adaptive Capacity Control Surge T ype (Open = Delta P/P, Made=Curren S P52
P53 P51 B D. Monitor BD 22 P53
P54 P52 B D. Monitor BD 23 P54
P55 P53 B D. Monitor BD 24 P55
P56 P54 AV.19 Code Monitor nvoAntiRecycle SNVT_time_minute ADI 1 Anti-Recycle Time Remaining S P56
P57 P55 SC.4 Code Monitor nvoWarningCode SNVT_str_asc ADI 2 Unit Warning Fault Code S P57
P58 P56 SC.1 Code Monitor nvoOperationCode SNVT_str_asc ADI 3 Operation Code S P58
P59 P57 SC.2 Code Monitor nvoSafetyCode SNVT_str_asc ADI 4 Safety Fault Code S P59
P60 P58 SC.3 Code Monitor nvoCyclingCode SNVT_str_asc ADI 5 Cycling Fault Code S P60
P61 P59 AI.58 Code Monitor n/a n/a ADI 6 Variable Speed Drive Internal Ambient Temperature S P61
P62 P60 AI.59 Code Monitor n/a n/a ADI 7 Variable Speed Drive Converter Heatsink Temperature S P62
P63 P61 AI.50 Code Monitor n/a n/a ADI 8 Pre Rotation Vanes Position S P63
P64 P62 AV.78 Code Monitor n/a n/a ADI 9 Adaptive Capacity Control Map Output Frequency S P64
P65 P63 C Code Monitor ADI 10 P65
P66 P64 A A. Monitor ADF 30 P66
P67 P65 A A. Monitor ADF 31 P67
P68 P66 A A. Monitor ADF 32 P68
P69 P67 AV.79 A. Monitor n/a n/a ADF 33 Adaptive Capacity Control Map PRV Position S P69
P70 P68 AI.51 A. Monitor n/a n/a ADF 34 Variable Speed Drive OutputVoltage S P70
P71 P69 AV.71 A. Monitor n/a n/a ADF 35 Variable Speed Drive Input Power S P71
P72 P70 AV.72 A. Monitor n/a n/a ADF 36 Variable Speed Drive Killowatt Hours S P72
P73 P71 AI.56 A. Monitor n/a n/a ADF 37 Variable Speed Drive DC Bus Voltage S P73
P74 P72 AI.57 A. Monitor n/a n/a ADF 38 Variable Speed Drive Inverter Link Current S P74
P75 P73 AV.75 A. Monitor n/a n/a ADF 39 Adaptive Capacity Control Surge Count S P75
P76 P74 AI.52 A. Monitor nvoVSDOutFreq SNVT_freq_hz ADF 40 Variable Speed Drive Output Frequency S P76
P77 P75 AV.83 A. Monitor n/a n/a ADF 41 Harmonic Filter Maximum Voltage T otal Harmonic Distortion S P77
P78 P76 AV.84 A. Monitor n/a n/a ADF 42 Harmonic Filter Maximum Current T otal Demand Distortion S P78
P79 P77 AV.82 A. Monitor n/a n/a ADF 43 Harmonic Filter T otal Supply KVA S P79
P80 P78 B D. Monitor BD 25 P80
P81 P79 B D. Monitor BD 26 P81
P82 P80 B D. Monitor BD 27 P82
P83 P81 B D. Monitor BD 28 P83
P84 P82 B D. Monitor BD 29 P84

Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 10
1/16/2008

ENG ASCII YTM Warning Code ENG ASCII YTM Operational Code ENG ASCII YTM Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P57 P55 WARNING.FLT P58 P56 OPER.CODE P59 P57 SAFETY.FLT
0 0 No Abnormal Condition 0 0 Unit Stopped - Ready To Start 0 0 No Abnormal Condition
1 1 Real-Time Clock Failure 1 1 Unit Stopped - Local Shutdown 1 1 Evaporator - Low Pressure
2 2 Default Setpoints Loaded 2 2 Unit Stopped - Remote Shutdown 2 2 Evaporator - Transducer Or Leaving Liquid Probe
3 3 Evaporator Or Condenser Transducer Error 3 3 Unit Stopped - Warning Active 3 3 Evaporator - Temperature Transducer
4 4 Evaporator - Low Pressure Limit 4 4 Unit Stopped - Cycling Shutdown 4 4 Condenser - High Pressure Contacts Open
5 5 Condenser - High Pressure Limit 5 5 Unit Stopped - Safety Shutdown 5 5 Condenser - High Pressure
10 10 Purge - High Pressure 6 6 Unit Start Inhibit 6 6 Condenser - Pressure Transducer Out Of Range
11 11 Purge - Float Switch Error 7 7 Unit Starting 7 7 Auxiliary Safety - Contacts Closed
12 12 Purge - Excess Purge 8 8 Unit Running - No Abnormal Condition 8 8 Discharge - Low Temperature
14 14 Motor - High Current Limit 9 9 Unit Running - Warning Active 9 9 Discharge - High Temperature
15 15 Vanes Uncalibrated 10 10 Unit Running - Chiller Unload Before Shutdown 10 10 Oil - High Temperature
16 16 Vanes Uncalibrated - Fixed Speed Operation 11 11 Unit Coastdown 11 11 Oil - Low Differential Pressure
17 17 Harmonic Filter - Operation Inhibited 12 12 Oil - High Differential Pressure
18 18 Harmonic Filter - Data Loss 21 21 Control Panel - Power Failure
19 19 Harmonic Filter - Input Frequency Out Of Range 23 23 Motor Or Starter - Current Imbalance
26 26 External I/O Board Serial Communications 29 29 VSD - High Heatsink Temperature
30 30 VSD - 105% Motor Current Overload
31 31 VSD - High Phase A Inverter Heatsink Temperature
32 32 VSD - High Phase B Inverter Heatsink Temperature
33 33 VSD - High Phase C Inverter Heatsink Temperature
34 34 VSD - High Converter Heatsink Temperature
35 35 VSD - Precharge Lockout
36 36 Harmonic Filter - High Heatsink Temperature
37 37 Harmonic Filter - High Total Demand Distortion
49 49 Starter - Invalid Motor Selection
51 51 Evaporator - Low Pressure
52 52 Evaporator - Low Pressure - Smart Freeze

Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 11
1/16/2008

ENG ASCII YTM Cycling Code ENG ASCII YTM Cycling Code
PAGE PAGE PAGE PAGE (continued)
P60 P58 CYCLING.CODE P60 P58 CYCLING.CODE
0 0 No Abnormal Condition 46 46 Harmonic Filter - High Phase C Instantaneous Current
1 1 Multi-Unit Cycling - Contacts Open 47 47 Harmonic Filter - Phase Locked Loop
2 2 System Cycling - Contacts Open 48 48 Harmonic Filter - Precharge - Low DC Bus Voltage
4 4 Oil - Low Temperature 49 49 Harmonic Filter - Low DC Bus Voltage
5 5 Control Panel - Power Failure 50 50 Harmonic Filter - DC Bus Voltage Imbalance
6 6 Leaving Chilled Liquid - Low Temperature 51 51 Harmonic Filter - 110% Input Current Overload
7 7 Leaving Chilled Liquid - Flow Switch Open 52 52 Harmonic Filter - Logic Board Power Supply
8 8 Condenser - Flow Switch Open 53 53 Harmonic Filter - Run Signal
9 9 Motor Controller - Contacts Open 54 54 Harmonic Filter - DC Current Transformer 1
10 10 Motor Controller - Loss Of Current 55 55 Harmonic Filter - DC Current Transformer 2
11 11 Power Fault
12 12 Control Panel - Schedule
13 13 Starter - Low Supply Line Voltage
14 14 Starter - High Supply Line Voltage
17 17 VSD Initialization Failure
18 18 VSD Shutdown - Requesting Fault Data
19 19 VSD - High Phase A Instantaneous Current
20 20 VSD - High Phase B Instantaneous Current
21 21 VSD - High Phase C Instantaneous Current
22 22 VSD - Phase A Gate Driver
23 23 VSD - Phase B Gate Driver
24 24 VSD - Phase C Gate Driver
25 25 VSD - Single Phase Input Power
26 26 VSD - High DC Bus Voltage
27 27 VSD - Logic Board Power Supply
28 28 VSD - Low DC Bus Voltage 73 73 VSD - Serial Communications
29 29 VSD - DC Bus Voltage Imbalance
30 30 VSD - High Internal Ambient Temperature
31 31 VSD - Invalid Current Scale Selection
32 32 VSD - Low Phase A Inverter Heatsink Temperature
33 33 VSD - Low Phase B Inverter Heatsink Temperature
34 34 VSD - Low Phase C Inverter Heatsink Temperature
35 35 VSD - Low Converter Heatsink Temperature
36 36 VSD - Precharge - DC Bus Voltage Imbalance
37 37 VSD - Precharge - Low DC Bus Voltage
38 38 VSD - Logic Board Processor
39 39 VSD - Run Signal
40 40 VSD - Serial Communications
41 41 VSD - Stop Contacts Open
42 42 Harmonic Filter - Logic Board Or Communications
43 43 Harmonic Filter - High DC Bus Voltage
44 44 Harmonic Filter - High Phase A Instantaneous Current
45 45 Harmonic Filter - High Phase B Instantaneous Current

Revision: YT OptiView (Rev J_02).xls Tab: with VSD Property of York International York, PA Page: 12