You are on page 1of 4

CLIENT IN SALAH GAS

PROJECT TITLE IN SALAH COMPRESSION PROJECT

CONTRACT NO. ISG/02/CON/7063

DOCUMENT NO. ISG-AB-KRE-EL-DAT-0001

DOCUMENT TITLE DATA SHEET - AC GENERATOR (KRECHBA)

TAG NO’s J-XM-080301

REVISION RECORD
REV. DESCRIPTION ORIGINATED CHECKED APPROVED BY
BY BY
ENG. PROJECTS CLIENT

Don Pope K.Martin Don Pope G.Budge


E1 For Enquiry
DP 201106 KGM 201106 DP 201106 GB 201106
Issued For (EPC) KMcCombie K.Martin D.Pope G.Budge O.J.Figved
E2
Enquiry ppKGM 190107 KGM 190107 DP 190107 GB 190107 OJF 190107
JOB NO. U 7063 U ITEM NO. U J-XM-080301
REQUISITION NO.
DATASHEET NO. U ISG-AB-KRE-EL-DAT-0001

A.C. GENERATOR REVISION NO. E2 DATE 19/01/07


DATA SHEET
U U U

PAGE 2 OF 4 BY DP
SI UNITS
U U U U U U

1 APPLICABLE TO: PROPOSAL PURCHASE AS BUILT


2 FOR U ISG U MANUFACTURER U ABB Automation Technology Products (or equal) U

3 SITE U KRECHBA U SERIAL NO.


4 SERVICE U MAIN GENERATION U NO. REQUIRED U ONE U

PURCHASER’S DATA
5 Design Output (MW) (NOTE 1) Max/Min 18.7MW @ 40°C Primary Coolant AIR
6 Rated Power Factor (cos Phi) 0.8 Secondary Coolant AIR
7 Service Voltage (V) 10,000 Cooling Classification CACA
8 Rated Frequency (Hz) 50 Cooling Temperature (°C) - Max 55
9 No. of Phases 3 - Min -5
10 Duty Type S1 Area Classification NOTE 2
11 Generator Neutral Earthing NOTE 3A Generator Enclosure Classification INDUSTRIAL
12 Earth Fault Current (A) 750A Generator Ingress Protection IP55
13 Neutral Earth Resistor Rating (A, secs) 750A, 10secs Current Transformers NOTE 3B
14 Excitation BRUSHLESS - In Phase: Line End YES
15 Direct Axis Sub-Transient Reactance (%) NOTE 4 - In Phase: Neutral End YES
16 Direct Axis Transient Reactance (%) - In Neutral Connection YES
17 Parallel Operation YES / NO Insulation Class
S S F
18 Unbalanced Load YES / NO Temperature Rise Class
S S B total
19 Surge Overvoltage Protection YES / NO Vibration Detection
S S YES
20 Mains Terminals - Cable YES Winding Temp. Detection YES
21 - Cable Size 9X1C x 630 mm2 Bearing Temp. DetectionP P YES
22 - Cable Type XLPEPVCSWAPVC Mounting FOOT
23 Neutral Terminals - Cable Size 1 x 630 mm2 Space Heater Voltage
P P 440 / 230 V A.C.
24 - Cable Type XLPEPVCSWAPVC Environmental Conditions NOTE 2
25 NOTES
26 NOTE 1 - GENERATORS SHALL BE CONTINUOUSLY RATED FOR THE MAXIMUM POTENTIAL POWER DEVELOPED BY THE GAS
27 TURBINE DRIVER WHEN OPERATING WITH THE MINIMUM SITE AMBIENT TEMPERATURE (EXISTING SITE GENERATORS ARE 25.375 KVA @ 0.8POWER FACTOR)
28 NOTE 2 - REFER TO COMBUSTION GAS TURBINE DATASHEET FOR SITE CONDITIONS, UTILITIES, AREA CLASSIFICATION, NOISE
29 LIMITS AND GENERAL REQUIREMENTS
30 NOTE 3 - A) NEUTRAL EARTHING RESISTOR BY GENERATOR SUPPLIER. REFER TO SKETCH ON PAGE 4. - B) CT’s REFER TO PROTECTION DIAGRAM ISG-AB-KRE-EL-
SCM-0001
31 NOTE 4 - 20% NOMINAL OR 17% (Saturated) NO NEGATIVE TOLERANCE.
32 NOTE 5 - REFER TO GENERATOR SPECIFICATION No.ISG-AB-KRE-EL-SPE-0001 FOR FULL DETAILS
33 NOTE 6 - ROGOWSKI COIL TO BE SUPPLIED AND FITTED WITH ACCESS TO TERMINALS FOR ‘ON LINE’ INSULATION CHECK
SUPPLIER’S DATA
34 Generator Generator Parameters (All)
35 Type Positive Sequence Resistance (R1) %, Tol ± +-15%
36 Frame Designation Zero Sequence Resistance (R0) %, Tol ± +-15%
37 Degree of Protection IP55 Negative Sequence Resistance (R2) %, Tol ± +-15%
38 Synchronous Speed rpm 1500 Zero Sequence Reactance (X0) %, Tol ± +-15%
39 1st Critical Speed
P P rpm Negative Sequence Reactance (X2) %, Tol ± +-15%
40 Direction of Rotation seen Towards Drive CW / CCW Direct Axis Synchronous Reactance (Xd) %, Tol ± Unsat/sat +-15%
41 Rated Voltage V 10000 Direct Axis Transient Reactance (X’d) %, Tol ± Unsat/sat +-15%
42 Rated Frequency Hz 50 Direct Axis Sub-Transient Reactance (X’’d) %, Tol ± Unsat/sat +-15%
43 Rated Output at 40°C base kVA MW Short Circuit Ratio
44 Rated Output at DE Side Max Power 10 degC MW Generator Parameters (>1MVA only)
45 Power Factor cos Phi 0.8 Quadrature Axis Synchronous Reactance (Xq) %, Tol ± Unsat/sat +-15%
46 Duty Type S1 Quadrature Axis Transient Reactance (X’q) %, Tol ± NA
47 Rated Current A Quadrature Axis Sub-Transient Reactance (X’’q) %, Tol ± Unsat/sat +-15%
48 Thermal Rating Direct Axis O.C. Transient Time Constant (T’do) secs
49 Max. Allowable Neg. Phase Seq. Current % Direct Axis S.C. Transient Time Constant (T’ds) secs
50 Max. Allowable Content of Overharmonics % Direct Axis O.C. Sub-Transient Time Constant (T’’do) secs
51 Efficiency - 100% base kVA % Direct Axis S.C. Sub-Transient Time Constant (T’’ds) secs
52 - 75% base kVA % Quad. Axis O.C. Transient Time Constant (T’qo) secs NA
53 - 50% base kVA % Quad. Axis S.C. Transient Time Constant (T’qs) secs NA
54 Field Current No Load A Quad. Axis O.C. Transient Time Constant (T’’qo) secs
55 Field Current Full Load A Quad. Axis S.C. Transient Time Constant (T’’qs) secs
56 Insulation Cla. - Stator / Rotor F/H Potier Reactance (Xp) %, Tol ± % +-15%
57 Temp. Rise Cla. - Stator / Rotor B total / B total Damping Factor
58 Overload Capability %, hrs Saturation Factor
59 Overload Capability %, secs % secs Basic Impulse Level kV
60 Substained Short Circuit %, secs % secs Dimensions & Weights
61 Moment of Inertia Rotor kg m2 Overall Dimensions - LxWxH
62 Cooling Method IC6A1A6 Weight of Machine kg
63 Cooling Water Flow Rate m3/h NA Weight of Stator kg
64 Cooling Water Design Pressure Barg NA Weight of Heat Exhanger - (Dry) kg
65 Leak Detection System NA Weight of Coolant kg NA
JOB NO. U 7063 U ITEM NO. U J-XM-080301
REQUISITION NO.
DATASHEET NO. ISG-AB-KRE-EL-DAT-0001

A.C. GENERATOR REVISION NO. E2 DATE 19/01/07


DATA SHEET
U U U

PAGE 3 OF 4 BY DP.
SI UNITS
U U U U U U

SUPPLIER’S DATA
1 System Response Bearings
2 Voltage Constant Speed Radial - Drive End Sleeve Diameter
3 - Load Change from 50 To 0% %, secs Radial - Non Drive End Sleeve Diameter
4 - Load Change from 100 To 50% %, secs Thrust Bearing NA
5 - Load Change from 0 To 50% %, secs Bearing Vibration Detector Type / Manufacturer 3300 / Bently Nevada
6 - Load Change from 50 To 100% %, secs Number in Each Bearing 2
7 Frequency Response: Bearing Temperature Detector Type PT 100
8 - Sudden Load Change From 50 To 0% %, secs Number In Each Bearing 1
9 - Sudden Load Change From 100 To 50% %, secs Method of Bearing Lubrication Forced
10 - Sudden Load Change From 0 To 50% %, secs Lubrication Oil Flow Rate m3/h
11 - Sudden Load Change From 50 To 100% %, secs Lubrication Oil Pressure Barg
12 Exciter Windings
13 Type Stator Connection Y
14 Full Load Current (40°C) A Number of Stator Winding Terminals 12
15 Full Load Voltage V Winding Temperature Detector Type PT 100
16 Ceiling Current (40°C) A Number In Each Phase 2
17 Ceiling Voltage V Heater Ratings
18 Nominal Exciter Response ratio 1/S Alternator kW
19 Current at Alternator base kVA A Exciter kW
20 Insulation Class Stator / Rotor F/F Aux. Cooling Fans
21 Temp. Rise Class Stator / Rotor B/B Rating kW
22 AVR Manufacturer
23 Model No. Frame Design
24 Manufacturer Number Off
25 Range of No Load Adjustment +-10% Duty %
26 Steady State Accuracy % 0.5 Neutral Earthing Resistor
27 AVR Data (>1MVA only) Type
28 Forward Gain (KA) Resistance Ohms 7.7
29 Feedback Gain (KF) Resistor Rating A, secs 750/10
30 Regulator Amplifier Time Constant (TA) secs Degree of Protection IP54
31 Regulator Feedback Time Constant (TF1) secs
32 Maximum Regulator Output (VR MAX)
33 Minimum Regulator Output (VR MIN)
34 Max. Rate of Change of Reg. Output (VR MAX)
35 Input Filter Time Constant (TR) secs
36 Exciter Gain (KE)
37 Exciter Time Constant (TE) secs
38 Exciter Output (E MAX)
39 Exciter Output (E MIN)
40 Exciter Saturation at 75% E MAX (SE75)
41 Exciter Saturation at 100% E MAX (SE100)
42 IEEE Model Type
43 Regulator Feedback Time Constant (TF2) secs
44
45 REMARKS:
46 AVR Data will be given as a transfer function
47
48
49
50
51
52
53
54
55
56
57
58
JOB NO. U 7063 U ITEM NO. U J-XM-080301
REQUISITION NO. U E1
DATASHEET NO. U ISG-AB-KRE-EL-DAT-0001

A.C. GENERATOR REVISION NO. E2 DATE 19/01/07


DATA SHEET
U U U

PAGE 4 OF 4 BY DP
SI UNITS
U U U U U U

SYSTEM DATA

CB 1 / 2 CB 2 / 3

10kV BOARD No.


J-EH-080001

NC

NC CB1 NC CB2 NC CB3

PURCHASER

SUPPLIER

G G G
G3 - SEE NOTE 2

N.E.R. N.E.R. N.E.R.


750 A 750 A 750 A
10 SECS 10 SECS 10 SECS
7,7 7,7 7,7
OHMS OHMS OHMS

*N.E.R. - NEUTRAL
EXISTING PROPOSED EARTHING RESISTOR

1 REMARKS:
2 1) THE REGULATION CAPABILITY OF THE MAIN A.C. GENERATOR AND AVR SYSTEM UNDER STEADY STATE AND TRANSIENT
3 CONDITIONS SHALL BE VOLTAGE REGULATION GRADE, 2.33 (VR2.33) AS DEFINED IN BS 4999 PART 140.
4 TRANSIENT PERFORMANCE IS DEFINED WITH RATED kVA AT 0.8 POWER FACTOR REJECTED.
5
6
7 2) THIS DATA SHEET USES A THIRD GENERATOR - G3 (PLANT No. J- XM 080301) WHICH WILL BE CONNECTED TO THE RHS OF
8 THE EXISTING 10kV SWITCHBOARD No. J-EH-080001.
9
10
11
12

You might also like