YIA IsoFlow Micro Panel II (Version 1 Protocol) York Talk 2 Microgateway / Elink Micro Board: 031-01065-xxx
Item Ref. Version Date YORK P N Checksum Baud COMMENTS
1 A.02F.00 07/30/93 031-01417-001 95FC 1200 First Production Release of Isoflow Software
2 A.02F.01.500.00 10/15/93 031-01417-001 3534 1200 Field Trial Release 0 - First German Language Version
3
4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC

ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 A. Control LCHW_TEMP.SP ADF 1 Leaving Chilled Water Setpoint S S P03
P04 P02 A. Control ADF 2 Remote Load Limit Setpoint S S P04
P05 P03 A. Control RMT_LOAD.SP ADF 3 N N P05
P06 P04 A. Control ADF 4 P06
P07 P05 D. Control START BD 1 Start / Stop S S P07
P08 P06 D. Control HISTORY BD 2 Display History Service Buffer #1 (0=No, 1=Yes) S S P08
P09 P07 D. Control BD 3 P09
P10 P08 D. Control BD 4 P10
P11 P09 A. Monitor LCHW.TEMP 8 - 11 ADF 5 Leaving Chilled Water Temperature S S P11
P12 P10 A. Monitor ECHW.TEMP 12 - 15 ADF 6 Entering Chilled Water Temperature S S P12
P13 P11 A. Monitor GEN_SH.PRESS 16 - 19 ADF 7 Leaving Condenser Water Temperature S S P13
P14 P12 A. Monitor 20 - 23 ADF 8 Entering Condenser Water Temperature S S P14
P15 P13 A. Monitor 24 - 27 ADF 9 Refrigerant Temperature S S P15
P16 P14 A. Monitor ECDW.TEMP 28 - 31 ADF 10 Strong Solution Temperature S S P16
P17 P15 A. Monitor LCDW.TEMP 32 - 35 ADF 11 Steam / Hot Water Supply Temperature S S P17
P18 P16 A. Monitor ADECRYS.TEMP 36 - 39 ADF 12 Automatic Decrystallization Temperature S S P18
P19 P17 A. Monitor CONDREF.TEMP 40 - 43 ADF 13 Refrigerant Temperature Leaving the Condenser S S P19
P20 P18 A. Monitor STM/HW.TEMP 44 - 47 ADF 14 Generator Shell Pressure S S P20
P21 P19 A. Monitor STMSUP.PRESS 48 - 51 ADF 15 Steam Supply Pressure (steam units only) O O P21
P22 P20 A. Monitor SUP_VALV.POS 52 - 55 ADF 16 Steam / Hot Water Actuator Valve Position (0-100%) S S P22
P23 P21 A. Monitor LOC_LCHW.SP 56 - 59 ADF 17 Total Operating Hours S S P23
P24 P22 A. Monitor PP_SERINT.SP 60 - 63 ADF 18 Total System Starts S S P24
P25 P23 A. Monitor LCHW_ACT.SP 64 - 67 ADF 19 Lifetime Purge Count S S P25
P26 P24 A. Monitor 68 - 71 ADF 20 Weekly Purge Counter S S P26
P27 P25 A. Monitor REFRIG.TEMP 72 - 75 ADF 21 Pulldown Demand - Minutes Left S S P27
P28 P26 A. Monitor STG_SOL.TEMP 76 - 79 ADF 22 Pulldown Demand - Present Limit S S P28
P29 P27 A. Monitor 80 - 83 ADF 23 P29
P30 P28 A. Monitor 84 - 87 ADF 24 P30
P31 P29 A. Monitor 88 - 91 ADF 25 P31
P32 P30 A. Monitor RUN.HOURS 92 - 95 ADF 26 Total Operating Hours N N P32
P33 P31 A. Monitor START.COUNT 96 - 99 ADF 27 Total System Starts N N P33
P34 P32 A. Monitor LTPRGE.COUNT 100 - 103 ADF 28 Lifetime Purge Count N N P34
P35 P33 A. Monitor 104 - 107 ADF 29 P35
P36 P34 D. Monitor REFPUMP.STAT 108 BD 5 Chilled Water Pump Status (0=Off, 1=On) S S P36
P37 P35 D. Monitor CDWPUMP.STAT 109 BD 6 Condenser Water Pump Status (0=Off, 1=On) S S P37
P38 P36 D. Monitor CHWPUMP.STAT 110 BD 7 Refrigerant Pump Motor Status (0=Off, 1=On) S S P38
P39 P37 D. Monitor STARTSW.STAT 111 BD 8 Solution / Absorber Pump Motor Status (0=Off, 1=On) S S P39
P40 P38 D. Monitor SPMPSOL.STAT 112 BD 9 Purge Pump Motor Status (0=Off, 1=On) S S P40
P41 P39 D. Monitor SOLPMP.STAT 113 BD 10 Generator Pump Motor Status (0=Off, 1=On) O O P41
P42 P40 D. Monitor GENPUMP.STAT 114 BD 11 Refrigerant & Solutn Pump Mtr Coolant Solnd Valve Status S S P42

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 1 (1993) Property of York International York, PA Page: 1
2/26/2009

ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive
Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 D. Monitor PRGPUMP.STAT 115 BD 12 Refrigerant Stabilizer Solenoid Valve Status (0=Off, 1=On) S S P43
P44 P42 D. Monitor CHWFLSW.STAT 116 BD 13 Refrigerant Level Solenoid Valve Status (0=Off, 1=On) S S P44
P45 P43 D. Monitor STABSOL.STAT 117 BD 14 Chilled Water Flow Switch Status (0=Open, 1=Closed) S S P45
P46 P44 D. Monitor CDWFLSW.STAT 118 BD 15 Condenser Water Flow Switch Status (0=Open, 1=Closed) S S P46
P47 P45 D. Monitor DIL_CYC.STAT 119 BD 16 Refrigerant Level Float Switch Status (0=Open, 1=Closed) S S P47
P48 P46 D. Monitor RLEVFSW.STAT 120 BD 17 Unit Switch Status (0=Stop, 1=Run) S S P48
P49 P47 D. Monitor J50.STAT 121 BD 18 J50 Status (0=Auto Restart, 1=Manual Restart) S S P49
P50 P48 D. Monitor J51.STAT 122 BD 19 J51 Status (0=Loding Ovrdes Active, 1=No Loading Overrides) S S P50
P51 P49 D. Monitor J52.STAT 123 BD 20 J52 Status (0=English Units, 1=Metric Units) S S P51
P52 P50 D. Monitor J54.STAT 124 BD 21 J53 Status (NA) S S P52
P53 P51 D. Monitor J55.STAT 125 BD 22 J54 Status (0=Limited CW Pump Cntrl, 1=Full CW Pump Cntrl) S S P53
P54 P52 D. Monitor J57.STAT 126 BD 23 J55 Status (0=Diagnostics Enabled, 1=Diagnostics Disabled) S S P54
P55 P53 D. Monitor J12.STAT 127 BD 24 J57 Status (0=RTC Disabled, 1=RTC Enabled) S S P55
P56 P54 Code Monitor DIL_CYC.CODE 128 ADI 1 Operating Mode (0=Service, 1=Local, 2=Remote) S S P56
P57 P55 Code Monitor OPR_MOD.CODE 129 ADI 2 Operational Code S S P57
P58 P56 Code Monitor OPER.CODE 130 ADI 3 Safety Shutdown Code S S P58
P59 P57 Code Monitor SAFETY.CODE 131 ADI 4 Cycling Shutdown Code S S P59
P60 P58 Code Monitor CYCLING.CODE 132 ADI 5 Warning Message Code S S P60
P61 P59 Code Monitor WARN.CODE 133 ADI 6 N N P61
P62 P60 Code Monitor 134 ADI 7 P62
P63 P61 Code Monitor 135 ADI 8 P63
P64 P62 Code Monitor 136 ADI 9 P64
P65 P63 Code Monitor 137 ADI 10 P65
P66 P64 A. Monitor RMT_LOAD.SP 138 - 141 ADF 30 Local Leaving Chilled Water Setpoint S S P66
P67 P65 A. Monitor VLVMAXLD.SP 142 - 145 ADF 31 Active Leaving Chilled Water Setpoint S S P67
P68 P66 A. Monitor WKPRGE.COUNT 146 - 149 ADF 32 Purge Pump Service Interval Setpoint - Hours S S P68
P69 P67 A. Monitor PD_LIM.SP 150 - 153 ADF 33 Pulldown Demand Setpoint - Minutes S S P69
P70 P68 A. Monitor PD_DMD.MIN 154 - 157 ADF 34 Pulldown Demand Setpoint - Start Load Limit S S P70
P71 P69 A. Monitor PD_START.SP 158 - 161 ADF 35 Pulldown Demand Setpoint - Stop Load Limit S S P71
P72 P70 A. Monitor PD_STOP.SP 162 - 165 ADF 36 Remote Temp Range Setpoint S S P72
P73 P71 A. Monitor PD_DMD.LIM 166 - 169 ADF 37 Remote Loading Setpoint S S P73
P74 P72 A. Monitor REMT_RNG.SP 170 - 173 ADF 38 Maximum Load Setpoint S S P74
P75 P73 A. Monitor VLVMAXUNL.SP 174 - 177 ADF 39 Maximum Entering Condenser Water Temperature Setpoint S S P75
P76 P74 A. Monitor ECDW_MAX.SP 178 - 181 ADF 40 Maximum Entering Condenser Water Temperature Setpoint N N P76
P77 P75 A. Monitor JP1.STAT 182 - 185 ADF 41 JP1 Status (0=Steam Operation, 1=Hot Water Operation) N N P77
P78 P76 A. Monitor JP3.STAT 186 - 189 ADF 42 JP3 Status (0=Stndrd Model, 1=50 Hz Mdl YIA10E3 - YIA14F3) N N P78
P79 P77 A. Monitor JP1_EXP.STAT 190 - 193 ADF 43 JP1 (Expansion I/O Board) (0= Roatry valve, 1 = Cage valve) N N P79
P80 P78 D. Monitor RLEVSOL.STAT 194 BD 25 JP1 Status (0=Steam Operation, 1=Hot Water Operation) S S P80
P81 P79 D. Monitor SST_LMT.STAT 195 BD 26 JP3 Status (0=Stndrd Model, 1=50 Hz Mdl YIA10E3 - YIA14F3) S S P81
P82 P80 D. Monitor ADECRYS.STAT 196 BD 27 Automatic Decrystallization Active (0=No, 1 = Yes) N N P82
P83 P81 D. Monitor RMTLOAD.STAT 197 BD 28 Remote Load Limiting Active ( 0= No, 1 = Yes) N N P83
P84 P82 D. Monitor PD_LMT.STAT 198 BD 29 Pulldown Limiting Active ( 0= No, 1 = Yes) N N P84

NOTE: The Appropriate Product Code Listing Summary Should Accompany Document

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 1 (1993) Property of York International York, PA Page: 2
2/26/2009

ENG ASCII YI Operational Code ENG ASCII YI Cycling Code


PAGE PAGE PAGE PAGE
P57 P55 OPER.CODE P59 P57 CYCLING.CODE
0 0 No Abnormal Condition 0 0 No Abnormal Condition
1 1 Lockout Delay Active 1 1 Power Failure (Auto-Restart Mode)
2 2 Dilution Cycle Active 2 2 Condenser Water Flow Switch Open
3 3 Unit Stopped - Unit Switch in Stop/Reset position 3 3 Low Water Temperature
4 4 Unit Stopped - Safety Shutdown 4 4 Daily Schedule Shutdown
5 5 Unit Stopped - Cycling Shutdown 5 5 Steam Valve Loaded Above 10%
6 6 Unit Stopped - Remote Shutdown 6 6 Remote / Local System Cycling Shutdown
7 7 Unit Starting 7 7 Multi-Unit Cycling Shutdown
8 8 Unit Running - Strong Solution Temp Limit
9 9 Unit Running - Automatic Decrystallization Active
10 10 Unit Running - Remote Load Limit
11 11 Unit Running - Pulldown Limiting Active

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 1 (1993) Property of York International York, PA Page: 3
2/26/2009

ENG ASCII YI Safety Code ENG ASCII YI Warning Code


PAGE PAGE PAGE PAGE
P58 P56 SAFETY.CODE P60 P58 WARN.CODE
0 0 No Abnormal Condition 0 0 No Abnormal Condition
1 1 Crystallization Lockout - Power Failure 1 1 Low Refrigerant Temperature
2 2 Crystallization Lockout - Pump Overload 2 2 High Generator Shell Pressure
3 3 Crystallization Lockout - Chilled Water Flow Switch 3 3 High Steam / Hot Water Supply Temperature
4 4 Crystallization Lockout - Cond Water Flow Switch 4 4 High Steam Supply Pressure
5 5 Crystallization Lockout - Low Refrigerant Temp 5 5 High Entering Condenser Water Temperature
6 6 Crystallization Lockout - Motor Coolant Float Switch 6 6 Faulty Strong Solution Temperature Sensor
7 7 Power Failure (Manual Restart Mode) 7 7 Purge Pump Overloads Open
8 8 Chilled Water Float Switch Open 8 8 Purge Pump Service Recommended
9 9 Solution / Absorber Pump Overloads Open
10 10 Refrigerant Pump Overloads Open
11 11 Generator Pump Overloads Open
12 12 Solution / Refrigerant Motor Coolant Switch Open
13 13 High Steam / Hot Water High Temperature
14 14 High Steam Supply Pressure
15 15 High Generator Shell Pressure
16 16 High Generator Shell Temperature
17 17 Low Refrigerant Temperature
18 18 Auxiliary Safety Shutdown

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 1 (1993) Property of York International York, PA Page: 4
2/26/2009

YIA IsoFlow Micro Panel II (Version 2 Protocol) York Talk 2 Microgateway / Elink Micro Board: 031-01065-xxx
Item Ref. Version Date YORK P N Checksum Baud COMMENTS
1 A.02F.01.500.01 03/29/94 031-01417-001 12EA 1200 Field Trial Release 1
2 A.02F.01.500.02 06/22/94 031-01417-001 C777 1200 Field Trial Release 2
3 A.02F.01.500.03 10/26/94 031-01417-001 9A8E 1200 Field Trial Release 3
4 A.02F.01.500.04 12/21/94 031-01417-001 ACB4 1200 Field Trial Release 4
5
6
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC

ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 A. Control LCHW_TEMP.SP ADF 1 Leaving Chilled Water Setpoint S S S S P03
P04 P02 A. Control ADF 2 P04
P05 P03 A. Control RMT_LOAD.SP ADF 3 Remote Load Limit Setpoint S S S S P05
P06 P04 A. Control ADF 4 P06
P07 P05 D. Control START BD 1 Start / Stop S S S S P07
P08 P06 D. Control HISTORY BD 2 Display History Service Buffer #1 (0=No, 1=Yes) S S S S P08
P09 P07 D. Control BD 3 P09
P10 P08 D. Control BD 4 P10
P11 P09 A. Monitor LCHW.TEMP 8 - 11 ADF 5 Leaving Chilled Water Temperature S S S S P11
P12 P10 A. Monitor ECHW.TEMP 12 - 15 ADF 6 Entering Chilled Water Temperature S S S S P12
P13 P11 A. Monitor GEN_SH.PRESS 16 - 19 ADF 7 Generator Shell Pressure S S S S P13
P14 P12 A. Monitor 20 - 23 ADF 8 P14
P15 P13 A. Monitor 24 - 27 ADF 9 P15
P16 P14 A. Monitor ECDW.TEMP 28 - 31 ADF 10 Entering Condenser Water Temperature S S S S P16
P17 P15 A. Monitor LCDW.TEMP 32 - 35 ADF 11 Leaving Condenser Water Temperature S S S S P17
P18 P16 A. Monitor ADECRYS.TEMP 36 - 39 ADF 12 Automatic Decrystallization Temperature S S S S P18
P19 P17 A. Monitor CONDREF.TEMP 40 - 43 ADF 13 Refrigerant Temperature Leaving the Condenser S S S S P19
P20 P18 A. Monitor STM/HW.TEMP 44 - 47 ADF 14 Steam / Hot Water Supply Temperature S S S S P20
P21 P19 A. Monitor STMSUP.PRESS 48 - 51 ADF 15 Steam Supply Pressure (steam units only) O O O O P21
P22 P20 A. Monitor SUP_VALV.POS 52 - 55 ADF 16 Steam / Hot Water Actuator Valve Position (0-100%) S S S S P22
P23 P21 A. Monitor LOC_LCHW.SP 56 - 59 ADF 17 Local Leaving Chilled Water Setpoint S S S S P23
P24 P22 A. Monitor PP_SERINT.SP 60 - 63 ADF 18 Purge Pump Service Interval Setpoint - Hours S S S S P24
P25 P23 A. Monitor LCHW_ACT.SP 64 - 67 ADF 19 Active Leaving Chilled Water Setpoint S S S S P25
P26 P24 A. Monitor 68 - 71 ADF 20 P26
P27 P25 A. Monitor REFRIG.TEMP 72 - 75 ADF 21 Refrigerant Temperature S S S S P27
P28 P26 A. Monitor STG_SOL.TEMP 76 - 79 ADF 22 Strong Solution Temperature S S S S P28
P29 P27 A. Monitor 80 - 83 ADF 23 P29
P30 P28 A. Monitor 84 - 87 ADF 24 P30
P31 P29 A. Monitor 88 - 91 ADF 25 P31
P32 P30 A. Monitor RUN.HOURS 92 - 95 ADF 26 Total Operating Hours S S S S P32
P33 P31 A. Monitor START.COUNT 96 - 99 ADF 27 Total System Starts S S S S P33
P34 P32 A. Monitor LTPRGE.COUNT 100 - 103 ADF 28 Lifetime Purge Count S S S S P34
P35 P33 A. Monitor 104 - 107 ADF 29 P35
P36 P34 D. Monitor REFPUMP.STAT 108 BD 5 Refrigerant Pump Motor Status (0=Off, 1=On) S S S S P36
P37 P35 D. Monitor CDWPUMP.STAT 109 BD 6 Condenser Water Pump Status (0=Off, 1=On) S S S S P37
P38 P36 D. Monitor CHWPUMP.STAT 110 BD 7 Chilled Water Pump Status (0=Off, 1=On) S S S S P38
P39 P37 D. Monitor STARTSW.STAT 111 BD 8 Unit Switch Status (0=Stop, 1=Run) S S S S P39
P40 P38 D. Monitor SPMPSOL.STAT 112 BD 9 Refrigerant & Solutn Pump Mtr Coolant Solnd Valve Status S S S S P40
P41 P39 D. Monitor SOLPMP.STAT 113 BD 10 Solution / Absorber Pump Motor Status (0=Off, 1=On) S S S S P41
P42 P40 D. Monitor GENPUMP.STAT 114 BD 11 Generator Pump Motor Status (0=Off, 1=On) O O O O P42

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 2 (1994) Property of York International York, PA Page: 5
2/26/2009

ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive
Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 D. Monitor PRGPUMP.STAT 115 BD 12 Purge Pump Motor Status (0=Off, 1=On) S S S S P43
P44 P42 D. Monitor CHWFLSW.STAT 116 BD 13 Chilled Water Flow Switch Status (0=Open, 1=Closed) S S S S P44
P45 P43 D. Monitor STABSOL.STAT 117 BD 14 Refrigerant Stabilizer Solenoid Valve Status (0=Off, 1=On) S S S S P45
P46 P44 D. Monitor CDWFLSW.STAT 118 BD 15 Condenser Water Flow Switch Status (0=Open, 1=Closed) S S S S P46
P47 P45 D. Monitor DIL_CYC.STAT 119 BD 16 P47
P48 P46 D. Monitor RLEVFSW.STAT 120 BD 17 Refrigerant Level Float Switch Status (0=Open, 1=Closed) S S S S P48
P49 P47 D. Monitor J50.STAT 121 BD 18 J50 Status (0=Auto Restart, 1=Manual Restart) S S S S P49
P50 P48 D. Monitor J51.STAT 122 BD 19 J51 Status (0=Loding Ovrdes Active, 1=No Loading Overrides) S S S S P50
P51 P49 D. Monitor J52.STAT 123 BD 20 J52 Status (0=English Units, 1=Metric Units) S S S S P51
P52 P50 D. Monitor J54.STAT 124 BD 21 J54 Status (0=Limited CW Pump Cntrl, 1=Full CW Pump Cntrl) S S S S P52
P53 P51 D. Monitor J55.STAT 125 BD 22 J55 Status (0=Diagnostics Enabled, 1=Diagnostics Disabled) S S S S P53
P54 P52 D. Monitor J57.STAT 126 BD 23 J57 Status (0=RTC Disabled, 1=RTC Enabled) S S S S P54
P55 P53 D. Monitor J12.STAT 127 BD 24 J12 (Expansion I/O Board) (0=English, 1=German) S S S S P55
P56 P54 Code Monitor DIL_CYC.CODE 128 ADI 1 Dilution Cycle Code S S S S P56
P57 P55 Code Monitor OPR_MOD.CODE 129 ADI 2 Operating Mode (0=Service, 1=Local, 2=Remote) S S S S P57
P58 P56 Code Monitor OPER.CODE 130 ADI 3 Operational Code S S S S P58
P59 P57 Code Monitor SAFETY.CODE 131 ADI 4 Safety Shutdown Code S S S S P59
P60 P58 Code Monitor CYCLING.CODE 132 ADI 5 Cycling Shutdown Code S S S S P60
P61 P59 Code Monitor WARN.CODE 133 ADI 6 Warning Message Code S S S S P61
P62 P60 Code Monitor 134 ADI 7 P62
P63 P61 Code Monitor 135 ADI 8 P63
P64 P62 Code Monitor 136 ADI 9 P64
P65 P63 Code Monitor 137 ADI 10 P65
P66 P64 A. Monitor RMT_LOAD.SP 138 - 141 ADF 30 Remote Loading Setpoint S S S S P66
P67 P65 A. Monitor VLVMAXLD.SP 142 - 145 ADF 31 Maximum Steam / Hot Water Valve Load Setpoint S S S S P67
P68 P66 A. Monitor WKPRGE.COUNT 146 - 149 ADF 32 Weekly Purge Counter S S S S P68
P69 P67 A. Monitor PD_LIM.SP 150 - 153 ADF 33 Pulldown Demand Setpoint - Minutes S S S S P69
P70 P68 A. Monitor PD_DMD.MIN 154 - 157 ADF 34 Pulldown Demand - Minutes Left S S S S P70
P71 P69 A. Monitor PD_START.SP 158 - 161 ADF 35 Pulldown Demand Setpoint - Start Load Limit S S S S P71
P72 P70 A. Monitor PD_STOP.SP 162 - 165 ADF 36 Pulldown Demand Setpoint - Stop Load Limit S S S S P72
P73 P71 A. Monitor PD_DMD.LIM 166 - 169 ADF 37 Pulldown Demand - Present Limit S S S S P73
P74 P72 A. Monitor REMT_RNG.SP 170 - 173 ADF 38 Remote Temp Range Setpoint S S S S P74
P75 P73 A. Monitor VLVMAXUNL.SP 174 - 177 ADF 39 Maximum Steam / Hot Water Valve Unload Setpoint S S S S P75
P76 P74 A. Monitor ECDW_MAX.SP 178 - 181 ADF 40 Maximum Entering Condenser Water Temperature Setpoint S S S S P76
P77 P75 A. Monitor JP1.STAT 182 - 185 ADF 41 JP1 Status (0=Steam Operation, 1=Hot Water Operation) S S S S P77
P78 P76 A. Monitor JP3.STAT 186 - 189 ADF 42 JP3 Status (0=Stndrd Model, 1=50 Hz Mdl YIA10E3 - YIA14F3) S S S S P78
P79 P77 A. Monitor JP1_EXP.STAT 190 - 193 ADF 43 JP1 (Expansion I/O Board) (0=Rotary Valve, 1 = Cage Valve) S S S S P79
P80 P78 D. Monitor RLEVSOL.STAT 194 BD 25 Refrigerant Level Solenoid Valve Status (0=Off, 1=On) S S S S P80
P81 P79 D. Monitor SST_LMT.STAT 195 BD 26 Strong Solution Temperature Limiting Active (0=No, 1=Yes) S S S S P81
P82 P80 D. Monitor ADECRYS.STAT 196 BD 27 Automatic Decrystallization Active (0=No, 1=Yes) S S S S P82
P83 P81 D. Monitor RMTLOAD.STAT 197 BD 28 Remote Load Limiting Active (0=No, 1=Yes) S S S S P83
P84 P82 D. Monitor PD_LMT.STAT 198 BD 29 Pulldown Limiting Active (0=No, 1=Yes) S S S S P84

NOTE: The Appropriate Product Code Listing Summary Should Accompany Document

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 2 (1994) Property of York International York, PA Page: 6
2/26/2009

ENG ASCII YI Dilution Cycle Code ENG ASCII YI Operational Code ENG ASCII YI Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P56 P54 DIL_CYC.CODE P58 P56 OPER.CODE P59 P57 SAFETY.CODE
0 0 Dilution Cycle Not Active 0 0 Unit Running 0 0 No Abnormal Condition
1 1 Dilution Cycle Active 1 1 Lockout Delay Active 1 1 Crystallization Lockout - Power Failure
2 2 Dilution Interrupted - Chilled Water Flow Switch 2 2 Unit Stopped - Unit Switch in Stop/Reset position 2 2 Crystallization Lockout - Pump Overload
3 3 Dilution Interrupted - Condenser Water Flow Switch 3 3 Unit Stopped - Safety Shutdown 3 3 Crystallization Lockout - Chilled Water Flow Switch
4 4 Dilution Interrupted - Refrigerant Level Float Switch 4 4 Unit Stopped - Cycling Shutdown 4 4 Crystallization Lockout - Cond Water Flow Switch
5 5 Unit Stopped - Remote Shutdown 5 5 Crystallization Lockout - Low Refrigerant Temp
6 6 Unit Starting 6 6 Crystallization Lockout - Motor Coolant Float Switch
7 7 Power Failure (Manual Restart Mode)
8 8 Chilled Water Float Switch Open
9 9 Solution / Absorber Pump Overloads Open
10 10 Refrigerant Pump Overloads Open
11 11 Generator Pump Overloads Open
12 12 Solution / Refrigerant Motor Coolant Switch Open
13 13 High Steam / Hot Water High Temperature
14 14 High Steam Supply Pressure
15 15 High Generator Shell Pressure
16 16 High Generator Shell Temperature
17 17 Low Refrigerant Temperature
18 18 Auxiliary Safety Shutdown

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 2 (1994) Property of York International York, PA Page: 7
2/26/2009

ENG ASCII YI Cycling Code ENG ASCII YI Warning Code


PAGE PAGE PAGE PAGE
P60 P58 CYCLING.CODE P61 P59 WARN.CODE
0 0 No Abnormal Condition 0 0 No Abnormal Condition
1 1 Power Failure (Auto-Restart Mode) 1 1 Low Refrigerant Temperature
2 2 Condenser Water Flow Switch Open 2 2 High Generator Shell Pressure
3 3 Low Water Temperature 3 3 High Steam / Hot Water Supply Temperature
4 4 Daily Schedule Shutdown 4 4 High Steam Supply Pressure
5 5 Steam Valve Loaded Above 10% 5 5 High Entering Condenser Water Temperature
6 6 Remote / Local System Cycling Shutdown 6 6 Faulty Strong Solution Temperature Sensor
7 7 Multi-Unit Cycling Shutdown 7 7 Purge Pump Overloads Open
8 8 Purge Pump Service Recommended

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 2 (1994) Property of York International York, PA Page: 8
2/26/2009

YIA IsoFlow Micro Panel II (Version 3 Protocol) York Talk 2 Microgateway / Elink Micro Board: 031-01065-xxx
Item Ref. Version Date YORK P N Checksum Baud COMMENTS
1 A.02F.01 12/07/95 031-01417-001 AA6B 1200 Release 1
2 A.02F.02.500.00 05/03/96 031-01417-001 4282 1200 Field Trial Release 0
3 A.02F.02.500.01 05/31/96 031-01417-001 21E2 1200 Field Trial Release 1
4 A.02F.02.500.02 08/22/96 031-01417-001 9CDD 1200 Field Trial Release 2
5 A.02F.02 11/19/96 031-01417-001 8CC7 1200 Release 2
6 A.02F.06 03/01/04 031-02513-001 1200 New eprom PN. now a 2 meg chip. added p29 "Solution Concentration %"
7 A.02F.08 07/18/05 031 02513 001 6643 1200
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC
A.02F.08
ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 A. Control LCHW_TEMP.SP ADF 1 Leaving Chilled Water Setpoint S S S S S S S S S S P03
P04 P02 A. Control ADF 2 P04
P05 P03 A. Control RMT_LOAD.SP ADF 3 Remote Load Limit Setpoint S S S S S S S S S S P05
P06 P04 A. Control ADF 4 P06
P07 P05 D. Control START BD 1 Start / Stop S S S S S S S S S S P07
P08 P06 D. Control HISTORY BD 2 Display History Service Buffer #1 (0=No, 1=Yes) S S S S S S S S S S P08
P09 P07 D. Control BD 3 P09
P10 P08 D. Control BD 4 P10
P11 P09 A. Monitor LCHW.TEMP 8 - 11 ADF 5 Leaving Chilled Water Temperature S S S S S S S S S S P11
P12 P10 A. Monitor ECHW.TEMP 12 - 15 ADF 6 Entering Chilled Water Temperature S S S S S S S S S S P12
P13 P11 A. Monitor GEN_SH.PRESS 16 - 19 ADF 7 Generator Shell Pressure S S S S S S S S S S P13
P14 P12 A. Monitor 20 - 23 ADF 8 P14
P15 P13 A. Monitor 24 - 27 ADF 9 P15
P16 P14 A. Monitor ECDW.TEMP 28 - 31 ADF 10 Entering Condenser Water Temperature S S S S S S S S S S P16
P17 P15 A. Monitor LCDW.TEMP 32 - 35 ADF 11 Leaving Condenser Water Temperature S S S S S S S S S S P17
P18 P16 A. Monitor ADECRYS.TEMP 36 - 39 ADF 12 Automatic Decrystallization Temperature S S S S S S S S S S P18
P19 P17 A. Monitor CONDREF.TEMP 40 - 43 ADF 13 Refrigerant Temperature Leaving the Condenser S S S S S S S S S S P19
P20 P18 A. Monitor STM/HW.TEMP 44 - 47 ADF 14 Steam / Hot Water Supply Temperature S S S S S S S S S S P20
P21 P19 A. Monitor STMSUP.PRESS 48 - 51 ADF 15 Steam Supply Pressure (steam units only) O O O O O O O O O O P21
P22 P20 A. Monitor SUP_VALV.POS 52 - 55 ADF 16 Steam / Hot Water Actuator Valve Position (0-100%) S S S S S S S S S S P22
P23 P21 A. Monitor LOC_LCHW.SP 56 - 59 ADF 17 Local Leaving Chilled Water Setpoint S S S S S S S S S S P23
P24 P22 A. Monitor PP_SERINT.SP 60 - 63 ADF 18 Purge Pump Service Interval Setpoint - Hours S S S S S S S S S S P24
P25 P23 A. Monitor LCHW_ACT.SP 64 - 67 ADF 19 Active Leaving Chilled Water Setpoint S S S S S S S S S S P25
P26 P24 A. Monitor 68 - 71 ADF 20 P26
P27 P25 A. Monitor REFRIG.TEMP 72 - 75 ADF 21 Refrigerant Temperature S S S S S S S S S S P27
P28 P26 A. Monitor STG_SOL.TEMP 76 - 79 ADF 22 Strong Solution Temperature S S S S S S S S S S P28
P29 P27 A. Monitor 80 - 83 ADF 23 Solution Concentation % N N N N N N N N N S P29
P30 P28 A. Monitor 84 - 87 ADF 24 P30
P31 P29 A. Monitor 88 - 91 ADF 25 P31
P32 P30 A. Monitor RUN.HOURS 92 - 95 ADF 26 Total Operating Hours S S S S S S S S S S P32
P33 P31 A. Monitor START.COUNT 96 - 99 ADF 27 Total System Starts S S S S S S S S S S P33
P34 P32 A. Monitor LTPRGE.COUNT 100 - 103 ADF 28 Lifetime Purge Count S S S S S S S S S S P34
P35 P33 A. Monitor 104 - 107 ADF 29 P35
P36 P34 D. Monitor REFPUMP.STAT 108 BD 5 Refrigerant Pump Motor Status (0=Off, 1=On) S S S S S S S S S S P36
P37 P35 D. Monitor CDWPUMP.STAT 109 BD 6 Condenser Water Pump Status (0=Off, 1=On) S S S S S S S S S S P37
P38 P36 D. Monitor CHWPUMP.STAT 110 BD 7 Chilled Water Pump Status (0=Off, 1=On) S S S S S S S S S S P38
P39 P37 D. Monitor STARTSW.STAT 111 BD 8 Unit Switch Status (0=Stop, 1=Run) S S S S S S S S S S P39
P40 P38 D. Monitor SPMPSOL.STAT 112 BD 9 Refrigerant & Solutn Pump Mtr Coolant Solnd Valve Status S S S S S S S S S S P40
P41 P39 D. Monitor SOLPMP.STAT 113 BD 10 Solution / Absorber Pump Motor Status (0=Off, 1=On) S S S S S S S S S S P41
P42 P40 D. Monitor GENPUMP.STAT 114 BD 11 Generator Pump Motor Status (0=Off, 1=On) O O O O O O O O O O P42

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 3 (1995+) Property of Johnson Controls, York, PA Page: 9
2/26/2009

ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive
Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 D. Monitor PRGPUMP.STAT 115 BD 12 Purge Pump Motor Status (0=Off, 1=On) S S S S S S S S S S P43
P44 P42 D. Monitor CHWFLSW.STAT 116 BD 13 Chilled Water Flow Switch Status (0=Open, 1=Closed) S S S S S S S S S S P44
P45 P43 D. Monitor STABSOL.STAT 117 BD 14 Refrigerant Stabilizer Solenoid Valve Status (0=Off, 1=On) S S S S S S S S S S P45
P46 P44 D. Monitor CDWFLSW.STAT 118 BD 15 Condenser Water Flow Switch Status (0=Open, 1=Closed) S S S S S S S S S S P46
P47 P45 D. Monitor DIL_CYC.STAT 119 BD 16 P47
P48 P46 D. Monitor RLEVFSW.STAT 120 BD 17 Refrigerant Level Float Switch Status (0=Open, 1=Closed) S S S S S S S S S S P48
P49 P47 D. Monitor J50.STAT 121 BD 18 J50 Status (0=Auto Restart, 1=Manual Restart) S S S S S S S S S S P49
P50 P48 D. Monitor J51.STAT 122 BD 19 J51 Status (0=Loding Ovrdes Active, 1=No Loading Overrides) S S S S S S S S S S P50
P51 P49 D. Monitor J52.STAT 123 BD 20 J52 Status (0=English Units, 1=Metric Units) S S S S S S S S S S P51
P52 P50 D. Monitor J54.STAT 124 BD 21 J54 Status (0=Limited CW Pump Cntrl, 1=Full CW Pump Cntrl) S S S S S S S S S S P52
P53 P51 D. Monitor J55.STAT 125 BD 22 J55 Status (0=Diagnostics Enabled, 1=Diagnostics Disabled) S S S S S S S S S S P53
P54 P52 D. Monitor J57.STAT 126 BD 23 J57 Status (0=RTC Disabled, 1=RTC Enabled) S S S S S S S S S S P54
P55 P53 D. Monitor J12.STAT 127 BD 24 J12 (Expansion I/O Board) (0=English, 1=German) S S S S S S S S S S P55
P56 P54 Code Monitor DIL_CYC.CODE 128 ADI 1 Dilution Cycle Code S S S S S S S S S S P56
P57 P55 Code Monitor OPR_MOD.CODE 129 ADI 2 Operating Mode (0=Service, 1=Local, 2=Remote) S S S S S S S S S S P57
P58 P56 Code Monitor OPER.CODE 130 ADI 3 Operational Code S S S S S S S S S S P58
P59 P57 Code Monitor SAFETY.CODE 131 ADI 4 Safety Shutdown Code S S S S S S S S S S P59
P60 P58 Code Monitor CYCLING.CODE 132 ADI 5 Cycling Shutdown Code S S S S S S S S S S P60
P61 P59 Code Monitor WARN.CODE 133 ADI 6 Warning Message Code S S S S S S S S S S P61
P62 P60 Code Monitor 134 ADI 7 P62
P63 P61 Code Monitor 135 ADI 8 P63
P64 P62 Code Monitor 136 ADI 9 P64
P65 P63 Code Monitor 137 ADI 10 P65
P66 P64 A. Monitor RMT_LOAD.SP 138 - 141 ADF 30 Remote Loading Setpoint S S S S S S S S S S P66
P67 P65 A. Monitor VLVMAXLD.SP 142 - 145 ADF 31 Maximum Steam / Hot Water Valve Load Setpoint S S S S S S S S S S P67
P68 P66 A. Monitor WKPRGE.COUNT 146 - 149 ADF 32 Weekly Purge Counter S S S S S S S S S S P68
P69 P67 A. Monitor PD_LIM.SP 150 - 153 ADF 33 Pulldown Demand Setpoint - Minutes S S S S S S S S S S P69
P70 P68 A. Monitor PD_DMD.MIN 154 - 157 ADF 34 Pulldown Demand - Minutes Left S S S S S S S S S S P70
P71 P69 A. Monitor PD_START.SP 158 - 161 ADF 35 Pulldown Demand Setpoint - Start Load Limit S S S S S S S S S S P71
P72 P70 A. Monitor PD_STOP.SP 162 - 165 ADF 36 Pulldown Demand Setpoint - Stop Load Limit S S S S S S S S S S P72
P73 P71 A. Monitor PD_DMD.LIM 166 - 169 ADF 37 Pulldown Demand - Present Limit S S S S S S S S S S P73
P74 P72 A. Monitor REMT_RNG.SP 170 - 173 ADF 38 Remote Temp Range Setpoint S S S S S S S S S S P74
P75 P73 A. Monitor VLVMAXUNL.SP 174 - 177 ADF 39 Maximum Steam / Hot Water Valve Unload Setpoint S S S S S S S S S S P75
P76 P74 A. Monitor ECDW_MAX.SP 178 - 181 ADF 40 Maximum Entering Condenser Water Temperature Setpoint S S S S S S S S S S P76
P77 P75 A. Monitor JP1.STAT 182 - 185 ADF 41 JP1 Status (0=Steam Operation, 1=Hot Water Operation) S S S S S S S S S S P77
P78 P76 A. Monitor JP3.STAT 186 - 189 ADF 42 JP3 Status (0=Stndrd Model, 1=50 Hz Mdl YIA10E3 - YIA14F3) S S S S S S S S S S P78
P79 P77 A. Monitor JP1_EXP.STAT 190 - 193 ADF 43 JP1 (Expansion I/O Board) (0=Rotary Valve, 1 = Cage Valve) S S S S S S S S S S P79
P80 P78 D. Monitor RLEVSOL.STAT 194 BD 25 Refrigerant Level Solenoid Valve Status (0=Off, 1=On) S S S S S S S S S S P80
P81 P79 D. Monitor SST_LMT.STAT 195 BD 26 Low Entering Condenser Water Temp Limit Active (0=No,1=Yes) S S S S S S S S S S P81
P82 P80 D. Monitor ADECRYS.STAT 196 BD 27 Automatic Decrystallization Active (0=No, 1=Yes) S S S S S S S S S S P82
P83 P81 D. Monitor RMTLOAD.STAT 197 BD 28 Remote Load Limiting Active (0=No, 1=Yes) S S S S S S S S S S P83
P84 P82 D. Monitor PD_LMT.STAT 198 BD 29 Pulldown Limiting Active (0=No, 1=Yes) S S S S S S S S S S P84

NOTE: The Appropriate Product Code Listing Summary Should Accompany Document

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 3 (1995+) Property of Johnson Controls, York, PA Page: 10
2/26/2009

ENG ASCII YI Dilution Cycle Code ENG ASCII YI Operational Code ENG ASCII YI Safety Code
PAGE PAGE PAGE PAGE PAGE PAGE
P56 P54 DIL_CYC.CODE P58 P56 OPER.CODE P59 P57 SAFETY.CODE
0 0 Dilution Cycle Not Active 0 0 Unit Running 0 0 No Abnormal Condition
1 1 Dilution Cycle Active 1 1 Lockout Delay Active 1 1 Crystallization Lockout - Power Failure
2 2 Dilution Interrupted - Chilled Water Flow Switch 2 2 Unit Stopped - Unit Switch in Stop/Reset position 2 2 Crystallization Lockout - Pump Overload
3 3 Dilution Interrupted - Condenser Water Flow Switch 3 3 Unit Stopped - Safety Shutdown 3 3 Crystallization Lockout - Chilled Water Flow Switch
4 4 Dilution Interrupted - Refrigerant Level Float Switch 4 4 Unit Stopped - Cycling Shutdown 4 4 Crystallization Lockout - Cond Water Flow Switch
5 5 Unit Stopped - Remote Shutdown 5 5 Crystallization Lockout - Low Refrigerant Temp
6 6 Unit Starting 6 6 Crystallization Lockout - Motor Coolant Float Switch
7 7 Power Failure (Manual Restart Mode)
8 8 Chilled Water Float Switch Open
9 9 Solution / Absorber Pump Overloads Open
10 10 Refrigerant Pump Overloads Open
11 11 Generator Pump Overloads Open
12 12 Solution / Refrigerant Motor Coolant Switch Open
13 13 High Steam / Hot Water High Temperature
14 14 High Steam Supply Pressure
15 15 High Generator Shell Pressure
16 16 High Generator Shell Temperature
17 17 Low Refrigerant Temperature
18 18 Auxiliary Safety Shutdown

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 3 (1995+) Property of Johnson Controls, York, PA Page: 11
2/26/2009

ENG ASCII YI Cycling Code ENG ASCII YI Warning Code


PAGE PAGE PAGE PAGE
P60 P58 CYCLING.CODE P61 P59 WARN.CODE
0 0 No Abnormal Condition 0 0 No Abnormal Condition
1 1 Power Failure (Auto-Restart Mode) 1 1 Low Refrigerant Temperature
2 2 Condenser Water Flow Switch Open 2 2 High Generator Shell Pressure
3 3 Low Water Temperature 3 3 High Steam / Hot Water Supply Temperature
4 4 Daily Schedule Shutdown 4 4 High Steam Supply Pressure
5 5 Steam Valve Loaded Above 10% 5 5 High Entering Condenser Water Temperature
6 6 Remote / Local System Cycling Shutdown 6 6 Faulty Strong Solution Temperature Sensor
7 7 Multi-Unit Cycling Shutdown 7 7 Purge Pump Overloads Open
8 8 Purge Pump Service Recommended

Revision: Absorption_Chillers (Rev J_03).xls Tab: IsoFlow Ver. 3 (1995+) Property of Johnson Controls, York, PA Page: 12
2/26/2009

YPC ParaFlow Micro Panel II York Talk 2 Microgateway / Elink Micro Board: 031-01065-xxx
Item Ref. Version Date YORK P N Checksum Baud COMMENTS
1 A.01F.09 11/14/96 031-01669-002 502C 1200 Standard Paraflow Absorption
2 A.01F.10 031-01669-002 9526 1200 Standard Paraflow Absorption
3 A.01F.12 3/3/99 031-01669-002 6C56 1200 Standard Paraflow Absorption
4 A.01F.12.133.00 Unassigned 1200 Standard Paraflow Absorption Field Trial
5 A.01F.13 Unassigned 1200 Standard Paraflow Absorption Field Trial
6 A.01F.15 6/27/05 031 02069 001 FF5C 1200 Standard Paraflow Absorption
7
8
9
10
Use ASCII page column for interfaces utilizing an ASCII XL Translator or MicroGateway to communicate to a chiller LINC

ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P03 P01 A. Control LCHW_TEMP.SP ADF 1 Leaving Chilled Water Setpoint S S S S S P03
P04 P02 A. Control HOTW_TEMP.SP ADF 2 Hot Water Temp Setpoint S S S S S P04
P05 P03 A. Control RMT_LOAD.SP ADF 3 Remote Load Limit Setpoint (must set value above minimum stated in OPs manual) S S S S S P05
P06 P04 A. Control ADF 4 P06
P07 P05 D. Control START BD 1 Start/Stop S S S S S P07
P08 P06 D. Control HISTORY BD 2 Display History Service Buffer #1 (0=No 1=Yes) S S S S S P08
P09 P07 D. Control BD 3 P09
P10 P08 D. Control BD 4 P10
P11 P09 A. Monitor LCHW.TEMP 8 - 11 ADF 5 Leaving Chilled Water Temperature S S S S S P11
P12 P10 A. Monitor ECHW.TEMP 12 - 15 ADF 6 Entering Chilled Water Temperature S S S S S P12
P13 P11 A. Monitor 1GEN1.PRESS 16 - 19 ADF 7 First Generator #1 Pressure S S S S S P13
P14 P12 A. Monitor 1GEN1.TEMP 20 - 23 ADF 8 First Generator #1 Temp S S S S S P14
P15 P13 A. Monitor 1GEN2.PRESS 24 - 27 ADF 9 First Generator #2 Pressure S S S S S P15
P16 P14 A. Monitor ECDW.TEMP 28 - 31 ADF 10 Entering Condenser Water Temperature S S S S S P16
P17 P15 A. Monitor LCDW.TEMP 32 - 35 ADF 11 Leaving Condenser Water Temperature S S S S S P17
P18 P16 A. Monitor 1GEN2.TEMP 36 - 39 ADF 12 First Generator #2 Temp S S S S S P18
P19 P17 A. Monitor LHOTW.TEMP 40 - 43 ADF 13 Leaving Hot Water Temp O O O O O P19
P20 P18 A. Monitor EHOTW.TEMP 44 - 47 ADF 14 Entering Hot Water Temp O O O O O P20
P21 P19 A. Monitor 48 - 51 ADF 15 P21
P22 P20 A. Monitor LOADING 52 - 55 ADF 16 Burner Command (Gas/Oil), Percent Loading (Steam) S S S S S P22
P23 P21 A. Monitor 56 - 59 ADF 17 P23
P24 P22 A. Monitor 60 - 63 ADF 18 P24
P25 P23 A. Monitor LCHW_ACT.SP 64 - 67 ADF 19 Leaving Chilled Water Temp Actual Setpoint S S S S S P25
P26 P24 A. Monitor LHOTW_ACT.SP 68 - 71 ADF 20 Leaving Hot Water Temp Actual Setpoint O O O O O P26
P27 P25 A. Monitor REFRIG.TEMP 72 - 75 ADF 21 Refrigerant Temp S S S S S P27
P28 P26 A. Monitor SOLTN.TEMP 76 - 79 ADF 22 Solution Temperature S S S S S P28
P29 P27 A. Monitor REF_TMP_CO 80 - 83 ADF 23 S S S S S P29
P30 P28 A. Monitor PRGPMP.PRESS 84 - 87 ADF 24 Purge Pump Pressure O O O O O P30
P31 P29 A. Monitor PRGTNK.PRESS 88 - 91 ADF 25 Purge Tank Pressure O O O O O P31
P32 P30 A. Monitor RUN.HOURS 92 - 95 ADF 26 Accumulated Operating Hours S S S S S P32
P33 P31 A. Monitor START.COUNT 96 - 99 ADF 27 Accumulated System Starts S S S S S P33
P34 P32 A. Monitor LTPRGE.COUNT 100 - 103 ADF 28 Automatic Lifetime Purge Count O O O O O P34
P35 P33 A. Monitor M_LTPRG.CNT 104 - 107 ADF 29 Manual Lifetime Purge Count S S S S S P35
P36 P34 D. Monitor REFPUMP.STAT 108 BD 5 Refrigerant Pump Status S S S S S P36
P37 P35 D. Monitor CDWPUMP.STAT 109 BD 6 Condenser Pump Status S S S S S P37
P38 P36 D. Monitor CHWPUMP.STAT 110 BD 7 Chilled Water Pump Status (0=Off 1=On) S S S S S P38
P39 P37 D. Monitor STARTSW.STAT 111 BD 8 Start Switch Status S S S S S P39
P40 P38 D. Monitor HOTWPMP.STAT 112 BD 9 Hot Water Pump Status O O O O O P40
P41 P39 D. Monitor SOLPMP1.STAT 113 BD 10 Solution Pump 1 Status S S S S S P41
P42 P40 D. Monitor SOLPMP2.STAT 114 BD 11 Solution Pump 2 Status O O O O O P42

Revision: Absorption_Chillers (Rev J_03).xls Tab: ParaFlow Property of York International York, PA Page: 13
2/26/2009

ENG ASCII GPIC York Talk ISN LINC York Talk N2 ENG
PAGE PAGE Object Point Descriptive
Character Address POINT LIST CODE: S = STANDARD O = OPTIONAL N = NOT AVAILABLE PAGE
REF REF Type Type Text Position POINT LIST DESCRIPTION 1 2 3 4 5 6 7 8 9 10 REF
P43 P41 D. Monitor PRGPUMP.STAT 115 BD 12 Purge Pump Motor Status (0=Off 1=On) S S S S S P43
P44 P42 D. Monitor CHWFLSW.STAT 116 BD 13 Chilled Water Flow Switch Status (0=Open 1=On) S S S S S P44
P45 P43 D. Monitor HOTWFLS.STAT 117 BD 14 Hot Water Flow Switch Status O O O O O P45
P46 P44 D. Monitor CDWFLSW.STAT 118 BD 15 Condenser Water Flow Switch Status (0=Open 1=Closed) S S S S S P46
P47 P45 D. Monitor DIL_CYC.STAT 119 BD 16 Dilution Cycle Active (0=No 1=Yes) S S S S S P47
P48 P46 D. Monitor 120 BD 17 P48
P49 P47 D. Monitor 121 BD 18 P49
P50 P48 D. Monitor 122 BD 19 P50
P51 P49 D. Monitor 123 BD 20 P51
P52 P50 D. Monitor 124 BD 21 P52
P53 P51 D. Monitor 125 BD 22 P53
P54 P52 D. Monitor 126 BD 23 P54
P55 P53 D. Monitor 127 BD 24 P55
P56 P54 Code Monitor UNIT_OP.CODE 128 ADI 1 Operating Code (0=clg; 1=htg; 2=htg/clg) S S S S S P56
P57 P55 Code Monitor OPR_MOD.CODE 129 ADI 2 Operating Mode (1=Service 2=Local 3=Remote) S S S S S P57
P58 P56 Code Monitor OPER.CODE 130 ADI 3 Operational Code (Warnings) S S S S S P58
P59 P57 Code Monitor SAFETY.CODE 131 ADI 4 Safety Shutdown Code S S S S S P59
P60 P58 Code Monitor CYCLING.CODE 132 ADI 5 Cycling Shutdown Code S S S S S P60
P61 P59 Code Monitor 133 ADI 6 P61
P62 P60 Code Monitor 134 ADI 7 P62
P63 P61 Code Monitor 135 ADI 8 P63
P64 P62 Code Monitor 136 ADI 9 P64
P65 P63 Code Monitor 137 ADI 10 P65
P66 P64 A. Monitor RMT_LOAD.SP 138 - 141 ADF 30 Remote Loading Setpoint S S S S S P66
P67 P65 A. Monitor MAX_LOAD.SP 142 - 145 ADF 31 Maximum Loading S S S S S P67
P68 P66 A. Monitor WKPRGE.COUNT 146 - 149 ADF 32 7 Day Purge Total S S S S S P68
P69 P67 A. Monitor PD_LIM.SP 150 - 153 ADF 33 Pulldown Minutes Setpoint S S S S S P69
P70 P68 A. Monitor PD_DMD.MIN 154 - 157 ADF 34 Pulldown Minutes Left S S S S S P70
P71 P69 A. Monitor PD_START.SP 158 - 161 ADF 35 Pulldown Loading Start Setpoint S S S S S P71
P72 P70 A. Monitor PD_STOP.SP 162 - 165 ADF 36 Pulldown Loading Stop Setpoint S S S S S P72
P73 P71 A. Monitor PD_DMD.LIM 166 - 169 ADF 37 Present Calculated Pulldown Loading S S S S S P73
P74 P72 A. Monitor 170 - 173 ADF 38 P74
P75 P73 A. Monitor 174 - 177 ADF 39 P75
P76 P74 A. Monitor 178 - 181 ADF 40 P76
P77 P75 A. Monitor 182 - 185 ADF 41 P77
P78 P76 A. Monitor 186 - 189 ADF 42 P78
P79 P77 A. Monitor 190 - 193 ADF 43 P79
P80 P78 D. Monitor ENERGY_SRCE 194 BD 25 Input Energy Supply (0=Gas/Oil 1=Steam) S S S S S P80
P81 P79 D. Monitor 195 BD 26 P81
P82 P80 D. Monitor 196 BD 27 P82
P83 P81 D. Monitor 197 BD 28 P83
P84 P82 D. Monitor 198 BD 29 P84

NOTE: The Appropriate Product Code Listing Summary Should Accompany Document

Revision: Absorption_Chillers (Rev J_03).xls Tab: ParaFlow Property of York International York, PA Page: 14
2/26/2009

ENG ASCII YP Operational Code ENG ASCII YP Safety Code ENG ASCII YP Cycling Code
PAGE PAGE PAGE PAGE PAGE PAGE
P58 P56 OPER.CODE P59 P57 SAFETY.CODE P60 P58 CYCLING.CODE
0 0 No Malfunction 0 0 No Malfunction 0 0 No Malfunction
1 1 Bad Battery 1 1 Solution Pump Fault 1 1 Hot Water Flow Fault
2 2 Refrigerant Temp < 40.0 F 2 2 Refrigerant Pump Fault 2 2 Cond Water Flow Fault
3 3 Gen Press > 12.76 PSIA 3 3 Gen HI Pressure-Digital 3 3 Power Failure-Auto Restart
4 4 Gen 1 Press > 12.76 PSIA 4 4 Gen HI Temp-Digital 4 4 Low Water Temp
5 5 Gen 2 Press > 12.76 PSIA 5 5 Auxiliary 5 5 Remote Cycling
6 6 Gen Temp > 326.0 F 6 6 Power Fail-Man Restart 6 6 Multi-Unit Cycling
7 7 Gen 1 Temp > 326.0 F 7 7 Low Solution Level 7 7 Time Clock
8 8 Gen 2 Temp > 326.0 F 8 8 Low Refrigerant Temp-Digital 8 8 Hot Water Temp
9 9 Low Cond Water Temp 9 9 Chilled Water Flow Fault 9 9 Unit Loaded Above 10%
10 10 Not Used 10 10 Burner Alarm Fault 10 10 Chilled Water Temp Below Setp
11 11 Not Used 11 11 Burner Manual Shutdown 11 11 Hot Water Temp Above Setp
12 12 Not Used 12 12 Low Sol'n Lvl @ Power Fail 36 36 Burner Rate Fault
13 13 Purge Pump Overloads Open 13 13 Low Sol'n Lvl @ Cond Flow Fail 38 38 Standby Power
14 14 Purge Transducer Fault 14 14 Low Refrigerant Temp-Analog 39 39 Standby Lockout
15 15 Purge Pump Fault 30 30 Cond Water Flow Lost
16 16 Solution Sensor Fault 31 31 Gen High Press-Analog
17 17 HI Cond Water Temp 32 32 Gen High Temp-Analog
18 18 Not Used 33 33 Sol'n Lvl/Refrig Sol'n OL'S
19 19 Excess Purge 34 34 Sol'n Lvl/Low Refrig Temp
20 20 High Concentration Warning 35 35 Sol'n Lvl/CW Flow SW Fault
21 21 High Purge Pressure Warning 37 37 High Concentration Fault
22 22 Auto Purge Fault 40 40 Sol'n Lvl/Limited Dilution
23 23 Purge Pump Error 41 41 Limited Dilution Override
24 24 Solenoid 2 Fault 42 42 Sol'n Lvl/Refrigerant Overloads
25 25 Solenoid 2 Absorber 43 43 Sol'n Lvl/Sol'n Overloads
26 26 Purge Pump Absorber

Revision: Absorption_Chillers (Rev J_03).xls Tab: ParaFlow Property of York International York, PA Page: 15